Military Engineer Services Tender

View complete overview of Uttarakhand MES Tender

Military Engineer Services - MES Tender

Works
Civil And Construction
Electrical and Electronics
Water Storage And Supply
Electrical Works
Eprocure
Opening Date26 Oct 2024
Closing Date16 Nov 2024
Tender Amount₹ 50,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Taking up or down 25 mm dia GI tubing, and connections, including cleaning for re-fixing or removal to store complete all as specified and directed.

168

-

-

... More
Taking up or down 20 mm bore GI tubing, and connections, including cleaning for re-fixing or removal to store complete all as specified and directed.

264

-

-

... More
Taking up or down 150mm bore GI tubing, and connections, including cleaning for re-fixing or removal to store complete all as specified and directed. Note : Working site for pipe line appx 3 to 4 KM away from road to hill slopes.

144

-

-

... More
Refixing & Laying 100mm bore GI tubing , medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed.

42

-

-

... More
Refixing & Laying 80mm bore GI tubing , medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed.

30

-

-

... More
Refixing & Laying 50mm bore GI tubing , medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed.

30

-

-

... More
Refixing & Laying 25mm bore GI tubing , medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed.

18

-

-

... More
Refixing & Laying 20mm bore GI tubing , medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed.

24

-

-

... More
Refixing & Laying of 150mm bore GI tubing, medium grade with and including all new fitting and fixture like union, flange, socket, nipple, bend, elbow, tee, reducer etc laid in trenches or laid in floors complete all as specified and directed. Note : Working site for pipe line appx 3-4 KM away from road to hill top.

54

-

-

... More
S&F, laying of 100 mm bore GI tubing, medium grade with and including all fittings and fixture like socket, nipple, elbow, reducer etc complete laid in trenches or laid in floor complete all as specified and directed.

150

-

-

... More
S&F, laying of 50 mm bore GI tubing, medium grade with and including all fittings and fixture like socket, nipple, elbow, reducer etc complete laid in trenches or laid in floor complete all as specified and directed.

60

-

-

... More
S&F, laying of 25 mm bore GI tubing, medium grade with and including all fittings and fixture like socket, nipple, elbow, reducer etc complete laid in trenches or laid in floor complete all as specified and directed.

150

-

-

... More
S&F, laying of 20 mm bore GI tubing, medium grade with and including all fittings and fixture like socket, nipple, elbow, reducer etc complete laid in trenches or laid in floor complete all as specified and directed.

240

-

-

... More
S&F, laying 150 mm bore GI tubing, medium grade with and including all fittings and fixture like socket, nipple, elbow, reducer etc complete laid in trenches or laid in floor complete all as specified and directed. Note : Working site for pipe line is appx 3 to 4 KM away from road to hill top & cost of laying, jointing, testing, and commissioning are deemed to be included in the rates quoted by tenderer.

90

-

-

... More
Fixing & laying of 80 mm bore GI tubing, any grade with and including all fittings and fixture to all and ceiling or laying in floors complete all as specified and directed.

90

-

-

... More
S&F GI bend of any angle, not exceeding 1.5 mtr length, suitable for the 150 mm dia of GI pipe complete all as specified and directed.

5

-

-

... More
S&F GI bend of any angle, not exceeding 1.5 mtr length, suitable for the 100 mm dia of GI pipe complete all as specified and directed.

4

-

-

... More
S&F GI bend of any angle, not exceeding 1.5 mtr length, suitable for the 80 mm dia of GI pipe complete all as specified and directed.

4

-

-

... More
Supply only rubber or fibre board gaskets for flanged ends suitable for 150mm bore pipe complete all as specified and directed.

50

-

-

... More
supply only rubber or fibre board gaskets for flanged ends suitable for 100mm bore pipe complete all as specified and directed.

20

-

-

... More
Supply only rubber or fibre board gaskets for flanged ends suitable for 80mm bore pipe complete all as specified and directed.

20

-

-

... More
Supply & fix HDPE flexible pipe 50mm dia bore PE 100, 3 to 3.4 mm wall thick PN 6 of capacity 4 Kg/SqCm black in colour as sample kept with AGE office including all fitting and fixtures for jointing for water supply purpose from intake point of source to existing pipe line all as required at site and complete all as specified. Note: These pipe shall be laid during summer season in Gad-Gad or galati nallah which is 6-7 Km away from MES office complete all as specified and directed.

250

-

-

... More
M&L for rectify the leaking joints of 150mm bore GI tubing by applying gas/ electric arc welding on both sides of socket/ flange/ union or any other portion of pipe to stop the leakage by arranging gas/ electric arc welding set at site of work on hill slopes/ plain area and testing on completion complete all as specified and directed. Note : Earth work shall be measured and paid under relevant item.

8

-

-

... More
M&L for rectify the leaking joints of 100mm bore GI tubing by applying gas/ electric arc welding on both sides of socket/ flange/ union or any other portion of pipe to stop the leakage by arranging gas/ electric arc welding set at site of work on hill slopes/ plain area and testing on completion complete all as specified and directed. Note : Earth work shall be measured and paid under relevant item.

6

-

-

... More
M&L for rectify the leaking joints of 80mm bore GI tubing by applying gas/ electric arc welding on both sides of socket/ flange/ union or any other portion of pipe to stop the leakage by arranging gas/ electric arc welding set at site of work on hill slopes/ plain area and testing on completion complete all as specified and directed. Note : Earth work shall be measured and paid under relevant item.

5

-

-

... More
S&F in replacement GI flange ISI marked suitable for the 150mm bore of GI pipe complete all as specified and directed.

