Military Engineer Services Tender

Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.

Military Engineer Services - MES Tender

Works
Eprocure
Opening Date7 Jan 2021
Closing Date3 Feb 2021
Tender Amount₹ 46,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M&L for rewinding of burnt submersible motor, 5 Hp to7.5 Hp capacity, 3 phase, 415 volts, 50 Hz of any make with PVC insulated super enmelled copper wire of same (old) gauge as per manufacturer's instruction / specifications after dismantling / cutting out old burnt winding from starter assembly, cleaning of slots properly complete with insulating materials, packing, sleeves, papers, matching works, including servicing / overhauling of pump and re-assemblying of motor and pump including painting with two coats of synthetic enamel paints over a coat of red oxide primer after preparation of external surfaces and water proof jointing for submersible cable 3 core complete all as specified and directed with and including transportation of unserviceable motor and pump assembly to nearest authorised workshop for repair from site and taking back the same after repair / servicing and overhauling at site. Note : The spare parts required for overhauling / servicing of submersible pump assembly except winding wire, labour charges, tools, and other items described above, shall be measured and paid as 'supply only' separately under relevant items.

1

-

-

... More
M&L for rewinding of burnt submersible motor, 1.5 Hp to 3.0 Hp capacity, 3 /1 phase, 415 volts, 50 Hz of any make with PVC insulated super enmelled copper wire of same (old) gauge as per manufacturer's instruction / specifications after dismantling / cutting out old burnt winding from starter assembly, cleaning of slots properly complete with insulating materials, packing, sleeves, papers, matching works, including servicing / overhauling of pump and re-assemblying of motor and pump including painting with two coats of synthetic enamel paints over a coat of red oxide primer after preparation of external surfaces and water proof jointing for submersible cable 3 core complete all as specified and directed with and including transportation of unserviceable motor and pump assembly to nearest authorised workshop for repair from site and taking back the same after repair / servicing and overhauling at site. Note : The spare parts required for overhauling / servicing of submersible pump assembly except winding wire, labour charges, tools, and other items described above, shall be measured and paid as 'supply only' separately under relevant items.

1

-

-

... More
Supply only following spare parts suitable for submersilble pump set vertical type (10 HP to 15 HP ) complete all as specified and as directed.

-

-

-

... More
Stainless steel impeller as per existing

2

-

-

... More
Thrust bearing as per exsiting

4

-

-

... More
Thrust plate set as per existing

2

-

-

... More
Sand guard as per existing

2

-

-

... More
Stainless steel bush as per existing

4

-

-

... More
Pump shaft as per existing

2

-

-

... More
Supply only following spare parts suitable for submersilble pump set vertical type (5 HP to 7.5 HP ) complete all as specified and as directed.

-

-

-

... More
Stainless steel impeller as per existing

2

-

-

... More
Thrust bearing as per exsiting

2

-

-

... More
Thrust plate set as per existing

2

-

-

... More
Sand guard as per existing

2

-

-

... More
Stainless steel bush as per existing

2

-

-

... More
Pump shaft as per existing

2

-

-

... More
Supply only following spare parts suitable for submersilble pump set vertical type (1.5 HP to 3 HP ) complete all as specified and as directed.

-

-

-

... More
Stainless steel impeller as per existing

1

-

-

... More
Thrust bearing as per exsiting

2

-

-

... More
Thrust plate set as per existing

2

-

-

... More
Sand guard as per existing

2

-

-

... More
Stainless steel bush as per existing

1

-

-

... More
Pump shaft as per existing

1

-

-

... More
Dismantling of GI Pipe Connections from the Pressure Flter Plant capacity 5000 GPH , and opening the Manhole and removal/taking out old Filter Medias completely from Oxidation Chamber, Pre-filter, Iron Removal Filter and depositing the same to a distance not exc. 100 Metre and re-fixing the pipes in the original/existing Position after replacement of unserviceable PVC Nozzle (Dom type) including replacement of Gasket of Manhole Cover and necessary Bolts, Nuts, Washers, etc. as required, complete all as specified and as directed. NOTE :- (a) PVC Nozzale shall be measured and paid separately under appropriate Item as 'Supply only' here-in-after. (b) Filling of Filter Media shall be measured and paid separately under appropriate Item of this Schedule of Works/BOQ.

2

-

-

... More
Supply and incorporation of MNO2 of size 1/8'' x 1/10'' as filter media of iron removal plant ,complete all as specified & directed.

160

-

-

... More
Supply and incorporation of GRAVEL of size 1 1/4'' x 1 1/2''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as filter media of iron removal plant ,complete all as specified & directed.

1.5

-

-

... More
Supply and incorporation of GRAVEL of size 1/2'' x 1''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as filter media of iron removal plant ,complete all as specified & directed.

1.5

-

-

... More
Supply and incorporation of GRAVEL of size 1/4'' x 1/2''(collection sourceBARAKAR river bank) as filter media of iron removal plant complete all as filter media of iron removal plant ,complete all as specified & directed.

1.5

-

-

... More
Supply & incorporation of SAND of size 1/6" x 1/8'' mesh (collection source BARAKAR river bank) as filter media of iron removal plant complete all as filter media of iron removal plant ,complete all as specified & directed.

1.4

-

-

... More
Supply & incorporation of Anthracite grit of size 1/8" x 1/4'' as filter media of iron removal plant complete all as filter media of iron removal plant ,complete all as specified & directed.

1.5

-

-

... More
Supply and fixing PVC strainers of size as dismantled of Make: PHI / RAMCO , complete all as specified and directed.

130

-

-

... More
M&L Painting to Internal Surfaces of Iron Removal Chamber, including Pipes complete of Filteration Plant capacity 5000 GPH with Two Coats of Black Bituminous Paint (Lead Free) suitable for Drinking Water grade including necessary surface preparation by means of scraping, brushing, cleaning, complete all as specified and as directed.

2

-

-

... More
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep in soft/loose soil getting out and levelling of bottom surface to required level for poles/stay assembly/cable all as specified and as directed.

732

-

-

... More
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick all as specified and directed.

510.87

-

-

... More
Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point all as directed.

276.35

-

-

... More
Supply and laying burnt clay sub class B brick as cable protection all as specified and directed.

1020

-

-

... More
Relaying only old recovered cable cover of any size in trenches all as directed by Engr-in-Charge.

10500

-

-

... More
Supplying & Laying in trenches Clear Sand for cushioning of under ground cable 8 cm below and 15 cm above complete in level all as specified. Note: Punned thikness shall be measured.

116.64

-

-

... More
M&L for PCC 1:3:6 Type C2 (using 40 mm graded sotne aggregate) for foundation of pole, stay incl form work where reqd all as directed.

3

-

-

... More
M&L for PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) for coping, grouting, finished even and smooth without using extra cement all as directed.

1

-

-

... More
M & L for laying "XLPE" LT underground Cable, XLPE insulated, heavy duty armoured sheathed 1100 volts grade 10 Sq mm, 2 core, with aluminium conductor, ISI marked as per IS : 7098(Part-1) including taking out unserviceable cable and removing from site complete all as specified.

300

-

-

... More
All as per item No 24 above but 16sqmm, 4 core all as specified.

100

-

-

... More
All as per item No 24 above but 25sqmm, 3.5 core all as specified.

100

-

-

... More
All as per item No 24 above but 35sqmm, 3.5 core all as specified.

150

-

-

... More
All as per item No 24 above but 70sqmm, 3.5 core all as specified.

150

-

-

... More
All as per item No 24 above but 95sqmm, 3.5 core all as specified.

150

-

-

... More
All as per item No 24 above but 120sqmm, 3.5 core all as specified.

100

-

-

... More
All as per item No 24 above but 150sqmm, 3.5 core all as specified.

150

-

-

... More
Taking down existing unserviceable/faulty LT UG cable 1100V of any size from existing location and relaying the same after necessery repair work all as specified and as directed. (Note: Items if required for repair and excavation works will be measured and paid seperately under relevant items)

400

-

-

... More
Supply and fixing cable joining kit for 1.1 KV grade for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 /4 core XLPE, armoured, AI conductor cable of size 25 to 50 Sqmm, including taking out & relaying damaged UG cable after repair complete all as specified and as directed. (Note: Excavation and connected items will be measured and paid separetely).

10

-

-

... More
All as per item No 26 above but size 70-120sqmm, 4 core all as specified.

5

-

-

... More
All as per item No 26 above but size 150-185sqmm, 4 core all as specified.

3

-

-

... More
Restring/Fixing only of existing ACSR conductor any size/any type drawn on fixed to insulator on the pole complete with permissible sags for OH Conductor as per Indian Electricity Rules 1956 - Para 77 and 79 all as specified and directed.

2

-

-

... More
Labour for cutting of trees branches 2 mtr above the conductor which are touching to the HT/LT over head lines in vertically & horizontally conductor and poles etc. Complete clear in a standard span in between two poles at forest/ high gradient/ any type of surfaces and removing cutting material not exc 50 mtr and depositing where directed at a level not exc 3 mtr from starting point, minimum 04 Nos of mazdoor with ropes/cutting tools complete will be engaged, follows safety measures as per IE Rules, complete all as speciied and as directed.

70

-

-

... More
M & L in repair GI tubing 40 mm bore light grade with all fitting fixed to wall/ceiling/floor as cable protection all as specifed and directed.

50

-

-

... More
M & L in repair GI tubing 50 mm bore light grade with all fitting fixed to wall/ceiling/floor as cable protection all as specifed and directed.

30

-

-

... More
M & L in repair GI tubing 80 mm bore light grade with all fitting fixed to wall/ceiling/floor as cable protection all as specifed and directed.

50

-

-

... More
M&L MCCB 4 Pole, including taking down old u/s having current rating 250 Amp, thermal magnetic setting adjustable 70%-100% breaking capacity 25 KA at 415V,50Hz, Frame size/type CH.along with spider links.

1

-

-

... More
M&L MCCB 4 Pole, including taking down old u/s having current rating 160 Amp, thermal magnetic adjustable 70%-100% breaking capacity 16kA at 415V,50Hz, Frame size/type CH along with spider links.

4

-

-

... More
M&L MCCB 4 Pole, including taking down old u/s having current rating 63-100 Amp, thermal magnetic adjustable 70%-100% breaking capacity 16 KA at 415V,50Hz, Frame size/type CH along with spider links .

12

-

-

... More
M&L cutting for raod crossing, PCC hard standing for laying of cable/protection pipe including making good the existing damaged surface with same finish using PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) to match the original finish complete all as specified and as directed.

4.5

-

-

... More
M&L for boring horizontal holes upto 2mtr deep in soil under roads/PCC as directed for cable passing through pipes of required size and disposal of soil to a distance not exc. 50m. (Note: Connected items like Pipes is measured and paid seperately under relevant items).

15

-

-

... More
M&L disconnecting the XLPE UG cable connection from existing MCCBs in the existing LT panel/feeder pillar box completely and repair the terminal point of cable by providing new cable lugs, nuts & bolts of appropriate size and crimp the cable lugs by crimping tools as per technical requirements, wrap PVC insulation tape as per colour coding and connect the cable in same way as per existing in existing MCCB complete incl excavationfor taking out burried cable if required all as specified and as directed by Engr-in-Charge.

20

-

-

... More
M & L for preperation of Metal surfaces of LT Panel/feeder pillar box (Size below 1.0x1.2x0.6m) of any description and aplying one coat of synthetic enamel paint by spray of colour match with original including cleaning grass/herbs etc from panel 1 meter nearby ground complete all as specified and as directed by the engr-in-charge

20

-

-

... More
M & L for preperation of Metal surfaces of LT Panel/feeder pillar box (approx size 2.0x2.5x0.6m) of any description and aplying one coat of synthetic enamel paint by spray of colour match with original including cleaning grass/herbs etc from panel nearby ground complete all as specified and as directed by the engr-in-charge

20

-

-

... More
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, made out of stainless steel sheet 2.00mm thick grade AISI-304, padestal mounted, factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in. Incoming :- (i) MCCB 250 Amps 4 pole breaking capacity 25 KA thermal megnetic protection with Icu = 100% & rated impulse with stand voltage (Vimp) 8 KV with over current & short circuit pro-tection having double insulation & positive insulation-01 No. Outgoing :- (i) Aluminium busbar rating 500 Amps rating 04 Nos with provision for making connections of outgoing cables all as required and as directed. (ii) MCCB 100A, 16KA breaking capacity with thermal magnetic protection 02 Nos (iii) MCCB 63A, 16KA breaking capacity with thermal magnetic protection 02 Nos (ii) Current transformer 400/5Amps class-1 15 VA - 1 Nos.(iii) Digital Ammeter with inbuilt selector switch -01 No. (iv) Digital Voltmeter with in built selector switch-01 No. (v) Modular Indication lamp LED type RYB (set of 3) "MCCB will be connected through busber"

