Military Engineer Services Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date5 Sep 2024
Closing Date4 Oct 2024
Tender Amount₹ 16,00,000
Costs
EMD
₹ 32,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_672020_1Bid Award Id
ViewTender No
CWE/136-WE/50 OF 2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Disconnecting the electric supply, taking down the old unserviceable disc insulator and supply & fixing of disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia, complete all as specified and directed.
12
-
-
Disconnecting the electric supply, taking down the old unserviceable pin type insulator and supply & fixing pin type insulator 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia, complete all as specified and directed.
12
-
-
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including taking out old unserviceable one, complete all as specified and directed.
1
-
-
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including taking out old unserviceable one, complete all as specified and directed.
1
-
-
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including taking out old unserviceable one, complete all as specified and directed.
1
-
-
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, laying of underground cables etc. or for shafts, wells, cesspits, manholes, pier holes, stay rod, under groung cables etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in hard / dense soil, complete all as specified and directed.
21.7
-
-
Excavation in trenches / foundation in hard / dense soil not exc. 1.5 metre wide and exc 1.5m depth and n exc. 3.0m depth for stay assembly /pole foundation or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out including forming bottom surface to required level or slope, complete all as specified and directed.
0.5
-
-
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm each layer of any kind of soil, all specified and directed.
12.3
-
-
Removal of surplus excavated soils to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.50m above the starting point, all as specified and directed.
7.8
-
-
M&L for sand cushioning for protection of PVC cable with approved sand of uniform thickness, laid dry, by filling in trenches and punning to proper required cover, complete all as specified and directed.
5
-
-
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm, all as specified and directed.
258
-
-
M&L for plain cement concrete (1:4:8), type D2 (using 40 mm graded stone aggregates) as in foundation, filling and mass concrete, complete all as specified and directed.
0.2
-
-
M&L for plain cement concrete (1:3:6), type C2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and as directed.
0.9
-
-
M&L for plain cement concrete (1:2:4), type B-1 (using 20 mm graded stone aggregates) in coping, bed plates, parepet, plinth course including weathering, slightly rounded or chamfered angles and throating, complete all as specified and directed.
0.2
-
-
Supply and lay GI tubing 100 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables, complete all as specified and directed.
3
-
-
Supply and lay GI tubing 80 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables, complete all as specified and directed.
3
-
-
Supply & lay in repair, connection testing and commissioning of 3 core, 95 Sqmm, 11000 Volts grade(Earthed) XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor laid in trench / under ground / wall / surafce / tunnel / duct including taking out unserviceable burnt out cable, complete all as specified and directed.
58
-
-
S&F in repairs test, erection & commissioning of steel tubalar swaged poles staying in a truely vertical position till the foundations are properly set with the help crane complete with cast iron base plate, finial taper plug, bolts, nuts & screws including drilling of holes to poles for clamps & hooks for running of earth wire/ strip type 410 SP-55 (11.0 metres long), complete all as specified and directed.
Note:- (i) Earth work, PCC, coping shall be measured and paid separately.
(ii) The rates include staying the poles in atruely vertical position till the foundations are properly set.
(iii) The rates include cast iron base plate,nuts,bolts,screws,painting of steel tubular poles,drilling of holes in steel tubular poles for fixing of clamps, hooks for continuous earth wire/strip
2
-
-
S&F in repairs test, install & commissioning of HT 11 KV outdoor type gang operated air break switch triple pole mechanically operated suitable for horizontal or vertical mounting (suitable for existing one) on insulator and steel frame with operating mechanism worked from ground level for current rating up to 400 Amps and connecting up with jumpers, testing and commissioning including dismantling / disconnecting & taking down the old unserviceable one, complete all as specified and directed.
3
-
-
S&F in repairs stay assembly comprising of MS stay plate 6 mm thick and of size 300 x 300 mm and 20 mm dia MS stay rod, 2150 mm long including thimbles, GI stay wire comprising of stay strand 7/3.15 mm dia of required length complete all as shown on electrical plate No.1 on page No.495 of MES SSR Part-I 2009 including necessary excavation, PCC (1:3:6) Type C2 (using 40mm graded stone aggregate), loop insulator as specified in SSR and including taking down old unserviceable one, complete all as specified and directed.
3
-
-
M&L for loop type insulator, vitreous porcelain, white, brown or green, large size with overall dimensions 90 x 140mm size, clearance of hole 25.5 mm, complete all as specified and directed.
3
-
-
Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including one under coat and one finishing coat with synthetic enamel paint over a coat of red oxide primer including taking down old unserviceable cross arms, complete all as specified and directed.
1.2
-
-
Supply and install lightening arrestor expulsion type complete with all fittings transmission class, discharge capacity 65 Kilo Amps suitable for 11 KV connecting testing including taking down old unserviceable lightening arrestor, complete all as specified and directed.
2
-
-
M&L for ACSR jumpers in HT/LT over head line upto 10 mm dia as that of existing size including sleeves/holding clamp/ binding wire, nuts & bolts washers etc. as required, complete all as specified and directed.
12
-
-
M&L of danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white, with letters, figures and convention skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 11 KV of size 25 x 20 cm, complete all as specified and directed.
6
-
-
M&L for cradles, hexagonal / rectangular fabricated with galvanised steel 4mm dia including taking down old unserviceable cradles, complete all as specified and directed.
0.5
-
-
M&L for ACSR conductor, steel reinforced for LT / HT over head lines on poles including streching tightining of poles insulator with binding wire of suitable size with insulator / streching of ACSR conductor including disconnecting / taking out old existing unserviceable ACSR conductors, complete all as specified and directed.
0.5
-
-
M&L for disconnection of all primary / secondary connections of the defective transformer rating up to 200kVA out door / indoor type, any make, taking down / out from plinth / pole / platform with the help of suitable crane and transporting the same carefully to workshop for repair and bringing back and test, install & commissioning in its original existing position by making all neccessary connections, complete all as specified and directed.
Note: Crane and Transporting Charges including in the Job.
1
-
-
All as per item no. 31.00 above but for capacity above 200 KVA and upto 400 KVA with complete testing and commissioning, all as specified and directed.
1
-
-
M&L for opening top cover of transformer taking out complete oil and keeping in clean and dry container, taking out core & winding from the body, remove the sludge from tank complete and segregation of HT / LT leg coil from transformer including job assembling of jointing the connections pf HT / LT coil in core assembling complete insulation works, setting of core, making new connections (as per existing connections), proper alignment of job including keeping in oven chamber of as per IS Specification of respective transformer capacity for remove the moisture as well as fixing of upper yoke lamination, checking, tightening, nuts, bolts, washers and all types of gasket (Bushing and tank) etc and megger including two coats of anti corrosive paint aftre cleaning inside transformer tanks and two coats of outside painting including writing KVA Capacity, repairs of body by means of welding, jointing if required complete for capacity up to 200 KVA with complete testing and commissioning, all as specified and directed.
1
-
-
All as per item no. 33.00 above but for capacity above 200 KVA and upto 400 KVA with complete testing and commissioning, all as specified and directed.
1
-
-
M&L for making primery coil with insulated copper wire of required gauge craft paper cotton tape HT insulation as per specification of old existing transformer including making of coil as required of various capacity of transformer, complete all as specified and directed.
30
-
-
M&L for making secondary coil with insulated copper wire of required gauge craft paper cotton tape LT insulation as per specification of old existing transformer including making of coil as required of various capacity of transformer, complete all as specified and directed.
30
-
-
M&L for reconditioning of over heated HT / LT coil of transformer up to 400 KVA after removing all old insulation any type and re-insulation as required and remaking of LT coil, complete all as specified and directed.
84
-
-
M&L for opening of the 11 KV / 0.433 KV distribution transformer rating up to 500 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level, check leaked cork seal (if any), check the un sericeable insulators & LT / HT bush (if any) complete from the shell and making connections of LT / HT bush, insulators & cork seals to avoid leakage and refilling oil back to existing postion into the transformer complete testing & commissioning, complete all as specified and directed.
Note: Spares shall be measured and paid separately under relevant items.
6
-
-
Supply only HT bushing including metal parts and washer complete for any make of transformer mounted on plinth / pole and transformer rating up to 400 KVA capacity complete including taking down old unserviceable one, all as specified and directed.
3
-
-
Supply only LT rod / studs for any make of transformer rating up to 400kVA mounted on pole / plinth, made of brass with nut and washers, Insulator and fittings etc as per size and shape of original complete including taking down old unserviceable one, complete all as specified and directed.
3
-
-
Supply only gasket set (crok sheet) for any make of transformer rating upto 400 KVA for top of transformer or conservator tank after decanning the required level of oil including taking down old unserviceable one, complete all as specified and directed.
2
-
-
M&L for Replacement of air breather with filled silica gel suitable for any make of tranformer rating up to 400 KVA mounted on plinth/pole including taking out old unserviceable one complete all as specified and as directed.
3
-
-
Supply and filling of transformer oil in transformer plinth / pole mounted including testing insulation and vescocity of oil, complete all as specified and directed.
Make : SERVO/POWER OIL/HP/SAVITA
104
-
-
M&L for dehydration including filtration cleaning of transformer oil in transformer indoor/ outdoor type by centrifusion / machine having minimum capacity 1000 ltrs/ hrs including testing insulation and vescocity of oil before and after dehydration, complete all as specified and directed.
1200
-
-
Dismantling pole by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed.
1
-
-
M&L for Painting the HT poles of OH lines and HT four poles / two poles and single pole structure complete with cross arms any height and any description thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt / dust / rust carefully and applying one coats of aluminum paint including marking yellow / black strips and white washing of pole coping, complete all as specified and directed.
18
-
-
Maintenance of earthings of installations like cleaning of earth pits, treatment of earthing by pauring salt water, replacement of perished wire mesh, unserviceable funnel and repair works, complete all as specified and directed.
10
-
-
Restreching / restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree, complete all as specified and directed.
90
-
-
Cutting and trimming trees branches any girth and any size touching to overhead lines and cleaning the distance 1.5 m length both side of OH line with in a span of 50 m each disposing the same, clearing the site, complete all as specified and directed.
100
-
-
Supply and fixing cable route indicator for HT UG Cable of 11000 Volts bolted with 40 x 6 mm flat iron member of height 0.60 mtr, and 80 mm dia CI plate embedded in PCC (1:3:6) type C2 of size 20 x 20 x 30 cm block, complete all as specified and directed.
10
-
-
Surface excavation n exc. (not exceeding) 30 cm deep and averaging 15cm deep and getting out hard / dense soil, all as specified and as directed.
36
-
-
M&L for course agreegate (Limestone, Sand stone, Flint or Quartzite) for filling as directed of grading 90 to 40 mm size or grading 2, 63 to 40mm size, deposited, spread and levelled in layers not exc.150mm thick, watered and rammed to a true surface, complete all as specified and directed.
3
-
-
M&L for preparation of old steel surfaces of any description over 10 cm width or girth and applying one coat of synthetic enamel paint, complete all as specified and directed.
26
-
-
M&L for providing, cement concrete (1:3:6), type C1 (using 20mm graded stone aggregate) in roof kerbs or mud stops, rounded or chamfered on edges, complete all as specified and directed.
1
-
-
Cutting anxious green growth / vegetation growth for cleaning out the area around transformer installations and four pole structure yards at ground level by cutting out roots, un-wanted plants bushes and removal of the same by excavation n exc. (not exceeding) 30 cm deep and averaging 15cm deep and getting out soft / loose soil, all as specified and as directed.
300
-
-
Arresting leakage of transformer fins by brazing / welding etc. after removing of oil from inside of transformer and refilling of oil by opening top cover of transformer of capacity upto 500KVA, complete all as specified and directed.
3
-
-
M&L in replacement of operating GI pipe 25mm dia / bore upto 7.5 m long with clamp, nut, bolts, washers and necessary operating handle suitable for GOD, complete all as specified and directed.
3
-
-
Servicing / calibration / trouble shooting / repairing / adjustment of over current relay, earth fault relay, spring, spring charge mechanism, close coil, trip coil, including connected accessories cleaning of all contacts with CTC of the 11KV HT VCB panel of 630Amps, 50 Hz by qulified technical personel including fixing of spares to make functional in all respects including identifying the deffective parts, complete all as specified and directed.
5
-
-
Supply only following spares in repairs suitable for 11KV HT VCB of maximum short circuit current rating 25/26.3 KA 630Amps / 400Amps after taking down the old spares, all as specified and directed:
-
-
-
LED indicating lamps R/Y/B 110V AC
3
-
-
LED indicating lamps amber 110V DC
3
-
-
LED indicating lamps white 110V DC
3
-
-
Trip circuit push button with NO contracts.
3
-
-
Door Limit switch
3
-
-
Tripping coil assembly
1
-
-
Closing coil assembly
1
-
-
PT Fuse 3.15A
3
-
-
Fuse Link 2A, 4A, 6A
10
-
-
Fuse Link 10A
5
-
-
Breaker control Switch 25A
3
-
-
Anti condensation space heater
5
-
-
Fuse Holder with base 32A
10
-
-
Thermostat
3
-
-
Test and Service Limit Switch
1
-
-
Single Phase Power Pack with capacitor back-up; input Voltage 230V AC 1Ph Output Voltage -110V DC,100W.
2
-
-
Spring charging motor/ motor coil 230V, RPM 7000.
Make: Siemens / ABB / CG
2
-
-
S&F of vacuum interrupter suitable for HT 11 KV busbar of VCB panel including all allied works, completeall as specified and directed
1
-
-
S&F of 11 KV Rasin cast CT, BIL 12 KV/28KV / 75KV P, Ratio 100/5+5A, Core- I :1.0 15VA, Core II: 5P10, 15VA, STC- 26.3KA for 1Sec on P2 Side, all as specified and directed
1
-
-
S&F of spout suitable for VCB panel of ABB Make for HT 11 including all allied works, complete all as specified and directed
1
-
-
Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR Part I including necessary excavation and earth work in any type of soil PCC (1:3:6) type C1 chamber with RCC (1:2:4) type B1, 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion.
1
-
-
Attending breakdown of VCB Panel as and where required trouble shooting / repairing / adjustment of the 11KV HT VCB panel of 630A, 50 Hz by qulified technical personel to make functional in all respects including identifying the deffective parts, complete all as specified and directed
6
-
-
M&L for fabrication of Panel / VCB cover plate / door made out of 3.15mm (10 SWG) thick CRCA duly painted with powder coated paint and making holes at desired position for fixing of bolts / screws / hinges etc., complete all as specified and directed.
6
-
-
M&L for Busbar re-insulation with heat shrinkable insulating material suitable for 11KV Busbars of VCB panel including all allied works complete all as specified and as directed. Note: Re-insulation with heat shrinkable insulating tape measured separately.
2
-
-
Heat shrink tube suitable for HT 11 KV busbar of VCB panel, all as specified and directed.
6
-
-
Self amalgamating suitable for HT 11 KV busbar of VCB panel, all as specified and directed.
3
-
-
Busbar support insulator for holding HT 11KV Busbars of VCB panel, complete all as specified and directed.
6
-
-
M&L for outdoor straight through cable jointing kit, heat shrinkable type suitable for 95 Sqmm arial bunch cable (AB Cable), complete all as specified and directed.
3
-
-
Note 1:- (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum / amendments and general condition of contracts before entry / quoting the rates.
Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements