Military Engineer Services Tender

If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Coronavirus COVID 19
Eprocure

Opening Date

8 Jan 2019

Closing Date

25 Mar 2019

Tender Amount

₹ 14,78,75,656 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Get the Best Price For TMT
Starting from
₹51,200/MT*
Uttar Pradesh

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
SCHEDULE 'A' PART-II B (INTER WATER SUPPLY)

-

-

-

... More
S & F Health faucet chromium plated 15mm bore with 1.00 mtr long metallic expendable tube and hanging arrangement complete all as specified and directed.

24

-

-

... More
Total amount of SCHEDULE 'A' PART-III-A (INTERNAL ELECTRIFICATION) (For details see Item No. 01 to 08 of Schedule 'A' Part-III-A in PDF folder)

1

-

189420.1

... More
SCHEDULE 'A' PART-III-B (INTERNAL ELECTRIFICATION)

-

-

-

... More
M & L for point wiring using 1.50 sqmm size, PVC insulated, unsheathed 1100 volts grade single core multi-stranded (FR) copper conductor cable in proper coding drawn into and including non metallic rigid PVC conduit medium grade (not less than 20 mm dia) with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.50 sqmm size stranded copper conductor cable as in earth wire and connecting all metal parts to common earth dolly complete all as specified and directed for the following: -

-

-

-

... More
(a) One light point / fan point / bell point / exhaust fan point controlled by one, one way switch 5/6 Ampere.

1228

-

-

... More
(b) One 5/6 Ampere 3 pin socket outlet point controlled by one, one way switch on independent board.

271

-

-

... More
(c) One 5/6 Ampere 3 pin socket outlet point controlled by one, one way switch on same board.

54

-

-

... More
(d) One light point controlled by two way switch 5/6 Ampere.

54

-

-

... More
M & L for point wiring for one 15/16 Ampere socket outlet independent point using 2.50 sqmm size, PVC insulated, unsheathed 1100 volts grade single core multi-stranded (FRLS) copper conductor cable in proper coding drawn into and including non metallic rigid PVC conduit medium grade (not less than 25 mm dia) with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 2.50 sqmm size stranded copper conductor cable as in earth wire and connecting all metal parts to common earth dolly complete all as specified and directed.

175

-

-

... More
NOTE FOR ITEM NO. 8.00 AND 9.00: - Switch, Socket outlet etc. shall be measured and paid separately.

-

-

-

... More
M&L for Distribution board (DB) made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 4 way with 200 Amps rated copper bus bar neutral bar ,earth bar, single pole and neutral 240 volts, Double door, flush to wall connecting with cable complete all as specified and directed.

16

-

-

... More
M&L for Distribution board (DB) made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 8 way with 200 Amps rated copper bus bar neutral bar ,earth bar, single pole and neutral 240 volts, Double door, flush to wall connecting with cable complete all as specified and directed.

48

-

-

... More
M&L for Distribution board (DB) made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 12 way with 200 Amps rated copper bus bar neutral bar ,earth bar, single pole and neutral 240 volts, Double door, flush to wall connecting with cable complete all as specified and directed.

5

-

-

... More
Supply and fixing Vertical load line type TPN DB, 4 way, as per IS - 8623, IP-43 protection, universal mounting with suitable capacity copper bus bar with nuetral bus bar, earth bar and cable ties for cable management, top and bottom removable gland plate suitable for MCCB TPN upto 125 Amp as incomer and TP&SP MCCB/MCBs as outgoing complete & making necessary electrical connection for incoming and outgoing cables, with copper lugs, crimpped with crimping tool complete all as specified and directed.

3

-

-

... More
Supply and fixing Vertical load line type TPN DB, 6 way, as per IS - 8623, IP-43 protection, universal mounting with suitable capacity copper bus bar with nuetral bus bar, earth bar and cable ties for cable management, top and bottom removable gland plate suitable for MCCB TPN upto 125 Amp as incomer and TP&SP MCCB/MCBs as outgoing complete & making necessary electrical connection for incoming and outgoing cables, with copper lugs, crimpped with crimping tool complete all as specified and directed.

2

-

-

... More
Supply and fixing Vertical load line type TPN DB, 8 way, as per IS - 8623, IP-43 protection, universal mounting with suitable capacity copper bus bar with nuetral bus bar, earth bar and cable ties for cable management, top and bottom removable gland plate suitable for MCCB TPN upto 125 Amp as incomer and TP&SP MCCB/MCBs as outgoing complete & making necessary electrical connection for incoming and outgoing cables, with copper lugs, crimpped with crimping tool complete all as specified and directed.

