Military Engineer Services Tender
View complete overview of Uttarakhand MES Tender
Military Engineer Services - MES Tender
Civil And Construction
Civil Works Others
Eprocure
Opening Date30 May 2024
Closing Date27 Jun 2024
Tender Amount₹ 13,22,000
Costs
EMD
₹ 22,440Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_656734_1Bid Award Id
ViewTender No
9927/DDN/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
All as per item No.1 above but with 4 Sqmm cable for one 6 pin 15A socket outlet point on independent board
10
-
-
M&L point wiring with 1. 5 Sqmm PVC insulated unsheathed multistranded single core copper conductor cable in exisiting concealed conduit with 1.5 Sqmm PVC insulated copper conductor earth continuity wire for one light/fan point controlled by one switch.
4
-
-
All as per item No.5 above but for one pin 5 A socket outlet independent point
2
-
-
All as per item No.5 above but for one pin 5 A socket outlet on same board
2
-
-
All as per item No.5 above but with 4 Sqmm cable for one 6 pin 15A socket outlet point on independent board
10
-
-
S&F switch modular 6 Amps 230 Volts one way switch.
8
-
-
S&F switch modular 10 Amps 230 Volts 2 way switch. Make : Cat part No. 675501 of Legrand'Mylinc' Anchor Roma / SEIMENS
10
-
-
S&F Socket 6 Amps AC 230 Volts 2/3 pin combined 2 modular type complete all as specified and as directed.
4
-
-
S&F Socket 6A/16 Amps-2/3 pin AC 230 Volts modular type complete all as specified and as directed.
10
-
-
S&F Switch modular type AC 230 volts 16 Amps one way complete all as specified and as directed.
10
-
-
S & F Modular white cover plate with frame 2 module and metal flush box 2 module complete all as specified and as directed.
10
-
-
All as per item No 14 here in before but size 3 module
2
-
-
All as per item No 14 here in before but size 4 module
4
-
-
All as per item No 14 here in before but size 6 module
4
-
-
All as per item No 14 here in before but size 8 module
4
-
-
All as per item No 14 here in before but size 12 module
4
-
-
All as per item No 14 here in before but size 16 module
4
-
-
S & F sheet metal enclosure TPN for DB's when MCB's to be used 8 way with 200 amps bus bar and double door complete all as specified and directed.
4
-
-
S&F Sheet metal enclosure SPN for DB's when MCB's to be used 8 way with 200 amps bus bar double door
6
-
-
S&F MCB TPN 415 Volt 10 KA 63 Amp conforming to IS complete all as specified & directed.
4
-
-
S&F MCB SPN 240 Volt 10 KA 40 Amp conforming to IS complete all as specified & directed.
6
-
-
S&F MCB SP 6 to 32A
24
-
-
M&L for submain wiring with 3 runs(1 run for Phase+1 run for Neutral &1 run for Earth, with approved colour code as per EI rules) of 4 Sqmm single core,PVC insulated, unsheathed, multistranded copper conductor FRLS cable 1100 volts grade drawn through and including concealed wiring with PVC conduit pipe of medium duty not less than 15 mm dia including necessary steel conduit specials and connecting with suitable size thimble, and making good surface of disturbed wall/ceiling/floor as match with existing complete all as specified and directed. Note:-3 runs of 4 Sqmm size PVC copper cable, and one run of PVC conduit shall be measured as one unit length.
200
-
-
All as per item No 26 here in above, but 3 run of 6 Sq mm. Note:-3 runs of 6 Sqmm size PVC copper cable, and one run of PVC conduit shall be measured as one unit length.
200
-
-
All as per item No 26 here in above, but 6 run of 6 Sq mm (3run -Phase, 1 for Neutral & 2 Runs for Earth with recommended colours) and drawn through not less tha 32 mm dia PVC conduit . Note:-6 runs of 6 Sqmm size PVC copper cable, e and one run of PVC conduit shall be measured as one unit length.
225
-
-
S&F Sheet metal enclosures with socket plug top and MCB' SPN enclosure with a two pin and earth plug and socket complete with one single pole 20 A MCB
12
-
-
M&L for earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI earth strip 4 Sqmm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point /transformer nuetral/body/ Lt panel etc. and testing on completion, complete all as specified & directed by Engr-in-Charge.
10
-
-
Supply and Laying XLPE insulated galvanised steel strip or wire armoured elctric power cable with stranded aluminium conductor 1100 V grade of size 70 sqmm 3½ core after cutting to required length with necessary glands, nuts, bolts, and lugs complete all as specified and directed
200
-
-
All as per item No 31 here in above, but cable of size 16 sqmm 4 core
215
-
-
Excavation in trenches n exc. 1.5 m wide and n' exc. 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed.
84.04
-
-
Sand filling in trenches with clean dry unwashed sand free from sharp particles, gently punning around the cables complete.
25.21
-
-
Bricks, old size sub class `B' laid in trenches with width wise along the alignment of the cable as protection complete.
2490
-
-
Returning, filling of excavated soil, including spreading leveling, watering and well ramming in layers, not exceeding 25cm complete all as specified.
53.89
-
-
Removing of surplus soil to a distance n exc 50 m and depositing where directed at a level n exc 1.5m above the starting point complete.
30.15
-
-
S&F tube 'Light' grade GI tubing with all fitting laid in trenches, fixed to wall and floor of 50 mm dia for cable protection complete all as specified.
6
-
-
S & F sheet metal enclosure TPN for DB's when MCB's to be used 8 way with 200 amps bus bar and double door complete all as specified and directed.
5
-
-
S&F MCB TPN 415 Volt 10 KA 63 Amp conforming to IS complete all as specified & directed.
5
-
-
S&F MCB SPN 240 Volt 10 KA 40 Amp conforming to IS complete all as specified & directed.
24
-
-
S&F MCB SP 6 to 32A
10
-
-
M&L for submain wiring with 3 runs(1 run for Phase+1 run for Neutral &1 run for Earth, with approved colour code as per EI rules) of 4 Sqmm single core,PVC insulated, unsheathed, multistranded copper conductor FRLS cable 1100 volts grade drawn through and including concealed wiring with PVC conduit pipe of medium duty not less than 15 mm dia including necessary steel conduit specials and connecting with suitable size thimble, and making good surface of disturbed wall/ceiling/floor as match with existing complete all as specified and directed. Note:-3 runs of 4 Sqmm size PVC copper cable, and one run of PVC conduit shall be measured as one unit length.
50
-
-
All as per item No 43 here in above, but 6 run of 6 Sq mm (3run -Phase, 1 for Neutral & 2 Runs for Earth with recommended colours) and drawn through not less tha 32 mm dia PVC conduit . Note:-6 runs of 6 Sqmm size PVC copper cable, e and one run of PVC conduit shall be measured as one unit length.
80
-
-
M&L for earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI earth strip 4 Sqmm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point /transformer nuetral/body/ LT panel etc. and testing on completion, complete all as specified & directed by Engr-in-Charge.
4
-
-
Supply ,Installation, commissioning & testing of factory made ,any CPRI approved ,LT switched gear panel board,IP-54(outdoor type) ,415 voils,50 Hz,AC supply,three phase and neutral (4 wie) ,300/315 Amps aluminium bus bars 4 pole ,duly insulted with heat shrinkable sleeve as per colour code supported on epoxy insulatators,having independent compartment for insulated busbar ,incoming feeder & each outgoing feeder ie cubical type ,made out of 3.00 mm thick CRCA sheet,rigid mild steel angle iron frame of 50mmx50mmx6mm with 900mm long extended legs grouting in PCC 1:3:6 type C2 block of size 300mmx200mmx300mm ,duly epoxy powder coated internally & externally with approved shade ,rubber gasket,hinged front & back openable doors with proper locking arrangements for dust and vermin proof ,complete including suitable size cable alley,lugs,cable glands,common earth bar of GI strip 32x6mm at bottom and making connections with MCCB spreaders/wiring with suitable size of single core PVC copper conductor cable ,locking arrangements 65mm size and lock with keys,earth work and excavation comprising the following : Make of Panel : ABB/Seimens/Schenider/L&T Incomer :- (i) 250 Amps 4P, 35 KA ,Adjustable tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link - 01 Nos.
(ii) Meter set : Digital voltmeter,Ammeter + CT : 400/5,
(iii) RYB Indicating Lamp LED type 240 V ,
(iv) MCB SP 6A, (v) Alluminium Bus Bar of rating 400 Amp, 3 Phase and neutal sys.
Outgoing :-
(i) 63 Amp FP,16 KA,Adj tharmal & fixed magnetic setting, Ics=100% of Icu with spreader link MCCB- 8 Nos.
1
-
-
Excavation in soft/loose soil as in post holes each not exc 0.5 cum & getting out, returning filling in and ramming earth in layers not exc 25cm thick, watering making good surfaces and removal of surplus soil to a distance not exc 50 mtr complete all as specified and directed.
70
-
-
M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation filling, mass concrete, etc complete all as specified and as directed.
6
-
-
S & F steel work in struts, poles and similar work including special shaped washer etc complete using ERW or induction butt welded tubes conforming to IS 1161-1998 grade St-240 quality-A complete all as specified and directed.
850
-
-
Supply and fix pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and directed.
395
-
-
S&F mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends each screwed end to be fitted with washer and one hexagonal or square nut n exc 5 cm long (05 to 10 mm dia of neck) complete all as specified and directed.
2.5
-
-
M&L for two coats of synthetic enamel paint on new steel surfaces over a coat of red oxide primer of any description including preparation of new surfaces exc.10 cms in width or girth complete all as specified and directed.
11.47
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements