Military Engineer Services Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date13 Sep 2024
Closing Date16 Oct 2024
Tender Amount₹ 29,99,000
Costs
EMD
₹ 60,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_674452_1Bid Award Id
ViewTender No
8680/KKD/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Materal and labour for heating charges of transformer oil complete all as directed by Engineer-in-Charge.
1
-
-
Materal and labour for total brazing work required for job complete all as directed by Engineer-in-Charge.
1
-
-
Materal and labour for filtration charges or old transformer oil complete all as directed by Engineer-in-Charge.
1
-
-
Material and labour for new Copper winding strips/wire for (HV+LV) transformer complete all as directed by Engineer-in-Charge.
70
-
-
Labour charges only for refixing of coil assembly and box up and final testing complete all as directed by Engineer-in-Charge.
1
-
-
Supply, replacement and topping up new Transformer oil EHV grade as per IS 335 of 1993 Part II having die electric strength not less than 40 KV in the Transformers at various location complete all as specified and direct by EIC. Make of Transformer oil : Transol/Power oil/any brand of Indian oil corporation). Note : Transformer oil should be heated and should having dielectic strength 60 KV (ii) Transformer oil shall be bring in sealed barrel having proper test certificate from manufacturer.
1600
-
-
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm - 95 Sqmm all as specified and directed incl taking down unsv one.
6
-
-
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm- 185 Sqmm all as specified and directed incl taking down unsv one.
2
-
-
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm- 95 Sqmm all as specified and directed incl taking down unsv one.
4
-
-
Material & labour for Cable jointing kit for 11 KV (Earthed) grade cable for out door end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm- 95 Sqmm all as specified and directed incl taking down unsv one.
4
-
-
Supply, Install, testing and commissioning of 33 KV single phase outdoor type oil cooled ,dead tank type CT of ratio 160-80/5-5-1 Amp accuracy class 0.5 for metering equipment of burden 15 VA as per IS:2705 including connection CT terminal to control panel through control cable and taking down unsv one complete all as specified and directed .
Note:
(i) Contractor has to make all arrangement for mounting/ placing CT`s in existing system without any extra cost.
4
-
-
Supply, install, testing and commissioning 33 KV single phase outdoor type oil cooled,dead tank type PT of ratio 33 KV /√3 : /110V/√3-110V/√3 ,accuracy class 0.5, Burden 150 VA conforming to IS:3156 including connection PT terminal to control panel through conntrol cable and taking down unsv one complete all as specified and directed.
Note: (i) Contractor has to make all arrangement for mounting/ placing PT`s in existing system without any extra cost.
2
-
-
Supply & fixing, installation VRLA batteries of capacity 55 Nos x 2 volt DC, 300 AH, total output voltage 110 volt DC including standard accessories and rack arrangement complete all as specified. Make- Exide or equivalent make as specified.
Note :- This item will not be paid for against material lying at site.
1
-
-
Supply & fiixing, installation battery charger automatic float cum boost charger of capacity 110 volt, 50 Amp. Load & charging : 50 Amp, Input : 415 volt AC (Three phase), output : 110 volt DC, float output cutoff :124 volt DC, Boost output cutoff : 131 volt DC. Protection : High Cut/ Low Cut; Overload cut-off Deep Discharge cut-off, Over charging cutoff
Automatic Voltage Regulation: 415V AC ± 10% complete all as specified.
2
-
-
Supply & installation of 3 phase copper 11 KV/110 V indoor draw out type potential transformer (PT) of ratio 11KV/√3 /110V/√3/110V/√3, class 0.5, burden 50 VA-50VA complete all as specified.
6
-
-
Supply and installation of 11 KV single phase in door resin cast dual core CT of ratio 100-50A/5-5A, class 0.5, burden 15 VA, protection core 5P10 complete all as specified.
6
-
-
Supply and installation of power packs with and including battery backup for 11 KV VCB, input voltage 230 V AC, output 110 V DC complete all as specified.
