Provision Of Admin Cum Training Block And Ancillary Facilities At Ins Mandovi

Are you looking for Materials and Services for this tender?
We will help YOU to find the right partner for your needs for FREE!
BOQ Items
... more
SCH 'A' PART-I "BUILDINGS & STRUCTURES" Total of Sch-'A' Part-I B/F to BOQ(Schedule ‘A’) Serial Page No. 42

1

-

-100

... more
SCH 'A' PART- II "SITE CLEARANCE, EXCAVATION & EARTH WORK. Total of Sch "A" Part-II B/F to BOQ at Sl page No 44

1

-

-100

... more
SCH 'A' PART-III "INTERNAL WATER SUPPLY" Total of Sch "A" Part-III B/F to BOQ at Sl page No 45

1

-

-100

... more
SCH 'A' PART-IV "INTERNAL ELECTRIFICATION" Total of Sch "A" Part-IV B/F to BOQ (Schedule 'A') on Serial Page No 48

1

-

-99

... more
SCH 'A' PART-V "ROAD/ HARDSTANDING/ CULVERTS" Total of Sch "A" Part-V B/F to BOQ on Serial Page No 50

1

-

-100

... more
SCH 'A' PART-VI "RETAINING WALL" Total of Sch "A" Part-VI B/F to BOQ (Schedule 'A') on Serial Page No 51

1

-

-100

... more
SCH 'A' PART- VII "AREA DRAINAGE" Total of Sch "A" Part-VIl B/F to BOQ (Schedule 'A') on Serial Page No 52

1

-

-100

... more
SCH 'A' PART-VIII "SEWAGE DISPOSAL" Total of Sch "A" Part-VIII B/F to BOQ (Schedule 'A') on Serial Page No 53

1

-

-100

... more
SCH 'A' PART-IX "LIGHTIENING PROTECTION" Total of Sch "A" Part-XI B/F to BOQ (Schedule 'A') on Serial Page No 55

1

-

-100

... more
SCH 'A' PART-X "FIRE FIGHTING" Total of Sch "A" Part-X B/F to BOQ (Sch 'A') on Serial Page No 59

1

-

-100

... more
SCH 'A' PART-XI "LIFT" Total of Sch "A" Part-XI B/F to BOQ (Schedule 'A') on Serial Page No 60

1

-

-100

... more
SCH 'A' PART-XII "DG SET" Total of Sch "A" Part-XII B/F to BOQ (Schedule 'A') on Serial Page No 61

1

-

-100

... more
SCH 'A' PART-XIII "EXTERNAL WATER SUPPLY" Total of Sch "A" Part-XIII B/F to BOQ on Serial Page No 63

1

-

-100

... more
SCH 'A' PART-XIV "EXTERNAL ELECTRIFICATION" Total of Sch "A" Part-XIV B/F to BOQ (Sch 'A') on Serial Page No 71

1

-

-100

... more
SCH 'A' PART-XV "RAIN WATER HARVESTING TANK" Total of Sch "A" Part-XV B/F to BOQ (Schedule 'A') on Serial Page No 72

1

-

-100

... more
SCH 'A' PART-XVI "TELEPHONE CONDUIT" Total of Sch "A" Part-XVI B/F to BOQ (Schedule 'A') on Serial Page No 73

1

-

-100

... more
SCH 'A' PART-XVII "AIR CONDITIONING" Total of Sch "A" Part-XVII B/F to BOQ (Sch 'A') on Serial Page No 77

1

-

-100

... more
SCH 'A' PART-XVIII "DEMOLITION" Total of Sch "A" Part-XVIII B/F to BOQ (Schedule 'A') on Serial Page No 80

1

-

-100

... more
"SOLAR PANNELS"

-

-

-

... more
SCH 'A' PART- XIX" MISCELLANEOUS ITEMS"

-

-

-

... more
"INTERNAL WATER SUPPLY"

-

-

-

... more
S&F of continental 2way bore bib taps (wall mount installation type) of brass,knob controlled,with chrome finish Make - Jaquar Model No Con-041KN.

49

-

-

... more
S&F Angular stop cock quarter turn(wall mount) with 1/2 inch hole diameter made of brass Make - Jaquar Model No ARI-CHR-39053.

135

-

-

... more
S&F for Stainless steel concealed stop cock, Regular body with adjustable wall flange, size 1/2inch dia, Make - Jaquar Model no CON-CHR-083KN.

30

-

-

... more
S& F overhead shower round shape single flow (ABS body crome plated with gray face plate) with rubit cleaning system Make - Jaquar Model No OHS-18736

9

-

-

... more
** S&F Florentine Pillar cock with extended liver(medi series) of brass, knob controlled, Make - Jaquar Model No. CHR -031

74

-

-

... more
S&F Health faucet (ABS body) with 01 meter long PVC tube & wall hook. Make - Jaquar Model No ALD-CHR- 583 or equivalent in Crab Tree/Kohler brand.

49

-

-

... more
S&F PVC connections 1m long of size 1/2 inch with end fiiting brass(drinking water pipe) jaquar brand.

22

-

-

... more
S&F Brass Urinal flush valve of 1/2 inch diameter (installation type :wall mount) jaguar model-snr-chr-51097

49

-

-

... more
S&F jaguar plastic concealed cistern tank with kit(item part no: JCS -WHT-2400S, Primary material : Plastic,Capaciy: 2x3)

49

-

-

... more
** S&F Brass LONG NECK BIB TAP, handle controlled,wall mount installation type, Make - Jaquar Model No. CON -021KN

6

-

-

... more
S&f Mixerof brass has a long pipe to connect shower. jaguar model-CON-273KNUPR

7

-

-

... more
"INTERNAL ELECTRIFICATION"

-

-

-

... more
S &F Lamp holder insulated body with back plate and Including LED lamp 9 watt for angle holder all as per specified

52

-

-

... more
S & F LED light fittings decorative 36/34 Watt Recess/surface mounting type extruded metal/aluminium body, and electronic LED driver, connector block ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size and mounting clamps etc. Make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

1086

-

-

... more
S & F LED light fittings decorative 36/34 Watt surface mounting type extruded metal/aluminium body, and electronic LED driver, connector block ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size and mounting clamps etc. Make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

2

-

-

... more
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x18/20 Watt ,4 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make-WIPRO /HAVELLS /JAQUAR /PHILLIPS

210

-

-

... more
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x10 Watt ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

6

-

-

... more
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x18/20 Watt ,4 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make-WIPRO /HAVELLS /JAQUAR /PHILLIPS

210

-

-

... more
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x10 Watt ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

6

-

-

... more
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x8/9 Watt ( for mirror light) ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

27

-

-

... more
S & F LED Security/Street light fittings 15 Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc. Make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

22

-

-

... more
Fabricate,supply & fix GI pipe bracket 25mm dia- 0.9m long & 2 set of clamps made out of 30x5mm ms flat & fixed with anchor bolt suitable for 15w ssecurity light fitting

22

-

-

... more
MCCB DB VERTICAL TYPE suitable for 250 amps MCCB as incommer made of sheet steel , powder painted with NUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 4 way Double door , L&T CAT NO-DBVTH004DD/ LEGRAND / schneider/ ABB ( main DB for

3

-

-

... more
MCCB DB VERTICAL TYPE , suitable for 125 amps MCCB as incommer,made of sheet steel , powder painted with NUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 4 way Double door , L&T CAT NO-DBVTL004DD/ LEGRAND CAT NO-607913/ / schneider/ ABB

14

-

-

... more
MCB TP 415 Volts, 'C' series, breaking capacity 10 KA of rating 100 Amps

12

-

-

... more
MCB TP 415 Volts, 'C' series, breaking capacity 10 KA of rating 63Amps

9

-

-

... more
MCB TPN 415 Volts, 'C' series, breaking capacity 10 KA of rating 63Amps

9

-

-

... more
MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 40 Amps

5

-

-

... more
MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 6-32Amps

24

-

-

... more
MCB SP 40 Amps 'C' series, breaking capacity 10 KA of rating

5

-

-

... more
MCB SP 6-32 Amps 'C' series, breaking capacity 10 KA of rating

350

-

-

... more
MCCB 63 A 25 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98603OOOO /Legrand cat no-420013/schneider cat no-LV510315

5

-

-

... more
MCCB TPN 100 Amps , 415Volts, 25KA ,4 POLE L&T CAT NO-CM91198OOLO/ LEGRAND CAT NO-420055 / / schneider/ ABB

9

-

-

... more
MCCB TPN 250 Amps , 415Volts, 25KA ,4 POLE L&T CAT NO-CM90634OOPO/ LEGRAND / schneider/ ABB

3

-

-

... more
S&F Exhaust fan heavy duty of size 230 mm sweep metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan. Make Make , - Havells/Crompton Greaves/Bajaj

27

-

-

... more
S&F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed. ( for Tech Building & Adm Building ) -Make : Crompton Greaves/ Bajaj/Orient

403

-

-

... more
Supply & fixing wall mounted fan 450 mm sweep high speed, thermally protected motor, heavy duty gear box, 90 degree oscillation for wide coverage conforming to IS-2997-1964 all as specified and directed by Engineer-in-Charge. , Make-Havells/Crompton Greaves/Bajaj/Orient

24

-

-

... more
M&L for non metalic PVC rigid conduit of size 25 mm dia including bend ,tee,elbow reducer fixing accessorries

1000

-

-

... more
M&L for PVC junction box up to 4 Way

100

-

-

... more
M&L for telephone jak with Modular metal flushed including flushed Box cover plate Box for 2 Way module

100

-

-

... more
M&L for TV SOCKET with Modular metal flushed including flushed Box cover plate Box for 2 Way module

10

-

-

... more
S &F enclosure flush mounting type SUITABLE FOR MCB TPN 2 WAY with MCB Spn 6 Amps ( Aviation light )

2

-

-

... more
AVIATION LIGHT type,LED TYPE IP 65 protection cat no -SLE AL 54 -LDR-SEN IP65 of SURYA /BAJAJ cat no -BGAV 302 LED/PHILIPS

2

-

-

... more
Hand Dryer

27

-

-

... more
S &F modular AC Box sheet metal with socket 3 pin, suitable for 20 Amps flush type universal including 20 amp c series MCB protected.

100

-

-

... more
"ROAD"

-

-

-

... more
S&F cat eyes

174

-

-

... more
M&L 80mm thick grass concrete paver complete

1250

-

-

... more
"FIRE FIGHTINING"

-

-

-

... more
S & F Gun metal one way fire hydrant valve of size 63 mm dia flange type complete with instantaneous coupling complete.

11

-

-

... more
Construction of brick masonary valve chamber of size 900x900x750 mm (internal diamension) above ground level 40 mm suitable for 100 mm dia sluice valve, 40 cm thick foundation using FCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) over 15 cm thick hardcore, 23 cm thick brick wall butts in cement and sand motor 1:4, 15 cm thick internal and external plaster including top floor in cement and sand motor 1:3, finished even and smooth, without using extra cement, 10 mm thick mild steel plate cover on 50 mm x 50 mm x 6 mm MS angle iron frame embeded in PCC 1:2:4 type 6-1 (using 20 mm graded stone aggregate) coping having rectangular hinged opening of size with locking arrangement & handle made out of 25 cm dia MS round bar, hold fast etc, applying one coats od red oxide primer and two coats of synthetic enemelted paint to all steel surfaces and earth work in any type of soil including disposal of surplus soil to a distance not ex 50 mtr complete.

6

-

-

... more
SITC LT panel, indoor type cubical board, made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 43 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators comprising of the following:- (a) MCCB 4 pole 160 A, incorner, 415V, 50Hz, 25 kA - 01 No. (b) MCCB TPN 100A, outgoing, 415V, 50Hz. 10 kA - 02 No.( for main fire pump) (c) MCB TPN 16A, 415V - 2 No. ( for Jockey Pump) (d) MCB SP 6-32A, 10kA - 2 Nos. (e) star delta starter 75 HP-2 Nos.( for main fire pump) (f) DOL starter 5 HP - 2 No.( for Jockey Pump) (g) 250 A rated copper bus bar with colour coded heat shrinkable sleeve (h) Ammeter,Digital type, with suitable CTs and selector switch- 02 sets (i) Voltmeter (0 - 500 V) - 2 Nos. (j)LED R-Y-B phase indicating lamp- 02 set (k) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. complete wiring of panel & Instailation all as specified.

1

-

-

... more
supply and fix flowswitch (Switzer/Oanfoss) on pipes with welded socket including stainless steel paddle suitable to pipe dia. 50 mm testing and commissioning etc. complete.

3

-

-

... more
supply and fix suitable Air release single valve (Zoloto/ZIP) of 150mm dia including. necessary support and painting with two coats of enamel paint over a coat of primer etc. complete, for wet riser termination.

6

-

-

... more
Supply & fix alarm check valve for sprinkler system size 150mm dia ,cast iron body complete all as specified.MAKE : TYCO TYPE

1

-

-

... more
Supply &fix control valve for sprinkler system size 100mm dia ,flanged end B16.5 class complete all as specified.MAKE: FLANGED END AS PER ASME B:16.5, MODEL NO: DMCV 01

6

-

-

... more
Supply &fix control valve for sprinkler system size 50mm dia ,flanged end B16.5 class complete all as specified.MAKE: FLANGED END AS PER ASME B:16.5, MODEL NO: DMCV 01

6

-

-

... more
Fire Extinguisher water type 9 Ltr capacity. Ceasefire 9Ltr Water type Fire Extinguisher, Stored pressure Type, Pressure Gauge,Gross Weight 14.6 Kg, empty Weight 5.6 Kg, Can Height 611MM, Diameter 175MM,Discharge Time less than 120 Secs, Controllable discharge mechanisum, Range minimum 6 mtrs applicable on class a fire a rating 13A, can construction : deep drawn & CO2 Mig welded, valve construction : Forging & machining internal coating of Can : Epoxy p[owder coating, External coating of Can : Epoxy polyster powder coating sheet meta thickness : 2.0MM, ISI and EN Approved, Hileum Leak Detection tested, 1 year warranty. Make Cease Fire Water-9 Ltr Stored Pressure - 1CO02CF.

4

-

-

... more
Fire Extinguisher DryChemical powder[ABC] type 9 Kg capacity. Ceasefire 9kg fire extinguisher mono Ammonium phosphate powder 50, stored pressure type, pressure Guage, Gross weight 15.6 Kg, empty weight 5.6 KG, can height 611 MM, Diameter 175 MM, discharge time less than 18 secs, controllable discharge mechanism, Range minimum 4 mtrs, applicable on class A,B,C & electrically started fire A rating 27A, B rating 558, can construction deep down & CO2 Mig welded, Valve construction : Forging & Machining internal coating of can : Epoxy powder coating external coating of Can : Epoxy polyster powder coating, Sheet metal thickness : 1.80MM, ISI and EN approved, 5 years warranty.Make Cease Fire ABC Powder Map 10 5Kg - 1AB06CF

12

-

-

... more
Fire Extinguisher Carbin Dioxide type of 4.5Kg capacity.Ceasefire 4.5kg CO2 Gas typre fire Extinguisher, Trolly mounted, Easy weight management Used Unused Mechanism Squeeze Grip, Gross weight 9.1kg empty weight 14.6kg, Can height 857MM, Diameter 140MM, Discharge timeless than 10secs controllable discharge mechanism Applicable on class B&C fire, B rating 21B, Can Construction : Hot Spinning/ Forging, Valve Construction : Forging & Machining, Internal coating of Can : Not Applicable, External Coating of Can : Spray painting sheet metal thickness 4.5MM, ISI Approved 1 year warranty. Make Cease Fire CO2-4.5Kg - Squeeze Grip - 1CO11CF

19

-

-

... more
Fire Extinguisher Carbin Dioxide type of 3kg capacity.Ceasefire 3 kg CO2 Gas typre fire Extinguisher, SQUEEZE TYPE, Easy weight management Used Unused Mechanism Squeeze Grip, Gross weight 9.1kg empty weight 14.6kg, Can height 857MM, Diameter 140MM, Discharge timeless than 10secs controllable discharge mechanism Applicable on class B&C fire, B rating 21B, Can Construction : Hot Spinning/ Forging, Valve Construction : Forging & Machining, Internal coating of Can : Not Applicable, External Coating of Can : Spray painting sheet metal thickness 4.5MM, ISI Approved 1 year warranty. Make Cease Fire CO2-4.5Kg - Squeeze Grip - 1CO11CF