1

-

-

... More
Supply and fixing Vertical load line type TPN DB, 12 way, as per IS - 8623, IP-43 protection, universal mounting with suitable capacity copper bus bar with nuetral bus bar, earth bar and cable ties for cable management, top and bottom removable gland plate suitable for MCCB TPN upto 125 Amp as incomer and TP&SP MCCB/MCBs as outgoing complete & making necessary electrical connection for incoming and outgoing cables, with copper lugs, crimpped with crimping tool complete all as specified and directed.

2

-

-

... More
S&F Miniature circuit breaker single pole with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, robust design and terminals having heat resistant moulding suitable for single phase circuit of 240 volts and 6 to 32 Amps current rating , B Series, 10 KA complete all as specifed and directed.

370

-

-

... More
S&F Miniature circuit breaker Single pole and Neutral with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, robust design and terminals having heat resistant moulding suitable for single phase circuit of 240 volts and 6 to 32 Amps current rating , C Series, 10 KA complete all as specifed and directed.

86

-

-

... More
S&F Miniature circuit breaker Single pole and Neutral with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, robust design and terminals having heat resistant moulding suitable for single phase circuit of 240 volts and 63 Amps current rating , C Series, 16 KA complete all as specifed and directed.

91

-

-

... More
S&F MCCB three pole and Neutral with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, fix type suitable for three phase circuit of 430 volts of current rating 63/100 Amps, C Series, 16 KA bracking capacity complete all as specifed and directed.

6

-

-

... More
S&F MCCB three pole and Neutral with thermal over load as well as magnetic short circuit tripping device with quick break trip free mechanism, fix type suitable for three phase circuit of 430 volts of current rating 125 Amps, C Series, 25 KA bracking capacitycomplete all as specifed and directed.

2

-

-

... More
S&F Aluminium extruded suspended LED fitting 20 Watt, 230V, ceiling hanging, with integrated electronic driver high transcluent frosted diffuser, bipin holders, connector block, etc. complete with all accessories internally pre-wired and including hanging arrangement under ceiling upto 1.5 mtr long duly painted as direction by EIC and connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. Model - CONSTA LED , Code No.- CONSTA 544lP20WLED840SPMMAWH of Make- Havells. or equvalient in Philips/BAJAJ

82

-

-

... More
S&F LUMILINE 20 watt LED, High lumen batten with efficacy of 100 lumens , 230V, Surface /Wall mounting, with integrated electronic driver high transcluent frosted diffuser, bipin holders, connector block, etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. Make:- Havells, Model- LUMILINE, LUMILINE BS20WLED840SPCWH or eqvlt in Philips/ Havells.all as specified and directed by engr-in-charge.

380

-

-

... More
Supply & Fixing Lamp holder/Batten holder with PVC/Polycarbonate body angular/straight fixed on plastic laminated sheet cover round shape 3 mm thick including 01 No LED 10 W suitable for 230 V complete all as specified and directed.

274

-

-

... More
S&F ENDURA NEO DL Porch light fitting 15 watt surface mounted LED downlighter with white powder coated aluminium housing with integrated electronic driver round shape including lamp complete with all acessories including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specifed and directed. Make -Havells, Code No- ENDURANEO SURFACEDLS 15WLED857S

7

-

-

... More
S&F ventilator fan 250 mm sweep PVC body with louver shutter complete fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulated three core 23/0.0076 copper cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black synthetic enamel paint 2.0 cm high for offrs toilets complete all as specified and directed.

10

-

-

... More
S&F Exhaust fan 300 mm sweep Metallic body with louver shutter complete including M&L for providing/cutting the round hole of required size in wall finishing the same supply and grouting the ragged bolts in wall, fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulated three core 23/0.0076 copper cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black synthetic enamel paint 2.0 cm high complete all as specified and directed.

41

-

-

... More
S&F Heavy duty, 450 mm sweep, 1400 rpm Exhaust fan Metal body with louvers shutter having Air delivery - 6800 Cu-mtr/min complete fixing the frame on the exhaust side (outer surface of the wall) and connecting with and including PVC insulated three core copper cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black synthetic enamel paint 2.0 cm high complete all as specified and directed.

8

-

-

... More
Supply & Fixing energy saving ceiling fan complete without regulator 230 volts single phase 1200 mm sweep including canopy set,down rod and shackle assembly, Fan hook including providing three core copper conductor cable of size 1.5 Sq mm 3 core from fittings to ceiling rose or connector and writing MES No. with black synthetic enamel paint 2.0 cm high complete all as specified and directed by EIC including cost of 15 mm GI Pipe medium grade upto 1.5 mtr duly painted with matching colour for hanging of ceiling fan where required complete all as specified and directed.