4
-
-
Supply & fixing VRLA battery 12V, 7AH for 11 KV VCB power pack complete all as specified.
4
-
-
Supply & fixing VRLA battery 12V, 300AH for 11 KV VCB complete all as specified.
4
-
-
Supply, laying, testing and commencing of HT cable XLPE insulated screnned PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts (Earth grade) , of size 95 Sq mm 3 core including taking down old all as specified and directed.
200
-
-
Supply, laying, testing and commencing of HT cable XLPE insulated screnned PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts (Earth grade) , of size 120 Sq mm 3 core including taking down old all as specified and directed.
25
-
-
Taking out saturated silica gel from existing breather and Supply and replace silica gel crystal 3/4 mesh, 6 mm to 9mm, (Blue to Pink to white) in breather of transformers complete all as specified and directed
25
-
-
Taking out old unserviceable breather and Supply and replace silica gel breather assy 250 gms , made up of aluminium TOP ,Powder coated, Transaparent Centre Portion made of Polycarbonate of size 80 mm x 80 mm, Nitirle rubber O ring connection1/2 " BSP thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity 100 KVA to 200 KVA complete all as specified and directed
5
-
-
Taking out old unserviceable breather and Supply and replace silica gel breather assy 500 gms , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size 90 mm x 140 mm, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity 250 KVA to 630 KVA complete all as specified and directed
8
-
-
Taking out old unserviceable breather and Supply and replace silica gel breather 1500 gms , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity upto 1600 KVA complete all as specified and directed
5
-
-
Taking out old unserviceable breather and Supply and replace silica gel breather 3000 gms , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity upto 4000 KVA complete all as specified and directed
2
-
-
Supply and replace in repair Pin Insulator porcelain vitreous, white brown or green , 150 mm height, 150 mm dia including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut for conductor working pressure 11000 volt grade complete all as specified and directed including taking down old unserviceable.
1
-
-
Supply and replace in repair Post Pin Insulator porcelain vitreous, white brown or green including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut for conductor working pressure 33000 volt grade complete all as specified and directed including taking down old unserviceable .
1
-
-
Material & labour for 33 KV Air break switch (isolator) outdoor type, off load, Triple pole, single break, consisting of hot dip galvanized channel iron base, mechanically operated, mounted on HT insulator and steel frame, with operating mechanism, copper or copper alloy high pressure heavily tinned complete with horizontal connecting sq.bar, GI pipe as down rod, coupling for pipe, lever and operating handle with locking arrangement worked from ground level, for current rating upto 1250 amps complete all as specified and as directed.
1
-
-
Material & labour for Gang operated Air break switches 11 KV Tripple pole, mechanically operated, mounted on insulator and steel frame with operating mechanism worked from ground level for current rating 400 Amp complete all as specified and as directed.
2
-
-
Material & labour for servicing/overhauling and decorbonising of 33/11 KV, out door PC VCB , replacement of un-serviceable spares, and serviceability check from remote operation, checking of all DC supply system, electrical circuit including connection of control cables to make it functional in all respect all as specified and directed by Engr -in - charge. Note :- (i) Spare parts/components required to replaced of above control panel shall be measured and paid separately under relevant items.
(ii) Unit rate quoted against this item shall also include labour required for fixing of replaced items, making the control panel serviceable and making all electrical connecto,.
(iii) For item No. 35 to 36 below, fixing charges of items are considered and included in item No 34 herein.
1
-
-
Supply only closing coil (control) assembly 35 volt DC. as per existing sample.
1
-
-
Supply only triping coil (control) assembly 35 volt DC. as per existing sample.
1
-
-
Material & labour in repair for Filteration and dehydration of HV grade transformer oil of distribution and Power transformer of out door type of 11/.433 KV, 100 KVA to 750 KVA and Power transformer of 33/11 KV 1000KVA to 4000KVA min three cycle to achive die elctric strength of 40 KV to 60KV for 1 Minute at 4 mm gap as per relevent IS with portable filteration plant, testing the oil for die elctric strength, break down voltage before filteration and after filteration complete all as specified and directed by EIC. Note : Filteration to be done by Dehydration machine till the desired level of dielectric strength of tranformer oil comes to 60 KV .
(ii) The contractor will test the dielectric strength of oil of each Tranformer & voltage stabilizer before starting dehydration & filteration and after completion of dehydration & filteration process and he will submit a record of same. (iii) Each sample of oil will be tested with a transformer oil test machine at site in presence of concerned JE's/Engr-in-charge and test result will be submitted accordingly).
(iv) Centrifugal machine with all T&P and Testing Machine , oil required shall be arranged by contractor.
(v) Oil required for topping up the transformer oil will be measured and paid seperately in relvent item.
3200
-
-
Excavation in trenches not exceeding 1.50 m wide and n.exc1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed.
Note :Excavation for laying of cable to be done manualy carefully without distrubing existing cable or water pipe lines. If any damaged occured to exiting cable and pipe line during excavation contractor has to repair it with in time limit without any extra cost. If contractor delayed in repairing Panality @ of 500/- per hour to be charghed if repairing is not carry out in 12 hours. In this GE diecision will be full and final.
50
-
-
Returning, filling in, of soil including spreading leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed .
34.5
-
-
Removing excavated material to a distance n.exc 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point complete all as specified and as directed .
15.5
-
-
Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured)
14
-
-
Supply & Fixing burnt clay fly ash bricks old size designation 75 (kg/cm2) in trenches on cable as cable protection across the length of the cable (width wise) complete all as specified and as directed.
1.4
-
-
Supply & fixing aluminium pipe (round bar) of size 1.5 inch approx 48.26 mm outer dia, wall thickness 3.69 mm, current rating 1160 Amp bend to shape as required and connection with existing bar and CT,PTs by using aluminium PG clamps, Pad clamps, nut, bolts etc as required at site complete all as specified.
40
-
-
Supply & fixing aluminium 33 KV grade PG clamps for existing aluminium bar system in switch yard by fixing with proper size nut, bolts complete all as specified.
20
-
-
Supply & fixing aluminium 33 KV grade Pad clamps for existing aluminium bar system in switch yard by fixing with proper size nut, bolts complete all as specified.
20
-
-
Materila & labour for fixing flexible control cable PVC insulated 12 core of size 2.5 sqmm FR PVC sheathed multistraded cable with bright annealed electrolytic bare copper conductor for voltage grade upto 1100 Volt for connecting control panel to VCB including taking down unsv one.
50
-
-
Material & labour for detecting of fault in 11KV (E) HT cable of any size(within 1-3 km length) , 3 core laid in trenches/ducts with the help of electronic fault locating machine comprising of surge generator pulse, echo fault locator with high frequency distance calculator etc and exposing the cable fault, removal of deteriorated portion of cable, treating the cable including making it ready for jointing work complete all as directed by Engineer-in-Charge.
Note: - (i) The quoted rate shall deemed to include for the cost of earthwork excavation as required.
(ii) Cable if replaced & Jointing kit shall be measured & paid separately.
(iii) As the work is releated to maintenance, the work of fault detection has to be carry out on Priority and on requirement basis as on occurance of fault within 24 hrs so as to rectify the fault and to restore the electric supply of stn. If contractor delay the job, necessary panlty at the rate of Rs 1000.00 per hrs (after 24 hrs) will be impose on contractor.
3
-
-
Material & labour for rectifying of transformer oil leakage problem from LT termernial, taking shut down, tracing out the cause of leakage , removing cable, draining out oil, removing of transformer top cover, replacement of seal, recitifying oil leakge, changing all gaskets, tightening of transformer core, tightening / replaceing of bushing/stud, refilling the oil, replacement of top cover gasket, reconnecting cables etc and testing and commissioning complete all as specified and up to the entire satisfication of Engr in charge.
1
-
-
Supply only spray Moisture absorbing spray WD-40 on electric terminals of VCB Breaker and panel and allied equipment all as specified and directed.
16
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements