Military Engineer Services Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date20 Jan 2025
Closing Soon10 Feb 2025
Tender Amount₹ 40,00,000
Costs
EMD
₹ 80,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_693932_1Tender No
8651/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
S&F Pre- painted coloured trapezoidal profiled Galvalume/ Zincalume sheet with min thickness 0.50mm TCT confirming to IS - 513(AZ-150 GSM, Al Zn allay metalic coating with 550 Mpa yield stress as per AS-1397) as in roof covering/cladding to wall, fixed with self tapping screws colour exterior coat of silicon modified polyster/BHP x RW paint system 20 micron top coat applied over 5 micron primer and 5 micron polyster back coat applied over 5 micron primer , all fixed with galvanized self drilling self tapping fastner (12-14 x 55 with EPDM seals) complete all as specified and directed.
150
-
-
... More
S&F Pre- painted coloured plain sheet Galvalume/ Zincalume sheet with min thickness 0.50mm TCT confirming to IS - 513(AZ-150 GSM, Al Zn allay metalic coating with 550 Mpa yield stress as per AS-1397) as in roof covering/cladding to wall, fixed with self tapping screws colour exterior coat of silicon modified polyster/BHP/ XRW paint system 20 micron top coat applied over 5 micron primer and 5 micron polyster back coat applied over 5 micron primer , all fixed with galvanized self drilling self tapping fastner (12-14 x 55 with EPDM seals) complete all as specified and directed.
15
-
-
... More
M&L for 75mm thick PCC 1:3:6 type C2 (Using 40mm graded stone aggregate) as in sub base of floor complete all as specified and directed.
445
-
-
... More
Taking down cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing down with water, etc. complete all as specified and directed.
40
-
-
... More
M&L for two coats of synthetic enamel paint over one coat of red oxide on new steel surfaces of any description over 10cm in width or girth including preparation of surfaces complete all as specified and directed.
40
-
-
... More
Demolition of cement concrete in ground floor and paving n.exc 15 cm thickness( below or above ground level) complete all as specified and directed.
35.25
-
-
... More
Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed.
2.85
-
-
... More
Dimantling of Asbestos cement (corrugated,semi corrugated, etc.) sheets in roof coverings including ridges etc complete all as specified anddirected
165
-
-
... More
M&L for 75mm thick PCC 1:3:6 type C1 (Using 20mm graded stone aggregate) as in plinth protection finished even and smooth without using extra cement complete all as specified and directed.
25
-
-
... More
M&L for exterior grade(Lequre coated), coloured glossy finish rubber pressed, cement concrete designer chequered tiles of size 30cm x 30cm x 25mm thick set, jointed and pointed in neat cement slurry with grey cement and pigment to match the shade / colour / matrix of tiles as in floor etc. complete including provision of 20mm screed in cement moertar 1:6, complete all as specified and directed.
145
-
-
... More
M&L for providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks,lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand; complete all as specified and directed.
300
-
-
... More
M&L for rendering 15 mm thick in cement mortar 1:6 on fair faces of brick work or concrete surfaces and finishing surfaces even and smooth without using extra cement complete all as specified and directed.
15
-
-
... More
M&L for rendering 15 mm thick in two layers 10mm +5mm in cement mortar 1:4 on external surfaces of brick work or concrete surfaces with using WPC finishing the surfaces even and smooth without using extra cement complete all as specified and directed.
Note:- WPC will be measured and paid separately under respective item of this schedule.
25
-
-
... More
M&L for preparation of newly plastered surfaces of walls and applying two coats of cement base paint over a coat of alkai registant primer complete all as specified and directed.
25
-
-
... More
M&L for preparation of new undecorated surface of walls and applying two coats of white wash complete all as specified and directed.
15
-
-
... More
S&F in repairs MCCB 160 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed.
2
-
-
... More
S&F in repairs MCCB 200 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA,Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed.
3
-
-
... More
S&F in repairs MCCB 250 Amps, 4 Pole, 415 V, Adjustable type, with breaking capacity 36 KA, 100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed.
3
-
-
... More
S&F in repairs MCCB 320 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed.