292

-

-

... More
S&F LED linear mirror light Aesthetically designed, Provided with a high output PMMA diffuser for glare free light 7 watt. Dimension: 300 mm. incl lamp etc. complete with all accessories in and including connecting up with twin core twisted flexible copper conductor cable with suitable size copper wire complete all as specified and directed.

18

-

-

... More
Supply and fix wall mounted type aircirculator,18 inch size ,450 mm, 230 V,1440 rpm, 3 bldes, air delivery 9000,100 Watt including providing three core copper conductor cable of size 1.5 Sq mm 3 core from fittings to ceiling rose or connector and writing MES No. with black synthetic enamel paint 2.0 cm high complete all as specified and directed by EIC including fixing arrangement such as nut, bolt and fasner etc complete all as specified and directed.

6

-

-

... More
S&F blanking plate complete all as specifed and directed.

60

-

-

... More
S & F of sub main wiring alongwith earthwire for the following sizes PVC insulated PVC unsheathed multi-stranded copper conductor cable in and including PVC conduit medium grade ISI marked, fixed concealed of size as mentioned below complete with all conduit all accessories / fittings as required at site and connecting of earthwire to common earth dolly complete all as specified and directed: -

-

-

-

... More
(a) Two single core 1.50 sqmm size sub main wiring with one single core 1.00 sqmm size earthwire drawn into and including one run 25 mm or higher dia PVC conduit fixed concealed. Note :- Two run of 1.50 sqmm copper cable, one run of 1.00 sqmm copper cable and one run of conduit shall be measured as one unit.

160

-

-

... More
(b) Two single core 2.50 sqmm size sub main wiring with one single core 2.50 sqmm size earthwire drawn into and including one run 25 mm or higher dia PVC conduit fixed concealed. Note :- Two run of 2.50 sqmm copper cable, one run of 2.50 sqmm copper cable and one run of conduit shall be measured as one unit.

200

-

-

... More
(c) Two single core 4.00 sqmm size sub main wiring with one single core 2.50 sqmm size earthwire drawn into and including one run 25 mm or higher dia PVC conduit fixed concealed. Note :- Two run of 4.00 sqmm copper cable, one run of 2.50 sqmm copper cable and one run of conduit shall be measured as one unit.

340

-

-

... More
(d) Two single core 6.00 sqmm size sub main wiring with one single core 4.00 sqmm size earthwire drawn into and including one run 25 mm or higher dia PVC conduit fixed concealed. Note :- Two run of 6.00 sqmm copper cable, one run of 4.00 sqmm copper cable and one run of conduit shall be measured as one unit.

280

-

-

... More
(d) Two single core 10.00 sqmm size sub main wiring with one single core 6.00 sqmm size earthwire drawn into and including one run 25 mm or higher dia PVC conduit fixed concealed. Note :- Two run of 10.00 sqmm copper cable, one run of 6.00 sqmm copper cable and one run of conduit shall be measured as one unit.

340

-

-

... More
Supply & fix Energy saving and environmental friendly long life LED street light 25 watt made up of pressure die cast aluminium housing with high power LED as lighting source and lens embendded PC cover having TOP OPENING separate driver compartment with IP 65 protection and impact resistance of IK07 including taking down of existing street light any type including cost of GI pipe, bracket, clamps, nut & bolts etc required for fixing of fittings complete all as specified and directed. Make:- Havells, Model-Endura Pearl, Code -LHETBXU7PA6S025 (Suitable for pole dia 43 mm max.)

108

-

-

... More
M & L for earthing complete with galvanised mild steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to galvanised earth lead wire 4 mm dia by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 5 of MES schedule 2009, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, CI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover in PCC 1:2:4, type B-1, duly reinforced with 6 mm dia mild steel TMT bars @ 150 mm both ways center to center with suitable lifting handle to cover, earth pit of PCC 1:2:4 type B-1, GI protection pipe light grade 15 mm bore including testing on completion of job complete all as specified and directed.

18

-

-

... More
NOTES: - ON TESTING AFTER COMPLETION OF JOB, IF DESIRED EARTH RESISTANCE (i.e. LESS THAN ONE OHM) IS NOT OBTAINED, THE EARTHING SHALL BE REDONE BY THE CONTRACTOR WITHOUT ANY EXTRA COST TO GOVT.

-

-

-

... More
Total amount of SCHEDULE 'A' PART-IV (SITE CLEARANCE AND EARTH WORK) (For details see Item No. 01 to 12 of Schedule 'A' Part-IV in PDF folder)

1

-

2601608.45

... More
Total amount of SCHEDULE 'A' PART-V A ( ROAD, PATH, CULVERT AND HARDSTANDING) (For details see Item No. 01 to 14 of Schedule 'A' Part- V A in PDF folder)

1

-

16622502.75

... More
SCHEDULE 'A' PART-V B ( ROAD, PATH, CULVERT AND HARDSTANDING)

-

-

-

... More
M&L for applying thermoplastic reflective paint as in road marking of minimum 2.5mm thick single coat of 100/150 mm wide using HOT MARK thermoplastic paint (Hot application) white or golden yellow by indigenous modern properly road marking machine as directed incl all ingredients such as binder glass beads shall titanium dioxide calcium carbonate inter filler thermoplastic complete all as specified and as directed.

560

-

-

... More
Supply &Fixing of 3 MUSA brand markers (Cat eyes) made of non breakable polycarbonate with electronically welded primatic Retro reflective in wet and dry condition body dust proof complete all as specified and as directed.

933

-

-

... More
S&F mild steel sign board made out of 50mm dia GI light grade pipe1.50 m heigh above G/L including board of size 1.20m x 0.90m made out of 1 mmm thick MS sheet including two coats of synthetic enamel paint and writing letters( both side) with flourscent paint ans fixing in position including necessary earth work and grouting in PCC 1:3:6 type B-1 of size300x 3000x 450mm complete all as specified and directed.

12

-

-

... More
Total amount of SCHEDULE 'A' PART-VI A (FENCING, GATE, AND COMPOUND WALL/SECURITY WALL) (For details see Item No. 01 to 18 of Schedule 'A' Part-VI A in PDF folder)

1

-

934656.2

... More
SCHEDULE 'A' PART-VI B ( FENCING, GATE, AND COMPOUND WALL/SECURITY WALL)

-

-

-

... More
Construction of Steel gate 6.00mtr wide (clear distance between pillar to pillar) 2.10 mtr high including RCC pillars,excavation and earthwork in soft/loose soil , PCC in foundation ,PCC block ,steel work incl wheel track and painting etc complete all as specified and shown on drawing.

2

-

-

... More
Construction of Steel gate 7.00mtr wide (clear distance between pillar to pillar) 2.10 mtr high including RCC pillars,excavation and earthwork in soft/loose soil , PCC in foundation ,PCC block ,steel work incl wheel track and painting etc complete all as specified and shown on drawing.

1

-

-

... More
Total amount of SCHEDULE 'A' PART-VII (AREA DRAINAGE) (For details see Item No. 01 to 07 of Schedule 'A' Part-VII in PDF folder)

1

-

2808007.5

... More
Total amount of SCHEDULE 'A' PART-VIII A (SEWAGE DISPOSAL) (For details see Item No. 01 to 12 of Schedule 'A' Part-VIII A in PDF folder)

1

-

544558.2

... More
SCHEDULE 'A' PART-VIII B (SEWAGE DISPOSAL)

-

-

-

... More
Construction of Septic tank 50 users with fly ash brick masonry wall, PCC in foundation, floor, RCC cover slab including sludge chamber, CI vent pipe, CI cowl, inlet and outlet pipe, RCC baffle wall and all necessary excavation and earth work complete all as specified, shown in drawings and as directed.

3

-

-

... More
Construction of Septic tank 100 users with fly ash brick masonry wall, PCC in foundation, floor, RCC cover slab including sludge chamber, CI vent pipe, CI cowl, inlet and outlet pipe, RCC baffle wall and all necessary excavation and earth work complete all as specified, shown in drawings and as directed.

2

-

-

... More
Construction of brick masonry soak well of 1.80 m dia and 6.00 m effective depth and excavation and earth work in ordinary soil, PCC in foundation, fly ash brick work solid/ honeycomb in CM1:6, PCC bend, RCC slab, RCC/ CI Manhole cover, filling in brick bats, RFR and removal etc complete all as specified, shown in drawings and as directed.

3

-

-

... More
Construction of brick masonry soak well of 2.40 m dia and 6.00 m effective depth and excavation and earth work in ordinary soil, PCC in foundation, fly ash brick work solid/ honeycomb in CM1:6, PCC bend, RCC slab, RCC/ CI Manhole cover, filling in brick bats, RFR and removal etc complete all as specified, shown in drawings and as directed.

