Military Engineer Services Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date20 Nov 2024
Closing Soon2 Dec 2024
Tender Amount₹ 14,65,000
Costs
EMD
₹ 30,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_679796_2Tender No
85001/SING/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply only servo motor assembly of capacity 10kg/cm2 oil immerse able type suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
3
-
-
Supply only control circuit assy suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
2
-
-
Supply only carbon bushings suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
2
-
-
Supply only of RC Network suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
2
-
-
Supply only digital volt meter suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
4
-
-
Supply only Control switch suitable for voltage stabilizer upto 250 KVA all complete all as specified and as directed
3
-
-
Supply only power pack online UPS of cap 1 KVA online suitable for 1 MVA automatic voltage regulator all complete all as specified and as directed.
1
-
-
M& L for load balancing 3 phase Voltage stabilizer input voltage 300 to 480V, output voltage 415 +/-1% by setting up gear speed through RC network, setting up relays and control circuits load cleaning the contacts, lubrication of moving parts including servo motor all as specified and re-fixing the same with checking of control wiring , testing & Calibration of Auto/Manual system for satisfactory functioning all as directed by Eng-in-Charge.
5
-
-
Supply and topping up /replacement of new voltage stabilizer oil of dielectric strength 35 KV at 4 mm gap in stabilizers of various cap installed in various locations. complete all as specified and as directed by eng-in-charge.
Make of Voltage stabilizer oil: Power Oil / Indian Oil / Rinkyl or equivalent Note :(a) New oil in the Voltage Stabilizer will be filled in the Voltage Stabilizer only after filtration and dehydration of existing oil of the Voltage Stabilizer. (b) New oil shall be supplied in sealed barrel with test result and test certificate.
400
-
-
Dehydration/Filtration of Transformer Oil by means of Centrifugal Filtration Plant to achieve the specified Di-electric Strength complete all as specified and as directed.
NOTE : Transformer Oil to be use for TOP UP shall be Measured and Paid for separately.
950
-
-
M&L for calibration all type of protection relays fixed in various type/make VCBs installed at different MRS/Sub Stations . The calibrations of protection relay is to ensure no ever and respective fault arresting. The relays to be calibrated and set in accordance with CT ratio and load of the feeder and sub-station. The tripping time of relays should be as per IS standards / manufacturer recommendation synchronized with existing panel / system. All the parameters of relays to be checked and corrected where necessary for proper functioning and the fault should not affect the next feeder / system/ equipment installed beyond the VCB. The minor repair / replacement required for calibration of relays observed to be incl in the item rate and as directed by Engri-in-Charge. The calibration should be carried out by the authorized representative from the respective manufacturer of VCB.
14
-
-
M&L for replacement of battery bank with 15 nos of battery 12 Volts, 7.5 AH for battery charger input 230 volts, Ph 1, 50 Hz, output 30 volts, 20 amps DC , output :110V DC Filtered/Unfiltered (+) , cap : 180VA suitable for 11KV, 630/800 Amps shall be matching with the existing make of VCB . All switches shall have provision to receive both 110V A.C from PT and 110V D.C voltage from Battery Bank and from inbuilt Rectifier Circuit / Power Pack Unit, to be incorporated in the switch. Suitable Contactor unit is to be incorporated in the circuit such that in normal condition, VCB Control Circuit will operate by 110 V DC from Rectifier Circuit/Power Pack Unit and 110 V DC from battery bank will be in circuit by auto changeover in case of failure of inbuilt rectified 110V DC. Inbuilt rectified 110V DC should have storage capacity to be capable of tripping the circuit at least 2 to 3 times in case of power failure from PT all complete all as directed by Engr-in-Charge
1
-
-
Supplying and laying synthetic Rubber insulated mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m all complete
6
-
-
M&L for Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 33000 volts all complete
3
-
-
Supply and fix ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps with enclosure 65kA including Taking down old unserviceable MCCB and fixed on LT Panels and connecting up all as specified and as directed & in the process of fixing of ACB minor drilling, clamping ,screw ,nut, bolt &washer all as directed by Eng-in-Charge included in quoted rate all complete as specified and as directed. Make L&T/ Havells / Hager/Legrand
2
-
-
Supply and fix MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA including Taking down old unserviceable MCCB and fixed on LT Panels and connecting up all as specified and as directed by Eng-in-Charge included in quoted rate all complete as specified and as directed. Make L&T/ Havells / Hager/Legrand
2
-
-
Supply and fix MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA including Taking down old unserviceable MCCB and fixed on LT Panels and connecting up all as specified and as directed by Eng-in-Charge included in quoted rate all complete as specified and as directed. Make L&T/ Havells / Hager/Legrand
2
-
-
M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size all complete
20
-
-
M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size all complete
16
-
-
S&F in repair 11 KV HT Bus bar panel of size 1100 x 900 x 800 mm, made out of 3.15 mm thick CRCA sheet outdoor typel cubicle, sloping canopy top roof, floor mounted, free standing, dust and vermin proof, air ventilation louvers both side openable hinged double door, front side operable hinged compartments with locking arrangements, detachable gland plate at bottom for cable entry / exit all opening will be covered with rubber gasket, danger plate all complete with copper bus bar 630 Amps including labelling incoming details and outgoing details incoming gear about termination of switch gear, and the nuts/ bolts etc used all complete all as per direction of Engr in charge.
1
-
-
Supply and fix cable joint kit for 11 KV grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm all as specified and directed by EIC.
1
-
-
Supply and fix cable joint kit for 11 KV grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm all as specified and directed by EIC.
1
-
-
M&L for straight through heat shrink cable jointing kit for 11KV ( Earthed ) grade cable for type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed by Engineer-in-Charge.
1
-
-
Supply and laying in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor (multistranded), 95 Sqmm 3 core , 11000 volts grade connected with suitable size brass cable gland and aluminium lugs of required size, laid in trenches or passing through pipes including testing after laying, including taking up old unserviceable cable complete of following size all as specified and directed by Engineer-in-Charge.
70
-
-
Supplying, laying, testing and Commissioning cable XLPE insulated aluminium conductor, stranded, armoured, PVC sheathed, LT 1100 volt grade 400 Sqmm, 3.5 core heavy duty as per IS-7098 and providing suitable lugs and cable glands, laid in trenches/ ducts/fixed to wall/ roof/ poles including taking down existing cables complete all as specified and directed.
85
-
-
Supplying and laying common burnt clay sub class ‘B’ bricks of size 230 mm x 113 mm x 75 mm, laid perpendicular to axis of cable for protection of LT cables complete all as specified and as directed.
800
-
-
Supply and laying in replacement of un-reinforced precast concrete cable cover, class HV, type 1 with peak, size 300mm x 180mm x 40 mm including taking down old unserviceable cable cover complete all as specified and directed by Engineer-in-Charge.
280
-
-
M & L road cutting of size (30x45) cm width and depth 30 cm width 45 cm depth for laying of cables incl making good the road with necessary returning filling and bituminous portion with concrete and bituminous mixture and cemented portion with PCC in 1:2:4 , 15 cm thick from top and matching the surfaces with existing all as directed.
5
-
-
Supplying and laying GI pipe Light grade (ISI marked) 50mm bore with connecting accessories, laid under road/ drain/fixed on wall etc for protection of cables complete all as specified and as directed
12
-
-
Excavation in trenches not exceeding 1.5 M wide and not exceeding 1.5 M in depth and getting out in soft/loose soil or hard/dense soil for taking up or laying of cable all as specified and directed.
27
-
-
Supply and laying dry river sand laid in trenches 8cm below the cable and 15cm above the cable and punned to 18cm as cable cushioning and covering complete all as specified and directed by Engineer-in-Charge. Note:- Punned quantity will be measured paid at this item.
9
-
-
Removing excavated material not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above starting point all as specified and directed by Engineer-in-Charge. .
5
-
-
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft /loose soil or hard/dense soil all as specified and directed by Engineer-in-Charge. .
22
-
-
M&L in replacement for Earthing complete with galvanised steel earth plate electrode of size 600x600x6mm thick burried in a pit to a depth of 2.25mtrs below ground level with top edge of earth plate at a depth of not less than 1.50 meters below ground level, earth plate packed on all sides with charcoal dust mixed with salt to a thickness of 15cm, connected with earthing lead of 32mm x 6mm galvanised iron strip, watering pipe 20mm dia light grade and water filling funnel and mess complete all as shown in plate No 4 of MES Schedule part II to the earthing test point, including PCC Work complete including protection pipe 40 mm dia light grade all as specified and directed by Engr-in-Charge. (Note :- The earth strip/lead up to 7.5 m shall be deemed to be included quoted unit rate.)
8
-
-
M&L for preparation of old painted surfaces of any description over 10 cm in width or girth and applying two coats of synthetic enamel paint of suitable colour to match the existing surface of LT panels over a coat of red oxide primer and all complete all as directed
25
-
-
Schedule of Credit
-
-
-20424
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%