2

-

-

... More
S&F Shackle type, porcelain, vitreous white, brown or green insulator including galvanized mild steel strap of 31x3mm size, washers, insulator bolts of 12mm dia, washers and nuts, working pressure 1100 volts grade, 90mm dia, 75mm height complete all as specified and all as directed by Engr-in-Charge.

20

-

-

... More
S&F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 1100 volts grade all as specified and as directed

40

-

-

... More
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strip 25x4mm as earth lead by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 3 of SSR part I including necessary excavation and earth work GI pipe 20mm dia light grade for watering and GI 32mm dia light grade pipe for protection of GI earth strip etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded stone aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to LT panel board as indicated including testing complete all as specified and as directed.

40

-

-

... More
M&L for replacement of steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts & screw as specified type 410 SP-31, 9.0 meter long all as specified and directed by Engr-in-Charge.

10

-

-

... More
M & L for Cross arms, bracings, supports, clamps fabricated rectangular pole structure ( for 33 KV CT, PT, Ganf & LA etc.) & back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending, cold or hot drilling holes for bolts, in any shape or size as indiacted or directed and inclusive of one primer coat, one under coat and one finishing coat of Aluminium paint all as directed.

2

-

-

... More
S&F in repair digital time switch with quick and easy programming having precision to the second and weekly overview on display including making necessery wiring and connections as directed by Engr in charge.

1

-

-

... More
S&F in repair contactor 3 pole 415Volt with integrated auxilary contacts 2NO + 2NC of 50A rating including making necessery connections all as specified.

1

-

-

... More
S&F earth continuty conductor or main earthing lead fixed to wall or batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x4mm aluminium strip all as directed.

15

-

-

... More
S & F lugs made out of aluminium for underground cable of size 150/120sqmm 3.5 C (03 Nos lugs for phase and 01 No for neutral) including taking down old lugs complete all as specified and directed.

20

-

-

... More
S & F cable lugs made out of aluminium for cable size 95/70 sqmm 3.5 C (03 Nos lugs for phase and 01 No for neutral) including taking down old lugs complete all as specified and directed.

37

-

-

... More
S & F cable lugs made out of aluminium for cable size 50/35 sqmm 3.5 C (03 Nos lugs for phase and 01 No for neutral) including taking down old lugs complete all as specified and directed.

39

-

-

... More
S & F cable lugs made out of aluminium for cable size 25 sqmm 4 C (03 Nos lugs for phase and 01 No for neutral) including taking down old lugs complete all as specified and directed.

30

-

-

... More
S & F cable lugs made out of aluminium for cable size 16/10/6 sqmm 2 C (01 Nos lugs for phase and 01 No for neutral) ncluding taking down old lugs complete all as specified and directed.

35

-

-

... More
Supply and fixing LED street light fittings,72 watts , IP 66 powder coated pressure die cast aluminium compact high power LED street light with heat resistant toughened glass and unique peanut lens to ensure uniform distribution, higher spacing between poles complete all as specified and as directed by the Engr-in-charge.

15

-

-

... More
S&F MCCB 40 amps, 4 pole, 415 volts, 50 Hz 16 kA breaking capacity with adjustable thermal magnetic release with spreader link on both sides complete all as specified and as directed including taking down us MCCB any type any size.

12

-

-

... More
S&F 4 pole MCCB of 125Amp with property thermal magnetic release, breaking capacity 25KA complete all as specified and directed.

6

-

-

... More
S&F Stay assembly complete with all accessories as shown in electrical plate No. 1 of SSR Part-I using 16mm dia stay rod and 1.80m long, stay bow 20mm dia, stay plate 23cmx23cm, stay wire 7/4.00mm (10.00m to 11.00m long), stay clamp made out from 50x5mm mild steel flat iron and porcelain loop insulator 90mmx65mm, clearance of hole 16mm complete all as specified and all as directed by Engr-in-Charge. (Note : Excavation, earth work and concrete shall be measured and paid separately)

4

-

-

... More
Dismantling of stay assembly embedded in concrete and removing materials from site of work complete all as directed by Engineer-in-Charge.

4

-

-

... More
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, made out of stainless steel sheet 2.00mm thick grade AISI-304, padestal mounted, factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in. BUSBAR :- 150 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance INCOMING:- (i) MCCB 4P of capacity100 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digi twith LED display-- 01 No (iii)3 Ph digital Ampere meter Class 1 accuracy , 0.5 VA burdenwith LED display-- 01 No (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (v) CT (100/5A) -03 Nos OUTGOING:- (a) MCB 4 Pole of capacity 80-63 Amp , breaking capacity 16 KA with thermal release -4Nos (b) MCB 4 Pole of capacity 40 Amp , breaking capacity 10 KA with thermal release - 3 Nos (c) MCB 2 Pole of capacity 32 Amp , breaking capacity 10 KA with thermal release -10Nos (d ) Spare pocket for MCCB - 1 "MCCB will be connected through busber"

1

-

-

... More
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, made out of stainless steel sheet 2.00mm thick grade AISI-304, padestal mounted, factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in. BUSBAR :- 100 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance INCOMING:- (i) MCCB 4P of capacity 63 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digi twith LED display-- 01 No (iii)3 Ph digital Amphere meter Class 1 accuracy , 0.5 VA burdenwith LED display-- 01 No (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (v) CT (100/5A) -03 Nos OUTGOING:- (a) MCB 4 Pole of capacity 32 Amp , breaking capacity 10 KA with thermal release -4Nos (b) MCB 2 Pole of capacity 32 Amp , breaking capacity 10 KA with thermal release -12 Nos (c) Time Switches astro type (having longitude and latitude of indian cities in memory) 250 V single phase of 20 Amp Rating With 3 phase 63A Contactor fitted inside steel enclosure (d ) Spare pocket fo MCCB - 1 "MCCB will be connected through busber"

1

-

-

... More
Supply,installing, testing and commissioning out door type LT feeder piller box of suitable size, made out of stainless steel sheet 2.00mm thick grade AISI-304, padestal mounted, factory made totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear side, framing with 50 x 50 x 6 mm thick MS angle iron and legs of size 0.5m long . duly fabricated and having proper locking arrangement in both front and rear door with 4 side slanting roof duly projected and suitable for 500 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Platform made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in. BUSBAR :- 250 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance INCOMING:- (i) MCCB 4P of capacity 160 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 16KA with thermal magnetic release -01 No (ii) 3 Ph digital volt meter Class 1, 0-500 volts, 3 Phase, 4 digi twith LED display-- 01 No (iii)3 Ph digital Ampere meter Class 1 accuracy , 0.5 VA burdenwith LED display-- 01 No (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (v) CT (100/5A) -03 Nos OUTGOING:- (a) MCB 4 Pole of capacity 125 Amp , breaking capacity 36 KA with thermal release -02Nos (b) MCB 4 Pole of capacity 40 Amp , breaking capacity 16 KA with thermal release -04 Nos (c) MCB 2 Pole of capacity 32 Amp , breaking capacity 10 KA with thermal release -08 Nos (d ) Spare pocket fo MCCB - 2 (e) MCB 2 Pole of capacity 16 Amp , breaking capacity 10 KA with thermal release -10 Nos (f) MCB 4 Pole of capacity 63 Amp , breaking capacity 16 KA with thermal release -04 Nos "MCCB will be connected through busber"

1

-

-

... More
Labour only for taking down any unserviseable street light fittings/bulk head fitting from any position and refixing after repair/replacement including retightening of loose connections with all accessories of any type and size from existing position/location and removing materials to store for keeping in safe custody for repair work or taking credit all as specified and as directed. Note :- (i)Accessories shall be measured and paid separately as supply only under respective items as mentioned here in after). (ii) Services to be provided daily basis on all the working days during the contract duration by employing minimum one electrician and one helper to attend all the street light complaints as & when required.

465

-

-

... More
Supply only the followinhg accessories for repair of street lighy fittings:-

-

-

-

... More
Silicon filled moulded type weather proof LED driver suitable for 72W/80W/90W LED street light fittings, driver operating voltage should be 140V-270V, 50 Hz, PF0.9 of existing make as approved by GE.

100

-

-

... More
Silicon filled moulded type weather proof LED driver suitable for 25-70 W LED street light fittings, driver operating voltage should be 140V-270V, 50 Hz, PF0.9 of existing make as approved by GE.

80

-

-

... More
LED street light , pressure die-cast with high power LED as light source lamp type 72W with SPD, IP 66 complete all as specified and as directed.

30

-

-

... More
M&L for water proof, 3core PVC insulated and PVC sheathed, copper conductor cable of size 1.5 sqmm, 1100 Volts grade for electrical connection of street light fittings, complete all as specified and directed.

350

-

-

... More
Supply and fixing thermoplastic cable junstion box having protection IP 66/67 "weather proof" for outside installation with knockout entry for cable of size 10 - 16 sqmm and 155x210x92mm with terminals and provision of one 6A MCB SP all as specified and as directed.

60

-

-

... More
Cutting of tree branches, tuching LT over head lines, to maintain a clearance of 1.50 m from the over head line to near by trees complete all as directed by Engr-in-Charge.

2

-

-

... More
S&F MCBs, 4P,415 volts, breaking capacity 10 kA, rating 63 amps,C curve complete all as specified and as directed including taking down us MCCB any type any size.

2

-

-

... More
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm burried directly in ground (in vertical position) earth pit not less then 2.25 mtr below narmal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L) and connected to galvanized iron earth wire 4mm dia with GI protection pipe upto pole junction box by means of bolts, nuts, check nuits, and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6 mm round bar, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mess, 15mm bore light grade galvanized steel tubing up to 7.5 mtr lenght for drawing earth lead GU wire protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No. 3 of SSR part 1 and testing on completion incl taking down old unsv earthing complete.

7

-

-

... More
Taking down or taking up steel water tubing , galvanised from trenches / walls / floors including all fittings, segregatting and stacking the serviceable pipes and fittings properly at site for re-use all as specified and directed for following bore of pipe : - Note Excavation and earth work shall be meassured and paid under relevant item of schedule separately.

-

-

-

... More
20 mm dia

90

-

-

... More
25 mm dia

250

-

-

... More
40 mm dia

200

-

-

... More
50 mm dia

200

-

-

... More
80 mm dia

250

-

-

... More
100 mm dia

250

-

-

... More
Re-laying only old serviceable steel water tubing, galvanised and connections in new or old situation / allignment including all new fittings (on Walls, floors etc, ) of pipe as recovered above including de-scaling /cleaning of pipe (internally and externally) cutting and threading of tubing ends all as specified and directed. of following size :-

-

-

-

... More
20 mm dia

30

-

-

... More
25 mm dia

30

-

-

... More
All as per item No.73 above but laid in trenches.

-

-

-

... More
20 mm dia

30

-

-

... More
25 mm dia

150

-

-

... More
40 mm dia

100

-

-

... More
50 mm dia

100

-

-

... More
80 mm dia

100

-

-

... More
100 mm dia

100

-

-

... More
S & F steel water tubing galvanised ,medium grade with all fittings and fixed complete to walls , or in floors, in old/new situation for bore of pipe following sizes: -

-

-

-

... More
20 mm dia

40

-

-

... More
25 mm dia

50

-

-

... More
40 mm dia

5

-

-

... More
All as per item No. 75 above but laid in trench of folliwng bore of pipe : -.

-

-

-

... More
20 mm dia

60

-

-

... More
25 mm dia

100

-

-

... More
40 mm dia

150

-

-

... More
50 mm dia

100

-

-

... More
80 mm dia

100

-

-

... More
100 mm dia

100

-

-

... More
Testing of water sample of various pump houses of Bagrakote Mil Stn for bacterio logical and chemical testing (Systematic analysis) from Govt approved laboratory of and submit the report to the department all as specified and directed by Engr-in-charge.

14

-

-

... More
M&L for cleaning and washing (inside area only) of RCC overhead tank of 50000 gallons capacity upto 70 feet height staging including scraping out all scaling, deposit and algae formations and silt / sticky matters adhering tank bottom surface, scraping and washing tank surface with approved grade of chemicals twice followed by re-cleaning with plain potable water to remove any trace of chemical, including white washing with one coat of lime to the internal surface of the tank and removing the green vegetation from outer surface of wall /on top surface of the tank etc complete all as directed. (i) On completion of cleaning of tank, date of cleaning to be marked / written clearly on tank surface in an accessible location with letters or figure not exc 20cm high viz “TANK CLEANED ON ----” (ii) Cleaning of tank to be carried out after instr issued by the Engr-in-Charge

1

-

-

... More
All as per serial item No 78 here-in-above but RCC over head tank of capacity 40,000 gallons.

1

-

-

... More
All as per serial item No 78 here-in-above but RCC over head tank of capacity 20,000 gallons.

3

-

-

... More
M&L for cleaning and washing (inside area only) of pressed steel overhead tank of 10000 gallons capacity upto 60 feet height staging including scraping out all scaling, deposit and algae formations and silt / sticky matters adhering tank bottom surface, scraping and washing tank surface with approved grade of chemicals twice followed by re-cleaning with plain potable water to remove any trace of chemical, including paint by black bituminous paint food grade two coat to the internal surface of the tank and removing the green vegetation from outer surface of wall /on top surface of the tank etc complete all as directed at various unit.

7

-

-

... More
All as per serial item No 81 here-in-above but UG Sump of capacity 50,000 gallons.

2

-

-

... More
All as per serial item No 81 here-in-above but PVC over head tank of capacity upto 5000 ltrs at various unit.

3

-

-

... More
Supply and fixing in replacement chlorine feed high pressure single head gear motorised adjustable dozing pump set with accessories including lead tubing, connecting ferrules, injection check valves, clay weight and ferrules, multi stage centrifugal pumps, stator control cabling etc of , capacity up to 1000 grams/hr complete all as specified and directed

6

-

-

... More
M&L for making drilling/welding and connection in main line for injection of Chemical complete all as specified and directed.

6

-

-

... More
S & F in replacement agitator Motor of RPM 1440 RPM single phase 0.25 HP suitable for Existing 100 ltr FRP tank for mixing water with chemical in granular form complete all as directed and specified

6

-

-

... More
S & F in replacement Gun-metal, globe or gate valves,with iron wheel head, screwed both ends for iron pipe and fixed of size 15mm

12

-

-

... More
Demolition of Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) unreinforced

4

-

-

... More
M&L for P.C.C. 1:4:8 (Type D-2,40mm graded aggregate) as in foundation filling or for mass concrete of of old poles,stays,struts or any other indicated work including form work(if required) complete all as directed by Engr-in-Charge

3.5

-

-

... More
M & L Cement concrete type B-1,1:2:4 (20mm graded stone aggregate) 40mm thick

12.5

-

-

... More
S & F in repairs Galvanised. 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed including all accessories (each line wire to be measured)

8

-

-

... More
Demolition of brickwork built in cement mortar including all quoins . Arches, pillars etc complete all as specified and as directed

2.22

-

-

... More
M&L for brickwork with sub class B brick using old size brick straight or curve on plan exc 6meter mean radious built in CM 1:4 complete all as specifiedand as directed

0.75

-

-

... More
M&L for brickwork with sub class B brick using old size brick straight or curve on plan to any radious in half brick thick wall built in CM 1:4 complete all as specifiedand as directed

14.7

-

-

... More
M&L for 15 mm thick rendering on fair faces of brick wth CM 1:4 using water proofing compound including finishing the surface even and smooth with using extra cement complete as specified and directed.(WPC shall be measured and paid separately)

29.4

-

-

... More
M&L for 15 mm thick rendering on fair faces of brick wth CM 1:6 using water proofing compound including finishing the surface even and smooth with using extra cement complete as specified and directed.(WPC shall be measured and paid separately)

6

-

-

... More
Supply only water proofing compound (integral) conforming to IS: 2645-1975 specifications complete as specified and directed.

1.18

-

-

... More
M&L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate as in surface channels and drains complete.

3

-

-

... More
Taking down burnt Agitator motor from site and transporting the same to nearest authorised workshop , dismanting the pump motor assembly & rewinding the burnt motor with same gauge of PVC insulated super enameled copper wire as per manufacture's instruction including servicing/ overhauling the pump ,reassembling & brought back to site complete all as directed by Engr-in-charge.

4

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.