Military Engineer Services Tender
View complete overview of Uttarakhand MES Tender
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date17 Feb 2023
Closing Date16 Mar 2023
Tender Amount₹ 28,14,000
Costs
EMD
₹ 56,280Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_581684_1Bid Award Id
ViewTender No
86395/RWL/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
REPAIR REPLACEMENT OF HT OVERHEAD DISTRIBUTION SYSTEM, REPAIR AND FILTRATION OF TRANSFORMER AND ALLIED WORKS AT RAIWALA UNDER AGE (I) RAIWALA.
BOQ Items
... More
M&L for servicing of indoor/ outdoor type HT 11 KV VCB/ RMUs type VCB of various capacity of Make Schneider/ ABB/ SIEMENS as under :- (a) Servicing and inspecting of draw out type trolly mounted, manual spring charge ON-OFF mechanism and testing for proper functioning of ON and OFF operation ,servicing of male female contacts, greasing all the mechanical components and applying dry graphite conductive sealent for contacts.
(b) Cleaning, inspecting and testing HT 11 KV bus bar, checking of insulators at input and output for any crack of damages, checking of cable termination for all the three phases, cleaning the copper bus bar, checking for proper insulation ,tightening all the nuts, bolts of bus bar.
(c) Cleaning, inspecting and testing of electrical wiring system, ammeter, voltmeter, VAF meter, selector switch, all illuminated indicators for RYB phase, DC supply healthy, spring charge, trip circuit healthy etc.
(d) Cleaning, inspecting and testing for over current relay, CT for ammeter, PT for voltmeter for display of voltage HT 11 KV.
(e) Setting of earth fault relay and over cuurrent relay as per, manufacturers's recommendation and site requirement.
4
-
-
... More
NOTE : (i) Cost of all the material, components, repairs, elements as per above as well as other elements (except supply only of the components considerd under items herein after to the extent required and operated ) to make the VCB complete functional shall deemed to be included in the quoted rate of the contractor. (ii)Individual Breaker VCB shall be considered as one unit and above job is to be carried out unitwise. Above job will be carried out by licenced technician as aproved by GE/AGE (I). (iii) Any accident/mishapenning occurred during the execution of work shall be responsibity of the Contractor. (iv) All necessary tools & plants required for carrying out above job will be provided by contractor and the cost of the same are deemed to be included in quoted rate. (v) Inventry of defective parts to be replaced by contractor will be prepared by joint inspection with contractor.
-
-
-
... More
Supply only gear box and charging motor 110V suitable for HT 11 KV out door VCB AC three phase 50Hz complete all as specified and directed.
1
-
-
... More
Supply only single phase circuit spout RYB phase suitable for HT 11 KV VCB AC three phase 50Hz complete all as specified and directed.
3
-
-
... More
M&L for detecting cable fault in HT 11 KV cable by 24hrs x 7days ie entire contract period with technician and desired equipments at Mil station Raiwala and Mil camp area Narendra Nagar with and including necessary earth work (excavation & returning filling) in any type of soil, joint the cable fault with new straight through jointing kit complete all as specfied and directed.
Note : (i) Cable joint of required size measured and paid separately.
(ii) Each job considered cable fault locator use in one day in any any length of cable.
2
-
-
... More
S&F cable jointing kit 11 KV (Earthed) grade cable for outdoor straight through heat shrinkable type joint complete with jointing material and accessories suitable for 95 Sqmm, 3 core XLPE armoured aluminum conductor cable complete all as specfied and directed.
2
-
-
... More
S&F in repairs cable jointing kit 11 KV (Earthed) grade cable for indoor termination Cold shrinkable type joint complete with jointing material and accessories suitable for 95 Sqmm 3 core XLPE armoured aluminum conductor cable complete all as specfied and directed.
2
-
-
... More
S&F in repairs cable jointing kit 11 KV (Earthed) grade cable for outdoor termination Cold shrinkable type joint complete with jointing material and accessories suitable for 95 Sqmm 3 core XLPE armoured aluminum conductor cable on HT pole, transformers etc complete all as specfied and directed.
10
-
-
... More
S&F in repair including installation, commissioning and testing of HT 11 KV outdoor type gang operated triple pole air break switch suitable for Horizontal or vertical mounting fixed type complete with 12 insulator 400 amps rating and steel frame mechanically oprated mechanism consisting of operating rod of 25 mm bore light grade GI pipe of suitable length worked from ground level and with locking arrangement flat iron clamp 50mm x 6mm including MS channel of suitable size length for fixing GOD including bolts, nuts and washer complete all as specified and directed.
3
-
-
... More
Dismantling and taking out old unserviceable ACSR conductor of any size complete all as specified and directed.
1.05
-
-
... More
Supplying, streching and fixing of over head ACSR conductor any size ie. weasel, Ferret and Dog and any type fixing on steel tubular pole including binding/ jointing the conductor to insulator with and incl 14 SWG binding wire complete all as specified and directed.