2

-

-

... More
Total amount of SCHEDULE 'A' PART-IX A (RAIN WATER HARVESTING) (For details see Item No. 01 to 15 of Schedule 'A' Part-IX A in PDF folder)

1

-

533748.72

... More
SCHEDULE 'A' PART-IX B (RAIN WATER HARVESTING)

-

-

-

... More
M&L for boring for 250mm dia diameter complete with DTH comrotary method upto 60 mtr depth below from ground level in any type of soil incl removal of surplus soil upto 50 mtr distance complete all as specified and all as directed

150

-

-

... More
M&L for lowering in bore 150mm dia UPVC pipe conforming to IS 13592 :1992 (Type-A) with fitting, perforated holes, as casing pipe located centrally in 250mm diameter bore complete all as specified and all as directed.

150

-

-

... More
Total amount of SCHEDULE 'A' PART-X A (EXTERNAL ELECTRIC SUPPLY) (For details see Item No. 01 to 05 of Schedule 'A' Part-X A in PDF folder)

1

-

571213.8

... More
SCHEDULE 'A' PART-XB (EXTERNAL ELECTRIC SUPPLY)

-

-

-

... More
Supply and laying cable XLPE insulated screened PVC bedded,galvanised steel strip or wire armoured,electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 6 sqmm 2 core complete all as specified and as directed.

455

-

-

... More
All as per item No 59.00 above but 10 sqmm 2 core

60

-

-

... More
All as per item No 59.00 above but 16 sqmm 2 core

80

-

-

... More
All as per item No 59.00 above but 16 sqmm 4 core

310

-

-

... More
All as per item No 59.00 above but 25 sqmm 4 core

420

-

-

... More
All as per item No 59.00 above but 50 sqmm 3.5 core

80

-

-

... More
All as per item No 59.00 above but 70 sqmm 3.5 core

50

-

-

... More
All as per item No 59.00 above but 120 sqmm 3.5 core

30

-

-

... More
All as per item No 59.00 above but 150 sqmm 3.5 core

465

-

-

... More
All as per item No 59.00 above but 240 sqmm 3.5 core

400

-

-

... More
Supply and laying cable XLPE insulated screened PVC bedded,galvanised steel strip or wire armoured,electric power cable (heavy duty) 11000 volts grade with stranded aluminium conductor of size 95 sqmm 3 core complete all as specified and as directed.

450

-

-

... More
Supply , installation, Testing & commissoning of transformer of capacity 63 KVA step down outdoor type copper wounded 11/0.433 KV (at no load) AC 3 phase 50HZ on secondry side double wound oil immersed naturally all air cooled with external cooling tubes /radiator , delta connected as on primary and star connected with netural brought on secondry) side and having tapping at (±) 2.5%,(±) 5% (±) 7.5% to be changed by hand operated OFF LOAD tap changing gear . The maximum temperature rise shoud not exceed 45 degree centigreade in oil and 50 degree centigrade in HV/ LV winding when measured by the resistance method after contineous full load run in ambient temprature the transformer shall confirming to IS 1180 part-I of 2014 and comprising of following accessories. CONTD....

1

-

-

... More
a) 03 Nos porcelains HV bushing with arching horns on HV side suitable for 11 KV complete with bushing rods nuts. b) b) 01 No cable end box on LV secondry side consisting of 04 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for reception of out 3.5 core 240 Sqmm cable LT 1100V grade XLPE insulated heavy duty including gland joint complete. c) Oil conservator with filter type drain valve and oil level guage. d) Dehydrating breather with first filling of dehydrating agent . e) Explosive vent. f) THERMOMETER pocket on tank cover g) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI strips. CONTD....

-

-

-

... More
h) One No 100mm thermometer dail type vapour pressure type having range 0-120 degree centigrade with maximum temprature indicator and re-setting device to maximum temprature including needle of temprature gauge : Max reading painted terminal. j) Rating plate with terminal plate. k) Oil level guage. l) Oil drain filter valve. m) Oil filter hole with cap/plug with connection complete. n) Air release valve/plug. o) 4 Nos plain solid cast steel dedtachable rollers. p) Extra bushing for neutral out side the cable box and providing independent earthing for neutral. q) First fill of tranformer oil conforming to relevent IS and tested upto 60 KV dielectric strength.

-

-

-

... More
M&L for earthing complete with galvanised iron earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, the earth plate surrounded by adequate quantity of char coal dust and salt all as arround earth plate 15 cm by and GI earth wire 4mm dia as earth conductor, bolts and rivetted to earth plate one end protected with GI pipe light grade 15mm bore upto 2.4 mtr on pole with flat iron clamp nut bolt complete earth work water pipe from earth chamber to earth plate, CI funnel with wiremesh fixed on water pipe and PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in pit chamber and Contd.....

8

-

-

... More
RCC pitcover 50mm thick RCC cover in PCC 1:2:4 type B-1, duly reinforced with 6mm dia mild steel TMT bars @ 150mm both ways center to center with suitable lifting handle to cover, earth pit of PCC 1:2:4 type B-1, GI protection pipe light grade 40mm bore including testing on completion of job complete all as specified and directed. NOTES: - ON TESTING AFTER COMPLETION OF JOB, IF DESIRED EARTH RESISTANCE (i.e. LESS THAN ONE OHM) IS NOT OBTAINED, THE EARTHING SHALL BE REDONE BY THE CONTRACTOR WITHOUT ANY EXTRA COST TO GOVT.

-

-

-

... More
M&L for earthing to poles GOD with incl MS earth plate of size 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to galvanised iron 32 x 6mm strip as earth lead wire by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part-I (Specifications) and connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150mm in all directions with & including watering pipe 20mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire guage, Contd.....

4

-

-

... More
50mm thick RCC cover in PCC 1:2:4 type B-1, duly reinforced with 6mm dia mild steel TMT bars @ 150mm both ways center to center with suitable lifting handle to cover, earth pit of PCC 1:2:4 type B-1, GI protection pipe light grade 40mm bore including testing on completion of job complete all as specified and directed. NOTES: - ON TESTING AFTER COMPLETION OF JOB, IF DESIRED EARTH RESISTANCE (i.e. LESS THAN ONE OHM) IS NOT OBTAINED, THE EARTHING SHALL BE REDONE BY THE CONTRACTOR WITHOUT ANY EXTRA COST TO GOVT.

-

-

-

... More
Providing platform for transformer of size 3.0x3.0x1m high from GL including excavation in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in CM 1:6, RCC M-25, PCC 1:2:4 type B1 in coping, plaster 10mm thick in CM 1:6 on brick /complete surface PCC 1:4:8 type B1 sub base 75mm thick, as in floor PCC 1:2:4 type B1 100mm thick floor using extra cement returning filling and removal on surplus soil, chain link fencing 1.8m high made out of 4mm dia GI wire 150x100mm mesh MS work angle iron 50x50x6mm as fencing post in embeded in brick /PCC work at 2mtr interval each side as approved 1 No steel gate (3.5m clear) span as shown in drawing with locking arrangement made out of 15mm dia ms rod &50x50x6mm angle iron frame . painting with 2 coat alu paint over a coat of red oxide primer and 3 coats of white washing on cement work including 2 Nos ISMB 100mm chanel for fixing transformer including ramp of suitable size mounting of transformer complete all as specified and directed.

1

-

-

... More
Supply installation testing and commissioning of LT feeder pillar box (KIOSK) type totally enclosed made of MS sheet 3.15 mm thick outdoor type weather proof having sloping canopy with both side openable and Aluminium busbar suitable capacity with air insulated for TPN, digital type Ammeter, Volt meter, frequency meter, selector switches, Indication lamps, danger notice plate with Panel wiring with 2.5 sqmm copper cable PVC single core,locking arrangement and painting etc (MP1) :- (i) Incoming MCCB TP, 415V, 100 Amps, with rupturing capcity 35 KA - 1 No. (ii) Outgoing MCCB TP, 415V, 63 Amps, with rupturing capcity 25 KA - 1 No (iii) Outgoing MCCB TP, 415V, 40 Amps, with rupturing capcity 25 KA - 2 Nos (iv) Outgoing MCCB TP, 415V, 32 Amps, with rupturing capcity 10 KA - 1 No Contd.....

2

-

-

... More
(v) Outgoing MCB SPN, 230 V, 32 Amps, with rupturing capcity 10 KA - 2 Nos (vi) Aluminium busbar 200 Amps with air insulated for TPN - One set. (vii) timer switches with contactor TP 40 Amp for street light fittings (viii) Panel wiring with 2.5 sqmm copper cable PVC single core - 1 Job (ix) PCC plate form with foundation 1 : 2 : 4 = 1 Job

-

-

-

... More
Supply installation testing and commissioning of LT feeder pillar box (KIOSK) type totally enclosed made of MS sheet 3.15 mm thick outdoor type weather proof having sloping canopy with both side openable and Aluminium busbar suitable capacity with air insulated for TPN, digital type Ammeter, Volt meter, frequency meter, selector switches, Indication lamps, danger notice plate with Panel wiring with 2.5 sqmm copper cable PVC single core,locking arrangement and painting etc (MP1) :- (i) Incoming MCCB TP, 415V, 100 Amps, with rupturing capcity 35 KA - 1 No. (ii) Outgoing MCCB TP, 415V, 63 Amps, with rupturing capcity 25 KA - 1 No Contd.....

