Military Engineer Services Tender

BidAssist is a very user-friendly website that helps us to explore all the new opportunities so as to achieve growth in our business. It helps us to attain all the information with respect to any e-tender the Arunachal Pradesh government has posted on its website in a very hassle-free manner.

Military Engineer Services - MES Tender

Works
Eprocure
Opening Date20 Sep 2021
Closing Date22 Feb 2022
Tender Amount₹ 3,02,93,04,948 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Construction of Garrage for B vehicle for (02 lorry 5/7.5 Ton and 1 army bus) including plinth protection with all fittings and fixtures etc. complete all as specified and shown on drawings No DIN/LOH/2021/AR-414 Sheet 1/1 dated 23.08.21 and DIN/LOH/2021/ST-414 Sheet 1/1 dated 23.08.21 ..

1

-

-

... More
Construction of Pump house for bore well including plinth proction with all fittings and fixtures etc. complete all as ecified and shown on drawings No DIN/LOH/2021/AR-436 Sheet 1/1 dated 23.08.21 and DIN/LOH/2021/ST-436 Sheet 1/1 dated 23.08.21 ..

2

-

-

... More
Surface excavation in soft/loose soil n exc 30 cm deep and averaging 15 cm deep and getting out complete all as specified and directed.

158934.71

-

-

... More
Surface dressing n exc 15cm deep in soft./loose soil complete all as specified and directed.

44587.56

-

-

... More
Surface dressing n exc 15cm deep in hard/dense soil complete all as specified and directed.

339740.15

-

-

... More
Rough excavation n exc 1.5m deep and getting out in hard/dense soil complete all as specified and directed. Note: For defination for rough excavation refer clause No 3.3.1 of SSR- Part-I 2009

1181999.9

-

-

... More
Bringing approved earth (as approved by Garrison Engineer) from sources outside defence land including all cost such as royalty if any, transportation, taxes etc. for area filling / forming embankments including raising (any height from existing OGL) by approved earth and including raising earth spreading in layers not exc 30 cm thick each layer, watering, compaction with 8 tonne to 12 tonne power roller and finished to required size and shape etc, any high / depth from OGL.

235.76

-

-

... More
Rough excavation n exc 1.5 m deep in soft/ loose soil and getting out complete all as specified and directed.

383907.33

-

-

... More
Excavation over areas not exc 1.5m deep and getting out in soft and loose soil complete all as specified and directed.

3921.93

-

-

... More
Excavation over areas not exc 1.5m deep and getting out in hard/dense soil complete all as specified and directed..

252846.32

-

-

... More
Add to item no 13 for each additional 1.5m or part thereof beyond 1.5m in hard/dense soil complete all as specified and directed

13781.34

-

-

... More
Excavation over areas exc 1.5m but not exc 3.0m deep in soft and loose soil

1294.17

-

-

... More
Add to item No 15 for each additional 1.5m or part thereof beyond 3.0m in loose/soft soil complete all as specified and directed

578.47

-

-

... More
Excavation in trenches n exc 1.5 m wide n exc 1.5 m deep in soft/ loose soil for foundation etc or for shaft, wells, manholes etc n exc 10 sqm on plan and not exc 1.5 m in depth and getting out complete all as specified and directed.

36801.09

-

-

... More
Excavation in trenches n exc 1.5 m wide , exc 1.5 m deep but n exc 3.00 m deep in soft/ loose soil for foundation etc or for shaft, wells, manholes etc n exc 10 sqm on plan and exc 1.5 m deep but n exc 3.00 m deep and getting out complete all as specified and directed.

616.64

-

-

... More
Excavation in trenches n exc 1.5 m wide n exc 1.5 m deep in hard/dense soil for foundation etc or for shaft, wells, manholes etc n exc 10 sqm on plan and not exc 1.5 m in depth and getting out complete all as specified and directed.

8134.38

-

-

... More
Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface complete all as specified and directed

4380

-

-

... More
Returning ,filling in including spreading ,levelling watering and well ramming of soft/loose soil in layers n exc 25 cm thick complete all as specified and directed

354449.96

-

-

... More
M&L for earth filling under floors including spreading, levelling and watering and well ramming complete all as specified and directed.

5254.88

-

-

... More
M&L for sand filling under floors or in foundation including spreading, levelling watering and well ramming in layers complete all as specified and directed.

12338.91

-

-

... More
Material and labour for filling of coarse sand as in filter media along Retaining wall complete all as specified and directed

3580.61

-

-

... More
Moorum/red bajri filling under floors or pavings, laid in layers n exc, 15cm thick, spread, levelled and ramming including watering complete all as specified and directed

4458.76

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required sizeand shape etc n exc 1.5 m high from base by using soil complete all as specified and directed

31868.42

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required sizeand shape etc exc 1.5 m high and not exc 3.00 from base by using soil complete all as specified and directed

23813.55

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required size and shape etc exc 3.00 m high and not exc 4.50 from base by using soil complete all as specified and directed

17086.72

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required size and shape etc exc 4.5m high and not exc 6.00 from base by using soil complete all as specified and directed

11076.83

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required size and shape etc exc 6.0m high and not exc 7.50 from base by using soil complete all as specified and directed

4159.33

-

-

... More
Forming embankments including raising or lowering earth spreading in layers not exc 30 cm thick watering ,ramming and rolling and finished to required size and shape etc exc 7.5m high and not exc 9.00 from base by using soil complete all as specified and directed

2789.71

-

-

... More
Removing excavated soil not exceeding 50 m distance and depositing where directed at a level n exc 1.5 metre above the starting point complete all as specified and directed .

988533.3

-

-

... More
Removing excavated material exc 50 m and n. Exc 250 m and depositing where directed at a level n. exc 1.50 m above the starting point complete all as specified and directed .

298565.78

-

-

... More
Removing excavated material exc 250 m and n. Exc 500 m and depositing where directed at al level n. exc 1.50 m above the starting point complete all as specified and directed .

271103.58

-

-

... More
Add for each additional 500m or part thereof beyond 500m and upto a total distance of 1.5km. For removal of soil complete all as specified and directed

271103.58

-

-

... More
M&L for hardcore of broken stones of gauge n exc 63 mm , deposited, spread and levelled in layers n exc 15 cm thick watered and rolled rammed to a true surface complete all as specified and directed.

2932.07

-

-

... More
M&L hardcore of broken stones of gauge exc 63 mm but n exc 100mm , deposited spread and levelled in layers n exc 15 cm thick watered and rolled rammed to a true surface complete all as specified and directed

16685

-

-

... More
M&L for treating the bottom and sides of excavation with anti termite treatment at the rate of 5 litres of emulsion per sqm of surface area complete all as specified and directed

2094.8

-

-

... More
M&L for treating the back fill in contact with foundation with anti termite treatment at the rate of 7.5 litres of emulsion per sqm of vertical surface complete all as specified and directed.

1451.7

-

-

... More
M&L for treating the top surface of filled earth with anti termite treatment at the rate of 5 litres of emulsion per sqm of surface area all as specified complete all as specified and directed

7975.27

-

-

... More
M&L for treating the soil alongwith external perimeter of the building with anti termite treatment at the rate of 2.5 litres of emulsion per Rm of surface area all as specified complete all as specified and directed

3967.4

-

-

... More
M& L Cement concrete 1:4:8 Type D 2 (using 40 mm graded stone aggregate) ,in foundations, filling and mass concrete complete all as specified and directed

14768.9

-

-

... More
M& L Cement concrete 1:3:6 Type C-2 (using 40 mm graded stone aggregate) as in kerb stone complete all as specified and directed

32.55

-

-

... More
M& L Cement concrete 1:2:4 Type B 2 (using 40 mm graded stone aggregate) ,in foundations, filling and mass concrete complete all as specified and directed

4

-

-

... More
Cement concrete 1:3:6 Type C 2 (using 40 mm graded stone aggregate) in suface channels and drains complete all as specified and directed

1023.23

-

-

... More
Providing cement concrete 1:2:4 Type B-1 (using 20 mm graded stone aggregate) in, lintel upto 1.5 mtr span; seismic and lintel bands, and lacing band parapet,railing, bed plate and similar items including formwork complete all as specified and directed

131.58

-

-

... More
Providing cement concrete 1:3:6 Type C 1 (using 20 mm graded stone aggregate) in, cills, steps; seismic and other similar bands, plinth courses, copings and the like including weathering, slightly rounded or chamfered angles and throating, complete all as specified and directed

296.1

-

-

... More
Providing Precast RCC M-25 (Design Mix ) using 20mm graded stone aggregate as in dunnage block of size 0.30M x 0.30M x 0.20M, set in CM 1:6 complete all as specified and directed

477.36

-

-

... More
Providing, precast M-20 cement concrete in manhole cover slab (for use with masonry), with plain fair faces, including chamfers weatherings, throating etc. and setting in mortar complete with joints to match complete all as specified and directed

9.14

-

-

... More
Providing, precast cement concrete type B-1 (1:2:4) (using 20mm graded stone aggregate) in manhole cover slab set in cement mortar 1:4 complete all as specified and directed

0.16

-

-

... More
Reinforced cement concrete design mix M-25 (using 20 mm graded stone aggregate) as in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete complete all as specified and directed

29384.75

-

-

... More
Reinforced cement concrete design mix M-30 (using 20 mm graded stone aggregate) as in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete

3998.53

-

-

... More
Reinforced cement concrete design mix M-20 (using 20 mm graded stone aggregate) as in walls, retaining walls, basement walls, ballast walls and the like; any thickness; above top of footings; including attached pilasters and buttresses.

7015.89

-

-

... More
Reinforced cement concrete design mix M-25 (using 20 mm graded stone aggregate) as in walls, retaining walls, basement walls, ballast walls and the like; any thickness; above top of footings; including attached pilasters and buttresses complete all as specified and directed.

23831.65

-

-

... More
Reinforced cement concrete design mix M-30 (using 20 mm graded stone aggregate) as in walls, retaining walls, basement walls, ballast walls and the like; any thickness; above top of footings; including attached pilasters and buttresses complete all as specified and directed.

4215.65

-

-

... More
Reinforced cement concrete design mix M-25 (using 20 mm graded stone aggregate) as in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like

8211.27

-

-

... More
Reinforced cement concrete design mix M-30 (using 20 mm graded stone aggregate) as in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed

1269.05

-

-

... More
Reinforced Cement Concrete M-25 (Design mix) using 20 mm graded stone aggregate as in chajja complete all as specified and directed

72.19

-

-

... More
Reinforced cement concrete design mix M-25 (using 20 mm graded stone aggregate)as in beams, cantilevers, bressummers, lintels over 1.5m span complete all as specified and directed

2239.66

-

-

... More
Reinforced cement concrete design mix M-25 (using 20 mm graded stone aggregate)as in columns, pillars, piers, posts and struts complete all as specified and directed

2727.19

-

-

... More
Extra for forming fair finished drain or channel 30CM inner girth in cement concrete using extra cement, including forms, moulds, mitred/ stopped ends etc. complete all as specified and directed

1821.87

-

-

... More
Supply only Integral Water Proofing Compound

5322.2

-

-

... More
M &L Brickwork with subclass 'B' old size bricks, straight or curved on plan exc 6m mean radius built in Cement mortar 1:6 complete all as specified and directed

8866.7

-

-

... More
M &L Brickwork with subclass 'B' old size bricks, straight or curved on plan exc 6m mean radius built in Cement mortar 1:4 complete all as specified and directed

761.04

-

-

... More
M&L Brickwork with subclass 'B' bricks, old size brick straight or curved on plan to any radius in half brick thick walls built in cement mortar 1:4 complete all as specified and directed

2140.1

-

-

... More
M&L 40 mm thick Damp proof course to horizontal or vertical surfaces including necessary formwork in cement concrete 1:2:4 Type B 0 using (12.5 mm graded stone aggregate) complete all as specified and directed

815.55

-

-

... More
M&L Firebrick work in linings to fire places, flues etc. (other than in chimney shafts) , set, jointed and pointed in fireclay

0.75

-

-

... More
M&L Continuous brick edging; with width equal to the width of the brick; laid dry on end vertically complete all as specified and directed

44587.56

-

-

... More
M&L Walling of random rubble, uncoursed, well bonded, bedded and solidly hearted, built in cement mortar 1:6 complete all as specified and directed

19786.89

-

-

... More
M&L Boulder pitching, laid dry, hand packed tightly complete all as specified and directed

450

-

-

... More
M&L 25mm thick Granite (of any type) work (table rubbed and polished) for wall lining (veneering to wall) 12mm thick in cement mortar (1:3) and pointing with white cement (1:2) using marble dust with admixture of pigment to match with shade of granite complete all as specified and directed

1.96

-

-

... More
Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; rough finished surfaces of concrete flat complete all as specified and directed

52979.08

-

-

... More
Formwork to faces of walls, retaining walls, abutments, parapets and staircase railings and similar work including attached pillasters, buttresses, etc.; vertical or to batter fair finished flat surfaces complete all as specified and directed

195436.72

-

-

... More
Formwork to soffits of suspended slabs such as roof slab , floor slabs , landing ; and similar work not exc 200mm (horizontal or sloping) thick; rough finished surfaces of concrete flat complete all as specified and directed

41194.6

-

-

... More
Formwork to chullah hoods, chajjas, troughs and similar items including edges, rough finished surfaces of concrete flat complete all as specified and directed

932.39

-

-

... More
Formwork to sides and soffits of floor or roof beams, beam haunchings, girders, bressum-mers, lintels, cantilevers, shelves including supports, overhangs, etc. also splays between floors and beams, etc rough finished surfaces of concrete flat complete all as specified and directed

16220.67

-

-

... More
Formwork to sides of walls rough finished surfaces of concrete flat complete all as specified and directed

16456.41

-

-

... More
Formwork to sides of square ,rectangular or polygonal pillars, posts, struts, piers, columns and stanchions rough finished surfaces of concrete flat complete all as specified and directed

22495.28

-

-

... More
Formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n exc 20cm wide and sides of RCC/PCC bands in walls, horizontal or sloping and similar work exc 10cm but n exc 20cm wide ,rough finished surfaces of concrete complete all as specified and directed

3879.52

-

-

... More
S&F 40mm thick flush shutters, solid core construction, with block board core and plywood face panels, both face is covered with decorative faces veneer with lipping/frame to match, complete all as specified and directed

1086.51

-

-

... More
S&F 2nd class HW small fittings such as brackets of any type, latch and hinge blocks, shaped door and window stops and the like, including all necessary labours; articles n exc 200 cu.cm each complete all as specified and directed

296

-

-

... More
S&F Solid PVC Double door frame of size 50mm x 95mm made out of 5mm Plain colour PVC sheet reinforced with M.S tube, supplying & fixing in opening complete all as specified and as shown in drawing

988.1

-

-

... More
S&F factory made solid PVC moulded door shutter, 28 to 30mm thick (stiles), with 2,4, or 6 raised panel design with 2mm thick moulded PVC sheet on the front face & 2mm plain colour PVC sheet on back face with particle board core supplying & fixing in frame as per specification and drawing and directed.

201.43

-

-

... More
S&F 200 mm long mild steel barrel tower bolts, stove enamelled black, with bright bolt and fixed, complete all as specified and as directed

302.9

-

-

... More
S&F 150 mm long mild steel barrel tower bolts, stove enamelled black, with bright bolt and fixed, complete all as specified and directed

310

-

-

... More
S&F 150mm long aluminium anodised barrel tower bolts of extruded section, complete all as specified and directed

363

-

-

... More
S&F 300mm long mild steel sliding door bolts, plate type, stove enamelled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed,complete all as specified and directed

284

-

-

... More
S&F 300mm long Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast aluminium alloy and fixed.complete all as specified and directed

183

-

-

... More
S&F Butt hinges of 100 mm size, medium weight, cold rolled mildsteel and fixed, complete all as specified and directed

573

-

-

... More
S&F 150mm mild steel pressed handles, oval type, stove enamelled black, complete all as specified and directed

496

-

-

... More
S&F 125mm extruded aluminium alloy handles, fabricated type., anodised complete all as specified and directed

366

-

-

... More
S&F tubular towel rail, 20mm dia, D type, 60cm long between flanges complete all as specified and directed

185

-

-

... More
Supply and fix Mild Steel galvanised wire cloth of 0.56mm nominal dia of wire and average width of aperture and 1.18mm and fixed to angle iron frame with tinned faces or galvanised wire staples complete all as specified and directed

37

-

-

... More
M&L Cast iron work grade FG 150, unmachined, in brackets, gully traps, gratings, railing, frames, manhole covers, fire and soot doors, dampers, stop valve boxes, gate stops, parts of ranges, balusters and similar articles complete all as specified and directed

4400

-

-

... More
S&F Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed

113632

-

-

... More
S&F framed work such as grills gratings, etc., with ends of bars shouldered and/ or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed baluster; walk ways; railings; framed work or water tanks and similar work conforming to Fe 290 gde E 165 complete all as specified and directed

11180.4

-

-

... More
S&F Bands, straps, supports or stays for rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples; chains; hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-290 Gde-E-165 complete all as specified and directed

15636.83

-

-

... More
S&F Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, n exc 5cm long complete all as specified and directed

2343

-

-

... More
M&L Mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.

7829713.32

-

-

... More
M&L Mild steel TMT bars 6 to 8mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.

122275.89

-

-

... More
Mild steel TMT bars 5mm dia and over upto and including 10mm dia cut to length, bent to shape required in stirrups, spacers and binders and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed

356479.79

-

-

... More
Mild steel TMT bars over 10mm dia as in stirrups, spacers and binders complete all as specified and directed

118809

-

-

... More
S&F Joist, channel, angle, or tee sections fixed independentaly, without connecting plates, etc. (cut to ordinary lengths i.e. within 20mm of the length indicated) conforming to grade Fe-410-w or E -250 quality A complete all as specified and directed

2234.61

-

-

... More
M&L for anchor plate of any size and any thick including welding to pipe complete all as specified and directed

1.33

-

-

... More
S&F Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and directed

3.64

-

-

... More
S&F Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment complete all as specified and directed

712

-

-

... More
S&F Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. doors, etc. to be prepared for hanging or sliding with and including either hooks and hanging; also fastening conforming to grade Fe-410-W or E -250 quality A complete all as specified and directed

41057.33

-

-

... More
S&F Welded Steel Wire Fabric to wood or steel member not exc 4Kg per Sqm complete all as specified and directed

39.01

-

-

... More
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and directed

27710

-

-

... More
S&F Galvanised 2 strand steel barbed wire 2.24mm dia steel barbed wire with 2mm dia barbs at 75mm spacing & straining & fixing to any type of standard rails straining bolt including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc.etc as directed (each line wire to be measured) complete all as specified and directed

1006

-

-

... More
Supply and fixing Pressed Steel Windows/Ventilator using box type hinges, MS Spring Latch, MS tower Bolt and telescopic stay complete all as specified and directed

1456.46

-

-

... More
S&F pressed steel frames for doors of size 105x60 mm with one or more rebates including necessary fixing lugs, hinges, lock strike plate, etc., complete, as specified,

1612.15

-

-

... More
S&F Mild steel in flat, round or square bars, in available lengths Fe 410-W (Gde E-250) quality A complete all as specified and directed

57808

-

-

... More
Supply only Chain link MS galvanised fencing, any size or type (size of mess 100x100mm & 4mm dia.) complete all as specified and directed

74103

-

-

... More
S&F 8mm thick clip of Mild Steel around the pole to hold the pully duly finished with primer & paint complete all as specified and directed

1

-

-

... More
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.63mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified complete all as specified and directed

160.02

-

-

... More
S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.80mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified complete all as specified and directed

37.8

-

-

... More
M&L for 100mm thick PCC M20 Design Mix (using 40mm graded stone aggregate) mixed with non metallic floor hardener as in floor finished by vacuum dewatering including supply of non metallic floor hardener as per manfacturers instruction complete all as specified and directed

4546.44

-

-

... More
M&L for 200mm thick PCC M20 Design Mix (using 40mm graded stone aggregate) mixed with non metallic floor hardener finished by vacuum dewatering including supply of non metallic floor hardener as per manfacturers instruction complete all as specified and directed

1626.49

-

-

... More
M&L 100mm thick cement concrete type B-2 1:2:4 (using 40mm graded stone aggregate) laid in panels over hardcore including spike rolling to surfaces or making impressions of expanded metal, whilst the concrete is green complete all as specified and directed

651.08

-

-

... More
M&L for 100mm thick PCC M15 (using 40mm graded stone aggregate) with chequered finish as in floor complete all as specified and directed

1087.24

-

-

... More
M&L 50mm thick Cement concrete type B-2, 1:2:4 (40mm graded aggregate) as in drain bed complete all as specified and directed

12461

-

-

... More
M&L 80mm thick Cement concrete type B-2, 1:2:4 (40mm graded aggregate) as in drain walls complete all as specified and directed

19389

-

-

... More
M&L for 50mm thick PCC 1:3:6 type C-2 (using 40mm graded stone aggregate) as in floor/plinth protection , finish even & smooth without using extra cement complete all as specified and directed

2850.89

-

-

... More
M&L for Cement concrete 1:3:6 type-C2(using 40mm graded stone aggregate) 100mm thick finished even and smooth without extra cement complete all as specified and directed

20

-

-

... More
M&L 75mm thick PCC 1:5:10 type E-2 (using 40mm graded stone aggregate) as in sub base complete all as specified and directed

291.49

-

-

... More
M&L 40mm thick PCC (1:2:4) type B1(using 20mm graded stone aggregate) finish even and smooth using glass including dividing strip over 75 mm thick PCC 1:5:10 type E2 over 75mm sand layer covering with ploythene film over rammed earth complete all as specified and directed

2870.74

-

-

... More
M&L for 100mm thick PCC 1:4:8 type D-2(using 40mm graded stone aggregate) as in sub base complete all as specified and directed

5970.5

-

-

... More
M&L 25 mm thick PCC 1:2:4 type B1 (using 20mm graded stone aggregate) finished even & smooth using glass dividing strip over RCC slab complete all as specified and directed

1479.81

-

-

... More
M&L 30mm thick PCC(1:2:4) type B-0 (using 12.5mm graded stone aggregate)as in coping to complete all as specified and directed

8.95

-

-

... More
M&L 46.5mm thick PCC(1:2:4) type B-0 (using 12.5mm graded stone aggregate) as in coping to complete all as specified and directed

9.77

-

-

... More
M&L 150 mm thick PCC (1:2:4) type B2 (using 40mm graded stone aggregate), trimixed concrete over 100 mm thick PCC 1:4:8 type D2 (using 40mm graded stone aggregate)over 100 mm thick hardcore over rammed earth, top layer shall be wear resistance using hardner complete all as specified and directed

1243

-

-

... More
M&L for 100mm Thick PCC M15 (using 40mm graded stone aggregate) nominal Mix as in sub base to floor complete all as specified and directed

868.83

-

-

... More
M&L 75mm thick PCC (1:2:4) type D-2 (using 40mm graded stone aggregate) as in floor complete all as specified and directed

207.4

-

-

... More
M&L for 10mm thick Wearproof topping as specified (incorporating an approved metallic floor hardner), laid on concrete floors and pavings, and finished even and smooth complete all as specified and directed

1087.24

-

-

... More
M&L for 40mm thick PCC 1:2:4 type B-1 (using 20mm graded stone aggregate), as in floor finish even & smooth without using extra cement complete all as specified and directed

2137.67

-

-

... More
M&L for rendering 5 mm thick in CM 1:3 over 10mm thick CM 1:6 as in skirting complete all as specified and directed

368.72

-

-

... More
M&L for rendering 5 mm thick in CM 1:3 over 10mm thick CM 1:3 as in skirting complete all as specified and directed

18.12

-

-

... More
S&F glass dividing strips 38mm wide and 3mm thick as in floor complete all as specified and directed

6163.7

-

-

... More
M&L Glazed ceramic tiles in vertical surface 300x 200x 7 mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match over 10 mm thick screed bed in CM 1:3 complete all as specified and directed

2588.82

-

-

... More
M&L Glazed ceramic tiles in vertical surface 600x 600x 9-10 mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match over 10 mm thick screed bed in CM 1:3 complete all as specified and directed

83.2

-

-

... More
M&L Non - skid Ceramic tiles 7 to 8 mm thick (square/rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 15mm thick screed bed in CM 1: 6 over 25mm thick PCC 1:2:4 type BO over 75 mm thick PCC 1:4:8 type D2 over 75 mm thick sand layer covering with polythene film over rammed earth complete all as specified and directed

1031.25

-

-

... More
M&L Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match screed bed in CM. 1:6 over 25 mm thick PCC 1: 2:4 type B0 over 75 mm thick PCC 1:5:10 type E2 over 75 mm thick sand layer covering with polythene film over rammed earth complete all as specified and directed

46.95

-

-

... More
Supplied and fixed 600x600x9 to 10 mm thick floor tiles over 15mm thick screed bed CM 1 : 6 over 25 mm thick PCC 1:2:4 type BO over 75 mm thick PCC 1:4:8 type D2 iver 75 mm thick sand layer covering with polythene film over rammed earth complete all as specified and directed

1922.55

-

-

... More
Supplied and fixed Non - skid Ceramic tiles 7 to 8 mm thick area of each tile exceeding 0.18 sqm but not exceeding 0.38 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match complete all as specified and directed.

183.92

-

-

... More
Supplied and fixed Virified Ceramic tiles light grade 10 mm thick (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match on vertical surfaces such as skirtings, dados and risers to steps etc.complete all as specified and directed

33.48

-

-

... More
S&F Polythene film 50 micron laid in floor complete all as specified and directed

5319.69

-

-

... More
Supply and laying 200 micron polythene film under floor in two layers as specified and directed

7222

-

-

... More
Supply and laying 200 micron polythene film under floor as specified and directed

7431.21

-

-

... More
Supply only sodium silicate, density 84 degrees twaddell (specific gravity 1.42) complete all as specified and directed

5000

-

-

... More
Supply only metallic floor hardener complete all as specified and directed

3041.76

-

-

... More
S& F Plastic dividing strips 98 x 1.5 mm laid and fixed in floors 2m x 2m grid complete all as specified and directed

6156.76

-

-

... More
M&L rendering 10 mm thick in cement mortar 1:3 on wall of brick work or concrete surface, finished fair and even complete all as specified and directed.

2523.32

-

-

... More
M&L 10 mm thick rendering in cement mortar 1:4 mixed with water proofing compound on wall of brick work or concrete surface, finished fair and even complete all as specified and directed

48278.81

-

-

... More
M&L 10 mm thick rendering in cement mortar 1:4 mixed with water proofing compound over 10mm thick rendering in CM 1:4 on wall of brick work or concrete surface, finished fair and even complete all as specified and directed

457.21

-

-

... More
M&L 10 mm thick rendering in cement mortar 1:4 mixed with water proofing compound over 10mm thick rendering in CM 1:6 on wall of brick work or concrete surface, finished fair and even complete all as specified and directed

231.68

-

-

... More
M&L rendering 15 mm thick in cement mortar 1:6 on brick work or concrete surface of walls finished even and fair complete all as specified and directed

21516.91

-

-

... More
M&L rendering 15 mm thick in cement mortar 1:6 on brick work or concrete surface of walls finished even and smooth without using extra cement complete all as specified and directed

5237

-

-

... More
M&L rendering 15 mm thick in cement mortar 1:4 in two layers (10+5mm)on brick work or concrete surface of walls finished even and smooth and without using extre cement complete all as specified and directed

4.5

-

-

... More
M&L rendering 5 mm thick in cement mortar 1:3 on concrete surface of walls, finished fair and even complete all as specified and directed

8409.03

-

-

... More
M&L rendering 5 mm thick in cement mortar 1:3 on ceiling of concrete surface, finished fair and even complete all as specified and directed

19879.79

-

-

... More
M&L for rendering 15mm thick in CM 1:4 finished fair and even complete all as specified and directed

126

-

-

... More
Screed bed or bedding layer of mortar 15mm thick in CM 1:6 for laying floor finishes complete all as specified and directed

2573.99

-

-

... More
M&L 5 mm thick rendering in cement mortar 1:3 over 10mm thick rendering in CM 1:6 on wall of brick work or concrete surface, finished even and smooth using extra cement complete all as specified and directed

7443.57

-

-

... More
M&L 5 mm thick rendering in cement mortar 1:4 mixed with water proofing compound over 10mm thick rendering in CM 1:6 on wall of brick work or concrete surface, finished fair and even complete all as specified and directed

8784.78

-

-

... More
M&L Raised pointing to random or polygonal rubble, uncoursed on brought upto courses in cement mortart 1:4 complete all as specified and directed

2176.54

-

-

... More
M&L Flush pointing to random rubble masonry, uncoursed or brought upto course in cement mortar 1:4 complete all as specified and directed

46037

-

-

... More
M&L for preparing the new plastered surfaces and applying two coats of color wash over a coat of white wash on walls complete all as specified and directed

28829.44

-

-

... More
M&L for preparing the new plastered surfaces and applying three coats white wash on walls complete all as specified and directed

1478.13

-

-

... More
Material and labour for Two Coats of Cement Base Paint over a coat of primer in camoflauge pattern including preparation of newly plastered surfaces complete all as specified and directed

16137.4

-

-

... More
M&L for preparing the new plastered surfaces and applying two coats of cement base paint on walls complete all as specified and directed

91233.53

-

-

... More
Preparation of new surfaces and applying 2 coats of colour wash over 1 coat of white wash on wall surfaces complete all as specified and directed

450.12

-

-

... More
Preparation of new surfaces and applying 3 coats white wash on ceiling surfaces complete all as specified and directed

12636.36

-

-

... More
M&L 3 mm thick sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 sq. m in each pane complete all as specified and directed

484.66

-

-

... More
M&L 4 mm thick frosted glass, and glazing with oil putty in square n exc 0.5 sq. m in each pane complete all as specified and directed

208.01

-

-

... More
M&L for preparation of new wooden surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and directed

2001.81

-

-

... More
Material and Labour for two coats of fire retardant paint over a coar red oxide primer to steel surfaces of doors complete all as specified and directed

338

-

-

... More
M&L for preparing the new plastered surfaces and applying two coat of FIRE RETARDANT PAINT over a coar red oxide primer on ceiling, complete all as specified and directed

219.03

-

-

... More
Painting 2 coats of synthetic enamel paint on steel and iron surfaces of any description over 10 cm in width or girth including preparation and one coat of red oxide primer complete all as specified and directed

10840.27

-

-

... More
Material and Labour for 2 coats fire retardant paint over a coar red oxide primer to walls and ceiling including preparation of newly plastered surfaces.complete all as specified and directed

12283.07

-

-

... More
M&L for preparing new steel surface n.exc 10cm in width or girth and apply two coat of synthetic enamel paint over a coat of redoxide zinc chrome primer complete all as specified and directed

14264

-

-

... More
Preparing ,cleaning new concrete/plastered surface and providing APP based polymeric membrane 3mm thick of weight not less than 3.6 Kg per Sqm re-inforced with non-woven fabric polyester over a coat of bitumen primer @ 0.30 liter/sqm and sealed with torch application and finish the surface with aluminium paint at top @ 0.2 kg/sqm as per manufacturer's instructions complete all as specified and directed.