1
-
-
... More
Restreching/ restringing only over head ACSR conductor / earth wire of any size and type comprising of one conductors/wire over steel tubular poles, incl opening, streching, binding and jointing the conductor to insulater with and incl 14 SWG binding wire and tape the jumper complete all as specified and directed.
6
-
-
... More
S&F in repairs pin type, porelain, vitreous, white brown or green insulator 11000 volts grade of size 150 mm height, 150 mm dia, including galivanized mild steel spindle with two galvanized iron washers and one galvanized nut bolt complete all as specifed and directed.
5
-
-
... More
S&F in repairs disc type insulator, procelain vitreous, 145 mm high and 255 mm dia ball and socket type, white or brown or green, single disc assembly for tension wtih tension clmps for conductors, working pressure 11000 volts complete all as specified and directed.
5
-
-
... More
Dismantling and taking out old unserviceable four pole structure of any type and any size including clamps insulators, cross arms etc of any type complete all as specified and directed.
1
-
-
... More
Dismanlting and taking down bend/damaged mild steel work such as cross arms, bracing, supported, clamps & back plates etc complete all as specified and directed.
1.6
-
-
... More
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed including of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
0.5
-
-
... More
M&L for painting of steel tubular HT Pole 11 mtr long, two pole structure and mild steel work such as cross arm, clamps, nuts, bolts, etc including preparation of old painted surface and painting two coats of aluminium paint including 5 Nos band/straps with yellow and black colour in alternatete way (250mm wide each) synthetic enamelled paint two coat at a distance 300mm from plinth block and marking pole nos with black synthetic enamelled paint complete all as specified and directed.
8
-
-
... More
M&L for painting of steel tubular HT Pole 11 mtr long, four pole structure and mild steel work such as cross arm, clamps, nuts, bolts, etc including preparation of old painted surface and painting two coats of aluminium paint including 5 Nos band/straps with yellow and black colour in alternatete way (250mm wide each) synthetic enamelled paint two coat at a distance 300mm from plinth block and marking pole nos with black synthetic enamelled paint complete all as specified and directed.
6
-
-
... More
Disconnecting and taking out existing old unserviceable HT cable of any size from trenches/from pole/walls including taking out old GI tubes, cable protection covers, etc complete all as specified and directed.
80
-
-
... More
S&F/Laying, connecting and testing of HT cable XLPE insulated screened PVC badded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 11KV (Earthed) as per IS 7098 (Part-II) with stranded aluminium conductor of following size complete all as specified and directed:- Note:- (i) The earth work, GI pipe shall be measured and paid sepretely.
(ii) Cable may fixing/ passing through pipe laid in trenches or fixed to pole/ wall or fixed to LT panel etc.
(iii) ACSR conductor & cross arms replaced with UG Cable.
-
-
-
... More
95 Sqmm, 3 core.
950
-
-
... More
Excavation in trenches in any type of soil not exc 1.5 m wide and not exceeding 1.5m in depth for laying UG cable/ foundation etc complete all as specified and directed.
364.5
-
-
... More
Returning filling in any type of soil including spreading levelling watering and well ramming in layers n.exc 25cm each layer complete all as specified and directed.
252.54
-
-
... More
Removal of excavated surplus hard/dense soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
111.96
-
-
... More
M&L for sand cushioning for under ground cable with layer of fine river dry sand 80mm thick before laying of cable and 150 mm thick after laying of cable in trenches complete all as specified and directed. Note:- Punned (consolidated ) thicness of sand will be measured and paid sepetarely under relevent item of Sch.
72.9
-
-
... More
Supply and laying un-reinforced precast concrete cable cover of class HVP, type-1 with peak, size 300mm x 180mm x 40mm (ISI marked) for protection of UG cable over sand cushoniing laid in trenches with axis of the cover perpendicular to the axis of the cable complete all as specified and directed.
5100
-
-
... More
M&L for road cutting of size min 15cm width x 10cm depth for laying of cable including making good the road with PCC (1:3:6) type C1 complete all as specified and directed.
8
-
-
... More
S&F galvanized steel water tubing (GI Pipe) light grade (ISI marked) with all fittings as in sleeving for cable protection & laid in trenches/ floor or fixed to wall, ceiling and pole of following bore complete as specified and directed :-
Note : MS Clamp, nut bolts and washer shall be measured and paid seperatly for fixing with pole etc.
-
-
-
... More
80mm bore
10
-
-
... More
S&F in repairs cast iron cable route indicator having min dia 120mm and thickness of plate not less than 6mm, embossed 11KV HT of bold letters, welded on 2 feet MS angle iron of size 40/40 mm on plates including grounding 1.5 feet under ground and PCC complete all as specified and directed.
26
-
-
... More
S&F in repair PG clamp suitable for any size of ACSR Conductor complete all as specified and directed.
10
-
-
... More
S&F in repair Rubber mat of size 1m x 2m x 12mm of ISI marked for operating voltage of 11 KV and di-electric strength 45 KV complete all as specified and directed.
5
-
-
... More
Supply only DO fuse of following capacity complete all as specified and directed :-
-
-
-
... More
15 Amps
50
-
-
... More
10 Amps
50
-
-
... More
05 Amps
50
-
-
... More
S&F in repair anti climbing devices, spike type, fabricated out of MS bar (round, square or flat) including nuts bolts washers and welding in two halves made of shape to suit the cross section of pole complete as specified and as directed.
0.1
-
-
... More
S&F in repair Danger Notice Plate of 1.6 mm thick mild steel sheet, vitreous enamelled white with letters in English and regional language, figures and conventional skull and bones in signal red colour and fixed with 2 Nos MS clamp of size 25 x 3mm, bolts and nuts of approved size for following size complete all as specified and as directed :-
-
-
-
... More
Size 25 x 20cm for HT
10
-
-
... More
Size 20 x 15cm for LT
10
-
-
... More
Supply, installation, testing and commissioning of 11 KV/12 KV, 630 Amps Non extensible, outdoor type, 3 Way RMU panel with 1 isolators and 2 VCB, SF6 gas insulated, 11 KV Ring Main Unit contained within stainless steel tank suitable for outdoor use free standing and comprising of :
(A) (i) 2 Nos - 630 Amp triple pole, manually operated vaccum circuit breaker encapsulated in SF6 stainless steel tank with independent spring mechanism and fully rated earth switch with provision for earth of the cable.
(ii) 2 Nos - Air insulated cable boxes with split gland plate suitable for front side bottom entry 3 core cable upto 300 sqmm.
(iii) 1 Nos - 630 Amp triple pole, single break, 3-position ('ON', 'OFF' and 'EARTH') ring main switches, each with independent manual charged spring mechanism and fully rated earth switch with provision for earth and test of the cable.
(iv) 1 Nos - Air insulated cable boxes and glands suitable for front and bottom cable entry 3 core cable upto 300 Sqmm.
1
-
-
... More
(B) The Ring Main Unit (RMU) should comprise of the following accessories : (a) 1 Mimic diagram on front panel complete with status indicators.
(b) 1 Set of positive standard mechanical interlocks.
(c) 2 Set of current transformers for metering and protective relays 100/50/1A, 2.5 VA, 5 P 10 class.
(d) 2 Nos- self powered Numerical relay with 3 o/c and E/F.
(e) 2 Nos- Master trip relay with auxilary relays for transformer fault indication.
(f) 2 Nos. Trip circuit supervision relay with auxiliary relays for transformer fault indication.
(g) 1 Nos. Power pack equipment with backup of 15 minutes for operation of relays.
(h) 3 Set of LED indicator lamps for cable live indicator.
(j) Potential transformer 11KV/R3//110/R3//110/R3 - accuracy class 0.5/3P Burden with HT fuse and auxiliary PT 11 KV/230 V AC 500 VA.
(k) 1 No. digital mutifunction meter, 3 line display.
(l) 1 No. External stud for earthing connections.
(m) 2 Nos. SF6 gas pressure indicator.
(n) 3 Nos. local 'PULL TO TRIP' mechanism.
(o) 1 No. operating handles.
(p) 1 Set copper bus bars common for outgoing feeders.
(q) Manual charging for operation arrangement.
(r) Fuses for metering and protection system.
(s) Front bottom entry of HT cables.
(t) Paint finish - All steel work will be finish painted in Dark grey shaded 632 as per IS.
-
-
-
... More
(C) RMU Panel should have following general characteristics:
(i) Enclosure degree of protection - IP54.
(ii) Type of Ventilation - Natural (iii) Rated Enclosure - IK 10
(iv) Rated power frequency withstand voltage KV RMS/min - 28/38 kv (v) Rated lighting impulse withstand Voltage kv, 1.2/50 micro sec - 75/95 kv
(vi) Short time current rating ka, for sec - 21 kA/3 sec.
(vii) Rated short circuit making current - 50 kA.
(viii) Reference standard - As given in PS. NOTE :- Necessary drawing shall be got approved before placing order and PDI including testing shall be carried out by the rep of accepting officer. The cost of PCC platform for mounting RMU panel as per manufacturers instruction is deemed to be included in the quoted rates. The quoted rates must include the cost of cable termination kit cold shrikable type, cable glands, outside panel, cable lugs, cable trenches etc., cable between RMU & metering cubicals, lugs & glands & arrangements for 1 run / phase.
-
-
-
... More
Supply only Driver for LED Street Light for following wattage complete all as specified and as directed :-
-
-
-
... More
45 watt
50
-
-
... More
60 watt
25
-
-
Evaluation Notes How It Works ?