6

-

-

... more
Fire Extinguisher mechanical Foam type trolly mouted of 9 Liters capacity.Ceasefire 9litrs fire Extinguisher AFFF Foam type , External Cartridge type, Pressure Guage Gross weight 14.6 Kg , empty weight 5.6 Kg, Can height 611 MM, Diameter 175 MM, Discharge timeless than 60 Secs controllable discharge mechanism, Minimum 6 Mtrs, Applicable on Class A,B,Can construction deep deawn & CO2 Mig welded Valve Constyruction : Forging & Machining, Internal coating of can : Epoxy powder coating, External coating of can : Epoxy poyster powder coating sheet metal thickness 2.0MM ,1 year warranty. Make Cease Fire AFFF - Foam 9 Ltr - 1FM02CF

2

-

-

... more
Fire Extinguisher dry chemical powder trolly moutnted of 9Kg capacity. Ceasefire 50Kg Fire Extinguisher MONO Ammonium Phosphate powder 90, Gross weight 125Kg, Empty weight 75KG, Can height 1190MM, Diameter Discharge Time leass than 50 Secs controllable discharge mechanism range minimum 8Mtrs, Applicable on class A,B,C & electrically started fire, Can Construction deep drawn and CO2 Mig welded valve construction Forging & machining internal coating of Can, Epoxy powder coating External coating of Can Epoxy Polyster powder coating sheet metal thickness 5.00MM 1 year warranty. Make Cease Fire.Make Cease Fire ABC Powder map 90 50Kg - 1MP50CF

12

-

-

... more
Fire Extinguisher clean agent of 4Kg capacity. Ceasefire 4Kg Fire Extinguisher MONO Ammonium Phosphate powder 90, Gross weight 125Kg, Empty weight 75KG, Can height 1190MM, Diameter Discharge Time leass than 50 Secs controllable discharge mechanism range minimum 8Mtrs, Applicable on class A,B,C & electrically started fire, Can Construction deep drawn and CO2 Mig welded valve construction Forging & machining internal coating of Can, Epoxy powder coating External coating of Can Epoxy Polyster powder coating sheet metal thickness 5.00MM 1 year warranty. Make Cease Fire.Make Cease Fire ABC Powder map 90 50Kg - 1MP50CF

19

-

-

... more
FIRE Bucket

4

-

-

... more
Supply &Fix First aid Hose reel with shut OFF valve 30mtr long and 20mm dia

13

-

-

... more
LT panel, indoor type cubical board 100A, made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 43 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators comprising of the following:- (a) MCB 4 pole 32 A, incorner, 415V, 50Hz, 10 kA - 01 No. (b) MCB TP 16A, outgoing, 415V, 50Hz. 10 kA - 03No.( for tarace pump). (e) star delta starter 10 HP-3Nos.( for tarace pump) (g) 50 A rated copper bus bar with colour coded heat shrinkable sleeve (h) Ammeter,Digital type, with suitable CTs and selector switch- 03sets (i) Voltmeter (0 - 500 V) - 3 Nos. (j)LED R-Y-B phase indicating lamp- 03set (k) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. complete wiring of panel & Instailation all as specified.

1

-

-

... more
Supply and fix CI foot valve, flanged end and drilled of size 150 mm dia ISI MARKED , FLANGED TYPE

3

-

-

... more
Supply and fix CI foot valve, flanged end and drilled of size 100 mm dia ISI MARKED, FLANGED TYPE

2

-

-

... more
"DG SET"

-

-

-

... more
(a) Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC to give an out put of 160 KVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500RPM, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, control panel & other accessories etc and comprising of following.

1

-

-

... more
(b)Diesel Engine: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories:. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete. Make: Kirloskar/ashok leyland/cummins

-

-

-

... more
(a) Radiator with blower fan or heat exchanger with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator.

-

-

-

... more
(n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet o 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class STIC 1" /1.5" /2" dia - 01 lot (s) Self starter 12 volts DC. (t) Electric operated electronic governor. (u) Fuel injection pump.

-

-

-

... more
(v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) 24V Battery. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (w) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Overspeed stop

-

-

-

... more
(x) Base frame: Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads. (y) Battery:-24 volts(02x12vBattery) DC, 180AH, maintenance free battery conforming to IS:14257 with leads & terminals (Make- Excide/Amron). (z) Fuel tank: 10 hrs. full load diesel storage capacity fuel tank with mounting brackets factory made of 5mm thick HR/MS sheet with level indicator fuel inlet, fuel outlet, air vent, drain plug, in let arrangement for diesel filling fro exterior canopy (without opening its panel) etc complete all as specified and directed.

-

-

-

... more
(c) Alternator: Suitable rated 40 KVA, 0.8 pf , 415 volts, 3 phase, 4 wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof , insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS: 5000 / IS: 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364(part-1) Make: stampford/crompten/kirloskar

-

-

-

... more
(d) Acoustic Enclosure:- M & L for acoustic enclosure for the above 40 KVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audible frequencies as per guide of Central Pollution Control Board and size 3490 x 1340 x 1885mm and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified :-

-

-

-

... more
(i) Sound insulation : 100mm thick Rock wool (Density 64 Kg/Cum). (ii) Outer body : 1.6mm thick CRCA (iii) Door : 1.6mm thick CRCA (iv) Base frame : ISMC 300 (v) Inside illumination : 1 No.- 1 x 18 watt FTL fitting of make Phillips/ Bajaj/ Crompton.

-

-

-

... more
(e) AMF Control panel:- Factory fabricated cubicle type, free standing, floor mounted, indoor type, IP-52, AMF control panel, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0mm thick CRCA sheet including two coats of powder coated paint over a coat of red oxide primer etc and comprising of following:

-

-

-

... more
(f) AMF control circuit with 4 pole MCCB 63 Amps - 2 nos, with ultimate breaking capacity Icu-36 KA at 415 volts and microprocessor release conforming to IEC 60947 Part-I with breaking capacity Ics=Icu at 415 volts , thermal overload setting 70% to 100%, short circuit setting 5 to 10 times-02 Nos. for main supply & DG set supply with HRC back up fuse complete with all DC control relays/ Line voltage monitor (LVM) as per OEM specifications incorporating motorised stored energy operating Engine start, stop, three attempt starting facility and failure to start etc.

-

-

-

... more
(g) Digital load manager : Three phase 4 wire indicating V,I,PF, KVA, KW, F of Enercon make with serial communication port model No.EM6400 with class 1.0 accuracy meter or equivalent make suitable rating of CT per phase- one No. (iii) Indication lamp R, Y, B with 3 Nos. of 2A HRC fuses-10 sets. (iv) Bottom gland plate for incoming and outgoing cables. (v) Circuit diagram plate.

-

-

-

... more
(h) Civil works:- All civil works related to foundation, installation of panel and equipment & depth of foundation shall be minimum 300mm with ant vibration pads, or as recommended by manufacturers. Cable from DG set to AMF panel, AMF panel to main panel will be measured under relevant schedule. Note:-The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department.

-

-

-

... more
Supply, Installation, test and Commissioning CPRI approved factory fabricated, indoor type, LT Pannel Board made out of 3.00 mm thick CRCA Sheet with projected globe roof for rain water protection dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Test-ing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -LEGRAND/L&T/HEGGER/SCHNEIDER (location - near transformer)

1

-

-

... more
(a) MCCB 400 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94105OOR1OG /Legrand cat no-025538/schneider cat no-LV540309 - 1 no INCOMING:-

-

-

-

... more
OUTGOINGS:-

-

-

-

... more
(a) MCCB TP 160 Amps , 415Volts, 35KA ,3 POLE, L&T CAT NO-CM92008OOM1OG/ LEGRAND CAT NO-420087 / equivalent of ABB- 1 NO (O/G) for fire fighting main panel

-

-

-

... more
(b) MCCB 250 A 35 KA, 3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no-CM92009OOP1OG /Legrand cat no-420239/schneider cat no-LV525333 -02 No ( for DG main DB TPN 4 way.)

-

-

-

... more
(c) MCCB TP 40 Amps , 415Volts, 35KA ,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98602OOOO /Legrand cat no-420013/schneider cat no-LV510316 - 8 nos (for main water supply pump panel 7.5 hp , Lift 4 nos , building pump panel 5 hp & st. light)

-

-

-

... more
(d) Aluminum TPN bus bar 600 Amps - 01 Set

-

-

-

... more
( e ) Ammeter Class-1,digital pannal mounting type 96mmx96mm L&T cat no WDS301FCA00 including CT .600X5 Amps 3 nos & selector switch

-

-

-

... more
(f) Voltmeter Class-1, digital pannal mounting type 96mmx96mm L&T CAT NO.WDS301FEV00 & selector switch

-

-

-

... more
(g) LED TYPE indicator lamp 1 set (set of three for R,Y,B)

-

-

-

... more
(h) Astronomical, Multifunctional digital time swithces cat no 004767 of legrand or equivalent of L & T cat no- T2 DD T7/MDS/GIC - 1 no

-

-

-

... more
(j )Power contactor ML-3 , 3 pole rating not less than 40 A with 230 coil make L&T/SEIMENS - 1 no.

-

-

-

... more
(k ) mcb spn 6 amps-1 no.

-

-

-

... more
"EXTERNAL WATER SUPPLY"

-

-

-

... more
Supply install test and commissiong of centrifugal pump set , electric driven complete with all accessories suitable for pumping water 550 LPM discharge at 30 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building)

2

-

-

... more
Supply install test and commissiong of centrifugal pump set , electric driven complete with all accessories suitable for pumping water 550LPM discharge at 120 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete ,complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for UGsump & fire sump)

2

-

-

... more
Supply install test and commissiong of monoblock pump set , electric driven complete with all accessories suitable for pumping water 90LPM discharge at 30 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete ,complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( rain water harvesting)

2

-

-

... more
Note for item no 1 to 3 - Energy Efficient Motors-Motors shall comply with following a. All permanently wired poly phase motors of 0.375kW or more serving the building and expected to operate more than 1500 hours per year and all permanently wired poly phase motors of 50kW or more serving the building and expected to operate more than 500 hours per year shall have a minimum acceptable nominal full load motor efficiency not less than IS 12615 for energy efficient motors b. Motors of horsepower differing from those listed in the table shall have efficiency greater than that of the next listed kW motor 0.64% c. Motor horse power rating shall not exceed 20% of the calculated maximum load being served,d. Motor nameplate shall list the nominal full- load motor efficiencies and the full load power factor e. Motor users should insist on proper rewinding practices for any rewound motors. If the proper rewinding practice can not be assured, the damaged motor should be replaced with a new, efficient one rather than suffer the significant efficiency penalty associated with typical rewind practices f. Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a motor is rewound, Appropriate measures shall be taken so that the core characteristics of the motor is not lost due to thermal and mechanical stress during removal of damaged parts after rewinding a new efficiency test shall be performed and a similar record shall be maintained

-

-

-

... more
Taking down CI pipe including fitting/fixture & connection including cleaning CI iron pipes with spigot and socket ends centrifugally cast, any class, in any length laid in trenches of size 200 mm dia complete all as specified and directed

40

-

-

... more
Taking down CI pipe including fitting/fixture & connection including cleaning CI iron pipes with spigot and socket ends centrifugally cast, any class, in any length laid in trenches of size 150 mm dia complete all as specified and directed

50

-

-

... more
Taking down CI/GI pipe including fitting/fixture & connection including cleaning CI/GI iron pipes any class/GRADE, in any length laid in trenches of size 100 mm dia complete all as specified and directed

50

-

-

... more
Taking down CI/GI pipe including fitting/fixture & connection including cleaning CI/GI iron pipes any class/GRADE, in any length laid in trenches of size 80 mm dia complete all as specified and directed

30

-

-

... more
Supply and laying Ductile iron pipes with spigot and socket ends centrifugally cast, Class K-7, in any length laid in trenches of size 200 mm dia Incuding rubbur Tytan joint

3500

-

-

... more
Supply and fix CI sluice valve Kirloskar/Upadhyay/L&T MAKE both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed of sizes :-200 mm dia

1

-

-

... more
Supply and laid spigot/flanged/ socketed DI fittings. Such as bends (any type radius and angle), tapers, tees, collars & tail piece socket/flanged/spigot etc of size 80mm to 300mm dia.

500

-

-

... more
Supply and fix CI sluice valve Kirloskar/Upadhyay/L&T MAKE both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed of sizes :-100 mm dia

1

-

-

... more
Supply and fix CI sluice valve Kirloskar/Upadhyay/L&T MAKE both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed of sizes :-80 mm dia

3

-

-

... more
Supply and fix CI double end flanged and drilled non return valve of size 200 mm dia PN-1.6 ISI MARKED Kirloskar/Upadhyay/L&T MAKE

1

-

-

... more
Supply and fix gunmetal non return valve of size 50 mm PN-1.6 dia ISI MARKED Kirloskar/Upadhyay/L&T MAKE

2

-

-

... more
Supply and fix CI foot valve, flanged end and drilled of size 100 mm dia ISI MARKED

4

-

-

... more
Supply and fix CI foot valve, flanged end and drilled of size 50 mm dia ISI MARKED

2

-

-

... more
Supply and fix CI 'Y ' Strainer screwed end or flanged type conforming to IS, size 100 mm dia.

4

-

-

... more
Supply and fix CI 'Y ' Strainer screwed end or flanged type conforming to IS, size 50 mm dia.

2

-

-

... more
Construction of brick masonry valve chamber of size 1200x 1200x1200 mm (internal dia) suitable for 150 mm dia sluice valve with necessary earth work excavation plain cement concrete 1:4:8 using 40 mm graded stone aggregate 75 mm thick in cement mortar 1:6 15 mm thick plastering 1:6 inter nally including flooring and externally rep to 15 mm below ground level plain cement concrete 1:4:8 type B1 using 20 mm graded stone aggregate in coping MS sheet cover made out of 3 mm thick MS sheet flat iron frame and bracing with locking arrangement applying two coat of synthetic enamel paint including dismantling removing the existing damage chamber completely removal of debris to a distance not exce eding 50 mtr distance depositing where as directed by Engr –

6

-

-

... more
Supply and fix Cast Iron Air Valves with single air Outlets, conforming to IS 14845 for Cast Iron Water supply mains of size 200 mm dia.

4

-

-

... more
EXTERNAL ELETRIFICATION:

-

-

-

... more
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT panel board ,made out of 2 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -MDS/LEGRAND/L&T/HEGGER ( main water supply pump )

1

-

-

... more
INCOMING:-

-

-

-

... more
(a) Incoming MCCB 200 A 25 KA, 4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98605OOOO /Legrand cat no-420055/schneider cat no-LV510317-01 No

-

-

-

... more
OUTGOINGS:-

-

-

-

... more
(a) MCCB TP 63 Amps, 50 Hz, 415 Volts, 25 KA -02 Nos (For main pump)

-

-

-

... more
(b)Automatic Starter delta starter for 35 HP pump -02 Nos( For main pump)

-

-

-

... more
(c) MCCB TP 100 Amps, 50 Hz, 415 Volts, 25 KA -01 Nos (For Exsisting pump pannel)

-

-

-

... more
( d ) Ammeter Class-1,digital pannal mounting type 96mmx96mm L&T cat no WDS301FCA00 including CT 200X5 Amps 3 nos & selector switch

-

-

-

... more
(e) Voltmeter Class-1, digital pannal mounting type 96mmx96mm L&T CAT NO.WDS301FEV00 & selector switch

-

-

-

... more
(f) LED TYPE indicator lamp 1 set (set of three for R,Y,B)

-

-

-

... more
(g) Single phasing preventer -02 No

-

-

-

... more
(h) MCCB TP 32 Amps, 50 Hz, 415 Volts, 25 KA -02 Nos (For capacitor & light load)

-

-

-

... more
(j) power capacitor bank , Utra heavy duty, BOX type Oil filled, LTXL OF L&T or equvalant of APCOS/siemens/momaya suitable for 480V,12.5 KVAR- 1 no

-

-

-

... more
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT panel board ,made out of 2 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -MDS/LEGRAND/L&T/HEGGER ( For building pump )

1

-

-

... more
INCOMING:-

-

-

-

... more
(a) Incoming MCCB 63 A 25 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98603OOOO /Legrand cat no-420013/schneider cat no-LV510315-01 No

-

-

-

... more
OUTGOINGS:-

-

-

-

... more
(b) Outgoing MCB, TP 32 Amp, 25 ka, 415 volts -02 Nos

-

-

-

... more
(c)Automatic Starter delta starter for 7.5 HP pump -02 Nos( For main pump of building )

-

-

-

... more
(d) single Phase Preventer -2 nos

-

-

-

... more
( e ) Ammeter Class-1,digital pannal mounting type 96mmx96mm L&T cat no WDS301FCA00 including CT 60X5 Amps 3 nos & selector switch

-

-

-

... more
(f) Voltmeter Class-1, digital pannal mounting type 96mmx96mm L&T CAT NO.WDS301FEV00 & selector switch

-

-

-

... more
(g) LED TYPE indicator lamp 1 set (set of three for R,Y,B)

-

-

-

... more
(h) msb spn 6-32 amps-02 No

-

-

-

... more
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT FEEDER PILLAR BOX ,made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -MDS/LEGRAND/L&T/HEGGER ( for Rain water harvesting and STP)

2

-

-

... more
INCOMING:-

-

-

-

... more
(a) Incoming MCCB 32 A 25 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T /Legrand /schneider-01 No

-

-

-

... more
OUTGOINGS:-

-

-

-

... more
(b) Outgoing MCB, TP 16 Amp, 415 volts -02 Nos ( for Rain water harvesting)

-

-

-

... more
(C) DOL starter suitanble for 5 HP motor- 2 nos

-

-

-

... more
(d) single Phase Preventer -2 nos

-

-

-

... more
( e ) Ammeter Class-1,digital pannal mounting type 96mmx96mm L&T cat no WDS301FCA00 including CT 60X5 Amps 3 nos & selector switch

-

-

-

... more
(f) Voltmeter Class-1, digital pannal mounting type 96mmx96mm L&T CAT NO.WDS301FEV00 & selector switch

-

-

-

... more
(g) LED TYPE indicator lamp 1 set (set of three for R,Y,B)

-

-

-

... more
(g) msb spn 6-32 amps-02 No

-

-

-

... more
Taking down of faulty HT under ground cable of size upto 120 sqmm from trenches /pole/wall etc for detecting fault including repair and jointing at site including relaying at the same location complete.Note- Excavation /earth work and cable jointing &jointing kit shall be measured and paid for separately under relevent item of schedule.

350

-

-

... more
Taking down unservisable U/G LT cable from trenches, wall, floor etc and removing to store for safe custody Note:- Excavation for taking will not paid for separatly, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables

150

-

-

... more
Taking up of under ground HT Cable of any size along with protection cover/ bricks and removing from site all as directed by Engr-in-Charge.

350

-

-

... more
Disconnecting the existing HT/LT cable from transformer terminal and taking down Transformer of 50KVA TO 500 KVA capacity from position and shift to new location on pole/ PCC platform including reconnection of existing HT/LT cable connection incl transportation distance not Exc 2500 meters of capacity up to 500 KVA complete all as specified and directed

1

-

-

... more
Taking down partly unserviceable / unserviceable ,SECURITY/STREET/GATE/FLOOD light fittings from pole/tower for necessary repair , all as specified and directed Engr-in-Charge

30

-

-

... more
supply & fix battary bank with AGM VRLA batteris 2 volt, 100 AH for operation of VCB including connectors

17

-

-

... more
Battary charger 0- 50 amps floating type

1

-

-

... more
Supply, Installation, test and Commissioning CPRI approved factory fabricated, out door type, LT Pannel Board made out of 3.00 mm thick CRCA Sheet with projected globe roof for rain water protection dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Test-ing after Installation including complete all as specified and comprising of the following :–Make of MCCB/MCB -LEGRAND/L&T/HEGGER/SCHNEIDER (location - near transformer)

1

-

-

... more
INCOMING:-

-

-

-

... more
(a)Aircircuit breaker 1600 amps fixed type type ,4pole ,breaking capacity 50ka ,ICU=ICS=ICW for 1 sec of total selectivity ,Draw-out type ,EF version inbuilt 6 NO+6NC aux contact,door ceiling frame , manually & electrically operated complete with 240 v shunt trip coil ,closing coil & motor for electrical charging , C power S-1 RANGE ,confirming to IS/IEC 60947-2,microprocessor base relay ,high short time withstand capcity,100% neutralpole,self dignoistic microprocessor based with onload testing through test button with cover ,inbuilt thermal memory,protection relese conform to EMI/EMC standerd,breaker control through MODBUS potocall complete all as specified -1 NO FOR ( I/C)s per L&T MODEL NO-SR18G & CAT NO -SL96075 / LEGRAND MODEL NO-DMX 3 -N2500 & CAT NO - 0287 34 or equivalant of SCHNEIDER/ABB-

-

-

-

... more
OUTGOINGS:-

-

-

-

... more
(a)Aircircuit breaker 630 amps ,3 pole ,breaking capacity 50ka ,ICU=ICS=ICW for 1 sec of total selectivity ,Draw-out type ,EF version inbuilt 6 NO+6NC aux contact,door ceiling frame , manually & electrically operated complete with 240 v shunt trip coil ,closing coil & motor for electrical charging , C power S-1 RANGE ,confirming to IS/IEC 60947-2,microprocessor base relay ,high short time withstand capcity,100% neutralpole,self dignoistic microprocessor based with onload testing through test button with cover ,inbuilt thermal memory,protection relese conform to EMI/EMC standerd,breaker control through MODBUS potocall complete all as specified as per L&T MODEL NO-SR18G & CAT NO -SL96051 / LEGRAND MODEL NO-DMX 3 -N2500 & CAT NO -0287 20 or equivalant of SCHNEIDER/ABB-1 NO (O/G) For AC Plant

-

-

-

... more
(b) MCCB 800 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/schneider cat no-LV540310- 1 no APFC PANNAL (1)

-

-

-

... more
(d)MCCB 400 A 35 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no-CM98401OOROOG /Legrand cat no-4220 60/schneider cat no-LV540309 -2NO (O/G) For ( for AMF panel&TF)

-

-

-

... more
(c)MCCB 250 A 35 KA, 3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no-CM92009OOP1OG /Legrand cat no-420239/schneider cat no-LV525333 -03 No. (FF&SF bldg supply)

-

-

-

... more
(d) MCCB TP 16 Amps , 415Volts, 35KA ,3 POLE L&T CAT NO-CM92008OOM1OG/ LEGRAND CAT NO-420087 / equivalent of ABB- 4NO (O/G) & SPARE

-

-

-

... more
(e) MCCB TP 100 Amps , 415Volts, 35KA ,3 POLE L&T CAT NO-SL98653OOOO/ LEGRAND CAT NO-420086 / equivalent of ABB - 2 nos (O/G) bldg supplyFF& SPARE

-

-

-

... more
(m) Aluminum TPN bus bar 2000 Amps - 01 Set

-

-

-

... more
( n ) Ammeter Class-1,digital pannal mounting type 96mmx96mm L&T cat no WDS301FCA00 including CT 1600X5 Amps 3 nos & selector switch

-

-

-

... more
(o) Voltmeter Class-1, digital pannal mounting type 96mmx96mm L&T CAT NO.WDS301FEV00 & selector switch

-

-

-

... more
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure

30

-

-

... more
Supply and fix LED street light fitting 45 Watts complete with bracket made out of 40mm dia GI light grade tubing not less than 1.5mtr long bent to shape 120 deg including pole clamps (2no), clamp for fixing GI conduit pipe bracket made out of 50x6mm flat and nut bolts and 15mm GI LG for controle cable from top of SMC box to bottam of light fitting bracket, washers etc all as directed

30

-

-

... more
Area lighting LED 90/100 Watts, energy saving environmental friendly, long life exclusive innovatiive die cast aluminium IP 66 flood light with high power LED as light source suitable for high lighting architectural features or retail spaces Make : WIPRO /HAVELLS JETA linear/JAQUAR /PHILLIPS

20

-

-

... more
S & F LED Bolard light fittings 6 Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc. Make- WIPRO /HAVELLS /JAQUAR /PHILLIPS

24

-

-

... more
Supply & fix PVC junction box IP 65 Protection of size 0.200 x 0.250 x 0.115 complete with 1 Nos of MCB SP 2.5 Amps & 4 way industrial connector including Clamp made out of MS flat 30X5 mm, connection from junction box to street light fitting with three single core PVC insulated , PVC sheathed wire 2.5 Sqmm copper & PVC coduit 20 mm dia. Make of Box- SPELS BERG/RITTAL/HENSEL CAT NO K8350

74

-

-

... more
Supply and fix cable route indicator made of round CI disc embossed LT Cable, of size 16cm dia 6mm thick duly revited with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B1 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.

80

-

-

... more
Supply and fix cable route indicator made of round CI disc embossed HT Cable, of size 16cm dia 6mm thick duly revited with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B2 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.

125

-

-

... more
AVIATION LIGHT type,LED TYPE IP 65 protection cat no -SLE AL 54 -LDR-SEN IP65 of SURYA /BAJAJ cat no -BGAV 302 LED/PHILIPS

6

-

-

... more
S &F enclosure flush mounting type SUITABLE FOR MCB SPN 2 WAY with MCB Spn 6 Amps ( for Aviation light )

6

-

-

... more
Supply and fix electric rubber hand gloves 11 KV

2

-

-

... more
Disconnecting the existing HT/LT cable from Lt pannel of any size from position and shift to new location on PCC platform including reconnection of existing HT/LT cable connection incl transportation distance not Exc 2500 meters complete all as specified and directed

3

-

-

... more
Supply and fix LT bus duct air insulated type made out of 3mm thick CRCA sheet flanged type of suitable cross section with copper bus bars three phase and half neutral of 2000A capacity duly supported on DMC /FRP insulators including provision of suitable supports from ground for outdoor portion of bus duct with canopy &from roof for indoor portion of bus duct, painting the bus duct with two coats of synthetic enamelled paint over a coat of red oxide primer and connection with flexible laminated copper strips of same capacity at both transformer and LT panel complete all as directed and specified Makes : L&T/schneider/ABB

20

-

-

... more
Supply & Fix elecronic energy trivactor meter,suitable for 3 phase 4 wire CT operated ,temper proof,operated on 240v AC ,three phase, 5 amps to 10 amps, base mounting meter, backlit LCD display with user friendly legend, accuracy class-0.5, MD recording, revenue protection ( in case of wrong electric connection),capability to disply & communicate ( in case of absence of main supply), with optical port,deficiency metering with either phase/netral current, IP 51 protection, as per IS13779,, L&T model no- ER300P & Cat no-WR300BC5200 of L&T or equivalant of secure

2

-

-

... more
current trasformer (CT) 1600x 5 amps

3

-

-

... more
current trasformer (CT) 150x 5 amps

3

-

-

... more
Supply, installation, testing and commissioning of HT, automatic power factor correction (APFC) panel, factory made, weather, dust & vermin proof made out of 16 gauge CRCA steel sheet duly powder coated paint with metalised poly propylene (MPP) type capacitors bank, heavy duty of square cap capacitor 500kvar. The panel shall have copper bus bar of suitable size, 3 phase and with neutral and with the following:- (a) MCCB, TP, 800 Amps (adjustable type), 85KA – 01No (incoming) (b) Heavy duty Contactors suitable frequent operation having current limiting resistors suitable for capacitive switching of variable KVAR correction of superior specifications. (c) MCCB/MCBs 'C' curve for back up protection of capacity as required. (d) Microprocessor based intelligent APFC relay for controlling variable connection KVAR (e) Indication lamp RYB (LED type) with toggle switch – 03 Set (f) MPP type heavy duty capacitor bank consisting of suitable No of switching sequences, 3 phase, 415 volts suitable for 10% over voltage & 30% over current having loses less than 0.5 W /KVAR with discharge resistors. (g) Suitable Nos & rating of contractors as required. (h) Internal wiring of panel with stranded copper cable of suitable size. (i) The design of panel shall be got approvedfrom GE before fabrication

1

-

-

... more
Precasted RCC post of 150x150mm along with chamfer

17

-

-

... more
Precasted RCC post of 150x150mm at corner post

4

-

-

... more
Supply, erecting, installing, testing and commissioning of grid connecting Solar Photovoltaic power plant of 100 KWp capacity including solar grade copper cable upto UPS, array junction boxes ncluding mounting structure with singke axis self powered tracking system as per conditions prevailing at Goa comprising of following sub components / sub systems and meeting the specifications as given subsequently all as specified and directed by Engineer -in -Charge. Note : The design of Solar power plant to be vetted by National Institute of solar energy (NISE) or independent agency approved by MNRE. a) To obtain 100 KWp minimum 307 numbers Poly crystalline silicon solar PV modules of 325 Wp each having high efficiency, fill factor more than 0.74 plant performance ratio more than or equivalent to 75% and made of high tyransmissivity glass front surface shall give high encapsulation gain, (Transmittance above 90 % and bending less than 0.3%) Electrical parameters of 325 Wp solar PV module under STC of irradiance 1000 W/m2 , AM 1.5 Spectrum and temperature 250o C will be as under.(Connecteed items are mentioned below)

1

-

-

... more
(i) Rated output of modules shall have positive tolerance of 3-5% and no negative tolerance is allowed. (ii) It shall perform satisfactorily in relatively humidity 100% with temperature 0 to 10 C to (+) 85 C (cell) and should withstand wind pressure 185 Km/Hr on the surface of the panel. (iii) PV modules(INDIAN ORIGIN ONLY) must be warranted for their output peak watt capacity, which shall not be less than 90% of the initial value at the end of 10 Years and 80% of the initial value at the end of 25 years.

-

-

-

... more
(iv) Each module shall have radio frequency identication ( RFID) tag bearing the following details. RFID reader will be provided by contractor. (a) Name of manufacturer of PV module (b) Name of manufacturer of solar cell (c) Month and year of manufacture (Separated for cell & module) (d) Country origin (separately of solar cell & module) (e) Peak wattage, Im, Vm and fill factor of the module. (f) Date of year of obtaining IEC PV module qualification certificate including the test lab issuing IEC certificate. (g) Unique Serial No. and Model No. of Module. (h) I-V curve of module (v) The temperature co-efficient for the module shall notbe more than 0.50%/C. (vi) Every odule must have by pass diode of suitable capacity. (vii) PV module must confirm o latest edition of IEC 61215/IS : 14286. IN addition the modules must conform to IEC 61730 Part - I & II for construction and testing & safety qualification.

-

-

-

... more
(viii) It shall also be in conformity of atest minimum technical specifications issued by MNRE from time to time. (ix) Provision of earthing & earth strip/ cables etc. for earth for solar PV module/Array etc. as per latest IS/MNRE norms to be provided and the cost of the same is to be included in this item and no extra amount will be paid to the contractor onthis account. (x) RFID reader to be provided by contractor.

-

-

-

... more
(b) Junction boxes : Supply and fix 4 (Min) Numbers of dustvermin and waterproof Array Junction Boxes and 4 Nos main junction boxes madeof FRP/Thermo Plates with IP 65 protection in complince with IEC62208 and shall be sunlight/UV resistance and well of ire retardant including over voltage protection, surge protection and manintenance free earthing as per relevant standard. The junctionboxes shall have suitable arrangements of followings: (i) Strings are required to be connected to the busbar through individual fuses with provision of arrangement for disconnection for each of the groups. (ii) Provision of a testpoint for each subgroup for quick fault loaction and to provide group array isolation. (iii) Each array junction box will have suitable by pass and reverse blocking diodes for maximum DC blocking voltage of 1000V with suitable arrangements for its connection. reverse blocking and by-pass diodes shall work for temperature extremes and shall have efficiency of 99.98% conformed by appropriate IEC standard.

-

-

-

... more
(c) cables : Suitable size of XLPE insulated copper cable of solar grade, 1100 volt & UV resistance and flame retardant for outdoor installations conforming IEC 60227/15694 & 60502/IS 1554 (Pt I &II). All cables and connectors for use of installations shall be of solar grade which can withstand harsh environment condition including high temperature, UV radians, rain. humidity, dirt, burial and attack by moss and microbes for 25 Years and volatge as per latest IEC/IS n standards. All cables/wires shall be provided with UV resistance printed copper ferrules for DC side. Size of cable shall be such that maximum voltage drop at full power from PV modules to invertor shall be less than 1.5% including diode voltage drop. cable Batch No./drum No. IS code and size make should be printed/ embossed at every one metre. The wiring of modules interconnection shall be in suitable size GI/HD pipe. Note: Cost of interconnection copper cables along with cable trays (floor/wall mounted) suitable to accommodate solar grade cables & cables upto inverter is included in the item and no extra payment will be made to contractor.

-

-

-

... more
Supply , fixing and commissioning of 50 KW - 02Nos, crystalline silicon normal string type grid tie power inverter outdoor type 3 phase 415 Volts 50+ 3 Hz, suitable to convert DC power of solar PV module/ array to AC for further feeding to grid confirming to IEC- 61683 for efficiency, IEC- 62109 (1&2) or equivalent for safety and IEC - 62093 for reliability with reverse polarity protection complete all as specified. The inverter shall include appropriate self protection and self diagnostic feature to protect iteself and the PV array from the damage in the event of inverter component failure or from parameters beyond the inverters safe operating due to internal and external causes.Inverter shall have protected arrangements against ground leakage faults, over voltage (SPD) & over current. Inverter shall have arrangements for adjusting DC input current and shall strip against sustainable fault down stream and shall not restart till fault is rectified.The inverter should hav the provisions of Galvanic isolation, Anti-islanding protection (IEEE 1547/UL 1741) equivalent BIS stranded and lightening.

-

-

-

... more
Lightning Protection for PV Array Design, supply & fix Lightning Arrestor-02 Nos, of required number of suitable Early Streamer Emission (ESE) lightning arrestors installed in the array field. Lightning Arrestors/ surge arrestors shall conform to IEC 600994 or IS:3070 except to the extent modified in the specifications.Arrestors shall be hermitically sealed units, self supporting constructions, suitable for mounting on lattice type support structures. The air terminal is Early Steamer Emission (E.S.E) type which shall be fixed at the top of a GI elevation pole with base so as be at leasr 2 meters above structure to be protected. Its height above roof level would be dependent on the level of protection radii required. The air terminal should be working on the principles of early steamer emission using non- radioactive technology, needing no external power source. The air terminal should be capable of racking the lightning stroke 60 micro seconds earlier as compare to passive lighting rod. The air terminal is of stainless steel and it has qualified diameter to resist high values of lighting currents. Roof connecting pipe should be capable of withstand in lightinf strikes havind dimension 50 mm ID and 60 mm OD. The terminal adaptor having inner dia 60mm OD. Note : Cost of all equipments, copper strip unto earth test point etc are included n this item. However cost of earthing will be paid searately to the Contractor under relevant item.

-

-

-

... more
M &L for earthing-06Nos, complete with copper earth plate electrode size 600 x600x 3.15 mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth pit not less than 1.5 mtr below normal ground level surrounded by from all sides by mixture of charcoal and common salt and electrode connected to and including copper strip 20 x 3 mm earth lead by means of bolts,nuts, check nuts and washers of galvanised steel and 40 mm dia GI pipe light grade for protection and medium grade 20 mm dia bore for watering funnel with wire mesh. CI cover with frame,PCC chamber pit with PCC 1:3:6 type C-2 excavtion and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion. Note : PCC pit shall be provided at least 500 mm away from the pit and not on the earthpit iteself and the extra cost of additional heeight of watering pipe bends elbow etc shall be deemed to be included in the quoted rate.

-

-

-

... more
Supply, lay and fix along the poles for passig through pipe, in trenches or under floor et. XLPE insulated armoured heavy duty cable 1100 Volts grade with aluminium conductor of cross sectional area 3.5 core x 95 Sqmm from Inverter to LT panel.(Length as required)

-

-

-

... more
Supply, laying and fixing along the poles or passing through pipes or laid under floor of through walls etc. jointing and testing (XLPE insulated) galvnised steel strip armoured electric cable 1100 volt grade heavy duty ISI marked with Copper conductor and overall served with an outer sheated of PVC, of cross sectional area 70 Sqmm with required number of runs/phase single core and 1 run for neutral suitabe for 3 phase systewm to lead ealectric supply from inverter to main panel.(Length as required) Note-I : One run of 70 sqmm cable will measured as one unit complete all as directed Note -II : Excavation, earth work, Sand cushioning, Cable covers, Pipe for cable protection are included)

-

-

-

... more
supply, installation, testing and commissioning of factory made LT cubical panel - 01No, outdoor type suitable to accommodate the following accessories made out of CRCA sheet 3.15mm thick duly power coated with Siemens grey shade RAL 7032, totally enclosed, dust and vermin proof with working voltage of 450V, 50 Hz, 3 phase 4 wire ,fully compartmentalized, for each control gear having back side of panel openable, and shall be provided with suitable louvers for ventilation including suitable size of MS medium channel of size 75 mm and necessary foundation work providing PCC 1:2:4 B1 with 20 mm graded aggregate. Bus Bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitable colour coded with heat shrinkable sleeve for phase indiction. The standard phase arrangement when facing the switch gear shall be R-Y-B from left ro right. The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon themin ordinary working due to fixing, vibration, fluctuations in temp, short-circuit

-

-

-

... more
or other causes. The bus bar will be supported on DMC. provisionshall be made for expansion and contraction of the bus bars and connections woth variation on temp. Inteernal wiring should be done 2.5sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeve etc. The bottom of the panel shoud contain detachable plate having provisionof entry of armoured cable of adequate size with glands. Threaded earthing studs -02 Nos shall be shall be provided at the bottom and lifting lugs of suitable size at top of lift the panel safety shall be made .The cubicle incomer MCCBs as well as outgoing shall have copper 4 pole / TP extenison links of current rating not less than 1.5 times the rated capacity of individual feeders. The cubicle should be inclusive of following (male : ABB/ Siemens/ Adlec legrand/L&T )(Note : Due to space constraint in enterance door of substation panel should be detahable type to enter the substation in two/three parts as required at site):-

-

-

-

... more
Incoming (a)MCCB 125 Amps 25 KA , 415 volt 4 pole, thermal magnetic release 50 HZ Make:Legrand/ Siemens/ Schneider -2 nos (B) Mulitfunctional meter having LCD display , AC Make L&T/ System Control & switchgear/ Schneider Electric (c)LED indicator lamp showing Red,Yellow ,Blue (d)Copper bus bar of capacity 400 Amps for phases and neutral Outgoing (a)MCCB with microprocessor release 4 pole 50 KA. 250 Amps electrically motor operated draw out type make : Legrand / Schnider /L&T

-

-

-

... more
M &L for maintenance free UL approved copper bonded Earth Rod of 10 feet length, 17.2mm dia made out of high tensile low carbon steel rod, molecularly bonded with 99.9% electrolytic grade copper on outer surface (minimum copper bonding thickness -250 microns and lenght of 3 meters). with exothermically jointed copper bus bar of 50 x 6 x 200mm for connection. the rod and exothermic joint successfully tested (Short time withstand current at 20 KA rms for 1.0 & 50 KA peak) by CPRI.With 50 Kg /Electrode Eco friendly Earth enhancing compound with each rod. The compound should comply to IEC - 6256-7 having passed TCLP (toxic test), resistivity test (0.2 Ohm M), leaching, corrosion,sulphur & resistivity test as per IEC 62651 -7 by NABI accredit Lab with FRP inspection pit cover. The rate shall include excavation of earth, filling with black filled compound, and earth pit making, The complete installation shall be as per the drawing and technical specifications. Make: JMV LPS Ltd/ OBO/ ENNOV Infra Solutions Pvt Ltd/ERICO/Power Bolt

-

-

-

... more
Supply and fixing Net Metering system along with CT,PT including structural work complete all as specified and directed.(01 Unit) NOTE:- (i) All necessary permissions of integrating the 100 KW solar plant with the existing MSEDCL system shall be the responsibility of contractor. The include repeated liasion with MSEDCL /local agencies. The rate/ amount quoted is deemed to be inclusive of this aspect and no claim whatsoever shall be entertained at later stage. (ii) Outsourcing of services for COmprehensive maintenance, operation and repair including spares required till defect liability period is deemed included in the contract sum quoted by the contractor and nothing extra shall be paid for the maintenance, operation and repair of solar power plant till th ecompletion of defect liability period. (iii) The employment of manpower and other details for maintenance, operation and repair during defect liability period shall be strictly as specified for Ph-II of the work.

-

-

-

... more
Supply and layinf PVC insulated flexible copper cable of size 1 x 70 Sqmm for connection from earthing to lighting terminal complete all as specified.(Length as required)

-

-

-

... more
Supply, laying and testing of RS-485 copper cable of size not less than 0.5 Sqmm, 2 pair , metal screened, armoured, PVC insulated copper conductor cable complete with round type lugs and coppper glands all as specifeied and directed.(Length as required) Make: Polycab, Havells, Glostar or equivalent from the list of makes.

-

-

-

... more
Supply and installation of LT outdopor type panel 02No of suitable size, factory manufactured CPRI approved made out of 03mm thick CRCA sheet duly powder coated paint IP-65, with 200 A rated bus bar and 125 Amps MCB isolator 4 pole and with appropriate ventiliation complete all as apecified and directed.

-

-

-

... more
M&L for installation of weather station and monitoring system covering temperature sensors, pyronometer wind velocity sensor etc complete all as specified and directed. Make : JAS (Jambekar Automation System), AERON ( Pune) , or equivalent consisting of equipments of makes specified in PS.

-

-

-

... more
Supply and installtion of data logging kit for all inverters and monitoring the same remotely complete all as specified and directed.