20289.03

-

-

... More
Supplied and fixed 110mm dia PVC(SWR) pipes single soketed in any length with rubber ring jointed fixed to wall complete all as specified

6923.11

-

-

... More
M&L for reinforced concrete pipe, 600mm bore class NP-2 laid and joint with collars complete all as specified and directed

142.5

-

-

... More
M & L for Reinforced concrete pipes class NP-3 , 300 mm bore for protection of cables under road crossing, in trenches etc complete all as specified and directed

54

-

-

... More
M & L for Reinforced concrete pipes, 450 mm bore class NP-2 , laid and jointed with collars complete all as specified and directed

633.6

-

-

... More
M&L for DWCPE(SN8) single hume pipe 150mm internal dia pipes laid over 100mm thick bed including all items and activities to execute and make sewer line functional complete all as specified and directed

90

-

-

... More
M&L Writing letters/ Signs/ Arrows with fluorescent paint on both sides as directed weld complete all as specified and directed

60.48

-

-

... More
M&L 150mm thick soling (or sub base) spread thickness with broken boulders or quarried stones (90mm to 63mm size of boulders), inter stices filled surface formed and rolled and consolidate to required gradient and camber complete all as specified and directed.

10789.22

-

-

... More
M&L 200mm thick soling (or sub base) spread thickness with broken boulders or quarried stones (90mm to 63mm size of boulders), inter stices filled surface formed and rolled and consolidate to required gradient and camber complete all as specified and directed

781.2

-

-

... More
M&L 150mm thick (compacted thickness) WBM in two layers of 75mm each with broken stone aggregate of grading 2 (63 to 40mm size) or of grading 3 (50 to 20mm size), spread, rolled and conoslidated to required gradient, camber, level, super elevation with 8 to 10 ton power roller complete all as specified and directed.

10789.22

-

-

... More
M&L 200mm thick (compacted thickness) WBM in two layers of 100mmm each with broken stone aggregate of grading 2 (63mm to 40mm size) or of grading 3 (50mm to 20mm size), spread, rolled and consolidated to required gradient, camber, level, super elevation with 8 to 10 ton power roller complete all as specified and directed.

781.2

-

-

... More
M&L for preparation unsurfaced water bound macadam surfaces by brushing with wire brushes for removing caked mud etc, sweeping with brooms and finally fanning the clean surface with gunny bags to remove all loose dirt etc.complete all as specified and directed

11569.42

-

-

... More
M&L for applying evenly a priming/tack coat with bituminous primer of paving bitumen @ 10 kg per 10 sqm. complete all as specified and directed

10644.22

-

-

... More
Rolling and consolidating formation surfaces in cutting by 8 to 10 tonne power roller including filling depression which occurs during rolling complete all as specified and directed

11569.42

-

-

... More
M&L bituminous premix asphaltic semi dense concrete 40mm consolidated thickness with 5.5% binder, (paving bitumen any penetration) content by weight of total mix, rolled and compacted to required camber and gradient complete all as specified and directed

10644.22

-

-

... More
Cement concrete work in pavement/hard standing of flexural strength 40 Kg/per square centimetre in field using 400 kg of cement per cubic metre, thickness of concrete 25cm or less including necessary form work complete all as specified and directed.

1951.75

-

-

... More
Forming 12mm thick Expansion joints filled with pre-formed bituminous filler and top 30mm primed and sealed with sealing compound Grade A for 100mm thick slab complete all as specified and directed.

3.2

-

-

... More
Add or deduct from item 206 above for every 3mm depth of joint over or under complete all as specified and directed

12

-

-

... More
Forming 20mm thick Expansioln joints filled with pre-formed bituminous filler and top 30mm primed and sealed with sealing compound Grade A for 200mm thick slab complete all as specified and directed.

78.8

-

-

... More
Forming construction joint 30mm deep x 10mm wide filled with sealing compound Grade A. complete all as specified and directed

377

-

-

... More
RCC NP3 150 mm diameter Pipes laid on 150 mm thick PCC 1:4:8 type D-2 (using 40mm graded stone aggregate) (cradle) bed with excavation in any type of soil, including manholes/drop manhole of standard size made of Brick masonry with SFRC ventilating cover and frame. Including all items and activities to execute and make sewer line functional. (Laying depth of pipe varies from 0.7m to 1.65m below original ground level)

890

-

-

... More
On site hume pipe septic tank for 5 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

2

-

-

... More
On site LLDPE septic tank for 5 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

23

-

-

... More
On site LLDPE septic tank for 10 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

6

-

-

... More
On site LLDPE septic tank for 20 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

1

-

-

... More
On site LLDPE septic tank for 25 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

1

-

-

... More
On site LLDPE septic tank for 35 users. designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc, complete all as shown in drawing.

1

-

-

... More
M & L for RCC Septic tank (coventional type)for 100 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls , Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft , manhole openings with cover connection etc.,complete with effective depth of 1.5 meter and overall depth of 3 meter complete all as specified and shown on drawing No DIN/LOH/2021/MISC/ST/454 sheet 1/1 dated 23.08.2021

1

-

-

... More
M & L for Soakage wells of size 1.2x3.0m, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and shown on drawing No. TD/EM/6 Sheet 1/2-2/2

24

-

-

... More
M & L for Soakage wells of size 1.8x3.0m, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and shown on drawing No. TD/EM/6 Sheet 1/2-2/2

6

-

-

... More
M & L for Soakage wells of size 1.8x4.5m, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and shown on drawing No. TD/EM/6 Sheet 1/2-2/2

2

-

-

... More
M & L for Soakage wells of size 2.4x4.5m, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and shown on drawing No. TD/EM/6 Sheet 1/2-2/2

3

-

-

... More
Testing drains as specified to filling the pipes with water to a head of 1.5m at the highest point including temporarily fixing of bends, etc. as required not exceeding 150mm dia complete all as specified and directed

890

-

-

... More
Testing manholes as specified by filling with water complete all as specified and directed

80

-

-

... More
S&F 15mm bore GI Pipe medium grade with all fitings and fixed to wall and ceiling or laid in floor complete all as specified and directed

2771.5

-

-

... More
Supply & laying galvanized steel tubing "Light grade" of size 100 mm bore with GI fittings and laid in trenches/ under roads/ along pole/ wall for cable protection complete all as specified and directed

520

-

-

... More
Supply & laying galvanized steel tubing "Light grade" of size 80 mm bore with GI fittings and laid in trenches/ under roads/ along pole/ wall for cable protection complete all as specified and directed

280

-

-

... More
Supply & laying galvanized steel tubing "Light grade" of size 50 mm bore with GI fittings and laid in trenches/ under roads/ along pole/ wall for cable protection complete all as specified and directed

810

-

-

... More
Supply & laying galvanized steel tubing "Light grade" of size 40 mm bore with GI fittings and laid in trenches/ under roads/ along pole/ wall for cable protection complete all as specified and directed

1400

-

-

... More
Supply & laying galvanized steel tubing "Medium grade" with GI fittings and laid in trenches/ under roads size 40 mm bore complete all as specified and directed

579

-

-

... More
Supply & laying galvanized steel tubing "Medium grade" with GI fittings and laid in trenches/ under roads size 25 mm bore complete all as specified and directed

418

-

-

... More
Supply & laying galvanized steel tubing "Medium grade" with GI fittings and laid in trenches/ under roads size 20 mm bore complete all as specified and directed

6659

-

-

... More
Supply & laying galvanized steel tubing "Medium grade" of size 80 mm bore with GI fittings and fixtures from borewell to UG sump complete all as specified and directed

1450

-

-

... More
S&F 40mmdia GI Pipe ligth grade, fixed in wall complete all as specified and directed

48

-

-

... More
S&F 50mmdia GI Pipe light grade fixed in wall complete all as specified and directed

195.6

-

-

... More
Supply and fix 40mm dia Tubes, 'Medium grade' galvanised, with all fitting and fixed complete to walls and roofs or laid in floor for supports while extending air termination rod complete all as specified and directed.

1285

-

-

... More
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR-Part-I 500 Liter capacity complete all as specified and directed

37

-

-

... More
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR- Part-I 300 Liter capacity complete all as specified and directed

49

-

-

... More
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR- Part-I 1000 Liter capacity complete all as specified and directed

85

-

-

... More
S&F bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule of 15 mm bore and fixed complete all as specified and directed

339

-

-

... More
Pillar taps 15mm, cast copper alloy, with capstan heads, chromium plated,screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts,screwed for iron pipe and fixed complete all as specified and directed

192

-

-

... More
Supply & fixed stop valves, 15mm dia, cast copper alloy,CP, fancy type screwed down, high pressure with crutch or butter fly handle, screwed both ends for iron pipes or for unions and fixed in pipe complete all as specified and directed

441

-

-

... More
Supplying and fixing Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed of size 40 mm dia (1.5") all inclusive complete all as specified and directed

6

-

-

... More
Supplying and fixing Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed of size 25 mm dia (1.5") complete all as specified and directed

8

-

-

... More
Supplying and fixing Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed of size 20 mm dia (1.5") all inclusive as directed by Engr-in-charge

65

-

-

... More
Supply and Fix 75mm bore cast iron soil, waste and vent pipe, (spun) in any length laid in Floor complete all as specified and directed.

849.5

-

-

... More
Supply and Fix 100mm bore cast-iron soil waste and vent pipe, (spun) in any length laid in trenches / floor complete all as specified and directed

465.5

-

-

... More
Supply and Fix 75mm bore cast iron soil, waste and vent pipe in any length fixed to walls complete all as specified and directed

763.45

-

-

... More
Supply and Fix 100mm bore cast iron bends or diminishing pieces or tapers( larger bore measured) complete all as specified and directed.

190

-

-

... More
Supply and Fix 75mm bore cast iron bends or diminishing pieces or tapers( larger bore measured) complete all as specified and directed.

189

-

-

... More
Supply and Fix 100mm bore cast iron branch piece, single (equal or unequal), and ordinary or inverted or with parallel branches complete all as specified and directed.

190

-

-

... More
S&F cast iron cowl 75 mm dia with complete all as specified and directed

173

-

-

... More
Supplyig and fixed 75mm cast iron floor trap, with grating including jointing to waste pipe fixed in cement concrete type B-1 (1:2:4)(using 20mm graded stone) complete all as specified and directed

449

-

-

... More
Supply and laying un-reinforced precast concrete cable cover class LV, Type - 1 flat size 250 mm x 150mm x 40mm thick, complete all as specified and directed

334666

-

-

... More
S&G Salt-glazed stoneware gully traps,150X150 mm square or round mouthed, type 'P' complete all as specified and directed

120

-

-

... More
Supply and fix Vitreous China wash down water closet pan (pedestal pattern), white (excluding fixing bolts, flushing cistern and flush pipe) complete all as specified and directed

93

-

-

... More
S&F sinks made of stainless steel 1 mm thick kitchen or laboratory with plugs, washers and wastes; including bedding in cement mortar on to dwarf wall or including fixing cantilever brackets and connecting union to pipe, overall size 495mm x 420mm bowl size 410mm x 330mm x 160mm complete all as specified and directed

3

-

-

... More
Supply and fix vitreous china squatting pan ‘Orrisa pattern’ size 580 x 440 mm white, with integral foot rest complete all as specified and directed .

120

-

-

... More
Supply and fix vitreous china urinal flat back type of size of 465 x 355 x 265 mm white with grating and union for discharge pipe including providing and fixing of plugs, bedding against wall in cement mortar 1:2, securing urinal to plugs complete all as specified and directed.

19

-

-

... More
Supply and fix , 10 litres capacity, PVC valve less, syphonic action type flushing cistern, low level, white with inlet ball valve float, handle and flush pipe including brackets complete all as specified and directed

190

-

-

... More
Supply and fix vitreous china, wash hand basin, white, flat back, size 550 x 400 mm including brackets, brass chromium plated waste fitting complete all as specified and directed.

133

-

-

... More
Supply and fix counter top WHB with 600mmx 900 high mirror cover plate all as specified including brass chromium plated waste fitting complete all as specified and directed.

31

-

-

... More
Supply and fix 600mmx450mm bevelled edge mirror of selected quality glass, mounted on 6mm thick AC building board or commercial plywood and fixed to wooden plugs with chromium plated brass screws and cup washerscomplete all as specified and directed

152

-

-

... More
Partition for Urinal vitreous china of size 310x700mm complete all as specified and directed

42

-

-

... More
S&F 1.6mm thick PGI sheet as in chute for hose complete all as specified and directed

12

-

-

... More
S&F Puddle Flange 100mm dia complete all as specified and directed

8

-

-

... More
S&F PGI Sheet 18 gauge as water bar complete all as specified and directed

128.77

-

-

... More
S&F SS peg set of 3 complete all as specified and directed

105

-

-

... More
S&F Steel rolling shutters, (lath thickness 1.25) with out ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated, complete: push pull or manual type complete all as specified and directed

7.56

-

-

... More
M&L for Prestressed concrete pole, 9.0 metres long, 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 including writting MES Pole No. with synthetic enamel paint (first grade quality) complete all as specified. Note: (a) Earthwork and PCC will be measured and paid under appropriate items in of Schedule 'A'/BOQ (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.

854

-

-

... More
Steel Tubular Swaged Poles Type 410-SP-55 (11 Metre long) including cast iron base plate, finial taper plug, cap, mild steel bolts, screws, etc. including applying two coats of black bituminous paint internally and externally upto planting depth and applying two coats of aluminium paint over a coat of aluminium primer (externally from top of PCC copping) including writting MES Pole No. with synthetic enamel paint (first grade quality) complete all as specified. Note: (a) Earthwork and PCC will be measured and paid under appropriate items in of Schedule 'A'/BOQ (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.

10

-

-

... More
S & F Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome primer and two coats of alluminium paint including preparation of surfaces complete all as specified and as directed.

30

-

-

... More
M & L for Aluminium Conductor,Steel Reinforced of any size and type on HT, LT Poles including straining,binding with insulators with copper binding wire with insulators as in OH conductors, providing PVC Sleeves for jumper complete all as specified and as directed.

0.4

-

-

... More
M & L for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole

0.75

-

-

... More
Danger notice plate of size 25 X 20 cm of 1.6 mm thick mildsteel sheet vitreous enamelled white , with letters ,figures and conventional skull and bones in signal red colour and fixed with MS clamps , bolts and nuts of approved size for HT conforming to IS - 2551 complete all as specified and as directed .

10

-

-

... More
M & L for Swing out expulsion fuse single pole (drop out fuse) for 11000 Volts of capacity up to 200 Amps complete all as specified and as directed.

15

-

-

... More
Supply and fixing of Air break gang operated switch triple pole mechanically operated out door with all fitting/ accessories mounted on and including 11 KV porcelain insulator and steel channel frame GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated as per site requirement including locking arrangement for operating handle complete suitable for current rating 200 Amps 11 KV working pressure with 15 Insulators complete all as specified and directed by Engr in charge.

5

-

-

... More
Supply and fix Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp, suitable for 11000 V complete all as specified and directed.

5

-

-

... More
Supply, install, testing and commissioning of distribution Tranformer out door, step down,copper wound having primary side for HT 11KV & secondary for 3 phase 433 Volts, 4 wire 50 Hz capacity of 160 KVA and Energy efficient Level -3 as per IS 1180 of 2014 Part-I with the following specification :- (i) No load voltage ratio-11/.433 KV. (ii) Nos of phase-three. (iii) Type of cooling- ONAN. (iv) Frequency 50 Hz. (v) Vector group-DYN 1. (vi) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing. (vii) First fill of oil, oil level gauge indicating oil level minmum and maximum. (viii) Lifting lugs. (ix) Rating and terminal marking plates. (x) dehydrating breathing divice which would not permit ingress of rain water and insects. (xi) Drain-cum-sampling valve (3/4" nominal size thread) preferably steel with plug. (xii) Thermometer pocket. (xiii) Oil filling hole( 1-1/4" Nominal size thread) with cover. (xiv) Connection-Delta/Star. (xv) Temperature rise in oil-45 deg Centigrade. (xvi) Temperature rise in windings- 55 deg Centigrade. (xvii) Material winding-Copper wound. (xviii) High voltage/low voltage-Bushing with box (xix) Service-Outdoor type. (xx) Neutral- Internally connected with earthing lead and bush. (xxi) Off load tap changing (+ or - 7.5% in step of + or - 2.5% or as per IS relevant)

1

-

-

... More
Supply, install, testing and commissioning of distribution Tranformer out door, step down,copper wound having primary side for HT 11KV & secondary for 3 phase 433 Volts, 4 wire 50 Hz capacity of 200 KVA and Energy efficient Level -3 as per IS 1180 of 2014 Part-I with the following specification :- (i) No load voltage ratio-11/.433 KV. (ii) Nos of phase-three. (iii) Type of cooling- ONAN. (iv) Frequency 50 Hz. (v) Vector group-DYN 1. (vi) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing. (vii) First fill of oil, oil level gauge indicating oil level minmum and maximum. (viii) Lifting lugs. (ix) Rating and terminal marking plates. (x) dehydrating breathing divice which would not permit ingress of rain water and insects. (xi) Drain-cum-sampling valve (3/4" nominal size thread) preferably steel with plug. (xii) Thermometer pocket. (xiii) Oil filling hole( 1-1/4" Nominal size thread) with cover. (xiv) Connection-Delta/Star. (xv) Temperature rise in oil-45 deg Centigrade. (xvi) Temperature rise in windings- 55 deg Centigrade. (xvii) Material winding-Copper wound. (xviii) High voltage/low voltage-Bushing with box (xix) Service-Outdoor type. (xx) Neutral- Internally connected with earthing lead and bush. (xxi) Off load tap changing (+ or - 7.5% in step of + or - 2.5% or as per IS relevant)

2

-

-

... More
Supply, install, testing and commissioning of distribution Tranformer out door, step down,copper wound having primary side for HT 11KV & secondary for 3 phase 433 Volts, 4 wire 50 Hz capacity of 315 KVA and Energy efficient Level -3 as per IS 1180 of 2014 Part-I with the following specification :- (i) No load voltage ratio-11/.433 KV. (ii) Nos of phase-three. (iii) Type of cooling- ONAN. (iv) Frequency 50 Hz. (v) Vector group-DYN 1. (vi) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing. (vii) First fill of oil, oil level gauge indicating oil level minmum and maximum. (viii) Lifting lugs. (ix) Rating and terminal marking plates. (x) dehydrating breathing divice which would not permit ingress of rain water and insects. (xi) Drain-cum-sampling valve (3/4" nominal size thread) preferably steel with plug. (xii) Thermometer pocket. (xiii) Oil filling hole( 1-1/4" Nominal size thread) with cover. (xiv) Connection-Delta/Star. (xv) Temperature rise in oil-45 deg Centigrade. (xvi) Temperature rise in windings- 55 deg Centigrade. (xvii) Material winding-Copper wound. (xviii) High voltage/low voltage-Bushing with box (xix) Service-Outdoor type. (xx) Neutral- Internally connected with earthing lead and bush. (xxi) Off load tap changing (+ or - 7.5% in step of + or - 2.5% or as per IS relevant)

1

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size3 core 95 sq mm complete all as specified and directed.

2

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3 core 185 sq mm.complete all as specified and directed

1

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3 core 95 sq mm.complete all as specified and directed

12

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 3 core 185 sq mm.complete all as specified and directed

1

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 sqmm, Outdoor type complete all as specified and directed

4

-

-

... More
Material and labour for laying un-reinforced precast concrete cable cover, class HV, type 1 with peak, size 300x180x40 mm complete all as specified and directed. Note : All cable covers to be embossed with letters "HT CABLE" complete all as specified and directed

22788

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core complete all as specified and directed

30

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core complete all as specified and directed

8385

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core complete all as specified and directed

25175

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and directed

11666

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½ core complete all as specified and directed

2649

-

-

... More
M & L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 core complete all as specified and directed

5865

-

-

... More
.M & L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 core complete all as specified and directed

2746

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3½ core complete all as specified and directed

1628

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3½ core complete all as specified and directed

30

-

-

... More
M & L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 Sq mm 3.5 Core. complete all as specified and directed

2055

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3½ core complete all as specified and directed

2509

-

-

... More
Supply, laying and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3½ core complete all as specified and directed

746

-

-

... More
Supply, laying & testing HT cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and directed

4680

-

-

... More
Supply, laying & testing HT cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 185 sq mm complete all as specified and directed

50

-

-

... More
M&L point wiring with multiple stranded color code copper conductor FRLSH, cable 2 x1.5 sqmm size 1100 V grade IS-64 marked, including one run of single core stranded FRLSH copper conductor 1.5 sqmm PVC insulated cable as earth wire and connected to earth dolly drawn through and including stove enamelled steel conduit with all accessories/fittings, fixed/laid concreate in wall/ceiling and quoted rates also included white plate cover with flame flush mounting sunken metal suitable as per site requirement for mounting of flame proof switches/ sockets and push etc. all as directed for For one light point controlled by one way switches complete all as specified and directed

582

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One light point controlled by one,one way switch complete all as specified and directed

1797

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One Ceiling/Exhaust fan point controlled by one,one way switch complete all as specified and directed

526

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One light point controlled by two 2 - way switches complete all as specified and directed

32

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One 3 pin socket outlet 5 amps on the same board with other switches complete all as specified and directed

73

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One socket outlet point 6 A on independent board complete all as specified and directed

324

-

-

... More
M & L for Concealed Point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches, socket, regulators etc complete including FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for One bell/buzzer point controlled by one push button on the same board with other switches or independent complete all as specified and directed.

30

-

-

... More
M&L point wiring with multiple stranded color code copper conductor FRLSH, cable 2 x 4 sqmm size 1100 V grade IS-64 marked, including one run of single core stranded FRLSH copper conductor 4 sqmm PVC insulated cable as earth wire and connected to earth dolly drawn through and including stove enamelled steel conduit with all accessories/fittings, fixed/laid concreate in wall/ceiling and quoted rates also included white plate cover with flame flush mounting sunken metal suitable as per site requirement for mounting of switches/sockets and push etc. all as directed for the flame proof socket complete all as specified and directed.

38

-

-

... More
M & L for concealed Point wiring with 2.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multi stranded copper conductor single core cable drawn through and including non-metallic rigid PVC conduit of adequate size with all fittings and accessories including mild steel terminal boxes with laminated sheet for mounting switches & socket, including one run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 2.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one 16 Amp socket outlet on independent board complete all as specified and directed.

237

-

-

... More
S&F Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed

175

-

-

... More
S & F Piano Switch single pole flush type 6 Amp, 230 Volt complete all as specified and directed

2323

-

-

... More
S & F Piano Switch two way pole flush type 6 Amp, 230 Volt complete all as specified and directed

64

-

-

... More
S & F bell push single pole flush type 6 Amp, 230 Volt complete all as specified and directed

30

-

-

... More
S & F Buzzer, Ding Dong AC. 230 volts, single pole complete all as specified and directed

30

-

-

... More
S & F Switch Socket combination outlet flush type universal 2 in 1, 3 pin 5 and 15 Amps, 230 volt complete all as specified and directed

237

-

-

... More
S & F Switch Socket Combination outlet flush type universal 2 in 1, 3 pin 5 Amps, 230 voltcomplete all as specified and directed

397

-

-

... More
Supply and fix epoxy powder coated Distribution Board, double door SPN 8 way for MCBs with common bus-bar at incoming end of outgoing MCBs grouted/ flush to wall complete all as specified and directed

105

-

-

... More
Supply and fix epoxy powder coated Distribution Board, double door SPN 4 way for MCBs with common bus-bar at incoming end of outgoing MCBs grouted/ flush to wall complete all as specified and directed

22

-

-

... More
Supply and fix epoxy powder coated Distribution Board, double door TPN 4 way for MCBs with common bus-bar at incoming end of outgoing MCBs grouted/ flush to wall complete all as specified and directed

45

-

-

... More
Supply and fix single pointed air termination, single pointed aluminium rod,12 mm dia, 300mm long complete all as specified and directed.

514

-

-

... More
S&F test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 nos 08 mm dia 25mm long hex head screw complete all as specified and directed

134

-

-

... More
Supply and fixing Aluminium strip 25 x 3.15mm saddles and fixing screws etc. for roof conductors and down conductor above ground complete all as specified and directed.

5210

-

-

... More
S & F Ceiling rose surface bakelite three terminals complete all as specified and directed

1940

-

-

... More
Materials and labour for Earthing complete with GI earth plate electrode 60 cm X 60 cm X 6 mm thick, burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.50 mtr below normal ground level connected to GI earth lead 4 mm dia by means of GI bolts, nuts, check nuts, washers made out of GI/steel, all as shown on electrical plate No 3 of MES schedule part-I, earth lead strip connected to indicated position including 7.5m long 15 mm bore GI pipe for earth wire protection and concrete pit in PCC(1:3:6, C1),Precast RCC cover slab 55 cm x 55 cm x 5 cm with reinforcement of 8 mm dia bar 100 mm c/c bothways including one handle made of 12 mm dia MS bar embedded in pre cast slab and 20 mm bore galvanised iron pipe"medium grade" for watering with GI funnel and wire mesh including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil and testing on completion complete all as specified and as directed by Engineer in Charge.

241

-

-

... More
M&L Earthing with Galvanised Earth Plate Electrode 600x600x6.0mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with and including Galvanised Earth Strip of size 32x6.0mm by means of Bolts, Nuts, Check nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar with GI 40mm bore (dia) Light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) Medium grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion complete all as per specified and as directed.

228

-

-

... More
M & L for 4mm dia GI wire for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire drawn through light grade 15mm dia GI protection pipe complete all as specified and directed.

700

-

-

... More
Supply and fixing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Galvanized iron strip 32 x 6mm buried in ground complete all as specified and directed

4210

-

-

... More
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc as required and complete all as specified and directed

443

-

-

... More
M & L for Concealed Sub main Wiring with two run of 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multistranded copper conductor single core cable drawn through and including PVC Conduit of adequates size and fittings and accessories concealed in walls, floors and ceilings complete including one run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly complete all as specified and directed

1990

-

-

... More
M&L submain wiring with two single core PVC insulated (FRLSH) unsheathed multi stranded copper conductor cable confirming to IS-694-1990 of size 6 sqmm (nominal area) drawn through and including stove enamelled steel conduit with all accessories/fittings, fixed/laid concreate in wall/ceiling and continous PVC insulated single core copper conduit (FRLSH) stranded unsheathed 6 sqmm as earth wire complete all as specified and directed Note:(Two single core cable and one No. earth wire and one run of conduit shall be measured together as one length) complete all as specified and directed.

720

-

-

... More
M & L for Concealed Sub main Wiring with two run of 6 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multistranded copper conductor single core cable drawn through and including PVC Conduit of adequates size and fittings and accessories concealed in walls, floors and ceilings complete including one run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 6 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly complete all as specified and directed. Note:(Two single core cable and one No. earth wire and one run of conduit shall be measured together as one length) complete all as specified and directed.

800

-

-

... More
Supply and fixing weather proof flat twin core 2.5 Sqmm aluminium conductor complete all as specified and directed.

9600

-

-

... More
S & F BEE star-rated energy efficient LED retrofit bulb 12W CDL (6500K) B22 ball lamp complete all as specified and directed.

175

-

-

... More
S & F TPN MCB, 10KA, 'C' curve 10 Amps complete all as specified and directed.

10

-

-

... More
S & F TPN MCB, 10KA, 'C' curve 25 Amps complete all as specified and directed. .

13

-

-

... More
S & F TPN MCB, 10KA, 'C' curve 40 Amps complete all as specified and directed.

12

-

-

... More
S & F TPN MCB, 10KA, 'C' curve 63 Amps complete all as specified and directed. .

10

-

-

... More
S & F SPN MCB, 10KA, 'C' curve 10 Amps complete all as specified and directed. .

28

-

-

... More
S & F SPN MCB, 10KA, 'C' curve 25 Amps complete all as specified and directed. .

55

-

-

... More
S & F SPN MCB, 10KA, 'C' curve 40 Amps complete all as specified and directed. .

44

-

-

... More
S & F Single pole MCB, rupturing capacity 10 kA, 'C' curve , 6 to 32 Amp complete all as specified and directed.

832

-

-

... More
S & F Blanking plates complete all as specified and directed. .

200

-

-

... More
S & F Ceiling fan 1200mm sweep BEE 5 star rated model: ES-50 Premium make: Havells or equivalent in Usha/ Bajaj/Crompton Greaves and suspended from fan hook and electrically connecting with twisted three core PVC insulated unsheated flexible cord of 0.70 Sqmm copper conductor cable from ceiling rose to fan complete all as specified and directed. .

443

-

-

... More
Supply and fixing Exhaust fan 225 mm sweep metal body AC single phase 230V with self closing louvers, electrically connecting with twisted three core PVC insulated unsheated flexible cord of 0.70 Sqmm copper conductor cable from ceiling rose to Exhaust fan complete all as specified and directed. .

83

-

-

... More
S & F of LED batten with inbuilt driver made out of high quality aluminum extruded housing and aluminium heat sink for mounting LEDs, mercury free and decorative end caps with maximum power consumption 24 Watts with min system luminous efficiency lumen/watt 100, CCT not less than 6500K and CRI 80, operating voltage of 140-270 volts AC, P.F. 0.90, 2.5 KV surge protection and current THD 15% complete and including all other standard accessories as per manufacturer's instructions, internally pre-wired including connecting up with twin core 0.75 Sqmm copper conductor flexible wire/cable complete all as specified.

352

-

-

... More
S & F of LED batten with inbuilt driver made out of high quality aluminum extruded housing and aluminium heat sink for mounting LEDs, mercury free and decorative end caps with maximum power consumption 20 Watts with min system luminous efficiency lumen/watt 100, CCT not less than 6500K and CRI 80, operating voltage of 140-270 volts AC, P.F. 0.90, 2.5 KV surge protection and current THD 15% complete and including all other standard accessories as per manufacturer's instructions, internally pre-wired including connecting up with twin core 0.75 Sqmm copper conductor flexible wire/cable complete all as specified.

835

-

-

... More
S & F of LED batten with inbuilt driver made out of high quality aluminum extruded housing and aluminium heat sink for mounting LEDs, mercury free and decorative end caps with maximum power consumption 9-10 Wattswith min system luminous efficiency lumen/watt 100, CCT not less than 6500K and CRI 80, operating voltage of 140-270 volts AC, P.F. 0.90, 2.5 KV surge protection and current THD 15% complete and including all other standard accessories as per manufacturer's instructions, internally pre-wired including connecting up with twin core 0.75 Sqmm copper conductor flexible wire/cable complete all as specified.

234

-

-

... More
S & F new generation energy saving and environmental friendly long life LED security light 20 watts made up of pressure die cast alluminium housing with high power LED as light source and lense embedded PC cover having TOP OPENING separate driver compartment with IP65 protection and impact resistance of IK07, with all accessories including suitable bracket with 25mm bore light grade GI pipe bemd to shape, including MS clamp of size of required size and PVC cable 1.5 Sqmm twincore from ceiling rose to light fittings complete all as specified and directed

199

-

-

... More
M&L for switch flame proof rotary type with termination box in LM6,16A, single pole 250V complete all as specified and directed. .

582

-

-

... More
M&L for flame proof switch & plug combined in LM6 cable termination box in LM6, 16A,250V,2P+ earth. complete all as specified and directed.

38

-

-

... More
S&F CIMFR certified 20W LED flameproof batten suitable for single T8 tube of 20 Watts, IP 65 protected complete all as specified and directed. .

470

-

-

... More
S&F CIMFR certified 30W LED flameproof Wellglass in die cast Aluminium housing with heat resistant toughened glass, IP 65 protected.

112

-

-

... More
S & F LED Bulk head light fitting comprising of pressure die cast housing with acrylic diffuser (IP65 protection) complete all as specified and directed.

2

-

-

... More
Single Phase Kwh meter with LCD display, base mounting type 1P LCD Meter 5-30A with BOX enclosed in Hot press moulded SMC Meter box of size 250x200x100mm with single door having viewing glass complete all as specified and directed. .

10

-

-

... More
Supply , installation, testing and commissioning of Flame proof EOT Crane of 3 MT capacity, class M-5 indoor operation (without cabin) as per IS 807 & 3177 , Double Girder and having a span 18.00 metre and hook height upto floor level, longitudinal travel 36.00 metre inside the shed area with electrically operated high speed & micro speed through pendent push button station floor operated type complete with supply of not less than 50mm sq bar rail at both side and trailing cables ( extra flexible having copper conductors only) should be travelling on rollers moving on separate I- beam parallel to Bridge Girder CT shall be supplied with ready chain system tongue and groove type. For LT shrouded busbar 200 A rated GI type PVC insulated current collector system totally enclosed flame froof type to be provided, complete with an including main frame, bridge girder , end carriages, trolley with frame, crabs, buffers, gear with boxes , shafts, rope drum , rope sheaves/rope guides,wire rope, wheels, lifting hooks, brakes, bottom blocks induction motor ,variable voltage & variable frequency drive( VVVF drive), limit switches, emergency switches , wrong connection prevention device, protection pannel/ control gear , resistor pendent push button station,current collection,wiring earthing connection etc and including all other standard accessories and all as specified in particular specifiations, section 24 of SSR part-I and manufature instruction and complete all as specified as directed. Note:- (a) The contractor shall measure the exact lenghts of span for cross travel (CT) and bay length for longitudinal travel (LT) before preparation of GA Drawings. The item shall be complete all as per manufacturers specifications including control panel (to be installed outside the room. (b) Gantry girder for LT travel shall be provided under lumpsum of Schedule 'A'. LT rail bar shall be provided by the EOT Crane manufacture rate is deemed to be included in above quated rate.

2

-

-

... More
Supply and fix Detectors flame proof complying with and type certified to EN-45 Addressable type smoke detector Photoelectric / Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed.

278

-

-

... More
Supply and fix Fire Alarm sounders / Sirens electronic type horizontal double mounting single phase, continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 meter with sound output variation of + 5 DB for not less than 3500 meter range (diameter) with DOL starter with addl auxillary control (NO+NC) complete. (to be fixed outside the building)

28

-

-

... More
Wiring 2 runs of 1.5 mm PVC insulated copper cable HRFR-LSH with ISI mark drawn through surface type flame proof 16 SWG steel conduit incl flame proof junction boxes and accessories complete all as specified.

6680

-

-

... More
Supplying and fixing valves, sluice, flanged of class 1.0PN of size 80 mm dia (3") complete all as specified and directed.

4

-

-

... More
Supplying and fixing valves, sluice, flanged of class 1.0PN of size 150 mm dia (6") complete all as specified and directed.

17

-

-

... More
Supplying and fixing valves, sluice, flanged of class 1.0PN of size 100 mm dia (4") complete all as specified and directed.

8

-

-

... More
Supplying and fixing Reflux Valves (NRV) with by pass arrangement supplied and installed complete of size 150 mm (6") complete all as specified and directed.

2

-

-

... More
Supplying and fixing Reflux Valves (NRV) with by pass arrangement supplied and installed complete of size 100 mm (4") complete all as specified and directed.

2

-

-

... More
Supplying and fixing Reflux Valves (NRV) with by pass arrangement supplied and installed complete of size 80 mm (3") complete all as specified and directed.

4

-

-

... More
Fire alarm control panel complying with BS EN 54 Single loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules all as specified in SSR Part-I. Note : The panel shall be fixed outside the building. Earthing wire 4mm dia for Fire Alarm control panel shall be measured and paid in relevant item under Sch-A.

13

-

-

... More
Supply and install Addressable control module complete all as specified and directed.

28

-

-

... More
Supply and fix Addressable manual call point resettable type complete all as specified and directed.

28

-

-

... More
Supply, installation, commissioning of 200 Ltrs Glass Top Deep Freezer single phase 240 volt, 50 Hz complete all as specified and directed. .

5

-

-

... More
Supply, installation, commis-sioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity of 40 litre and nominal cooling capacity of 40 Litres per hour complete all as specified and directed.

2

-

-

... More
Supply, installation, commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity of 80 litre and nominal cooling capacity of 40 Litres per hour complete all as specified and directed. .

8

-

-

... More
Supply, installation, commis-sioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity of 120 litre and nominal cooling capacity of 60 Litres per hour complete all as specified and directed. .

1

-

-

... More
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 1 KVA complete all as specified and directed.

4

-

-

... More
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2 KVA complete all as specified and directed.

15

-

-

... More
Supply and fix refrigerator, electric driven (single phase), capacity 195 Litres .BEE 5 star rated complete all as specified and directed.

2

-

-

... More
Supply and fix refrigerator, electric driven (single phase), capacity 310 Litres.BEE 5 star rated complete all as specified and directed.

3

-

-

... More
Constructing Solid blocks masonary chamber 1250x1250x1100mm inside with 75 class designation brick work in cement mortar 1: 4 ( 1 cement : 4 coarse sand ) for sluice valve with 600x600mm internal dimension(10 Ton load bearing) FRP cover with frame and RCC top slab 1:2:4 mix(1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size) necessary excavation, foundation concrete 1:5:10 (1 cement :5 fine sand:10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3(1 cement :3 coarse sand) 12mm thick finished with a floating coat of neat cement complete as per standard design. Solid blocks of approved quality and class designation 5 having compressive strength of 4-6 N/sq.mm. complete all as specified and shown in drawing

19

-

-

... More
Constructing Solid blocks masonry Chamber 60x60x60 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for valve chamber, with FRP cover with frame 600x600mm internal dimensions (10 ton load bearing) i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design with Solid blocks of approved quality and class designation 5 having compressive strength of 4-6 N/sq.mm complete all as specified and shown in drawings .

79

-

-

... More
Supply & laying and jointing 100mm dia Ductile Iron pipe, with spigot and socket ends suitable for push on rubber joint centrifugally cast Class “K-9” inner side cement lining and outer side black bitumen coating laid in trenches including push on rubber (EPDM) ring with ISI marked complete all as specified and directed. .

129

-

-

... More
Supply & laying and jointing 150mm dia Ductile Iron pipe, with spigot and socket ends suitable for push on rubber joint centrifugally cast Class “K-9” inner side cement lining and outer side black bitumen coating laid in trenches including push on rubber (EPDM) ring with ISI marked complete all as specified and directed. .

5446

-

-

... More
Supply & fixing of ductile iron pipe fittings / special sutable for flange, spigot & socket ductile pipe as per IS 9523/2000 of class K-12, PN-10 upto 150 mm dia complete all as specified and directed.

1200

-

-

... More
Supplying and fixing flanged Cast Iron Air release Valves with two air Outlets, 150 mm dia bore and fixing Up in cast iron water supply mains complete all as specified and directed. .

2

-

-

... More
Supplying and fixing flanged Cast Iron Air release Valves with two air Outlets, 100 mm dia bore and fixing Up in cast iron water supply mains complete all as specified and directed. .

4

-

-

... More
Supply, install, testing and commissioning of centrifugal pump set mono block, electrically driven 3 ph, 415 volts, 'F' class insulation IP 55 protection completed with pumpset MS metal body, CI impeller with discharge 630 LPM & minimum head 100 mtr, suction and delivery size 100x100 mm make Kirloskar or equilent including base frame and brass metal body footvalve 100 mm dia ISI mark dia, pressure guage 0 to 7 Kg/cm2, necessary electrical connections from starter to motor with 10 sqm copper conductor incl. foundations as per manufactures specifications complete all as specified and directed by Engr-in-Charge.

2

-

-

... More
Supply, install, testing and commissioning of centrifugal pump set mono block, electrically driven 3 ph, 415 volts, 'F' class insulation IP 55 protection completed with pumpset MS metal body, CI impeller with discharge 420 LPM & minimum head 100 mtr, suction and delivery size 100x100 mm make Kirloskar or equilent including base frame and brass metal body footvalve 100 mm dia ISI mark dia, pressure guage 0 to 7 Kg/cm2, necessary electrical connections from starter to motor with 10 sqm copper conductor incl. foundations as per manufactures specifications complete all as specified and directed by Engr-in-Charge.

2

-

-

... More
Supply, install, testing and commissioning of booster pump set mono block type, electrically driven 3 ph, 415 volts, 'F' class insulation IP 55 protection completed with pumpset MS metal body, CI impeller with discharge 40 LPM & minimum head 160 mtr, Make: Kirloskar or equilent including base frame and PVC/MS sheet to cover the pumpset from rain & dust, necessary electrical connections from starter to motor with 4 Sqmm PVC insulated and armoured copper conductor cable, including foundations as per manufactures specifications complete all as specified and directed by Engr-in-Charge.

6

-

-

... More
Supply and fix PVC Tank of capacity 6000 Ltrs( Two tanks of 6000 ltrs each for booster pumps at one location- Total six tanks for three locations) on PCC staging 300mm above ground level.

6

-

-

... More
Supply, install , testing and commissioning of Chemical Dozing System alongwith Injector with following specification with complete accessories like lead tubing, connecting ferrules, check valves etc all as specified and as directed. Specification:- (i) Preparation Tank: Capacity of not less than 170 Ltrs FRP dozing tank of size not less than 650mm x net height, 375mm + conical 300mm gross height with stand 100mm consisting of:- (a) Water inlet line. (b) Outlet with strainer, (c) Drain, (d) Overflow, (e) Conical bottom for sludge deposition, (f) Pot hole with cover, (g) Level gauge, (h) Agitator 120W, 900 RPM, 1 phase flange mounted motor with plastic shaft and impeller. (ii) Service Tank : Capacity of not less than 100 Ltr of FRP dozing tank of top dia not less than 540mm x bottom dia 480mm x height 575mm consisting of :- (a) Water inlet line, (b) Outlets with Y strainer, (c) Drain, (d) Overflow, (e) Level gauge, (f) Agitator 120W, 900 RPM, 1 Phase flange mounted motor with plastic shaft and impeller, (g) Inspection port, (h) Provision of mounting pump on lid/wall. (iii) Dozing Pump/Injector: Maximum pressure 4 Kg/cm² and max flow rate 6 litre/hr. (Note: (i) Dosing system suitable for sodium hypochlorite solution. (ii) The dosing will be acomplished at the settling tank before discharge of treated waste water to environment.

2

-

-

... More
Supplying , installation , testing & commissioning of cubical type LT panel floor mounted indoor type suitable for 415 V , 3 phase, 4 wire, 50 HZ A C supply system having front surface area 4.5 sq. mts (app.) comprising of the followings :- (Pump House No:01) (i )Enclosure fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates, i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade having 500 Amp capacity extensible type TPN Aluminium bus bars of high condutivity, DMC/SMC bus bar supports, with short circuit protection, bottom base channel of MS not less than 100mm x 50 mmx 5 mm fabrication shall be done in transpotable sections, entire enclosure shall have a common copper earth bar of size 25mm x 5 mm at the rear with 2 nos earth studs, solid connection from main bus bar to swich gears with required size of al. bus bars and control wiring with minimum 2.5 sq. mm PVC insulated copper conductor single core , cable alleys, cable gland plates in two half etc complete as required. Incoming (i) MCCB FP 63 Amps, 16KA - 01 No (ii) Supply and install ON LOAD change over switch 415V in sheet metal enclosures 3 pole of capacity 63 Amps - 01No (iii) Volt meter 0-500 Volts with selector switch - 01 No (iv) Amp meter 0 to 200 with CT's selector Switch - 02 Nos (v) Indicating lamp set of 3 - 01 No (vi) Aluminium busbar FP 400 Amps, - 01 set Outgoing (i) MCCB TP 40 Amps, 16KA - 2 Nos (ii) MCCB TP 25 Amps, 16KA - 2 Nos (iii) Star Delta starter suitable for item No 18 - 2 Nos with Start/Stop push button with single phase preventer.

1

-

-

... More
Supplying , installation , testing & commissioning of cubical type LT panel floor mounted indoor type suitable for 415 V , 3 phase, 4 wire, 50 HZ A C supply system having front surface area 4.5 sq. mts (app.) comprising of the followings :- (Pump House No:02) (i ) Enclosure fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates, i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade having 500 Amp capacity extensible type TPN Aluminium bus bars of high condutivity, DMC/SMC bus bar supports, with short circuit protection, bottom base channel of MS not less than 100mm x 50 mmx 5 mm fabrication shall be done in transpotable sections, entire enclosure shall have a common copper earth bar of size 25mm x 5 mm at the rear with 2 nos earth studs, solid connection from main bus bar to swich gears with required size of al. bus bars and control wiring with minimum 2.5 sq. mm PVC insulated copper conductor single core , cable alleys, cable gland plates in two half etc complete as required. Incoming (i) MCCB FP 63 Amps, 16KA - 01 No (ii) Supply and install ON LOAD change over switch 415V in sheet metal enclosures 3 pole of capacity 63 Amps - 01No (iii) Volt meter 0-500 Volts with selector switch - 01 No (iv) Amp meter 0 to 200 with CT's selector Switch - 02 Nos (v) Indicating lamp set of 3 - 01 No(vi) Aluminium busbar FP 400 Amps, - 01 set Outgoing (i) MCCB TP 40 Amps, 16KA - 2 Nos (ii) MCCB TP 25 Amps, 16KA - 2 Nos (iii) Star Delta starter suitable for item No 18 - 2 Nos with Start/Stop push button with single phase preventer.

1

-

-

... More
Supply, installation, commissioning and testing of cubical type main control panel outdoor type made out of CRCA sheet 3.15 mm thick with powder coated painting and four Nos of 100 amps Aluminium strips / bars duly insulated mounted on insulators / suitable size bakelite sheet and including voltmeter, ammeter with selector switches for incomming and outgoing, CT's, RYB indicating lamp, PVC insulated copper cable for control wiring, steel cable glands of suitable size, complete all for following incomming / outgoing configuration complete all as specified and as directed. Incoming (i) MCCB FP 32 Amps 16 KA - 01 No (i) Volt meter 0-500 Volts with selector switch - 01 No (iii) Amp meter 0 to 200 with CT's selector Switch - 02 Nos (iv) Indicating lamp set of 3 - 01 No (v) Aluminium busbar FP 100 Amps, - 01 set Outgoing (i) MCCB TP 25 Amps, 10KA - 2 Nos (i) MCCB TP 25 Amps, 10KA - 2 Nos (ii) DOL starter suitable for item No 19 above - 02 Nos with single phase preventer.

3

-

-

... More
Supply, installation, commissioning and testing of cubical type main control panel outdoor type made out of CRCA sheet 3.15 mm thick with powder coated painting and four Nos of 200 amps Aluminium strips / bars duly insulated mounted on insulators / suitable size bakelite sheet and including voltmeter, ammeter with selector switches for incomming and outgoing, CT's, RYB indicating lamp, PVC insulated copper cable for control wiring, steel cable glands of suitable size, complete all for following incomming / outgoing configuration complete all as specified and as directed. (i) MCCB FP 63 Amps - 01 No(ii) Volt meter 0-500 Volts with selector switch - 01 No (iii) Amp meter 0 to 200 with CT's selector Switch - 01 No(iv) Indicating lamp set of 3 - 01 No(v) Aluminium busbar FP 200 Amps, - 01 set(vi) Cxapacitor 5 KVAR with Contactor - 01 No(vii) Single phase preventer - 01 No(viii) Submersible Pump Starter fully automatic 415 volts suitable for item No 17 above.(ix) Supply and fix time switches 415 V three Phase of 20 Amp rating with contactor Fitted inside steel enclosure

2

-

-

... More
M&L for drilling of bore not less than 400 mm dia suitable for 200 mm dia housing pipe upto 30 mtrs depth below ground level (BGL) and 30 to 100 m BGL for 150 mm dia pipe by combination rig (DTH + Reverse Rotary Rig Method), through any kind of soil, boulders, rocks etc. as required at site including disposal of spoil from the site of work complete all as specified & as directed. Note:(i) After complete drilling of the trial bore/ bore electric logging shall be carried out for exact selection of strata & the same will be measured & paid separately under relevant items of schedule. Pipe quanties/ Gravel given below shall be measured and paid accordingly for the depth of borewell required and quantity executed at site irrespective of quantity of material brought at site (ii) In case the results of the borehole/ strata are found un-satisfactory & the tubewell is not likely to yield the specified quantity of water, the site will be abandoned & the contr shall be paid for the boring only.

400

-

-

... More
Shifting of T&P to site and back for and including Electric logging of bore for precise delineation of granular zones & also the quality of ground water including report interpretation complete all as specified & as directed. NOTE:- Electric logging shall be carried out by any approved Govt Agency

2

-

-

... More
Supplying and assembling including jointing, lowering & fixing in position ERW casing pipe fine cut of internal dia 200 mm bore of thickness 6.35 m confirming to IS 4270-2001 or IS 3589 (ISI marked), screwed, socketed including jointing of pipe by necessary electric arc welding with 04 Nos stiffners of flat iron 40 x 6mm thick, 300 mm long both sides. The pipe shall be duly painted with anti-corrosive paint suitable for drinking water purpose complete all as specified & directed by Engr-in-Charge.

80

-

-

... More
Supplying and assembling including jointing, lowering & fixing in position ERW casing pipe fine cut of internal dia 150 mm bore of thickness 6.35 m confirming to IS 4270-2001 or IS 3589 (ISI marked), screwed, socketed including jointing of pipe by necessary electric arc welding with 04 Nos stiffners of flat iron 40 x 6mm thick, 300 mm long both sides. The pipe shall be duly painted with anti-corrosive paint suitable for drinking water purpose complete all as specified & directed by Engr-in-Charge.

254

-

-

... More
Supply lowering and fixing/ jointing 150 mm bore low carbon galvanised (LCG) strainer min 6.35 mm thickness each conforming to IS 8110:2000 including mild steel socket threaded/ by electric arc welding both sides all as specified and directed with aperture 0.75 mm to 1 mm as per requirement. Note for item No 3 to 5: Pipes shall be of length ~ 6 m unless required in smaller lengths as per borewell requirement.

60

-

-

... More
M&L for MS Taper reducer of 200 x 150 mm made out of 10 mm thick sheet with and including socket threaded as per IS 226: 1975and by electric arc welding both sides complete all as specified and as directed.

2

-

-

... More
Supply and fixing bail plug of 150 mm internal dia threaded of minimum thickness 6.35 mm and 3 mtr long made up of mild steel and continuous welded by electric arc welding at both ends complete all as specified as per IS 226: 1975 and directed.

2

-

-

... More
Material and labour for packing pea graval 3 to 5 mm (or as per Geologist report) of size as per IS of natural shape brought directly from river bed duly screened and packing around the casing pipe of MS to entire depth of tubewell upto ground level complete all as specified & as directed.

22

-

-

... More
Supply and fixing well cap as per IS 226 : 1975 suitable for 200 mm bore housing pipe made out of 6 mm thick steel plate complete all as specified and directed. NOTE : After completion of the work well cap will be used to keep the bore well closed until the submersible pumping set is installed.

2

-

-

... More
M&L for development of tube well with air compressor as per IS 11189-1985 of suitable capacity till sand/mud free water of potable quality is obtained & to achieve minimum discharge capacity of 36000 LPH /max yield or as directed by GE (Compressor with accessories & tube etc. shall be arranged by the contractor) complete all as specified & as directed.

24

-

-

... More
Development of tube well as per IS 11189: 1985 by over pumping 25% using suitable size/type pump after completion of item above, including yield testing for both tube well as per IS 2800-2 1979. NOTE :- Yield test of both bore well shall be carried out in the presence of rep of Accepting Officer.

12

-

-

... More
Supply only strata sample box with glass cover 3mm thick having internal dimension 1000x600x100mm made out of 20mm thick wrought Ist class hard wood shisham with hinges, hasp and staple including polishing complete with samples at various depth evenly 2 mtr interval met in boring including lithological log strata chart in duplicate all as directed and specified. Note : The contractor should also make and provide a record of discharge, draw down and depth to water level duly recorded in duplicate for official information and record.

2

-

-

... More
M&L for sanitary sealing of tube well with PCC (1:2:4) type B1 of suitable size using 20 mm graded aggregate of size 1mx1mx1m with embedded gravel feed pipe of GI medium grade 80 mm size 2 m long with cap complete all as specified and as directed

2

-

-

... More
Testing of raw water & treated water from approved Govt lab for potability by doing chemical (specially for iron (Fe, fluroide (F) and arsenic (As)) and bacteriological analysis as per norms of WHO and submission of test reports to the entire satisfaction of Engineer-in-Charge.

2

-

-

... More
S&F mild steel well clamp suitable for 200 mm dia MS column pipe made out of 12 mm thick MS plate fabricated to shape, including drilling holes, nuts, bolts, washers etc complete all as specified as per IS 226: 1975 complete all as specified and as directed

2

-

-

... More
S&F centering guide suitable for 150 mm dia screen pipe with sizes as per IS 2800 Part I complete all as specified and as directed

2

-

-

... More
Supply, install, testing and commissioning of Submersible pumpset, electric driven 415 V, TP suitable for150 mm dia bore well with discharge 125 LPM & minimum head 100 mtr, necessary electrical connections as per manufactures specifications complete all as specified and directed by Engr-in-Charge. (In case head & discharge required for pumps is different based on actual yield of borewell, rate of pump will be paid pro-rata) complete all as specified and as directed

2

-

-

... More
Material & Labour for PVC insulated sheathed waterproof flat submersible cable 3 core 6 Sqmm complete all as specified and as directed

160

-

-

... More
Supply & laying galvanized steel tubing "Heavy grade" of size 50 mm bore with long GI sockets and GI fittings in borewell all as specified & directed by EIC.

80

-

-

... More
Fixing cost for MS reducer , bail plug , well cap, MS strip for centering , MS Iron clamps, electric logging and sample strata box complete all as specified and as directed

2

-

-

... More
Water test analysis (chemical & biological) for bore well insttalation conferming to relevant IS Codes complete all as specified and as directed

2

-

-

... More
Supply, installation, testing and commissioning of 2.0 Ton capacity chain pully block with 6 mt chain and all acessories all as per detailed specifications and direction of engineer in charge

2

-

-

... More
Supply and Installation of Iron Removal cum Pressure Fiter plant (to improve iron content 10 PPM incoming to 0.3 PPM) shell: 8 mm, dish & bade plate 10 mm working pressure 3.5 kg / cm2 with oxidation chamber, inlet, outlet, backwash, rinse facilities, and complete provn of man hole, hand hole, under bed plate fitted with pvc strainer, air vent system, C I Butter Fly valves ( wefer and lever operated ) , MS / UPVCFrontal Pipeline (medium grade), suitable air compressor, 06 ltrs/hr @ 04 kg back pressure, 100 ltrs cap. Solution preparation cum settling tank model: CDS 100 of Ramco or equivalent of others fitted with gear motor and S S agitateor, filter medis, Mno2 etc as complete including Suitable CIVIL PLATFORM with foot stool foundation including drain and pit to accommodate the entire plant ,PAINTING - Entire filtration plant as final paint, MISC. FITTINGS - like TEE, BEND, Sluice valves, MS pipe in required length and quantity including welding ch. to connect filter plant with existing raw water line of capacity 250 LPM.

1

-

-

... More
Supply, installation, testing and commissioning of silent type Diesel Engine driven Generating set Water cooled type, 415 volts, 3 phase 4 wire (Engine as per IS: 10001/10002 and alternator as per IS: 13364) complete with foundation as per manufacturer's recommendation, standard control panel with necessary protection and meters including sound proof canopy of capacity 100 KVA including the following: - (a) ENGINE Diesel engine prime mover of suitable BHP to drive 100 KVA alternator with the following: - (i) Fuel level indicator(ii) Fuel tank of suitable capacity for storing minimum 8 hrs consumption capacity at 75% load.(iii) Fuel inlet arrangement from outside the acoustic enclosure with locking arrangement.(iv) Robust, MS base frame with anti vibration damper pads(v) Continuous 10% overload capacity in every 12 Hrs running.(vi) Self starting with and including suitable maintenance free battery of suitable AH rating as per OEM including charging circuit.(vii) Mechanical or Electronic governor as per OEM.(b) ALTERNATOR 100 KVA at 0.8 PF (lag), 415 volt, 3 phase, 4 wire, 50 Hz, 1500 RPM copper wound with the following: -(i) Self regulated brushless self excitation.(ii) Automatic voltage regulator with band of voltage regulation: + 2.5% of rated voltage.(c) CONTROL PANELFactory fabricated free standing of suitable size copper bus bar with the following: -(i) MCCB 4 pole, 415 Volt, 3 phase of 160 Amps, 25 KA as per OEM.(ii) Internal wiring with suitable size copper conductor(iii) Start and Stop push button(iv) Digital voltmeter with selector switch(v) Digital frequency meter(vi) Digital ammeter with 3 Nos CT and selector switch(vii) Digital power factor meter(viii)Three phase energy meter(ix) Tripping arrangement with hooter for 'High engine temp', 'Low lub oil pressure', 'High lub oil temp', Low and high engine speed' etc as per manufacturers' design.(d) ACOUSTIC ENCLOSURE It should be compact, modular construction and approved by ARAI (nodal agency of CPCB) with the following: -(i) Overall noise level less than 75 dB measured at 1 mtr distance in free field condition.(ii) Inside illumination provide with 2 Nos 1 x 9 watt LED light fitting or as per manufacturers' design. Note: - (i) The cost of foundation for installing the DG Set as per manufacturers' recommendation and is deemed to be included in the quoted rate (ii) First filling of fuel (DHPP(N) for 12 hours load test purpose shall be provided and cost deemed to be included in the quoted rate.(ii) Any accessories not mentioned but included in manufacturers standard modules are deemed to be included in the quoted rate.]

1

-

-

... More
Supply, installation, testing and commissioning of silent type Diesel Engine driven Generating set Water cooled type, 415 volts, 3 phase 4 wire (Engine as per IS: 10001/10002 and alternator as per IS: 13364) complete with foundation as per manufacturer's recommendation, standard control panel with necessary protection and meters including sound proof canopy of capacity 30 KVA including the following: - (a) ENGINE Diesel engine prime mover of suitable BHP to drive 30 KVA alternator with the following: -(i) Fuel level indicator(ii) Fuel tank of suitable capacity for storing minimum 8 hrs consumption capacity at 75% load.(iii) Fuel inlet arrangement from outside the acoustic enclosure with locking arrangement.(iv) Robust, MS base frame with anti vibration damper pads(v) Continuous 10% overload capacity in every 12 Hrs running.(vi) Self starting with and including suitable maintenance free battery of suitable AH rating as per OEM including charging circuit.(vii) Mechanical or Electronic governor as per OEM.(b) ALTERNATOR 30 KVA at 0.8 PF (lag), 415 volt, 3 phase, 4 wire, 50 Hz, 1500 RPM copper wound with the following: -(i) Self regulated brushless self excitation.(ii) Automatic voltage regulator with band of voltage regulation: + 2.5% of rated voltage.(c) CONTROL PANEL Factory fabricated free standing of suitable size copper bus bar with the following: -(i) MCCB 4 pole, 415 Volt, 3 phase of 63 Amps, 25 KA as per OEM.(ii) Internal wiring with suitable size copper conductor(iii) Start and Stop push button(iv) Digital voltmeter with selector switch(v) Digital frequency meter(vi) Digital ammeter with 3 Nos CT and selector switch(vii) Digital power factor meter(viii)Three phase energy meter(ix) Tripping arrangement with hooter for 'High engine temp', 'Low lub oil pressure', 'High lub oil temp', Low and high engine speed' etc as per manufacturers' design.(d) ACOUSTIC ENCLOSURE It should be compact, modular construction and approved by ARAI (nodal agency of CPCB) with the following: -(i) Overall noise level less than 75 dB measured at 1 mtr distance in free field condition.(ii) Inside illumination provide with 2 Nos 1 x 9 watt LED light fitting or as per manufacturers' design.[Note: - (i) The cost of foundation for installing the DG Set as per manufacturers' recommendation and is deemed to be included in the quoted rate (ii) First filling of fuel (DHPP(N) for 12 hours load test purpose shall be provided and cost deemed to be included in the quoted rate.(ii) Any accessories not mentioned but included in manufacturers standard modules are deemed to be included in the quoted rate.]

4

-

-

... More
Supply and installation,testing and commissioning of indoor type VCB panel board (with 01 Incomer + 2 Outgoing) motorised as well as manually charged fully interlocked, horizontal draw-out type with ingress protection rating IP4X, floor mounted, 11 KV, 3 Ph, 50 Hz AC supply system, indoor metal clad type, factory built fabricated out of 2mm thick CRCA sheet steel and extensible on either sides, free standing, floor mounted type with track mounted VCB vertical isolation, Aluminium busbar capacity not less than 800 Amps, pre wired for controller & acessories using copper conductor, provn for cable entry / outgoing system complete and comprising of the following:- (i) HT Vacuum Circuit Breaker switch gear of working voltage 11 KV, Current rating 800 Amps, 3 Phase, 50 Hz Ac supply, breaking capacity 25 KA for 3 seconds at rated voltage making capacity 65.75 kA at rated voltage, impulse withstand voltage 75kVp, Min. power frequency withstand voltage 28 kV, closing & shunt trip coils suitable for 110V DC, etc from power pack of suitable capacity. (ii) Numerical relay REJ 601 or equivalent model for E/F, O/L and short circuit fault incl antipumping operation and accordingly trip coil operations. (Make : Seimens/Alstom/ABB) (iii) Alarm annunciator for DC supply fail/trip. (iv) Multifunction meter 3 Ph, 4 wire, CL-1 with RS485 Port (digital flush mounted typy) to indicate various parameters incl Current, Voltage, KVA, Demand, KW, PF, Frequency, etc. (v) LED indicator lamp for RYB, phase healthy, breaker ON/OFF, trip circuit healthy, spring charged. Breaker control switch. (vi) Push button for check trip healthy & emergency trip. (vii) Switch for closing/tripping of VCB. (viii) CTs with ratio 200/100/5-5 Amps (Accuracy class-1, 10 VA for metering, 5 P10, 15 VA for protection. (ix) PTs (3P/3L Drawout, 11KV/RT3/110V/RT3 Core-1-50VA, CL-1) shall be provided on the incoming side and the PT shall be mounted independently on a seperatre drawout type trolley with HT fuses. (x) Inbuilt Power pack of suitable capacity with I/P voltage 220V AC & O/P voltage 110V DC for protection relay operation with capcity calculation details with min waranty of 2 years. (xii) Other standard accessories shall be of reputed make as specified by the manufacturer. Note: (i) CT and PT to be provided in incoming VCBs only. (ii) CT tobe provided in all the out going VCBs only. (iii) VCB and the HT Panel should be of the same Make.

1

-

-

... More
Supply and fixing glass fibre reinforced UV protected polycabonate Cable junction box IP 66, weather proof for mounting on the street light pole of size 205x255x112mm complete with 01 No 5 way ELMEX terminal suitable for 10 sqmm to 25 sqmm cable complete with knockouts for cable entry - Black colour complete all as specified and directed

854

-

-

... More
M&L for PCC Type-1, Grade M-15, mix 1:2:4, 20mm graded stone aggregate in mass concrete for coping complete all as specified and directed.

80.4

-

-

... More
Supply , fixing ,Testing and commisioning of 16M high mast shaft in two sections suitable for 55m/sec wind speed, with raising lowering system comprising, head frame, luminaries carriage suitable to install 08 nos luminaries in symmetrical arrangement, drum winch, 5mm diameter SS wire rope, trailing cable,connector, integral power tool motor, manual handle, junction box, lightening finial including Supply & fixing of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template. ERRECTION PART : Construction of shallow foundation with M20 grade concrete for the highmast considering the safe soil bearing capacity at site as 10 T/sqmtr at 2 metre depth with all materials and labour. Erection of the high mast with the help of suitable tools and plants WIRING PART : wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq. mm, lugs, MCB and labour. Provision of GI pipe earthing for High mast with 2.5 M long 40 mm dia GI Pipe including connection to High mast earth terminal with 25 x 3 mm GI flats with all materials and labour- 02 Nos. including Installation of the mast feeder pillar by grouting the stand in concrete. The Lightning Items as under (a) Supply of LED type single dome aviation obstruction light - 01 Nos. (b) Supply, Install and testing of outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminaries, power tool control with 2 Nos 9A contactors and raise lower push button, Incoming 35 sq. mm and out going 16 & 2.5 sq. mm terminals including installation of the mast feeder pillar by grouting the stand in concrete. Make of HM set : Bajaj Electrical Specification For Item No 51 above as under Height of mast : 16 Meter, No. of sections : Two Material construction : S 355 grade as per BS-EN10 025 Base dia. and top diameter (A/F) : Plate thickness : Cross section of Mast : 20 side polygon. Standard for of galvanisation : As per BS EN ISO 1461 Size of opening and door at base : 1050 x 225 mm

6

-

-

... More
ITEM NO 412 Cont... Diameter of base plate : 520 mm Thickness of base plate : 25 mm Lightning protection finial : G.I single spike of length 1200 mm Max.wind speed : 55m/s as per IS : 875 (Part - III) Number of foundation bolts : 06 nos. PCD of foundation bolts : 445 mm Type / diameter / length of foundation bolts : TS 600 / 24 mm dia / 850 mm long LUMINAIRES CARRIAGE Material of construction : 40 NB ERW Class B - M. S. Pipe Diameter of carriage ring (mm) : 450 mm (ID) Construction : 8 Arm, Welded, 2 sections Load carrying capacity : 8 Luminaire TRAILING CABLE Conductor : Copper, 5 core, 2.5 sq mm Insulation : PVC flexible No. of circuits per mast : One no. cable per mast WINCH / POWER TOOL Type / SWL of winch : Double drum, SWL 350 Kg Method of operation : Integral Motor Motor capacity : 0.75 HP No of speeds : 6 Pole, Single speed STAINLESS STEEL WIRE ROPE Grade / construction : AISI 304, 7/19 construction Number of ropes : Two continuous Diameter (mm) : 5 mm Breaking load capacity : 1450 kg x 2

-

-

-

... More
Supplying & fixing of high mast light fixture 1x 120 W LED Flood light fitting suitable for highmast lighting with in built electronic driver with surge protection upto 4 KV , high grade extruded aluminium housing (IP66) with high grade corrosion resistence powder coating for excellent durability , high efficiency lense for excellent light distribution and its wiring with 2x2.5 sq. mm PVC insulated copper wire and 14 gauge bare copper earth wire from junction box complete all as specified and as directed

48

-

-

... More
Supply & fixing LED street light fitting with pressure die-cast housing with toughened glass and individual LEDs with secondary optics and IP 66 protection. complete all as specified and as directed

854

-

-

... More
S & F GI 40mm dia 1.2mtr long bendded at suitble angle for street light fitting including fixing arrgements all as required at site complete all as specified and as directed

854

-

-

... More
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable, Indoor/Outdoor type for the size 25 to 50 sqmm complete all as specified and as directed

36

-

-

... More
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable, Indoor/Outdoor type for the size70 to 95 sq mm complete all as specified and as directed

2

-

-

... More
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable, Indoor/Outdoor type for the size120 to 150 sq mm complete all as specified and as directed.

2

-

-

... More
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable, Indoor/Outdoor type for the size 185 to 240 sq mm complete all as specified and as directed

4

-

-

... More
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable, Indoor/Outdoor type for the size 300 to 400 sq mm complete all as specified and as directed.

2

-

-

... More
Supply and fix cable route indicator oval shaped of size 200x150x6mm thick made out of Cast Iron with letter embossed as "HT UG Cable" or "LT UG Cable" fixed to 25x25x6mm mild steel angle iron 450mm long embedded in PCC block of size 200x200x200mm in PCC 1:3:6 type C1 using 20mm graded stone aggregate and including painting two coats of synthetic enamel paint over a coat of redoxide zinc chrome premier on exposed steel surfaces complete all as specified and as directed

430

-

-

... More
Supply, install, test and commisioning of factory fabricated LT panel, indoor type mounted on 50 mm x 50 mm x 6 mm thick angle iron frame, cubicle modular made out of 2.00 mm thick CRCA sheet with epoxy powder coated after dip coated primer manual type control, rust proof Siemens grey, structural RAL 7032, 6 mm thick fibre sheet for mounting MCB's/ MCCBs and other accessories, earth bus strip etc & connection with existing PVC/XLPE insulated cable with provision of joints, Lugs, glands etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete, suitable for operation 3 Phase, 4 wire , 440 volt, 50 Hz AC system & consisting of following accessories complete all as specified & as directed.(Installed at Power House Sub Stn -1):-(a) Aluminium bus bar 600 Amps rating, 4 Pole, 415 volts, TPN, colour coated with PVC/epoxy insulation & mounted insulator - 1 set of TPN (RYBN) (b) RYB Phase indicator LED type with protection MCB - 1 set (c) CRCA sheet chamber for bus bar, MCCB/ MCB, Meter etc complete(d) MCCB 4 Pole with thermal-magnetic release, 250 Amps TPN, 35 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (incoming) (e) MCCB, 415 Volts, 100 Amps, 25 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 2 No's (outgoing)(f) -Ditto- but MCCB, 63 Amps, 25 KA, TP, 3 Pole (relay range 30-63) complete with earth fault protection - 5 No's (outgoing) (g) -Ditto- but MCCB, 32 Amps, 25 KA, TP, 3 Pole, (relay range 20-32) complete with earth fault protection - 2 No's (Outgoing) (h) Change Over Switch suitable for AMF Panel (Auto matic transfer switch) Rating 160 Amps - 01 No(j) Digital multifunction meter with all electrical parameters like V,A,F,PF,KW,KVA,KWh, etc. - 1 No.(L&T 4405 series)(k) Control wiring with FR grade PVC insulated copper cable of suitable rating with necessary CTs & locking arrangement with DC panel lock Note : Panel shall be CPRI approved and contractor shall submit CPRI Test Certificate to the Engineer-in-Charge

1

-

-

... More
Supply, install, test and commisioning of factory fabricated LT panel, outdoor type mounted on 50 mm x 50 mm x 6 mm thick angle iron frame, cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated after dip coated primer manual type control, rust proof Siemens grey, structural RAL 7032, 6 mm thick fibre sheet for mounting MCB/MCCB's and other accessories, earth bus strip etc & connection with existing PVC/XLPE insulated cable with provision of joints Lugs gland etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete, suitable for operation 3 Phase, 4 wire , 440 volt, 50 Hz AC system & consisting of following accessories complete all as specified & as directed.(Installed at Sub Stn -2):-(a) Aluminium bus bar 800 Amps rating, 4 Pole, 415 volts, TPN, colour coated with PVC/epoxy insulation & mounted insulator - 1 set of TPN (RYBN) (b) RYB Phase indicator LED type with protection MCB - 1 set (c) CRCA sheet chamber for bus bar, MCCB/ MCB, Meter etc complete(d) MCCB 4 Pole with thermal-magnetic release, 400 Amps TPN, 35 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (incoming) (e) MCCB, 415 Volts, 315 Amps, 35 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing)(f) MCCB, 415 Volts, 125 Amps, 25 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing)(g) MCCB, 415 Volts, 100 Amps, 25 KA, AC, 50 Hz, 3 Pole,TP with extended terminal with thermal & magnetic setting including necessary connections - 1 No (outgoing)(h) -Ditto- but MCCB, 63 Amps, 25 KA, TPN, 4 Pole (relay range 30-63) complete with earth fault protection - 3 No's (outgoing) (i) Digital multifunction meter with all electrical parameters like V,A,F,PF,KW,KVA,KWh, etc. - 1 No.(L&T 4405 series)(k) Control wiring with FR grade PVC insulated copper cable of suitable rating with necessary CTs & locking arrangement with DC panel lock Note : Panel shall be CPRI approved and contractor shall submit CPRI Test Certificate to the Engineer-in-Charge

1

-

-

... More
Supply, install, test and commisioning of factory fabricated LT panel, outdoor type mounted on 50 mm x 50 mm x 6 mm thick angle iron frame, cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated after dip coated primer manual type control, rust proof Siemens grey, structural RAL 7032, 6 mm thick fibre sheet for mounting MCB/MCCB's and other accessories, earth bus strip etc & connection with existing PVC/XLPE insulated cable with provision of joints Lugs gland etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete, suitable for operation 3 Phase, 4 wire , 440 volt, 50 Hz AC system & consisting of following accessories complete all as specified & as directed.(Installed at Sub Stn -3):-(a) Aluminium bus bar 800 Amps rating, 4 Pole, 415 volts, TPN, colour coated with PVC/epoxy insulation & mounted insulator - 1 set of TPN (RYBN) (b) RYB Phase indicator LED type with protection MCB - 1 set (c) CRCA sheet chamber for bus bar, MCCB/ MCB, Meter etc complete(d) MCCB 4 Pole with thermal magnetic release, 400 Amps TPN, 35 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (incoming) (e) MCCB, 415 Volts, 200 Amps, 35 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing) (f) MCCB, 415 Volts, 150 Amps, 35 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing) (g) MCCB, 415 Volts, 125 Amps, 35 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing)(h) MCCB, 415 Volts, 100 Amps, 25 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 2 No (outgoing) (j) -Ditto- but MCCB, 63 Amps, 25 KA, TP, 3 Pole (relay range 30-63) complete with earth fault protection - 3 No's (outgoing) (k) -Ditto- but MCCB, 40 Amps, 25 KA, TP, 3 Pole (relay range 30-63) complete with earth fault protection - 4 No's (outgoing) (l) Digital multifunction meter with all electrical parameters like V,A,F,PF,KW,KVA,KWh, etc. - 1 No.(L&T 4405 series)(m) Control wiring with FR grade PVC insulated copper cable of suitable rating with necessary CTs & locking arrangement with DC panel lock Note : Panel shall be CPRI approved and contractor shall submit CPRI Test Certificate to the Engineer-in-Charge

1

-

-

... More
Supply & install, test and commssioning of automatic power factor control (APFC) panel indoor type for 35 KVAR, 3 Phase, 440 Volts, 50 Hz with multistage correction (MPP-H capacitor) copacitor operate in 4 steps configuration will be (3 x 10 KVAR and 1 x 5 KVAR prewired all suitable for fairly balance load factory made mounted on 50 mm x 50 mm x 6 mm thick angle iron frame front operated factory made prewired with suitable size copper conductor cable fabricated out of 2 mm thick CRCA shete painted with epoxy powder coating after dip coated rust proof treatment in havells grey colour structural RAL-7035, 6mm thick fibre sheet for mounting electrical accessories and connection with PVC/XLPE insulated UG Cables with provision of glands lugs etc with suitable gland plates at bottom including fixing arrangements cement concrete work for foundation of panel etc & Panel consisting of the following all as specified & directed. (Installed at Sub Stn -1)(a) MCCB, 100 Amps, 25 KA, TPN, 4 Pole, 415 Volts - 1 No (Incomer) (b) CT's Shall be provide for measuring the capacitor current at incoming side of the panel(c) The APFC Panel shall be provide with emergency push button to de-energies the control circuit incase of emergency or any fault occuring in the panel (d) APFC relay displaying various selectable/programmable electrical parameters like voltage input current capacitive current KVA demand KW Power factor etc( e) Fast response time of switching ON of Power factor (f) The Panel shall contain suitable rated with filter for cooling (g) Capacitors shall conform to IS-13340 & IEC-83, Contactor shall conform to IS-13947 and APFC relay shall be microprocessor based to operate in 6 stages(h) For individual capacitor bank MCB shall be provided(i) RYB Phase indicator LED type with protection MCB - 1 set(j) Locking arrangement complete

1

-

-

... More
Supply & install, test and commssioning of automatic power factor control (APFC) panel indoor type for 65 KVAR, 3 Phase, 440 Volts, 50 Hz with multistage correction (MPP-H capacitor) copacitor operate in 5 steps configuration will be (2 x 20 KVAR, 2 x 10 KVAR and 1 x 5 KVAR prewired all suitable for fairly balance load factory made mounted on 50 mm x 50 mm x 6 mm thick angle iron frame front operated factory made prewired with suitable size copper conductor cable fabricated out of 2 mm thick CRCA shete painted with epoxy powder coating after dip coated rust proof treatment in havells grey colour structural RAL-7035, 6mm thick fibre sheet for mounting electrical accessories and connection with PVC/XLPE insulated UG Cables with provision of glands lugs etc with suitable gland plates at bottom including fixing arrangements cement concrete work for foundation of panel etc & Panel consisting of the following all as specified & directed. (Installed at Sub Stn -2 &3)(a) MCCB, 160 Amps, 35 KA, TPN, 4 Pole, 415 Volts - 1 No (Incomer) (b) CT's Shall be provide for measuring the capacitor current at incoming side of the panel (c) The APFC Panel shall be provide with emergency push button to de-energies the control circuit incase of emergency or any fault occuring in the panel(d) APFC relay displaying various selectable/programmable electrical parameters like voltage input current capacitive current KVA demand KW Power factor etc(e) Fast response time of switching ON of Power factor (f) The Panel shall contain suitable rated with filter for cooling (g) Capacitors shall conform to IS-13340 & IEC-83, Contactor shall conform to IS-13947 and APFC relay shall be microprocessor based to operate in 6 stages(h) For individual capacitor bank MCB shall be provided(i) RYB Phase indicator LED type with protection MCB - 1 set(j) Locking arrangement complete

2

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.1 (Sub Stn-1)]Incoming: 1 No. of 100 Amp 4P MCCB of 25 KA Breaking capacity.Metering for incoming:Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.RYB Phase indicator LED type with protection MCB - 01 SetBus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 400 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints.Outgoing:06 Nos. 25 A TP MCCB of 10 KA breaking capacity 03 Nos. 16 A TP MCB of 10 KA breaking capacity.

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.1 (Sub Stn-2)]Incoming:1 No. of 315 Amp 4P MCCB of 35 KA Breaking capacity.Metering for incoming:Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 600 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Outgoing : (a)01 No. 200 A TP MCCB of 35 KA breaking capacity 04 Nos. (b)40 A TP MCCB of 10 KA breaking capacity (c)04 Nos. 40 A TP MCCB of 10 KA breaking capacity (d)07 Nos. 25 A TP MCCB of 10 KA breaking capacity (e)04 Nos. 10 A TP MCB of 10 KA breaking capacity

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.1 (Sub Stn-3)]Incoming:1 No. of 150 Amp 4P MCCB of 35 KA Breaking capacity.Metering for incoming:(a) Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 400 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Outgoing :(a) 03 No. 63 A TP MCCB of 10 KA breaking capacity (b)05 Nos. 25 A TP MCCB of 10 KA breaking capacity (c) 13 Nos. 10 A TP MCB of 10 KA breaking capacity

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.2 (Sub Stn-3)]Incoming:1 No. of 100 Amp 4P MCCB of 25 KA Breaking capacity.Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Outgoing: (a)14 Nos. 10 A TP MCB of 10 KA breaking capacity (b)02 Nos. 32 A TP MCCB of 25 KA breaking capacity

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- (FP No.1 & 2 of Sub Stn-2)Incoming (a)1 No 63 A FP MCCB, 25 KA service breaking capacity with heavy duty solid neutral link alongwith Earth fault relay and CBCT.(b)1 No ON Load Change over switch TPN 63 Amps,415 V. Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars 200 Amps TPN Aluminium Bus Bars of suitable length Bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints.Outgoing : (a) 04 Nos. 25 A TP MCCB of 10 KA breaking capacity (b)04 Nos. 20 A TP MCB of 10 KA breaking capacity (c)01 No 3 Phase contactor (d)01 No Timer switch

2

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- (FP No.3 of Sub Stn-3)Incoming (a)1 No 63 A FP MCCB, 25 KA service breaking capacity with heavy duty solid neutral link alongwith Earth fault relay and CBCT.(b)1 No ON Load Change over switch TPN 63 Amps,415 V. Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars 200 Amps TPN Aluminium Bus Bars of suitable length Bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints.Outgoing : (a)02 Nos. 25 A TP MCCB of 10 KA breaking capacity (b)05 Nos. 20 A TP MCB of 10 KA breaking capacity (c)01 No 3 Phase contactor (d)01 No Timer switch

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- (FP No.4 of Sub Stn-1)Incoming 1 No 63 A FP MCCB, 25 KA service breaking capacity with heavy duty solid neutral link alongwith Earth fault relay and CBCT.Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars 200 Amps TPN Aluminium Bus Bars of suitable length Bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints.Outgoing :(a) 06 Nos. 20 A TP MCB of 10 KA breaking capacity (B)01 No 3 Phase contactor (c)01 No Timer switch

1

-

-

... More
Supply, install, test & commissioning of factory fabricated Busbar panel out door type mounted on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens grey, 400 Amps Aluminium busbar and other accessories & connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system complete all as specified and as directed.

4

-

-

... More
Supply and fix Microprocessor based three phase electrronic tamper proof HT metering with optical communication port, accuracy class 0.5 rating 3 x 110 V, 1/5A confirming to IS: 13779 enclosed in MS sheet enclosure made out of 3.15 mmthick CRCA sheet with epoxy powder coated after dip coated primer manual type control, rust proof Siemens grey and other accessories & connecting complete all as specified and as directed

1

-

-

... More
Supply and installation of 11 KV, single phase, out door oil cooled CT/PT combination with CT of ratio 400/55 Amp, class 1.0 / 5P10, burden 15 VA and PT of ratio 11 KV/rt3/110V/rt3/110V/ rt3, class 0.5-3, Burden 50 VA - 50 VA including other accessories & connecting complete all as specified and as directed

1

-

-

... More
Supply and fix LED Post Top Light fitting 40W, made in cast aluminium with decorative opal polycarbonate diffuser with IP65 protection complete all as specified and directed by Engr-in-charge.

10

-

-

... More
Supply and fixing glass fibre reinforced UV protected polycabonate Cable junction box IP 66, weather proof for mounting on the street light pole of size 205x255x112mm complete with 01 No 5 way ELMEX terminal suitable for 10 sqmm to 25 sqmm cable complete with knockouts for cable entr - Black colour complete all as specified and as directed

10

-

-

... More
Supply and installation of High intensity, energy saving, long range, directional controlled, manually swiveble, LED search light, beam range 700 meters, 1x300W in multi circuit SMD LED, Effciency 100 lm/w, PF0.95, CCT 5500K - 6500K, Optical grade PMMA-PC lens, anti-UVoxidation, narrow beam 8 degree, die cast LM6 body with air fins, fully powder coated, working voltage 100 - 300v, 50Hz, constant current, reflector / lens efficiency 90%, minimum lux level at 10meter - 6000 with circle of approx 500mm,IP-66, confirming to LM79, LM80, IS:10322 / BIS. The above search - light to be installed on "UDCA" stand (1 Meter above from roof) & the operating lever (Hydraulic) of UDCA shall be in shoulder height to enable to rotate the luminaire easily frominside of the watch tower at 3600 horizontally & 450 vertically with built-in locking knob. All bushes of UDCA shall be made by gun metal, hardware shall be in S.S. and other metal parts would be Zinc electroplated / powder coated for outdoor installations and having 3 fountain loles at bottom complete all as specified and as directed

17

-

-

... More
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed

60

-

-

... More
Supply, install, test and commisioning of factory fabricated LT panel, outdoor type mounted on 50 mm x 50 mm x 6 mm thick angle iron frame, cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated after dip coated primer manual type control, rust proof Siemens grey, structural RAL 7032, 6 mm thick fibre sheet for mounting MCB/MCCB's and other accessories, earth bus strip etc & connection with existing PVC/XLPE insulated cable with provision of joints Lugs gland etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete, suitable for operation 3 Phase, 4 wire , 440 volt, 50 Hz AC system & consisting of following accessories complete all as specified & as directed.(Installed at Sub Stn -4):-(a) Aluminium bus bar 1000 Amps rating, 4 Pole, 415 volts, TPN, colour coated with PVC/epoxy insulation & mounted insulator - 1 set of TPN (RYBN) (b) RYB Phase indicator LED type with protection MCB - 1 set (c) CRCA sheet chamber for bus bar, MCCB/ MCB, Meter etc complete(d) MCCB 4 Pole with thermal magnetic release, 630 Amps TPN, 50 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (incoming) (e) MCCB 4 Pole with thermal magnetic release, 400 Amps TP, 50 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (outgoing) (f) MCCB 4 Pole with thermal magnetic release, 200 Amps TP, 35 KA, 415 volt, AC, 50 Hz with necessary connection control wiring & accessories etc complete all as specifed & directed -1 No (incoming) (g) MCCB, 415 Volts, 150 Amps, 35 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No's (outgoing)(h) MCCB, 415 Volts, 100 Amps, 25 KA, AC, 50 Hz, 3 Pole,TP with thermal & magnetic setting including necessary connections - 1 No (outgoing)(j) -Ditto- but MCCB, 63 Amps, 25 KA, TP, 3 Pole (relay range 30-63) complete with earth fault protection - 1 No (outgoing) (k) Digital multifunction meter with all electrical parameters like V,A,F,PF,KW,KVA,KWh, etc. - 1 No.(L&T 4405 series)(l) Control wiring with FR grade PVC insulated copper cable of suitable rating with necessary CTs & locking arrangement with DC panel lock Note : Panel shall be CPRI approved and contractor shall submit CPRI Test Certificate to the Engineer-in-Charge

1

-

-

... More
Supply & install, test and commssioning of automatic power factor control (APFC) panel indoor type for 110 KVAR, 3 Phase, 440 Volts, 50 Hz with multistage correction (MPP-H capacitor) copacitor operate in 7 steps configuration will be (4 x 20 KVAR and 3 x 10 KVAR) prewired all suitable for fairly balance load factory made mounted on 50 mm x 50 mm x 6 mm thick angle iron frame front operated factory made prewired with suitable size copper conductor cable fabricated out of 2 mm thick CRCA shete painted with epoxy powder coating after dip coated rust proof treatment in havells grey colour structural RAL-7035, 6mm thick fibre sheet for mounting electrical accessories and connection with PVC/XLPE insulated UG Cables with provision of glands lugs etc with suitable gland plates at bottom including fixing arrangements cement concrete work for foundation of panel etc & Panel consisting of the following all as specified & directed. (Installed at Sub Stn - 4)(a) MCCB, 200 Amps, 35 KA, TPN, 4 Pole, 415 Volts - 1 No (Incomer) (b) CT's Shall be provide for measuring the capacitor current at incoming side of the panel (c) The APFC Panel shall be provide with emergency push button to de-energies the control circuit incase of emergency or any fault occuring in the panel(d) APFC relay displaying various selectable/programmable electrical parameters like voltage input current capacitive current KVA demand KW Power factor etc(e) Fast response time of switching ON of Power factor (f) The Panel shall contain suitable rated with filter for cooling (g) Capacitors shall conform to IS-13340 & IEC-83, Contactor shall conform to IS-13947 and APFC relay shall be microprocessor based to operate in 6 stages(h) For individual capacitor bank MCB shall be provided(i) RYB Phase indicator LED type with protection MCB - 1 set(j) Locking arrangement complete

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.1 (Sub Stn-4)]Incoming:1 No. of 150 Amp 4P MCCB of 35 KA Breaking capacity.Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 400 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Outgoing : (a)02 Nos. 25 A TP MCB of 10 KA breaking capacity (b)06 Nos. 20 A TP MCB of 10 KA breaking capacity (c)04 Nos. 10 A TP MCB of 10 KA breaking capacity

1

-

-

... More
Supply, install, test & commissioning of factory fabricated outdoor LT Feeder piller panel weather & vermin proof double door totally enclosed on 40 mm x40 mmx 6 mm thick angle iron frame, Cubicle modular made out of 3.15 mm thick CRCA sheet with epoxy powder coated dip coated primer, manual type control rust proof Siemens gray structural RAL 7032, 6mm thick fiber sheet for mounting MCB/MCCB's and other accessories earth bus strip etc & with all interconnections, risers, internal wiring, labels, terminal blocks etc. complete as required and connection with existing PVC/XLPE insulated cable with provision of joints, lugs, gland, etc all as specified & directed and consisting of the following including necessary PCC work for foundation excavation & earthwork etc complete., suitable for operation 3 Phase, 4 wire, 440 volt, 50 Hz, AC system & consisting of following accessories:- [MDB No.2 (Sub Stn-4)]Incoming:1 No. of 400 Amp 4P MCCB of 50 KA Breaking capacity.Metering for incoming:(a)Digital VAF + PF meter, Cl 1 (L&T 4110 series) flush mounting type with CTs as required.(b)RYB Phase indicator LED type with protection MCB - 01 Set Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 600 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Outgoing : (a)04 No. 63 A TP MCCB of 10 KA breaking capacity (b)10 Nos. 40 A TP MCCB of 10 KA breaking capacity(c)02 Nos. 20 A TP MCB of 10 KA breaking capacity (d)3 Nos. 10 A TP MCB of 10 KA breaking capacity

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.