20

-

-

... More
S&F in replacement GI flange ISI marked suitable for the 100mm bore of GI pipe complete all as specified and directed.

25

-

-

... More
S&F in replacement GI flange ISI marked suitable for the 80mm bore of GI pipe complete all as specified and directed.

6

-

-

... More
S&F in replacement GI nipple ISI marked medium grade length upto 2" for the 50 mm bore of GI pipe complete all as specified and directed.

4

-

-

... More
S&F in replacement GI nipple ISI marked medium grade length upto 2" for the 25 mm bore of GI pipe complete all as specified and directed

5

-

-

... More
S&F in replacement GI nipple ISI marked medium grade length upto 2" for the 20 mm bore of GI pipe complete all as specified and directed

5

-

-

... More
S&F in replacement GI union ISI marked suitable for the 50 mm bore of GI pipe complete all as specified and directed.

4

-

-

... More
S&F in replacement GI union ISI marked suitable for the 25 mm bore of GI pipe complete all as specified and directed.

6

-

-

... More
S&F in replacement GI union ISI marked suitable for the 20 mm bore of GI pipe complete all as specified and directed.

5

-

-

... More
S&F in replacement GI socket ISI marked suitable for the 50 mm bore of GI pipe complete all as specified and directed.

10

-

-

... More
S&F in replacement GI socket ISI marked suitable for the 25 mm bore of GI pipe complete all as specified and directed.

10

-

-

... More
S&F in replacement GI socket ISI marked suitable for the 20 mm bore of GI pipe complete all as specified and directed.

12

-

-

... More
S&F in replacement GI Tee threaded ISI marked medium grade for the 100 mm bore of GI pipe complete all as specified and directed

1

-

-

... More
S&F in replacement GI Tee threaded ISI marked medium grade for the 80 mm bore of GI pipe complete all as specified and directed

1

-

-

... More
S&F in replacement GI Tee threaded ISI marked medium grade for the 50 mm bore of GI pipe complete all as specified and directed

2

-

-

... More
S&F in replacement GI Tee threaded ISI marked medium grade for the 25 mm bore of GI pipe complete all as specified and directed

5

-

-

... More
S&F in replacement GI reducer threaded ISI marked medium grade for the 25/20 mm bore of GI pipe complete all as specified and directed

5

-

-

... More
S&F in replacement GI reducer threaded ISI marked medium grade for the 20/15 mm bore of GI pipe complete all as specified and directed

5

-

-

... More
Excavating in trenches in soft/loose soil, n exc 1.5m wide and n exc 1.5m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out complete all as specified and directed.

156.37

-

-

... More
Returning filling in soil in trenches including spreading, leveling watering and well ramming in 25mm thick layer complete all as specified and as specified.

81.25

-

-

... More
Removing excavated soil exc. 50m and not exc 100m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and directed.

75.12

-

-

... More
Supply, Fixing & jointing cast iron air release valve ISI marked confirming 14846 class PN-1.6 with flanged and drilled ends suitable for 150mm nominal bore pipe/ fitting with iron wheel high tensile steel spindle & including jointsand jointing material such as bolts, nuts, washers and rubber gaskets etc incl taking down old unserviceable complete all as specified and directed.

1

-

-

... More
S&F in replacement cast iron sluice valve 150 mm dia, flanged ends,stem (spindle) of SS (forged) and check nut of gun Metal, PN rating 1.6,working parts conforming to IS :14846, and flanged ends having drilling as per IS:1538 including taking down old unserviceable sluice valve complete all as specified and directed.

1

-

-

... More
S&F in replacement cast iron sluice valve 100 mm dia, flanged ends,stem (spindle) of SS (forged) and check nut of gun Metal, PN rating 1.6,working parts conforming to IS :14846, and flanged ends having drilling as per IS:1538 including taking down old unserviceable sluice valve complete all as specified and directed.

2

-

-

... More
S&F in replacement cast iron sluice valve 80 mm dia, flanged ends,stem (spindle) of SS (forged) and check nut of gun Metal, PN rating 1.6,working parts conforming to IS :14846, and flanged ends having drilling as per IS:1538 including taking down old unserviceable sluice valve complete all as specified and directed.

3

-

-

... More
Cutting existing steel tubing 40 to 50 mm dia, screwing for alterations or additions for fitting such as unions gate valves etc complete all as specified and directed.

4

-

-

... More
Cutting existing steel tubing 25 mm dia, screwing for alterations or additions for fitting such as unions gate valves etc complete all as specified and directed.

16

-

-

... More
S&F in replacement gun metal gate valve with Iron wheel head screwed both ends for GI steel tubing 50mm dia including taking down unserviceable valves complete all as specified and directed.

2

-

-

... More
S&F in replacement gun metal gate valve with Iron wheel head screwed both ends for GI steel tubing 25mm dia including taking down unserviceable valves complete all as specified and directed.

25

-

-

... More
S&F in replacement gun metal gate valve with Iron wheel head screwed both ends for GI steel tubing 20mm dia including taking down unserviceable valves complete all as specified and directed by Engr-in-Charge.

11

-

-

... More
S&F in replacement 25 mm bore PTMT ball valve, high pressure, with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed complete all as specified and directed.

80

-

-

... More
S&F in replacement 20 mm bore PTMT ball valve, high pressure, with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed complete all as specified and directed.

40

-

-

... More
Disconnecting/ taking down carefully 3 HP electric motor & pump set from existing position dismantling overhauling & cleaning thorughly oiling, greasing and rectifying minor defects, replacing nuts/bolts, rubber gasket, seal any type, bearings, impellers and compleate insulating with proper varnishing and reassembling duly connected with new PVC coppper conductor cable of existing size, testing complete all as specified and directed.

2

-

-

... More
Disconnecting/ taking down carefully 5 HP electric motor & pump set from existing position dismantling overhauling & cleaning thorughly oiling, greasing and rectifying minor defects, replacing nuts/bolts, rubber gasket, seal any type, bearings, impellers and compleate insulating with proper varnishing and reassembling duly connected with new PVC coppper conductor cable of existing size, testing complete all as specified and directed.

2

-

-

... More
Disconnecting/ taking down carefully air blower of capacity 3 HP from existing position dismantling overhauling & cleaning thorughly oiling, greasing and rectify minor defects, replacing nuts/bolts, rubber gasket, bearings, seal and reassembling duly connected with elecrtical connections as existing complete all as specified and directed.

2

-

-

... More
S&F in replacement V-belt for air blower of suitable size as existing for 3 HP capacity motor all as specified and directed.

2

-

-

... More
Taking out the burnt electric motor of capacity 2 HP to 5 HP from existing position, transporting to civil work shop, separating the stator and rotor housing, cutting and removing the existing winding of stator completely, cleaning the slots and rewinding with existing gauge of super enamelled copper winding wire with suitable insulation, applying insulation varnish and heating in heating chamber till completely dried and reassembling the motor including supply and replacement of DE(01 No.) & NDE(01 No) bearings, transporting back to site and re-installing in its original position including proper alignment for smooth running and testing on completion complete all as specified and directed.

1

-

-

... More
Cleaning of RCC semi U/G water storage tanks of capacity 50000 Glns by removing of dumped sand,silt,debris and dirt any other foreign materials present in tanks/ walls and scrubbing out the floor etc from tank and clean the ventilating system, make outer surface and white wash with existing colour complete all as specified and directed. Note-1.Date of cleaning shall be mentioned on tank with synthetic enamel paint and cost of same shall be deemed inclusive in quoted unit rate. 2. All tools and materials for cleaning the tank should be arranged by contractor.

5

-

-

... More
Cleaning of RCC semi U/G water storage tanks of capacity 11000 Glns by removing of dumped sand,silt,debris and dirt any other foreign materials present in tanks/ walls and scrubbing out the floor etc from tank and clean the ventilating system, make outer surface white wash with existing colour for white wash complete all as specified and directed. Note-1.Date of cleaning shall be mentioned on tank with synthetic enamel paint and cost of same shall be deemed inclusive in quoted unit rate. 2. All tools and materials for cleaning the tank should be arranged by contractor.

2

-

-

... More
Taking out 150mm dia sluice valves and re-facing, regrinding replacing stuffing boxes of sluice valve spindle and gland plate replacement of gasket, nuts, bolts, washers and reassembling in existing state including excavation and earth work and making the disturbed surface as per existing surface after making the sluice valve serviceable to the entire satisfaction of Engineer-in-Charge complete all as specified and directed.

2

-

-

... More
Collect sample of water from Officer Mess RCC sump and Kandy filter RCC sump for testing of "Chemical & Bacteriological tests" from approved laboratory and submitting to Engineer-in-Charge for ensuring the potability of water complete all as specified and directed.

2

-

-

... More
S&F in replacement of chlorination dosing pump set ½ HP, single phase of same model as existing on site complete all as specified and directed.

1

-

-

... More
M&L for random rubble stone masonry, uncoursed, well bounded, bedded and solidly hearted built in cement mortar 1:4 brought uoto course complete all as specified and directed.

10

-

-

... More
M&L for rendering 15mm thick on stone masonary surfaces externally finished even and smooth without using extra cement in CM 1:4 complete all as specified and directed.

25

-

-

... More
Supply only integral water proofing compound complete all as specified and directed.

2.5

-

-

... More
M&L for 1:2:4 cement concrete type B1 using 20mm graded stone aggregate as in coping/ benching/ bed block etc complete all as specified and directed.

1.77

-

-

... More
M&L for 1:4:8 cement concrete type D2 using 40 mm graded aggregate in foundations, filling and mass-concrete complete all as specified and directed.

9.91

-

-

... More
M&L for valve pit cover made of 3 mm thick MS sheet/ plate, welded with 50X50X65mm angle iron frame fixed on top of valve pit by means of hold fast 150mm long/ grouting including provision of hinges, handle and locking arrangementcomplete all as specified and directed.

60

-

-

... More
M&L for preparation of new steel surfaces any description, over 10cm in width or girth, not otherwise applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.

6

-

-

... More
Dismantling of old rusted support for pipe of channel, angle, I-section of MS channel or angle sections etc complete all as specified and directed.

1.1

-

-

... More
Material and labour for bracing supports, clamps and blacksheet plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated and inclusive of one coat of black bituminous paint over a coat of redoxide primer and a final coat with synthetic enamel grey paint over the coat of black bituminous paint over a coat of redoxide primer and a final coat with synthetic enamel grey paint over the coat of black bituminous paint complete all as specified and directed.

1.1

-

-

... More
Demolition of brickwork or stone/boulder masonary built in cement mortar complete all as specified and directed.

10

-

-

... More
M&L for boulder filling dry, handpicked tightly, as in wire crate appron bound complete all as specified and directed. Note: (i) Wire crate shall be measured and paid. (ii) Working site for the same is approx 7-8 km away from AGE office.

9

-

-

... More
S&F 4mm dia galvanised steel wire, 150x100 mm mesh made up into mattresses or cages, lapped, wired and laid in position including closing after filling complete all as specified and directed.