-

-

-

... more
Supply and installation of PC with 17" LED screenwith 2TB HDD, 8GB RAM, 8GB graphics card etc. for monitoring system complete all as specified and directed.Make: HP/DELL/ACER/HCL

-

-

-

... more
Supply and fix copper eart strip 20x 3mm size complete all as specified and directed.(Length as required)

-

-

-

... more
STP

-

-

-

... more
Supply and installation Package Sewage Treatment Plant of 20,kld capacity consisting of Fiber glass reinforced Plastic (FRP) tank made by filament winding process from suitable polyester resin and glass fiber  of the tank with suitable polyester resin and fiber glass to make tank suitable for underground application  process variation. The tank to have three zones – first zone to work as anaerobic septic zone created with suitable partition of FRP; second zone to be created by partition of FRP with advanced fab media with a surface area to volume ratio of minimum of 400 Sq. Mtr / Cubic meter suitably encased    free movement of the media within fixed space created by the net; the third zone to work as sedimentation zone in the remainder area of the tank. Aerobic zone have Twin Lobe Air Blowers installed for providing air flow coarse aeration in the zone for speedy reduction of BOD. Sedimentation zone have submersible pump of the  for pumping the activated sludge back to the anaerobic zone by way of PVC pipes  The whole plant to be controlled by automatic control panel made from sheet molded compound.

1

-

-

... more
A. EFFLUENT TYPE 1.Type of Waste - Domestic Sewage 2. Total Waste Volume - 20 KLD 3. Stage of Treatment - 03 (Primary, Secondary, Tertiary) 4.Use of treated water - Gardening, Floor Washing

-

-

-

... more
SPECIFICATION OF EQUIPMENT AND MACHINERY: 1. SEWAGE TRANSFER PUMP: Sewage pump for sewage transfer from collection tank to aeratio tank (a) Nos required: 2(1+1) stand by (b) Type:0.5HP mud pump-2.nos (c) Make:Kirloskar /b tali (d)Flow/ Head: 1.0 m3/ hr ( peak )-6m Head 2.COMPRESSOR: TWIN LOBE BLOWER (a) Type :AGS (b) NOs required : 2(1+1) stand by (c) Flow head:16.0 m3/ hr/2.0 mt (d) Power: 2HP 3 Phase 3. AIR DIFFUSER (a) Type: GI header with membrane diffuser of 0.6mt long 2 NOs

-

-

-

... more
4.MEDIA (a) Fab Media : PVC/PP (one lot) (b) Tube deck Media: One lot 5. FILTER FEED PUMP (a) Nos required: 2(1+1) stand by (b) Type: Centrifugal mono block (c) Make: Kirloskar/ Crompton (d) HP : 0.5 HP 6.DOSING PUMP (a) Nos required: 1 (b) Type: Electronic Diapharm Type Metering Pump (c) Make: Seiko or equivalent (d) Electric Panel :Automation with level sensor

-

-

-

... more
DETAILS OF MODULAR UNIT: A. SPECIFICATION: 1. Qty. of sewage water -20 cum/day 2. Average flow rate- 1.0 cum/hr 3.Peak flow- 2 times normal flow 4.Collection Tank size with oil& grease trap - 15 cum/day B. FAB REACTOR & CLARIFIER TANK 1. Type : Fab reactor aeration Tank with Humus type clarifier 2. Materials of construction: MS with FRP lining 1.1 mm inside and synthetic Paint outside. 3.Microbe Decay time: 8 day sludge age 4.Aeration tank size: 2.0.mt length x 1.8 mt width x 1.6 SWD . volume 3.12m3 (inside FRP coating 1.1mm thick) 5. HUMUS type clarifier tank &Presedimentation Tank:1.0 mt length x 0.9 mt width x 1.0 mt height x 0.8 mt cone ( inside FRP coating 1.1mm thick)

-

-

-

... more
6. Holding Pump: HDPE tank 2.0 m3 cap. 7. Pressure sand filter: MOC: MS/PVC , Flow rate : 0.5 m3/hr 8. Air required per day: 115m3/ day for aeration & 200m3/day for collection tank 9. Air Blow capacity: 16 m3/hr with 0.5 kg/cm3 pressure 10. Type Of Aeration: Membrane Type Diffuser 11. Efficiency of Oxygen Transfer: 12% 12. Details of Aeration Equipment: GI Header 13. Settling Rate: 0.5m3/m2/hr or 6.0m3/m2/day 14. Sludge Recirculation: Through Air. 15.TSS Produced: 3.0 kg / day 16. Sludge Recirculation: 6g/ L C.Sludge Drying Bed 1. Nos. required-3 2.SIZE:1.2mt x 1.2mt x 1.2mt Depth each 3.MOC: Brick Masonary

-

-

-

CA NO: CENM- OF 2019-20 SERIAL PAGE NO: 4 APPENDIX ‘A’ TO NOTICE INVITING TENDER (NIT) NIT NO : 80000/NIT/ /E8, CENM -2019-20 1. Name of work : PROVISION OF ADMIN CUM TRAINING BLOCK AND ANCILLARY FACILITIES AT INS MANDOVI 2. Estimated Cost of Work : Rs.5150 lakhs (At par market) (Approximate) 3. Period of Completion : 660 days ( 22 months) 4. Cost of tender documents : Rs. 3,000/- (Rupees three thousand only) in the shape of DD/Banker’s cheque from any Scheduled bank in favour of Garrison Engineer (P) Vascoand payable at Vasco 5. Website/portal address : https://defproc.gov.in and www.mes.gov.in 6. Type of contract : The tender shall be based on drawings and specifications (IAFW- 2159) and GCC (IAFW-2249) with Schedule ‘A’ (list of items of work) to be priced by tenderer. The tenderers are required to quote their lump sum amounts for prepriced parts of Schedule ‘A’ and quote rates against items of other parts of Schedule ‘A’. 7. Information and details : (a) Bid submission start date Refer critical dates.** (b) Last date of bid submission (c) Date of bid opening 8. Eligibility Criteria : (A) For MES Enlisted Contractors : They should satisfy the following criteria:- (a) They should have enlisted in class “SS” and Category (b) They should not carry adverse remarks in WLR of competent engineer authority. (c) They should qualify as per the pre Qualification Criteria as per Annexure -I (B) For other contractors : The firms not enlisted with MES shall satisfy the following criteria:- (a) They should meet enlistment criteria of “SS” class MES contractor and category a(i), i.e with regard to having satisfactorily completed requisite value works, Annual turnover, Solvency, working capital, immovable property/fixed assets, T&P, Engineering establishment, no recovery outstanding in any Govt Department, Police verification/Passport etc. Enlistment criteria may be seen in Para 1.4 of Section 1 of Part I of MES Manual on Contract - 2007 (Reprint-2012) as available in all MES formations. These firms shall also submit copy of Police verification from police authority of the area where the registered office of the firm is located / notarized copy of valid passport of proprietor/each partner/each Director. (b) They should not carry adverse remarks in WLR/or any other similar report of any authority. (c) They should qualify as per the pre Qualification Criteria as per Annexure -I 9. Tender issuing and Accepting Officer : CE (Navy) Mumbai 10. Executing agency : Garrison Engineer (P) Vasco 11. Earnest Money : Rs.15,00,000/- in favour of Garrison Engineer (P) Vasco in the form of FDR from any Nationalized/ Scheduled Bank. MES enlisted contractor are exempted for submission of EMD. BGB or DD are not acceptable for EMD CA NO: CENM- OF 2019-20 SERIAL PAGE NO: 5 APPENDIX ‘A’ TO NOTICE INVITING TENDER (NIT) (Contd…) **CRITICAL DATES Para 7. Publishing date and time of tender documents : 18 JULY 2019 at 1800 hrs Starting date & time for downloading of tender documents : 17 AUGUST 2019 at 1800 hrs Starting date and time of bid submission (Cover No. 1 & 2) : 24 AUGUST 2019 at 1800 hrs Closing date and time of bid submission (Cover No. 1 & 2) : 31 AUGUST 2019 at 1800 hrs Date and time of bid opening (Cover No. 1) : 2 SEP 2019 at 1200 hrs or subsequently Date and time of bid opening (Cover No. 2) : Will be intimated online after completion of evaluation of tech bids/applications (cover No. 1) NOTES:- (a) The contractors enlisted upto one class below the eligible class may also apply/bid. Applications/bids from one class below the eligible class applicants may be considered in the event of inadequate response / bids from the applicants of eligible class.

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.