3
-
-
... More
Dismantling insulators any type any sizes complete all as specified and directed.
20
-
-
... More
M&L for earthing complete with galvanised steel earth plate electrode 60×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron 25x4mm earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to earthing test point including testing on completion including watering GI pipe 20mm bore medium grade, 15mm bore light grade GI pipe for protection of earth lead including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm including 8mm dia TMT bars both ways @ 15cm centre to centre with one handle for lifting made out of 8mm dia MS bar, funnel & wire mesh, excavation and earth work in any type of soil complete including dismantling existing all as specified & directed.
8
-
-
... More
M&L for repair, serviceing and replacement of unserviceable accessories of LT Panel any make type/size including welding, brazing and drilling work etc complete all as specified and directed.including the followings.
(a) Tightening of all loose conectiont of cable inside the panel and welding the broken door of the panel.(b) Clean all the rusted busbar through emery paper and fixing insulation heat shrink sleeves through out the busbar including strip connected with out going MCCB.
(c) Cut the damage insulation portion end of cable inside the panel and reconnecting its into positions after fixing the end termintion/Sleeves complete with suitable size of aluminium lugs and stainless steel nut bolts including excavation and earth work in any type of soil for taking out the existing cable loop to fixing the end joint or reconnection in position.
(d) Repair/Replacement of burn/unserviceable voltmeter, ammeter,indication lamp including control wiring of the panel between voltmeter, Ammeter and their selector switch and CTs .
(e) Repair/Replacement of all burn lugs inside the panel.(f) Replacement of all the GI rusted nut, bolts,and washers with made of stainless steel nuts, bolts and washers.(g) Clean the dust inside the panel by air blower/vaccum cleaner complete.
Note : (a) The cost of nut bolts, washers, insulation tape, lugs etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separately under relevant items of schedule.
16
-
-
... More
Supply only epoxy type insulator for support of busbar grade 1100 volt as per existing size complete all as specified and directed.
20
-
-
... More
Material only for control wiring of the panel with 1.5 sq mm multistranded, PVC insulated copper conductor 1100 Volt grade FRLS cable complete all as specified and directed.
100
-
-
... More
Supply only LED phase indicator lamp colour RED/YELLOW/BLUE AC 220 Volt 50 Hz. complete all as specified and directed.
15
-
-
... More
Supply only cast resin insulated type CT, Ratio 300/5A with capable of with standing momentary short circuit and symmetrical short circuit for 01second complete all as specified and directed.
2
-
-
... More
Supply only cast resin insulated type CT, Ratio 400/5A with capable of withstanding momentary short circuit and symmetrical short circuit for 01 second complete all as specified and directed.
2
-
-
... More
Supply only LED phase indicator lamp colour BLUE 220 Volt 50 Hz. complete all as specified and directed.
25
-
-
... More
Supply only LED phase indicator lamp colour WHITE AC 220 Volt 50 Hz. complete all as specified and directed.
15
-
-
... More
Supply only LED phase indicator lamp colour AMBER AC 220 Volt 50 Hz. complete all as specified and directed.
15
-
-
... More
Supply only copper bus bar any size (5x20, 10x20, 10x25, 10x40, 10x50,10x80) mm duly insulated with heat shrink busbar insulation sleeves complete all as specified and directed.
25
-
-
... More
M&L for spray painting on existing steel surface of Panel/FPB/JB etc with two coats of synthetic enamel paint including one coat of red oxide on rusted area after proper cleaning and prepration of old painted surfaces steel / Iron of any description with spray machine complete all as specified and directed.
Note:- Painting of panels / feeder filler boxes shall be carried out in different colour of paints as required at site and as directed).
90
-
-
... More
M & L for repair, serviceing, release testing and comprehensive maintenance of fully automatic LT panel including Air Circuit Breaker (ACB) . Repair/maintenance work comprises the following:-
(a) Disconnecting the ACB from existing position and opening, cleaning the dust of all contact points , servicing by using CRC and throughly cheking to detect any fault then rectified the same by supplying and replacing the defect parts and after rectified the fault refitted the ACB in its position and commissioning and testing the panel.
(b) Opening the panel and cleaning dust of the panel throughly vaccum cleaner, blower should not be used for cleaning. (c) After cleaning, checking all cable connection, Busbar joint and tightening the loose connection and oiling all the nut Bolt of the same.
(d) Cleaning and checking the servicibity condition of all the relays, contactor, fuse, Indicator switch, push buttom, control wiring, connector and replacing all the burn out parts assembled the panel contactor, relay, and servicing all the contactor assembeled at the point of Bus Bar, joint through nut bolt.
Note - (i) Spare parts shall be measured and paid separately under relevant items.
(ii) Minimum one ACB shall be produce to contractor for restand / repair for one visit. Contractor will not demand all VCB repair in one visit. Visit and repair charges of electrician and helper are included in the quoted rate. no extra charges shall be paid to the contractor.
38
-
-
... More
Supply only aux contactor MX0 31E (3NO +1NC) operating voltage 240 Volt AC Make : L&T Cart Part No CS94019 or equivalent make Legrand/ Schnieder/ Siemens.
15
-
-
... More
Supply only aux contactor MX0 31E (3NO +1NC) operating voltage 110 Volt DC Make : L&T Cart Part No CS94028 or equivalent make of Legrand/ Schnieder/ Siemens.
10
-
-
... More
Supply only aux contactor MX0 22E (2NO +2NC) operating voltage 240 Volt AC Make : L&T Cart Part No CS94020 or equivalent make of Legrand/ Schnieder/ Siemens
15
-
-
... More
Supply only aux contactor MX0 22E (2NO +2NC) operating voltage 110 Volt DC Make : L&T Cart Part No CS94029 or equivalent make of Legrand/ Schnieder/ Siemens.
10
-
-
... More
Supply only aux contactor MXO 40E (4NO) operating voltage 240 Volt AC Make : L&T Cart Part No CS94018 or equivalent make of Legrand/ Schnieder/ Siemens.
8
-
-
... More
Supply only Panel control switch (TNC 02 NO + 02 NC) operating voltage 240 Volt AC Make : L&T or equivalent make of Legrand/ Schnieder/ Siemens.
8
-
-
... More
Supply only Digital VAF meter LCD display flush mounting type of size 96 mm x 96 mm (4”x4”) square dial Accuracy Cl-0.5S with Rs 485 input voltage measurement range 50-520 Volt VAC (P-P) , aux supply 80-300 volt AC/DC, CT secondary site selectable 1A/5A, 3 phase four wire system with inbuilt selector switch. Make :L&T Cat Part No WC441021OOOO or equivalent make of Legrand/ Schnieder/ Siemens.
4
-
-
... More
Supply only XT series HMI size 4.5 inch with colour TFT display option with ethernet model, touch screep higher brightness level upto 440cd/m2 long backlight life upto 50000 hours for display, shock and vibration protection as per IEC standard, RAM 32 Mb and ROM 128 MB complete all as specified and directed. Make: L&T Cart Part No LTOP-S04EDAA or equivalent make of Legrand/ Schnieder/ Siemens.
6
-
-
... More
Supply only Instantaneousdifferential protection relay CAG Type CT Sec 1 amp.
Model No CAG34AF71A Make ALOSTOM or equivalent make of Legrand/ Schnieder/ Siemens/ABB.
2
-
-
... More
Supply only push buttons red, green and black with aux contacts 1 NO and 1 NC all as specified and directed. Make: Scheneider/Siemens/L&T/Ashida.
10
-
-
... More
Supply only flush type micro processor based alarm annunciator with P.B window 08 and aux voltage 110 Volt DC as per sample in site in complete all as specified and directed.
4
-
-
... More
Supply only Hooter flush type 96 x 96 mm aux voltage 110 Volt DC as per sample in site in complete all as specified and directed.
4
-
-
... More
Supply only shunt release for ACB supply voltage 110 VDC as per sample in existing size complete all as specified and directed. Make: L&T /Legrand/C&S/ABB/Schneider.
10
-
-
... More
Supply only Closing release for ACB supply voltag 240 Volt AC as per sample of existing in site complete all as specified and directed. Make: L&T/Legrand/C&S/ABB/Schneider.