1

-

-

... More
(iii) Outgoing MCCB TP, 415V, 40 Amps, with rupturing capcity 25 KA - 1 Nos (iv) Outgoing MCCB TP, 415V, 32 Amps, with rupturing capcity 10 KA - 1 No (v) Outgoing MCB SPN, 230 V, 32 Amps, with rupturing capcity 10 KA - 8 Nos (vi) Aluminium busbar 200 Amps with air insulated for TPN - One set. (vii) Panel wiring with 2.5 sqmm copper cable PVC single core - 1 Job (viii) PCC plate form with foundation 1 : 2 : 4 = 1 Job

-

-

-

... More
Supply and fix capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 10 KVAR capacity complete all as specified and directed.

1

-

-

... More
Supply & fixing of Cable route markers made of galvanized iron with supporting GI angle of size 40 X 40 X 6 mm for stand and plate size 150X150X5mm thick and primering, painting, writting of HT/LT cable route mark for suitable size letters including M/L PCC 1:3:6 type C2 using 40mm graded aggregades in mass concrete or plinth block complete all as specified and directed.

100

-

-

... More
Total amount of SCHEDULE 'A' PART-XI A (EXTERNAL WATER SUPPLY) (For details see Item No. 01 to 10 of Schedule 'A' Part-XI A in PDF folder)

1

-

567607.2

... More
SCHEDULE 'A' PART-XI B (EXTERNAL WATER SUPPLY)

-

-

-

... More
Supply and laying ductile iron pipes of size 100mm nominal bore with socket and spigot ends suitable for tyton joint centrifugally cast class `K-7' in any length laid in trenches complete all as specified and directed .

410

-

-

... More
M&L for ductile iron serials and fittings class `K-12' as per IS for spigot and socketed pipes for water mains/branches link such as bends (any type radius and angle) tapers any type, (straight bend, increasing, decreasing or double socket etc) tee pieces single branches function double branch cross (all sockets socket and spigot) collars, caps and plugs, suitable for non lead joint upto 250mm bore complete all as specified and directed

300

-

-

... More
M & L for construction of brick masonry valve pit of size 950 X 950 X 900 mm (internal dimensions) with excavation & earthwork in any type of soil, brick work of flyash old size bricks built in cement mortar 1:4, PCC 1:2:4 type B-1 using 20 mm graded aggregate as in foundation, concrete floor / coping and 10 mm thick rendering on internal and exposed external surfaces with water proofing compound @ 2% by weight of cement with and including 20 mm X 25 mm X 6 mm mild steel angle iron frame, 3.15 mm thick mild steel sheet cover with appropriate size lifting handles and locking arrangement and 01 No. 50 mm size 4 levers lock with keys in duplicate make Navtal including painting steel and iron surfaces with two coats of black bituminous paint over a coat of red oxide primer complete all as specified, shown on drawings and as directed.

3

-

-

... More
M & L for construction of brick masonry valve pit of size 450 X 450 X 450 mm (internal dimensions) with excavation & earthwork in any type of soil, brick work of flyash old size bricks built in cement mortar 1:4, PCC 1:2:4 type B-1 using 20 mm graded aggregate as in foundation, concrete floor / coping and 10 mm thick rendering on internal and exposed external surfaces with water proofing compound @ 2% by weight of cement with and including 20 mm X 25 mm X 6 mm mild steel angle iron frame, 3.15 mm thick mild steel sheet cover with appropriate size lifting handles and locking arrangement and 01 No. 50 mm size 4 levers lock with keys in duplicate make Navtal including painting steel and iron surfaces with two coats of black bituminous paint over a coat of red oxide primer complete all as specified, shown on drawings and as directed.

24

-

-

... More
Total amount of SCHEDULE 'A' PART-XII A (HOT WATER SUPPLY) (For details see Item No. 01 to 04 of Schedule 'A' Part-XII A in PDF folder)

1

-

33499

... More
SCHEDULE 'A' PART-XII B (HOT WATER SUPPLY)

-

-

-

... More
Supply & Fix water heater storage type 25 liters capacity with and including all necessary Electric connection and providing vent pipe of approx 4 mtr length of GI pipe medium grade or suitable length as per requirements with necessary fittings of 15mm dia complete with fixing and also writing MES No with black paint and provision of 16 mm dia bolts and nuts minimum length 150mm long for fixing of geysers with 4 star rating all as specified and directed.

6

-

-

... More
Supply & Fix water heater storage type 50 liters capacity with and including all necessary Electric connection and providing vent pipe of approx 4 mtr length of GI pipe medium grade or suitable length as per requirements with necessary fittings of 15mm dia complete with fixing and also writing MES No with black paint and provision of 16 mm dia bolts and nuts minimum length 150mm long for fixing of geysers with 4 star rating all as specified and directed.

1

-

-

... More
Total amount of SCHEDULE 'A' PART-XIII A (COOLING APPLIANCES) (For details see Item No. 01 to 04 of Schedule 'A' Part-XIII A in PDF folder)

1

-

100055.2

... More
SCHEDULE 'A' PART-XIII B (COOLING APPLIANCES)

-

-

-

... More
Supply installation, commisoning of Non CFC refrigerant water cooler electric driven (Single Phase), of minimum 3 Star rating having storage capacity of 80 Ltr and nominal cooling capicity 40 Ltr/Hr complete including connecting cord, PVC connection & electrical plug Top, connection up with 20mm GI Pipe medium grade, 01 no Gate Valve 20mm and PVC drain pipe 25mm complete all as specified and directed. Make:- BLUE STAR/USHA/ WHIRLPHOOL

8

-

-

... More
Supply installation, commisoning of Non CFC refrigerant water cooler electric driven (Single Phase), of minimum 3 Star rating having storage capacity of 120 Ltr and nominal cooling capicity 60 Ltr/Hr complete including connecting cord, PVC connection & electrical plug Top, connection up with 20mm GI Pipe medium grade, 01 no Gate Valve 20mm and PVC drain pipe 25mm complete all as specified and directed. Make:- BLUE STAR/USHA/ WHIRLPHOOL

1

-

-

... More
Supply and Installation and testing of Desert Coolers having nominal air flow capacity 1800 Cum/hrs, steel body fabricated with 22 SWG sheet, electric Driven (Single phase) 230 volts, AC, 3 Speed 1400 RPM, blade size 406/16 mm, PVC body, 3 speed, 1400 RPM, 160 watt, 45 ltrs water tank capacity, motorised loures movement, top water inlet with pump & motor including fixing arrangement with angle iron 50x50x6mm bracket & suitable size of ply wood work and water connection with stop cock valve complete all as specified and directed. ( Note: Water pipe line and gate valve measured and paid seperatly)

64

-

-

... More
Supply installation and testing of Refrigerator of capacity 195 Ltrs non CFC refrigerant type electric driven single phase 230 V, 50 Hz, frost free double door including filling of refrigerator gas as per manufacturere instruction, minimum 3 star rating with PVC bottom stand complete all as specified & directed. Make:- Whirlpool/Samsung/LG.

5

-

-

... More
Supply installation and testing of Refrigerator of capacity 310 Ltrs non CFC refrigerant type electric driven single phase 230 V, 50 Hz, frost free double door including filling of refrigerator gas as per manufacturere instruction, minimum 3 star rating with PVC bottom stand complete all as specified & directed. Make:- Whirlpool/Samsung/LG.

2

-

-

... More
Supply installation and testing of Deep freezer hard top 320 ltrs capacity having single door air cooled sealed unit compressure complete with PVC button stand complete all as specified and directed.

2

-

-

... More
Supply and fixing of automatic boost/bulk transformer for low & high voltage correction equipped with electronic transistorized relay suitable for correction on single phase 50 c/s A/C supply complete with Digital voltmeter and designed for input voltage 170 V to 250 V and output voltage stabilized between 200 V to 240 V with accuracy of +/- 2.5 % with time delay relay 2 minutes of capacity 1 KVA complete all as specified and directed. Make- Sinetrac/Bluebird/Vgaurd

1

-

-

... More
Supply & Fix automatic boost/bulk transformer for low and high voltage correction and out put equipped with electronic transistorised relay suitable for correction on single phase 50 cycles AC supply complete with connecting cord with top plug voltmeter and designed for input voltage of 170 V to 250 V and output voltage stablised between 200 V to 240 V with accuracy of +/- 2.5 % and capcity 0.5 KVA time delay relay complete all as specified & directed. Make- Sinetrac/Bluebird/Vgaurd

9

-

-

... More
Total amount of SCHEDULE 'A' PART-XIV (SOLAR WATER) (For details see Item No. 01 to 06 of Schedule 'A' Part-XIV in PDF folder)

1

-

417125.25



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.