Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair/maint To External Electric Supply Lt Panels Mccb Earthing Cables And Their Connected Item At Mp Golai And Burdong Under Ge Gangtok in East Sikkim, Sikkim, with an estimated contract value of Rs. 22,00,000. The bid opening date for this tender is 13-10-2026 and the last date for bid submission is 10-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - Sikkim Tender
Opening Date13 Oct 2026
Closing Date10 Nov 2026
Tender Amount₹ 22,00,000
Costs
EMD
₹ 44,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Repair/maint To External Electric Supply Lt Panels Mccb Earthing Cables And Their Connected Item At Mp Golai And Burdong Under Ge Gangtok
Corrigendums and Tender Updates
Contact
Tender Id
2026_MES_793752_1Bid Award Id
ViewTender No
c/8518/A/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
M&L for PCC 1:2:4 type C–2 (using 20 mm crushed graded stone aggregate/as in foundation for stay and necessary form work for rough finished surface complete all as specified and as directed.
3
-
-
... More
M&L for 50mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed.
12
-
-
... More
M&L for 80mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed.
8
-
-
... More
Supply, laying, testing and commissioning in trenches or fixing on wall or passing through pipe or in cable ducts XLPE insulated PVC Inner sheathed , screened , PVC bedded and PVC tape sheathed galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm 4 core including cable lugs, glands, insulation tape etc complete all as specified and as directed.
200
-
-
... More
All as per Item No 7.00 here in above but 16 Sqmm 4 core.
200
-
-
... More
All as per Item No 7.00 here in above but 25 Sqmm 3.5 core.
280
-
-
... More
All as per Item No 7.00 here in above but 35 Sqmm 3.5 core.
100
-
-
... More
All as per Item No 7.00 here in above but 50 Sqmm 3.5 core.
100
-
-
... More
All as per Item No 7.00 here in above but 95 Sqmm 3.5 core.
100
-
-
... More
S&F in repairs MCCB of 50Hz, 415 V adjustable type including necessary cable lugs & wire etc. of size 63 Amps, 4 pole & 16 KA thermal magetic based complete all as specified and as directed.
3
-
-
... More
All as per item No 13.00 but here in before but 100 Amps, 4 pole & 16 KA.
3
-
-
... More
All as per item No 13.00 but here in before but 160 Amps, 4 pole & 25 KA.
3
-
-
... More
All as per item No 13.00 but here in before but 200 Amps, 4 pole & 25 KA.
3
-
-
... More
All as per item No 13.00 but here in before but 250 Amps, 4 pole & 36 KA.
2
-
-
... More
All as per item No 13.00 but here in before but 400 Amps, 4 pole & 36 KA
2
-
-
... More
M&L for cutting the existing road / PCC / drain for taking out / laying of underground cable including necessary earthwork excavation and making good to match with the exisitng surface with 100mm thick PCC 1:3:6 type C1 (using 20 mm graded stone aggregates) complete all as specified and directed. Note- (i) GI pipe shall be measured and paid separately.
(ii) Any damages made/caused to the HT/LT cables,water supply pipelines, OFC cables etc during the excavation works shall be made good by the contractor as per original and cost of the same is deemed to be included in the unit quoted rate.
20
-
-
... More
Taking up/down existing defective cable of sizes 2/3/3.5/4 core 10 to 70 sqmm from the trenches / ducts/ along walls / poles / through poles / under roads/ inside sub station complete all as specified and as directed.
1230
-
-
... More
All as per item No 20.00 here in above but 95 to 185 qmm complete all as specified and as directed.
100
-
-
... More
Laying, jointing, testing and commissioning of serviceable cable obtained from taking out in same or new location or position i.e. in trenches/on walls/floord/roof/ceiling etc of size 2/3/3.5/4 core 16 to 120 sqmm including necessary cable lugs, gland etc complete all as specified and as directed.
250
-
-
... More
M&L for straight through joint (Heat Shrinkable) for under ground PVC insulated and PVC sheathed armoured heavy duty XLPE cables with aluminium conductor including jointing kit, including making joints for the cable of size 10-16 sqmm 3/3.5/4 core cables including testing complete all as specified and as directed.
3
-
-
... More
All as per item No 23.00 here in above but 25-50 sqmm 3/3.5/4 core.
3
-
-
... More
All as per item No 23.00 here in above but 70-120 sqmm 3/3.5/4 core.