10
-
-
... More
Supply only under voltage trip device for ACB supply voltage 240 Volt AC as per sample of existing in site complete all as specified and directed.
Make: L&T /Legrand/C&S/ABB/Schneider.
10
-
-
... More
Supply only automatic spring charge motor operating voltage 220 Volt AC for ACB as per sample of existing in site complete all as specified and directed.
Make: Crompton/L&T/ Legrand/ C&S/ABB/Schneider.
3
-
-
... More
Supply only Door interlock of ACB as per sample of existing in site complete all as specified and directed.
8
-
-
... More
M&L for Repair, serviceing and replacement of unserviceable accessories of LT Capacitor Panel of any make any size comprises the following repair work:- (a) Tightening of all loose connection of cable inside the panel and welding the broken door of the panel.
(b) Cut the damage/burn portion end of cable inside the panel and reconnecting its into positions after fixing the copper lugs with suitable size and stainless steel nut bolts and reconnection in position.
(c) Opening, checking and testing the serviceabilty of capacitor bank and detect any fault of the same should be rectified by supplying and replacing the deffective parts with new one. (d) Repair/Replacement of all burn lugs inside the panel with copper lugs suitable size.
(e) Replace all the GI rusted nut, bolts and washers with stainless steel nuts, bolts and washers.
(f) Clean the dust inside the panel by air blower/vaccum cleaner.
Note : (a) The cost of steel nut bolts, washers, copper lugs, etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separately under relevant items of schedule.
4
-
-
... More
Supply only automatic power factor controller EPCOS BR 6000 12 stage operating voltage 240 VAC complete all as specified and directed.
3
-
-
... More
Supply only Power contactor 3phase AC3 ratin 110A and AC1 rating 160 amp Type MNX 110 with 2 NO + 2NC complete all as specified and directed.
Make L&T Cat Part No CS 94137 or equivalent make of Legrand/ Schnieder/ Siemens.
2
-
-
... More
Supply only Power contactor 3phase AC3 ratin 80A and AC1 rating 1100 amp Type MNX 80 with 2 NO + 2NC complete all as specified and directed.
Make L&T Cat Part No CS 97077 or equivalent make of Legrand/ Schnieder/ Siemens/ABB.
2
-
-
... More
Supply only PVC cable 6 sq mm 4 core copper conductor FRLS multidtranded with rope insulation complete all as specified and directed.
100
-
-
... More
Supply and fixing Copper lugs 10 sqmm complete all as specified and directed.
65
-
-
... More
Supply and fixing Copper lugs 16 sqmm complete all as specified and directed.
50
-
-
... More
Supply and fixing Copper lugs 25 sqmm complete all as specified and directed.
50
-
-
... More
supply an fixing in repair LT APP box type capacitor bank capacity 25 KVAr 440 V AC 3 Ph 50 Hz complete all as specified and directed.
Make EPCOS Cat part No B25160C4025T40 or equivalent make of Legrand/ Schnieder/ Siemens.
2
-
-
... More
supply an fixing in repair LT APP box type capacitor bank capacity 50 KVAr 440 V AC 3 Ph 50 Hz complete all as specified and directed.
Make EPCOS Cat part No B25160C4050T40 or equivalent make of Legrand/ Schnieder/ Siemens.
2
-
-
... More
Supply and fixing of CS7-12 chloride safepower , SMF type sealed Lead acid Battery capacity 12 Volt 7 Ah used for UPS backup complete all as specified and directed.
Make : Exide/ Amron/ E- Power
42
-
-
... More
Supply and fixing Eaton Bussman series 170M1565D high speed square body fuse 690 V (IEC) 63A 700 Volt AC , Combination fuse indication indicator blade end complete all as specified and directed.
16
-
-
... More
M&L for PLC programming and updation of software of DG Synchronisation Panel and Main power supply synchronisation panel complete all as specified and directed.
1
-
-
... More
(Note : The Scope of Work contained in 'Sch of Credit' amounting to Rs. 36,845.00 (refer Tender Srl Page No 29). The Quoted sum shall be arrived at after deducting the amount of “Sch of Credit” from the total amount of the ‘BoQ’
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%