24

-

-

... More
S&F in replacement of 3 pole contactor MNX 18 1NC 18 Amp conforming to IS/ IEC 60947-4-1 & IEC 60947-4-1 complete all as specified and directed.

2

-

-

... More
S&F in replacement of thermal overload relays 14-23 Amp for MNX contactor as mentioned in Items No 70 above conforming to IS/IEC 60947-4-1 complete all as specified and directed.

1

-

-

... More
Supply and fix in replacement 125 Amp 4 pole ON LOAD change over switch 415V, 50 Hz AC in sheet metal enclosures complete all as specified and directed.

1

-

-

... More
M&L for preventive maintenance/ servicing of diesel engine generating set 20 KVA/ 125KVA, 2 cylinder, air cooled 4 stroke 1500RPM, including valve seal cutting, valve grinding, head facing, water pump, cleaning of exhaust manifold, radiator & fuel tank etc and repairs of worn out parts and replacement of spares parts such as nut-bolts, washers, engine oil etc. complete all as specified and directed. Note:- Spare parts shall be measured and paid separately under respective items.

4

-

-

... More
Supply only Air/ oil/ fuel and by pass filter

16

-

-

... More
Supply only Fan/ Alternator/ water pump belts

4

-

-

... More
Supply only Hose pipe suitable size

4

-

-

... More
Supply only fuel pipe line of suitable size

8

-

-

... More
Supply only Oil seal set

4

-

-

... More
Supply only Washer set

4

-

-

... More
Supply only Battery leads copper cable of suitable size (16-25sqmm) with brass connectors / terminals, nuts & bolts in red colour-03mtr & black colour -03mtr complete all as specified and directed.

2

-

-

... More
Supply only Engine oil best grade 10W30/ 20W40 complete all as specified and directed.

25

-

-

... More
Taking down Radiator assembly from DG set of capacity 20 KVA including cleaning, brazing of water tubes if found leakage during cleaning. Radiator shall be cleaned thoroughly and remove scale deposits by suitable cleaning material radiator shall be tested for leakage by means of injecting pressure. The complete DG set housing/ block shall also be de-carbonized/cleaned by means of suitable cleaning material and re-fixing the same after testing complete all as specified and directed.

1

-

-

... More
Disconecting and taking down self starter assembly of 20 KVA DG set from the existing position, opening and servicing by rectiffying defect / faults and repair replacement of internal parts like coils, corbon bushes, crcuits etc with ew ISI marked parts, assembling and fixing with DG set inlcuding testing and commissioning complete all as specified and directed.

1

-

-

... More
S&F in replacement of Automatic voltage regulator (AVR) for 20 KVA DG Sets complete all as specified and directed.

1

-

-

... More
Supply only First Aid Box for the E/M installation complete all as specified and directed.

2

-

-

... More
Dismantling of stay assembly complete all as specified and directed.

4

-

-

... More
S&F stay assembly complete with all accessories, such as stay plate 300x300x6mm, stay rod 215cm long and 20 mm dia with nuts including GI bow turn buckle etc., all as per Electrical plate No 1 or SSR -2009 Part I complete all as specified and as directed.

4

-

-

... More
M&L for loop type insulators vitreous porcelain white, brown or green large size with overall dimensions 65x90 mm clearance of hole 25.5 mm complete all as specified and directed.

4

-

-

... More
Dismantling of ACSR or AAC conductors complete all as specified and directed.

2

-

-

... More
S&F ACSR conductor of any type and size stretching properly on insulators and binding with aluminium binding wires, jumpers including fixing on insulators on each poles in span and tightening with permissible sag in between spans etc complete all as specified and directed.

2

-

-

... More
Dismantling insulators any type, any size complete all as specified and directed.

57

-

-

... More
S&F pin type procelain white/ brown/ green/ insulator (inplace of defective one) including galvanised mild steel spindle, two galvanised iron Washers and one galvanised iron nut,100mm height 65mm dia for 1100 volts grade complete all as specified and directed.

10

-

-

... More
S&F shackle type insulator (inplace of defective one) vitreous procelain white/ brown/ green with and including galvanised mild steel straps, washers, insulator, bolts and nuts, insulators of size 100mm height and 115mm max dia with working pressure 1100 volt and galvanised steel straps 31X 5 mm size and dia of bolts 14mm complete all as specified and directed.

20

-

-

... More
S&F 1100 volts grade heavy duty 2 core x 10 sqmm cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular complete all as specified and directed.

400

-

-

... More
S&F in replacement of 1100 V grade straight through cable jointing kit complete with jointing material heat shrink type and accessories suitable for 3.5/4 core XLPE, armoured, Al conductor cable and taking down of old one for cable size 4 core x 10-16 sqmm complete all as specified and directed.

1

-

-

... More
S&F in replacement of 1100 V grade straight through cable jointing kit complete with jointing material heat shrink type and accessories suitable for 3.5/4 core XLPE, armoured, Al conductor cable and taking down of old one for cable size 4/3.5 core x 25-50 sqmm complete all as specified and directed.

1

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq mm 4 core including taking down old unserviceable cable complete all as specified and directed.

280

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq mm 2 core including taking down old unserviceable cable complete all as specified and directed.

300

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq mm 4 core including taking down old unserviceable cable complete all as specified and directed.

200

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq mm 4 core including taking down old unserviceable cable complete all as specified and directed.

200

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sq mm 3½ core including taking down old unserviceable cable complete all as specified and directed.

200

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq mm 3½ core including taking down old unserviceable cable complete all as specified and directed.

120

-

-

... More
Supply, laying, testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sq mm 3½ core including taking down old unserviceable cable complete all as specified and directed.

110

-

-

... More
S&F factory made weather prrof outdoor pole mounted MCB kisok box made out of min 1 mm thick MS sheet of size not less than 240x130x110mm with and including MCB SP 6 Amp, 240 V 'B' series 10 KA and bus bar including fixing with two FI clamps 25x3mm including nut-bolts and washers etc duly painted and taking down old unsv kiosk box complete all as specified and directed.

25

-

-

... More
S&F LT overhead lines on existing 09 mtr LT steel tubular poles with XLPE insulated AB cable 3-core x 95 sqmm (insulated phase conductors) + 1 x 70 sqmm (bare neutral messanger conductor) + 1 x 16 (street light phase) ISI marked complete all as specified and directed.

250

-

-

... More
S&F LT overhead lines on existing 09 mtr LT steel tubular poles with XLPE insulated AB cable 3-core x 70 sqmm (insulated phase conductors) + 1 x 50 sqmm (bare neutral messanger conductor) + 1 x 16 (street light phase) ISI marked complete all as specified and directed.

220

-

-

... More
S&F insulation piercing connectors (IPC) for main cable of 16-50 Sqmm with taps or main cable of 70-120 Sqmm ranging from 4-50 Sqmm for connecting service cables from LT OH aerial bunched cable (AB Cable) complete all as specified and directed.

40

-

-

... More
S&F suspension clamp, eye hook suitable for 16-70 Sqmm size neutral conductor including fixing with MS clamps, nut-bolts and washers complete all as specified and directed. Note: MS clamp, nut-bolts and washers shall be measured seperately.

20

-

-

... More
S&F anchoring clamp suitable for cable size 16-50 sqmm with Al. alloy bracket, stainless steel strap, buckles, eye hook including fixing with MS clamps, nut-bolts and washers complete all as specified and directed. Note: MS clamp, nut-bolts and washers shall be measured seperately.

20

-

-

... More
S&F fire retardant engineering thermoplastic (PC) three phase distribution box of size not less than 275x310x210mm IP 65 rated, with spring loaded busbar connection with a provision of 1 No main incomer and 02 Nos outgoing cable connections including fixing with MS clamps, nut-bolts and washers complete all as specified and directed. Note: MS clamp, nut-bolts and washers shall be measured seperately.

8

-

-

... More
Labour only for tightening, stringing of ACSR conductor or aerial bunched (AB) cable of any size for LT over head lines on poles including binding with aluminium winding wire & testing complete all as specified and directed. Note:- Distance between two pole considered as one span.

20

-

-

... More
M&L for GI pipe in replacement, light grade 80 mm for cable protection etc complete all as specified and directed.

30

-

-

... More
M&L for GI pipe in replacement, light grade 50 mm for cable protection etc complete all as specified and directed.

20

-

-

... More
Labour only for repair of LT feeder pillar/ panel cubical type 3 phase 4 wire, 415 volts, 50 HZ, AC supply system as per latest IS/ IEC standards & regulations, madeout of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable single door:- Rate for these item shall include:- (i) Checking of unserviceable voltmeter ammeters CTs & control wiring of the panel. (ii) Rewiring of unserviceable control wiring of panel as per requirement by 2.5 Sqmm, 4Sqmm or 6 Sqmm copper wire. (iii) Making necessary connection with suitable size lugs of incoming and outgoing cables. (iv) Testing and commissioning the LT panel after repair work complete all as specified and directed.

5

-

-

... More
S&F in replacement of ammeter three phase 96x96/ 144x144 mm square type, digital 0-400 volts complete all as specified and directed.

5

-

-

... More
S&F in replacement of voltmeter three phase 96x96/ 144x144 mm square type, digital 0-500 volts complete all as specified and directed.

5

-

-

... More
S&F in replacement of CTs of suitable range (100/5, 200/5 ratio) with marking necessary connection and testing complete all as specified and directed.

10

-

-

... More
S&F in replacement of 3 pole power contactor with 1 No & 1 NC & of capacity range 9-30 Amp with making necessary connection and testing complete all as specified and directed.

4

-

-

... More
S&F in replacement of time switch FM1/quartz daily 240 V AC base/DIN mounting with making necessary connection and testing complete all as specified and directed.

4

-

-

... More
S&F in replacement of 03 Nos of 600 Amp rating & 01 No of 400 Amp rating electrolytic aluminium bus bars of high conductivity and proper insulated with red, yellow, blue & black colour respectively and fixing aluminium bus bars on porcelain support in existing LT panel including making all necessary connections, testing and commissioning complete all as specified and directed.

4

-

-

... More
M&L for MCCB of capacity 63 Amp 4 pole, 415 V, 50 Hz 16 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

2

-

-

... More
M&L for MCCB of capacity 100 Amp 4 pole, 415 V, 50 Hz 16 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

2

-

-

... More
M&L for MCCB of capacity 125 Amp 4 pole, 415 V, 50 Hz 16 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

2

-

-

... More
M&L for MCCB of capacity 160 Amp 4 pole, 415 V, 50 Hz 16 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

2

-

-

... More
M&L for MCCB of capacity 200 Amp 4 pole, 415 V, 50 Hz 25 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

1

-

-

... More
M&L for MCCB of capacity 400 Amp 4 pole, 415 V, 50 Hz 25 kA with adjustable thermal and adjustable magnetic protection release to existing LT panel board, making all connections including suitable lugs, testing commissioning including taking out unserviceable MCCBs by disconnecting all electrical connection on existing position from LT Panel board and complete all as specified and directed.

1

-

-

... More
M&L for sand cushioning under ground cable for cable protection provided with layers 8cm thick before laying and 15cm thick after laying the cable and punned down to 23 cm thickness complete all as specified and directed. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 18cm as mentioned in para19.75 of SSR Part-I

48.6

-

-

... More
Supply and laying sub class B brunt clay bricks old size for protection of cables laid lengthwise perpendicular to the axis of cable, adjecent to each other complete all as specified and directed.

4.8

-

-

... More
Dismantling and taking down street light for repair or replacement of burnt/ worn out accessories complete all as specified and directed.

24

-

-

... More
S&F LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.

24

-

-

... More
S&F in replacement of old bracket made out of 32 mm bore light grade GI pipe bent to shape fixed as bracket suitable for street light fittings not less than 1.2 m long bent/welded to shape including necessary nut, bolt and clamp-02 No made of MS flat 40x5mm as required duly painted by unscrewing nut and bolts complete all as specified and directed.

20

-

-

... More
M&L for 1100 volts grade heavy duty cable with PVC insulated aluminium solid / stranded conductor served with an inner sheathing of PVC tape armoured with overall PVC sheathed 3 core x 1.5 sqmm nominal cross sectional area including taking down unserviceable cable complete all as specified and directed.

90

-

-

... More
Dismantling steel tubular pole any size complete all as specified and directed.

15

-

-

... More
Supply and erection, in truly vertical position steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) including painting of poles with two coats of synthatic enamel paint in black and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles complete all as specified and directed.

11

-

-

... More
M&L for painting to steel tubler poles 9 m long including cross arms, street light brackets, earth pipe, clamps with one coat of aluminium paint including preparation of old painted surfaces properly and providing 3 bands /straps 25 cm wide with paint red signal post office colour and 2 band 25 cm wide with white synthetic enamell paint 300 mm apart from plinth block and numbering of poles 100 mm height with white paint in black box of size 125x125mm, complete all as specified and directed.

40

-

-

... More
M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation/ for stay assembly etc. complete all as specified and directed.

0.96

-

-

... More
Cutting/ Trimming the tree branches of any size touching/ embracing the OH line of LT/HT up to 1.5 Mtr on both side of the OH line & upto 1.5 RM above the overhead line including removing the same from site to a distance not less than 250 Mtr away complete all as specified and directed. Note:- Distance between two pole considered as one span.

60

-

-

... More
Labour only for repair of burnt out/ perished cable ends 4 Nos each on incoming and outgoing feeders of panels equipment and other machinery by removing burnt ends including cleaning and preparing the cable ends including making necessary connection with suitable size of cable lugs of any size with R, B, Y, N colour code complete all as specified and directed.

2

-

-

... More
Supply, installation, testing and commissioning LT 415 volt, 4 wire AC 50Hz cubical panel factory made outdoor (KIOSK) floor mounted type, weather and vermin proof fabricated from angle of size 50x50x6.0mm and 3.00mm thick MS black sheet, powder coated inside and outside with approved paint over a coat of red oxide primer locking arrangement comprising 50mm godrej type pad lock with duplicate key, two earth terminal, suitable cable glands for incoming and all outgoing cables including grouting KIOSK on floor (60cm above the ground surface) in floor angel iron 50x50x6mm imbedded to fixed the KIOSK with nut bolt, floor PCC (1:2:4) type B1 using 20mm grade stone aggregate complete all as specified and directed by EIC including consisting of following accessories and components:- (i) Incoming- MCCB 200 Amp capacity, adjustable thermal and fixed magnetic setting type 10 kA, 4 pole-1 Nos (ii) Outgoing - (a) MCCB 160 Amp capacity, adjustable thermal and fixed magnetic setting type 10 kA, 4 pole-02 Nos (b) MCCB 100 Amp capacity, adjustable thermal and fixed magnetic setting type 10 kA, 4 pole-02 Nos (iii) Volt meter (0-500V) three phase, digital type with selector switch-01 No (iv) Ammeter (0-500V) three phase, digital type with selector switch with suitable capacity of CTs-01 Set (v) On/ OFF indication lamp with toggle switch - Set of 3 (vi) 04 Nos electrolytic aluminium bus bars of high conductivity proper insulated of 1½ times of the incoming capacity with provision of extension and mounting on porcelain support. (vii) Internal or control wiring of feeder pillar with suitable size cables including thimbles etc.

1

-

-

... More
Supply, installation, testing and commissioning street light timer panel LT 415 volt, 4 wire AC 50Hz cubical pannel factory made outdoor (KIOSK) floor mounted type, weather and vermin proof fabricated from angle of size 30x30x5.0mm and 3.00mm thick (outer shell) MS black sheet, 2.00mm thick inner shell, duly spray painted with powder coated paint, suitable locking arrangement, two earth terminals, internal or control wiring with suitable size PVC insulated copper conductor cables, suitable cable glands for incoming and all outgoing cables including grouting KIOSK on floor (60cm above the ground surface) in floor angle iron 50x50x6mm imbedded to fix the KIOSK with nut bolt, floor PCC (1:2:4) type B1 using 20mm grade stone aggregate complete all as specified and directed by EIC including arrangement of operation both in auto and manual mode and consisting of following accessories and components:- (i) Incoming- MCCB 63 Amp capacity, adjustable thermal and fixed magnetic setting type 10 kA, 4 pole (ii) Outgoing - (a) MCCB 40 Amp capacity, adjustable thermal and fixed magnetic setting type 10 kA, 4 pole (iii) On/ OFF indication lamp with toggle switch - Set of 3 (iv) 3 way selector switch for manual ON/OFF/Auto switching of street light luminaires (v) 3P contactor with 1 No & 1 NC & of capacity range 9-30 Amp & time switch FM1/quartz daily 240 V AC base/DIN mounting.

2

-

-

... More
Demolition of cement concrete (un-reinforced) any description and in any position complete all as specified and directed.

6

-

-

... More
Labour only for repair of APFC panel cubical type 3 phase 4 wire, 415 volts, 50 HZ, AC supply system as per latest IS/IEC standards & regulations, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable single door. Rate for this item shall included:- (i) Checking of unserviceable MCBs, contactors & capacitors and taking down/ disconnecting the unserviceable one. (ii) Fixing of MCBs, contactors, control relay & capacitors. (iii) Rewiring of unserviceable control wire of APFC panel as per requirement by 2.5 sqmm, 4 sqmm or 6 sqmm copper wire. (iv) Testing and commissioning the APFC panel after repair work complete all as specified and directed.

5

-

-

... More
Supply only three phase capacitor duty contactor 5KVAR

8

-

-

... More
Supply only three phase capacitor duty contactor 10KVAR

5

-

-

... More
Supply only capacitor 5 to 15KVAR

40

-

-

... More
Supply only APFC controller for contactor switching with 1 CT input

3

-

-

... More
Supply only MCBs 3P 415 Volt, 16 to 32 Amp 10kA 'C' curve type

5

-

-

... More
Supply only MCBs 3P 415 Volt, 40 Amp 10kA 'C' curve type

5

-

-

... More
Labour only for repair of solar street light system by cleaning the solar photvoltic module (SPV) panel, checking the battery system by measuring the battery gravity and electrical connetions of solar charge controller and replacing the unserviceable accessories complete for making the serviceable the solar powered LED street light system complete all as specified and directed . Note: spare parts(accessories) shall be measured and paid seperately.

6

-

-

... More
Labour only for transporting the solar powered discharged battery from site to workshop for charging and return back the same after full charging of battery complete all as specified and directed .

3

-

-

... More
Supply only 36 watt integrated solar street light

4

-

-

... More
Supply only 12 volt 150 Ah solar powered battery

3

-

-

... More
Supply only distilled water for filling in old serviceable batteries

50

-

-

... More
Supply only MPPT solar charge controller generation 5LV-12V, 24V, 36V, 48V in 100A model

2

-

-

... More
M&L GI tubing light grade 100mm dia with all fitting laid in tranches across the road or in culvert or fixed to pole for protection of cables complete all as specified and directed.

6

-

-

... More
M&L for disconnecting the transformer of capacity upto 315 KVA from the electrical system, taking out and shifting the same for repair to workshop, drain out old transformer oil, opening the top cover of the transformer and taking out core with limbs and primary windings after the disconnecting and removing iron core, removing damaged primary windings etc. re-assembling transformer winding and core heating including insulating and packing material in order to take out all moisture from the transformer assembly complete, lowering the core assembly with winding in transformer body, connection work and re-assembling in position top cover, conservator, breather with relay control wiring complete including transportation of transformer back from workshop to site, installation of transformer on foundation, commissioning and testing with system satisfactorily complete all as specified and directed.

1

-

-

... More
M&L for copper wire complete as per existing guage for existing numbers of turns for LV coil/leg rewinding of transformer capacity 63-315 KVA complete all as specified and directed.

44

-

-

... More
M&L for copper wire complete as per existing guage for existing numbers of turns for HV coil/leg rewinding of transformer capacity 63-315 KVA complete all as specified and directed.

27

-

-

... More
M&L for gasket set made out of cork sheet cut into shape sticking on transformer body with adequate quantity of adhesive to make the complete transformer body leak proof complete all as specified and directed.

1

-

-

... More
Supply and filling topping up and replacement of old transformer oil with new transformer oil in the existing tronsformer 11/0.433 KV for topup or to achieve the required level after centrifuging by the centrifuging machine complete all as specified and directed.

200

-

-

... More
S&F in replacement of silicagel pot filled with fresh dehydrating agents (Silca gel) and oil in bowl/ cap of the transformer 63-160 KVA, 11/0.433 KV tronsformer outdoor/indoor type complete all as specified and directed.

2

-

-

... More
S&F in replacement of silicagel pot filled with fresh dehydrating agents (Silca gel) and oil in bowl/ cap of the transformer 200-315 KVA, 11/0.433 KV tronsformer outdoor/ indoor type complete all as specified and directed.

2

-

-

... More
S&F in replacement of LT bushing (brass stud and bolts with poreclien insulator) suitable size to fixed the transformer capacity range 63-160 KVA, 11/0.433 KV including replacement of gasket, cable glands etc to make the transformer leak proof complete all as specified and directed.

4

-

-

... More
S&F in replacement of LT bushing (brass stud and bolts with poreclien insulator) suitable size to fixed the transformer capacity range 200-315 KVA, 11/0.433 KV including replacement of gasket, cable glands etc to make the transformer leak proof complete all as specified and directed.

4

-

-

... More
S&F in replacement of HT bushing (brass stud and bolts with poreclien insulator) suitable size to fixed the transformer capacity range 63-315 KVA, 11/0.433 KV including replacement of gasket etc to make the transformer leak proof complete all as specified and directed.

3

-

-

... More
M&L for painting of HT steel pole 11 mtr long including painting of MS work like crass arms, clamps, pipe channel, bracing etc after cleaning and preparation surface painting externally above plainting depth with one coat of alumunium paint including 30cm width of circular band 3 Nos alternative above 1 Mtr height from pole copping with red paint and wiriting pole No complete all as specified and directed.

20

-

-

... More
Dismantling cross-arms of M.S. channel or angle sections etc. complete all as specified and directed.

0.8

-

-

... More
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.

0.8

-

-

... More
Dismantling air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. complete all as specified and directed.

4

-

-

... More
Supply, installation, commissioning and testing of switch air break gang operated HT 11KV grade triple pole with 12 insulator 200Amp rating with drop out fuse assembly with fuse carrier fuse element mounted on insulator and fitted on steel frame mechanically operated mechanism from ground level consisting of operating rod 25mm bore light grade GI pipe to suitable length work from ground level consisting of operation rod 25mm bore complete all as specified and directed.

4

-

-

... More
Supply and laying cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 Sqmm 3 core complete all as specified and directed.

220

-

-

... More
M&L CI cable path indicator, voltage written on IT and fixed on angle iron, shall be painted brown for HT cables or yellow for LT cables complete all as specified and directed.

10

-

-

... More
M&L cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.

2

-

-

... More
M&L cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.

4

-

-

... More
M&L cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.

1

-

-

... More
S&F lightening arrestor expulsion type suitable for 11000 volts complete with all fittings, transmission class, discharge capacity 65kilo Amp including taking down/out old unserviceable complete all as specified and directed.

1

-

-

... More
M&L for pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 550 volts grade including taking down old complete all as specified and directed.

15

-

-

... More
M&L for disc type, porcelain, vitreous white, brown or green insulator 145mm high and 255mm dia ball and socket type, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts including taking down old complete all as specified and directed.

12

-

-

... More
M&L for steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11 metres long), staying the poles in a truly vertical position including painting steel tubler pole exposed surface with two coats of aluminium paint over a coat of red oxide primer and providing 3 bends/ straps with paint red signal post colour and two bends with black synthetic enamel paint 300 mm apart from plinth block and numbering of pole and painting embedded portion of pole with one coat of bituminious paint including dismantling old pole complete all as specified and directed.

4

-

-

... More
Unbinding ACSR conductor of any type from insulators and re-fixing the same on insulators of HT poles after tightening/ re-stretching to achieve the permissible sag in between spans with and including 2mm dia aluminium binding wire complete all as specified and directed. Note :- Distance between two poles considered as one span.

20

-

-

... More
S&F cradles, hexagonal/ rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia including dismantling of old wire complete all as specified and directed.

0.45

-

-

... More
Cutting of bushes/ grass, unwanted veg growth in and around the electrical installations, transformers, panel boards, HT 4 pole / 2 pole structures, HT electric poles, etc in complete station and disposed off to the location not less than 50 Mtr all as required at site complete all as specified and directed.

300

-

-

... More
M&L for painting to 2 poles structure of 11 mtr long steel tubular pole including cross arms, channel bracing, earth pipe , anti climbing device, clamps, GOD insulators mounting channels, with one coat of aluminium paint including preparation of old painted surfaces properly and providing 3 bands/ straps 25 cm wide with paint red signal post office colour and 2 band 25 cm wide with white synthetic enamel paint 300 mm apart from plinth block and numbering of poles 100 mm height with white paint in black box of size 125x125mm complete all as specified and directed.

4

-

-

... More
Maintenance and complete overhauling of 11 KV VCB of existing make/ type/ mode/ capacity including disassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board, main bus bar, decarbonizing all joints bus bar CTS, PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented in service by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board including submission of calibration certificate complete all as specified and directed. Note:- Spare parts required to make VCB functional will be measured and paid separately under respective items.

4

-

-

... More
Supply only Breaker control switch 10A 660V

1

-

-

... More
Supply only Closing coil

2

-

-

... More
Supply only Tripping coil

2

-

-

... More
Supply only Breaker on off switch plastic handle

2

-

-

... More
Supply only Vaccum interrupter bottle module with ceramic housing as same as existing or approved by GE/ suitable for outgoing VCB of 400 Amp rating

2

-

-

... More
Supply only Red,Yellow, Blue phase indicator neon light

3

-

-

... More
Supply only contactor for 630 Amp VCB

1

-

-

... More
M&L for earthing of GOD & LA with galvanised cost iron earth plate of size 600x600x6mm thick burred directly in ground not less than 2.25mtr below normal ground level, earth plate packed on all side with charcoal mixed with salt to a thickness of 150mm connected by GI earth strip of size 32x6mm thick soldered and riveted to earth plate. GI earth strip will be protected by using 50mm bore light grade GI pipe earth plate to steel tubular pole including flat iron clamp 25x3mm including bolts nut and washers complete including watering GI pipe 20mm dia light grade 2.5mtr long the earthing include PCC pit including necessary earth work and disposal of surplus soil to a distance not less than 50mtr, chamber of PCC (!:4:8) type D2 using 40mm graded stone aggregate, coping shall be PCC(1:3:6) type C1 using 20mm graded stone aggregate, RCC pit cover 50mm thick (1:2:4) type B1 using 20mm graded stone aggregate, reinforced with 8mm MS bar at 80mm C/C both way in lieu of CI pit cover and angle iron frame including flame funnel, wire mess, GI earth wire, 8SWG under the earth and on the pole upto height of 1.5mtr shall be protected by 15mm dia GI pipe (Light grade) GI pipe to be fixed with pole by means of 2 Nos flat iron clamps 25x 3mm size complete with bolts, nuts and washers etc. complete all as specified and shown in electrical plate No 5 of MES sch part -I 1991.

4

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.