Kerala Industrial Infrastructure Development Corporation Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Kerala Industrial Infrastructure Development Corporation - KINFRA Tender
Eprocure
Opening Date29 Aug 2018
Closing Date14 Sep 2018
Tender Amount₹ 8,70,403 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 24,683Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Supply and Installation of 82.5KVA DG at KINFRA Corporate Office at Sasthamangalam, Trivandrum
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_KINFR_230227_1Bid Award Id
ViewTender No
KINFRA/HO/15/2018-19Tender Authority
Kerala Industrial Infrastructure Development Corporation ViewPurchaser Address
-Website
http://http://kinfra.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
DG AMF PANEL
Fabrication, supply, erection, testing and commissioning of type cubicle type, dust and vermin proof, floor mounted, front operated MV panel board made out of 16 SWG thick CRCA sheet, fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel etc including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable as per general specifications and drawings complete with all interconnections, powder coating , control wiring etc as per IS,KSEB / Inspectorate Regulations and General conditions/ Technical Specifications.
RYB phase indicating LED lamps with control fuses and switches - 1 set.
200A ATS with AMF-1 Nos
Supply
1
-
-
-do- Installation, testing and commisioning
1
-
-
EXHAUST PIPES
Supply, erection, commissioning of additional length of exhaust pipes with long radius bend from residential silencer with necessary clamps, fixtures, civil works and painted with heat resistant, rust proof, bituminous paint of approved colors to an appropriate height of following sizes including suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. It is also recommended that horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other acessories as instructed by the Engineer and the rate inclusive of all minor civil works required, bolts, clamps etc as required for istallation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbocharger. Exhaust pipe height shall be 3m more than the top of any adjacent building withing 10m radius of the exhaust.
110mm dia Supply
10
-
-
-do- Labour
10
-
-
LT CABLE SUPPLY
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx240sq.mm Al Cable
20
-
-
-do- 3.5cx95sq.mm Al Cable
25
-
-
LT CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
Above 35 sq. mm and upto 95 sq. mm
15
-
-
END TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5cx240sq.mm Al Cable
4
-
-
-do-3.5cx95sq.mm Al Cable
2
-
-
CONTROL CABLES
Supply and laying of XLPE insulated screened stranded copper cable, strictly conforming to IS:1554 (part I) 1964 of the following sizes for control directly in ground / in seperate cable trays with suitable clamps(distance between clamps not to exceed 60cm).
12x2.5 sqmm Cu cable Supply & Labour
30
-
-
-do- 2x2.5 sqmm Cu cable Supply & labour
30
-
-
EARTHING Supply, installation and tesing of 1200mmx1200mmx12mm CI plate electrode earth station conforming to IS:3043-1987 / NEC / IEE complete with brick masonry chamber, CI cover, CI frame, GI watering pipe of 50 mm dia with funnel having 20G GI wire mesh etc. The CI cover frame/ chamber shall be of 1000mm x 500mm x 600mm size. CI manhole cover with frame shall be painted with bitumastic paint, identification of earthpit with yellow paint below the chamber cover, mixtures of charcoal & common salt around electrode including digging of pit up to permanent moisture level but not less than 3 metre depth and back filling. ( value of earth resistance should be less than 1 ohm )
Supply
3
-
-
-do- Installation & testing
3
-
-
Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling ,including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 25x3mm Cu strips tinned at the point of contact
Supply
60
-
-
-do- Installation & testing
60
-
-
Evaluation Notes How It Works ?