Military Engineer Services Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Military Engineer Services - MES Tender
Security and Emergency Services
Eprocure
Opening Date11 Dec 2024
Closing Soon16 Jan 2025
Tender Amount₹ 40,00,000
Costs
EMD
₹ 80,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Repair And Maint Of Em Equipments At Fire Fighting Installations, Fire Fighting Automation System, Control Panels, Replacement Of Ms Ci Di Pipes
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_688197_1Tender No
8111A/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
All as per item No 1 here in before but of capacity 50000 Gln
10
-
-
... More
All as per item No 1 here in before but of capacity 30000 Gln
5
-
-
... More
All as per item No 1 here in before but of capacity 20000 Gln
8
-
-
... More
All as per item No 1 here in before but of capacity 10000 Gln
10
-
-
... More
Excavation in trenches not exc 1.5 wide and not exc 1.5 mtr deep and getting out in soft soil for laying pipes complete all as specified and directed.
132
-
-
... More
Returning and filling in soils, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed.
114
-
-
... More
Removal of excavated material to a distance not exc 50 mtr away from starting point and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed
18
-
-
... More
Cutting of exsiting PCC road / hard standing / floor, etc. exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of pipe, tubing, etc. and making good and finished & matching the disturbed surfaces with existing surfaces complete all as specified and directed.
20
-
-
... More
Cutting of exsiting Bituminous road exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of pipe, tubing, etc. and making good and finished & matching the disturbed surfaces with existing surfaces complete all as specified and directed.
20
-
-
... More
Taking down UNSV DI water mains with spigot and socket ends of any class including all fittings complete all as specified and directed by Engineer -in -charge for 200 mm dia bore pipe complete all as specified and directed.
100
-
-
... More
Taking down UNSV DI water mains with spigot and socket ends of any class including all fittings complete all as specified and directed by Engineer -in -charge for 150 mm dia bore pipe complete all as specified and directed.
170
-
-
... More
Taking down UNSV DI water mains with spigot and socket ends of any class including all fittings complete all as specified and directed by Engineer -in -charge for 100 mm dia bore pipe complete all as specified and directed.
90
-
-
... More
Supply and laying of ductile iron (DI) pipe spigot and socket ends class 'K-9' suitable for tyton joint or any length properly laid in trenches all as specified and directed by Engr-In-Charge of 200 mm dia bore pipe complete all as specified and directed.
100
-
-
... More
Supply and laying of ductile iron (DI) pipe spigot and socket ends class 'K-9' suitable for tyton joint or any length properly laid in trenches all as specified and directed by Engr-In-Charge of 150 mm dia bore pipe complete all as specified and directed.
170
-
-
... More
Supply and laying of ductile iron (DI) pipe spigot and socket ends class 'K-9' suitable for tyton joint or any length properly laid in trenches all as specified and directed by Engr-In-Charge of 100 mm dia bore pipe complete all as specified and directed.
90
-
-
... More
Supply and fix DI fitting for spigot socketed pipe , bends ( any type , radius and angle ) tapers any type , (straight , bend increasing , decreasing or double socket etc ) tee pieces single branch , Y junction double branch, cross of size - up to 200 mm dia complete all as specified and directed.
350
-
-
... More
Supply and fix in repair CI sluice valve flanged of class PN 1.6 conforming to IS - 14846 complete with iron wheel head , SS/Gun metal spindle and check nut , including jointing material such as rubber insertion nuts, bolts and washers etc complete for 80 mm dia bore pipe .
4
-
-
... More
All as per item no 19 but size of 100 mm dia bore.
4
-
-
... More
All as per item no 19 but size of 150 mm dia bore.
3
-
-
... More
All as per item no 19 but size of 200 mm dia bore
1
-
-
... More
Supply and fix in repair CI 80mm bore Non - Return Valves , ISI marked , heavy duty , flanged type including rubber sheet & nut bolts etc complete all as specified by the Engr-in-charge
2
-
-
... More
All as per item no 23 but size of 100 mm dia bore
2
-
-
... More
All as per item no 23 but size of 150 mm dia bore
2
-
-
... More
All as per item no 23 but size of 200 mm dia bore
1
-
-
... More
Supply and fix in repair 80 mm dia foot valve as per IS-4038 of cast iron with brass diaphragm heavy duty screwing type complete all as specified by the Engr-in-charge
2
-
-
... More
All as per item no 27 but size of 100 mm dia
4
-
-
... More
All as per item no 27 but size of 150 mm dia
2
-
-
... More
Supply and fix in repair 80 mm dia bore butterfly valve, ISI marked, heavy duty, flanged type including rubber sheet & nut bolts etc complete all as specified and directed.
11
-
-
... More
Supply and fabrication of fire hydrant hose box of size 800mmx 600mmx 250mm made of 18 mm gauge MS sheet with 3 mm thick double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet and 40mmx 40mm x 6mm thick iron angle support at 1.5 mtr height including grouting, painted FIRE with red outside and brilliant white inside box including taking down old unserviceable complete all as specified and directed.
9
-
-
... More
S&F in repairs fire fighting canvas hose pipe, fire chief brand, cotton synthetic fibre, circular woven jacketed rubberized fabric reinforced rubber lined (RRL) , 35.7 Kg/cm2 burst pressure and 22 Kg/cm2 proof pressure, 63 mm dia of 15 mtr long with male and female GM coupling of 63 mm dia complete all as specified and directed.
(Make – Zenith/ Jyoti/Fire Shield).
18
-
-
... More
S&F in repairs fire fighting GM landing valve (Hydrant valve single headed) with 80 mm NB flanged inlet brass spindle 63 mm dia female oblique outlet including rubber washer complete all as specified and directed.
(Make – Zenith/ Jyoti/ Fire Shield).
6
-
-
... More
Dismantling and taking down the electric motor of fire pump set 25 HP capacity and transporting to work Shop and carrying out winding of motor unit as per the following maintenance work:-
(a) Opening of electric motor and carry out winding of armature with required size of copper wire, changing of bearing, insulation and including varnishing and greasing
(b) Cleaning of used/ old lubricated substance
(c) Cleaning of starter and rotor unit
(d) Checking and tightening of coupling, nuts, bolts and replacement of rubber insert.
(e) Carrying out heat varnishing with varnish solution of best quality for field and armature coil.
(f) Replacement of oil worn out bearings.
(g) Reassembling the complete motor and carrying out testing at work Shop and transporting back to installation and coupling with pumping set including necessary alignment, cable connection all as directed.
1
-
-
... More
Disconnecting and taking out the electric driven Jockey pump of discharge capacity 500 LPM at 7.5 kg/sqcm by disconnecting the pump motor coupling, inlet and outlet pipe line for foundation etc. Repair to pump by replacement of worn out gland cap, gland bush, coupling and bearing, repairing of worn out shaft, impeller by suitable re-metalling, finishing up to suitable size and doing necessary heat treatment, replacement of impeller key with new one including necessary heat treatment, reassembling the pump after repairs, including replacement of all nuts, bolts, washers, gland packing, greasing etc and fixing the pump in its original position / foundation and testing on load complete and all as directed and as specified.
2
-
-
... More
Dismantling and taking down the electric motor of fire pump set 100 HP capacity and transporting to work Shop and carrying out winding of motor unit as per the following maintenance work:-
(a) Opening of electric motor and carry out winding of armature with required size of copper wire,changing of bearing, insulation and including varnishing and greasing
(b) Cleaning of used/ old lubricated substance
(c) Cleaning of starter and rotor unit
(d) Checking and tightening of coupling, nuts, bolts and replacement of rubber insert.
(e) Carrying out heat varnishing with varnish solution of best quality for field and armature coil.
(f) Replacement of oil worn out bearings.
(g) Reassembling the complete motor and carrying out testing at work Shop and transporting back to installation and coupling with pumping set including necessary alignment, cable connection all as directed.
1
-
-
... More
Disconnecting the suction and delivery pipe line and electric connections of unserviceable centrifugal pump of head-90 m, discharge-180 cum per hour coupled with electric motor 100 HP, 3 Phase and removing it from its position carefully and transporting to the work shop and refixing the same in its original position after servicing including replacement of bushes , machining the pump shaft to suit in new bushes all as specified and as directed.
Note : (i) Consumable stores like cotton waste/cleaning materials lubricants, gland packing metal filling, machining and transportation from site to work shop are deemed to be included in rate quoted
1
-
-
... More
Supply and fixing in repairs PVC insulated and sheathed Copper Flexible Cable cable, 3 core multistranded copper conductor of 1100 volts grade conforming to IS-694, of size 25 sqmm in PVC conduit from starter to motor, complete all as specified and directed.
100
-
-
... More
Supply and fixing in repairs PVC insulated and sheathed Copper Flexible Cable cable, 3core multistranded copper conductor of 1100 volts grade conforming to IS-694, of size 50 sqmm in PVC conduit from starter to motor, complete all as specified and directed.
105
-
-
... More
S&F in repair on load change over switch 200 Amps 4 pole for open mount including taking down old change over switch, complete all as specified and directed.
2
-
-
... More
S&F in repairs MCCBs 200 Amps with fixed thermal and fixed magnetic type , 35 KA 4 pole in existing panel, complete all as specified and directed.
2
-
-
... More
S&F in repairs MCCBs 250 Amps with fixed thermal and fixed magnetic type , 35 KA 4 pole in existing panel, complete all as specified and directed.
2
-
-
... More
S&F MS ERW pipe of 80 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe, complete all as specified and directed.
28
-
-
... More
S&F MS ERW pipe of 100 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe, complete all as specified and directed.
22
-
-
... More
S&F MS ERW pipe of 150 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer ant testing including taking down old MS pipe, complete all as specified and directed.
13
-
-
... More
M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to 32x6 mm GI iron strip earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (light grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with RCC cover slab of size 42cm x 42 cm and 10mm thick , funnel, wire mesh, 20 mm bore galvanized iron pipe (light grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing.(note :- 7.5 mtr GI strip with 40 mm GI pipe is included in above item)
9
-
-
... More
Supply & fixing in replacement of earth continuity conductor GI strip 32x6 mm, complete all as specified and directed.
42
-
-
... More
S&F in repir over load relay 60-100 amp, including taking down one, complete all as specified and directed.
3
-
-
... More
S&F in repair over load relay 90-150 amp, including taking down one, complete all as specified and directed.
2
-
-
... More
S&F in repair 3 pole power contactor of capacity AC3 rating 95 Amps and AC1 rating 160A, 415 volts main contactor coil voltage 110 Volt, complete all as specified and directed.
2
-
-
... More
S&F in repair 3 pole power contactor of capacity AC3 rating 80 Amps and AC1 rating 100A, 415 volts main contactor coil voltage 110 Volt with, complete all as specified and directed.
2
-
-
... More
S&F in repair 3 pole power contactor of capacity AC3 rating 25 Amps and AC1 rating 45A, 415 volts main contactor coil voltage 110 Volt with, complete all as specified and directed.
1
-
-
... More
S&F in repair Auxiliary contact 2 NO + 2 NC for Power contactor range of 25A-95A, complete all as specified and directed.
6
-
-
... More
S&F in repair LED Panel indicator lamp of any type to match with existing and of colour Red, Yellow, Blue. 22 mm Dia, complete all as specified and directed.
12
-
-
... More
M&L for painting to Fire boxes and exposed pipe lines of steel / iron surfaces of any description, over 10 cm in width or girth, not otherwise described after preparation of old painted surface, with one coat of red oxide primer and two coats of synthetic enamel paint as per colour code and all as directed and approved.
81
-
-
... More
Supply and fix female outlet stainless steel as per IS: 3444 Gr.1 outlet adapter for fire fighting hydrant valve after taking down old one, complete all as specified and directed.
15
-
-
... More
M&L for brickwork with subclass ‘B’ old size bricks with cement mortar (1:4) straight or curved on plain exc 6 m mean radius, complete all as specified and directed.
2
-
-
... More
M&L for cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregate) as in copping, complete all as specified and directed.
1.25
-
-
... More
M&L for Rendering cement plaster 15 mm thick with cement mortar (1:4) on fare faces of brick work or concrete surfaces, complete all as specified and directed.
40
-
-
... More
M&L for applying with two coats of white wash after preparation of surafces of any description,of wall of repaired / existing valve pits or in any description complete all as specified and directed.
40
-
-
... More
S&F pressure gauge 100 mm dia with 0-14 kg/cm2 rating including taking down old u/s, complete all as specified and directed.
10
-
-
... More
Supply and fix rubber seat washer as per IS 937 for fire fighting hydrant valve after taking down old one, complete all as specified and directed.
20
-
-
... More
S&F fully Automatic star delta starter for fire pump controller(IP54) 25 HP capacity ,415 coil voltage with relay range 24-38 Amps including combined V/A meter,voltmeter selector switch, star delta timer and SPP suitable for 25 HP Centrifugal pumping set including taking down old star delta starter all as specified and directed. Model -MU G25 FASD of Make - L&T or equivalent of model & make in Havells/Crompton Greaves/BCH etc
1
-
-
... More
Supply and fix of Voltmeter with selector switch of range 0-500V complete all as directed.
3
-
-
... More
Supply and fix of Ampere meter with selector switch of range 0-150 A complete as directed.
3
-
-
... More
S&F pressure gauge 100 mm dia with 0-14 kg/cm2 rating including taking down old u/s complete.
5
-
-
... More
Supply , installation, testing and commissioning of Compact type factory made CPRI Approved LT Panel board as per specicified make ,Indoor type,floor mounted as per equipment made out of CRCA sheet of 3.15mm thick outer sheet cover and 2mm thick inner comprtment sheet cover with 75x75x6 mm of angle iron frame by using PCC 1:2:4 type B-1(using 20mm graded stone) for fixing of panel and duly painted with powder coating over a coat of red oxide primer all over with canopy totally enclosed weather, dust and vermin proof with openable shutters/compartments with locking arrangement on front and back side of panel suitable for 3 phase 4 wire LT AC, 50 Hz, 415 Volts including suitable copper bus bar. PCC foundation/platform as per manufacturer guide lines for installing the panel board complete for accommodating the following accessories.
1
-
-
... More
Incoming:-
(a) MCCB 320 amps with fixed thermal and fixed magnetic type, four pole ,35 KA 01 No
(b) On load change over switch 320 Amps , 4 pole - 01 No (c) LED Multi function meter - 01 No (d) CT 100/5 - 03 Nos (e) LED type Indicating lamp R, Y, B, 415 V (set of 3 ) -01set (f) copper bus bar TPN of rating not less than the 1.5 times the rated capacity of the incomer MCCB with necessary wiring including wiring material .
Outgoing:-
(a) MCCB fixed thermal and fixed magnetic type, 63 amps, four pole ,25 KA - 01 No (b) S&F Fully Automatic star delta starter Fire pump controller (IP54) 100 HP capacity, 80 KW,415 with suitable contactors, MPCB, coil voltage and relay range 90-160 Amps including combined V/A meter,voltmeter selector switch, star delta timer and single phase preventor with 3 indicator light (for start,stop and trip). All accessories V/A meter, selector switch, indicator light and start and stop button will be fixed on outer cover of respective compartment. - 01 Nos
-
-
-
... More
(c) S&F Fully Automatic star delta starter Fire pump controller (IP54) 75 HP capacity, 60 KW,415 with suitable contactors, MPCB, coil voltage and relay range 66-110 Amps including combined V/A meter,voltmeter selector switch, star delta timer and single phase preventor with 3 indicator light (for start,stop and trip). All accessories V/A meter, selector switch, indicator light and start and stop button will be fixed on outer cover of respective compartment. - 01 Nos (d) S&F Fully Automatic star delta starter Fire pump controller (IP54) 25HP capacity, 20 KW,415 with suitable contactors, MPCB, coil voltage and relay range 24-38 Amps including combined V/A meter,voltmeter selector switch, star delta timer and single phase preventor with 3 indicator light (for start,stop and trip). All accessories V/A meter, selector switch, indicator light and start and stop button will be fixed on outer cover of respective compartment - 01 Nos
(e) MCCBs fixed thermal and fixed magnetic type 160A, 4 pole, 25KA, 50HZ, 415V - 01 nos mounted on 100HP starter compartment.
(f) MCCBs fixed thermal and fixed magnetic type 125 A, 4 pole,25KA, 50HZ, 415V - 01 nos mounted on 75HP starter compartment.
(g) MCCBs fixed thermal and fixed magnetic type 63A, 4 pole, 25KA, 50HZ, 415V - 01 nos mounted on 25HP starter compartment
(h) MCB TPN 63A, C curve ,10KA - 02 Nos
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%