2
-
-
... More
All as per item No 23.00 here in above but 150-185 sqmm 3/3.5/4 core.
2
-
-
... More
All as per item No 23.00 here in above but 240-300 sqmm 3/3.5/4 core.
2
-
-
... More
S&F in repairs Onload Change over switch, 100 Amps, 4 Pole, I-O-II Operation, manual type, with sheet steel enclosure or panel mounted as per site requirement including necessary cable lugs & Wire etc complete all as specified and as directed.
1
-
-
... More
All as per item No 28.00 here in above but 160 Amps, 4 Pole.
1
-
-
... More
S&F in repairs wornout/heated/detoriated replace aluminium lugs suitable for 25 Sqmm LT UG XLPE aluminium conductor cable including nuts, bolts, washers and PVC tape complete all as specified and as direcred.
8
-
-
... More
All as per item No 30.00 here in above but 50 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
All as per item No 30.00 here in above but 70 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
All as per item No 30.00 here in above but 95 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
All as per item No 30.00 here in above but 120 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
All as per item No 30.00 here in above but 185 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
All as per item No 30.00 here in above but 240 sqmm LT UG XLPE aluminium conductor cable.
8
-
-
... More
M&L for servicing of LT panels/Feeder piller box of any size by complete cleaning of panel and bus bar at chamber with CTC solution, and welding the door using arc welding and fixing of haevy duty hinges/Locking Handles/latches and necessary nut, bolts, washers/Leads/busbar and made it completely functional for open/close and incl checking of incoming and out going cable connections, Re-fixing of existing Cables, ACBs & MCCBs, and repair to connected PCC foundation and frame works, rewiring of control and power wiring of LT panel/Feeder with suitable size of FRLS cable but not less than 1.5 sqmm, replaceing of various unserviceable ON/OFF switches, lugs/Gland/Base plate/indicating Lamp/CT Coil etc making the panel fully functional including numbering the LT panel/feeder box and marking on panels (incoming and locations of outgoing MCCBs), to the satisfaction of Engr-in-Charge complete all as specified and as directed
20
-
-
... More
M&L for painting of LT panel of area exc 10 sqm but not exc 20 sqm by spraying two coats of epoxy based weather proof paint of ivory/Red colour over a coat of red oxide primer after cleaning of rusty panel surface of both inside/ outside by emery paper and necesary preparation of old steel surface complete all as specified and as directed.
10
-
-
... More
M&L for painting of LT panel of area not exc 10 sqm by spraying two coats of epoxy based weather proof paint of ivory/Red colour over a coat of red oxide primer after cleaning of rusty panel surface of both inside/ outside by emery paper and necesary preparation of old steel surface complete all as specified and as directed.
15
-
-
... More
M&L for Earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 25x4mm as earthing lead by means of nut, bolts and washers made out of galvanized iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead/Strip and connected to control board or main switch or as directed by Engineer -in-Charge including earthing pit in PCC (1:3:6) type C1 for chamber & Pre-cast RCC cover of size 380 x 380 x 40 mm with one handle made out of 8 mm dia round bar, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work complete all as shown in Electrical Plate No 3 of MES Schedule Part I and testing complete inclduing taking down old one/ dismantling complete all as specified and as directed.
Note- Rate quoted included the cost of earthwork , GI protection & GI strip from earthpit to LT panel upto 15 mtr.
5
-
-
... More
M&L for repair of damaged earthing chamber and rusted GI earth strip and provision of new inspection chamber by using RCC foundation slab of external diamension 800x800x80mm with internal opening of 300x300x80mm thick RCC 1:2:4 type B1 20mm graded stone aggregates rainforced with 8mm TMT Bars at 10cm center to centre both ways including finishing and PCC chamber in 1:2:4 type B1 of internal dimension 300x300x100 mm height with 80mm thick wall and 50mm thick Pre cast RCC cover slab 1:2:4 type B1 using 20mm graded stone aggregates rainforced with 8mm TMT bars at 10cm centre to centre including one lifting handle and replacement of GI earth strip 25 x4 mm dia jointing it by arc welding and nuts, bolts and washers of suitable size upto 01mtr length complete all as specified directed.
Note. The quoted rate includes cost of the following:- (a) Demolation the dammasged earth chaamber and remove to a distance not exceeding 50mtrs from starting point specified and directed by engr-in-charge.
(b) Removing the existing unserviceable earth pit complete including exacavation and refilling after fixing new earth chamber incl connecting the existing GI/copper earthing strip/wire to existing test point.
10
-
-
... More
S&F LED Multifunctional meter with CTs complete all as specified and directed.
Make: L&T/ABB/Siemens
2
-
-
... More
S&F in repairs Indication Lamp (LED type) Set of 3 complete all as specified and directed.
3
-
-
... More
S&F in repairs of three phase digital type Ammeter 0-400 Amps, class 1.0 with selector switch complete all as specified and directed.
3
-
-
... More
S&F in repairs of three phase digital type Voltmeter 0-500 Volts, class 1.0 with selector switch complete all as specified and directed.
3
-
-
... More
S&F in replacement of LT CTs copper wound capacity as per site requirement complete all as directed
3
-
-
... More
S&F in repairs DWC HDPE pipe, ISI marked in trenches or in cable ducts or fixed on walls using clamps along with all accessories like socket, bend, couplers etc confirming to IS 6205 (part 24)/IS 14930 complete with fitting cutting, jointing etc of size 50 mm outer dia complete all as specified and directed.
624
-
-
... More
S&F in repairs DWC HDPE pipe, ISI marked in trenches or in cable ducts or fixed on walls using clamps along with all accessories like socket, bend, couplers etc confirming to IS 6205 (part 24)/IS 14930 complete with fitting cutting, jointing etc of size 63 mm outer dia complete all as specified and directed.
80
-
-
... More
S&F in repairs DWC HDPE pipe, ISI marked in trenches or in cable ducts or fixed on walls using clamps along with all accessories like socket, bend, couplers etc confirming to IS 6205 (part 24)/IS 14930 complete with fitting cutting, jointing etc of size 77 mm outer dia complete all as specified and directed.
80
-
-
... More
M&L for painting of steel tubular poles 09 mtr long complete incl cross arms bracing supports and clamps with two coats spray painting of aluminium paint including two coats of synthetic enamel painting for making 30cm wide strip (total 05 Nos) with black and yellow paint after preparation of old paint surfaces complete all as specified and directed.
25
-
-
... More
M&L for cable loop of size upto 70 Sqmm by taking out with excavation, repair /cutting disturbed portion of loop, fixing of suitable size cable lugs, testing the cable, fixing in original position, make good the excavated portion complete all as specified and directed.
50
-
-
... More
M&L for cable loop of size 95 Sqmm and above by taking out with excavation, repair /cutting disturbed portion of loop, fixing of suitable size cable lugs, testing the cable, fixing in original position, make good the excavated portion complete all as specified and directed.
20
-
-
... More
M&L for steel tubular swaged pole 410 SP-31 (9 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
Note : Excavation and Earth work, PCC filling shall be measured and paid separately.
5
-
-
... More
M&L for PCC (1:3:6) type C2 (using 40 mm graded stone aggregates) as in foundations and mass concrete complete all as specified and directed.
4
-
-
... More
S&F in repairs MCB of 4 pole, 63 Amps, 25 KA, 415 volt complete with connection, testing and commissioning all as specified and directed.
3
-
-
... More
Supply, installing, testing and commissioning out door type LT Panel of suitable size, CPRI approved, factory made totally enclosed, dust and vermin proof, IP 55 ingress protection, conforming to IS : 60947 : 2004 double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, framing with MS angle iron 40 x 40 x 5 mm having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected, powder coated, and suitable for 415 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form of suitable size, complete with the following items :-
1
-
-
... More
BUSBAR :- Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of capacity 400A and good insulation resistance (set of 4)
INCOMING:-
(i) MCCB 4Pole, 415 Volts, 125 Amps, 25 KA, 4Pole, Ics=100%Icu - 01 No
(ii) Indicator lamp LED type (R-Y-B) - 01 set of three (iii) Digital volt meter (0-500V) with selector switch - 01 No
(iv) Digital Ammeter (0-500A) - 01 No with CT's and selector switch - 01 No OUTGOING:-
(i) MCCB 4 Pole, 415 Volts, 63 Amps, 10 KA, adjustable thermal magnetic release, Ics=100%Icu - 04 Nos (ii) CT of appropriate sizes
(iii) BUS Bar chamber 400 AMPS 4 strips copper-04 Nos
(iv) Enclosure of suitable size Make Universal
-
-
-