Military Engineer Services Tender
View complete overview of Uttarakhand MES Tender
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date3 Jan 2025
Closing Date2 Feb 2025
Tender Amount₹ 2,43,00,000
Costs
EMD
₹ 3,18,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_691601_1Tender No
CEBZ/DDN(H)/T-34 of 2023-24Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Note :
(i) The defect liability period will be 2 years from the date of completion.
(ii) Any variaiton in quantity of Smart Prepaid Meter (AMI) will be paid/ deducted as per pro- rate basis of serial item No-02
(iii) The rent and water supply bills and any other charges or levy will be included in software's as decided by GE.
Note: Supplementary rate for single and three phase smart meter beyond the quantity mentioned here-in-before are as under:-
(a) single phase meter to be installed as per BOQ item No. 2 - Rs 8000/- per meter
(b) three phase meter to be installed as per BOQ item No. 2 - Rs 9000/- per meter
-
-
-
... More
Supply, installation two broadband connections for Clement Town and Raiwala station with high speed internet connection for two years complete all as directed.(One connection in the name of Garrison Engineer Clement Town and another coneection in the name of Asst Garrison Engineer (I) Raiwala).
24
-
-
... More
Material and labour for integration of additional single/ three phase Smart Electric Meters (as per IS-16444) in the AMI being provided in this contract complete all as specified and directed by Engr-in-Charge.
700
-
-
... More
Provision of wireless Report Printer with 12 pages per minute capacity, 600 x 600 dpi with HP, REt, 1200 dpi effective output quality (600 x 600 x 2 dpi with REt, with duty cycle 3,000 single-sided pages per month for report printing complete as required, Make: HP LaserJet 1020 or equivalent in Canon, Epson and Samsung printer all as specified.
2
-
-
... More
Provision of computer PC desktop with processor i-7- 12700 , 9 Generation, 8-GB RAM, hard disk 1TB, 4-USB Port including 18.5" monitor of same make, keyboard, mouse, Make-HP/DELL/IBM/ with licensed Operating system (Windows 10), along with 1KVA capacity online UPS all as specified.
2
-
-
... More
Supply and install hi wall five star rated split units indoor/outdoor complete with cordless remote control unit and with in built Heating and Cooling arrangement and Digital Inverter twin rotary of capacity 2 TR complete all as directed.
2
-
-
... More
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA
2
-
-
... More
MISC ITEMS
-
-
-
... More
Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type wall mounted, of size not less than 1500X900X250mm suitable for 415 Volts 3 Phase and neutral, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated electrolyted Aluminium bus bars TPN of capacity 200 Amps rating insulated on DMC insulators with bus bar chamber, front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLSH cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens gray RAL-7035 shade. The scope of work also comprising of the following :- (a) BUS BAR CHAMBER :- i) 200 Amps 3 Strips and Neutral Strip 100 Amps, Aluminium Conductor with current density 0.8/ sqmm color coded heat shrinkable sleave and shall be mounted on non hygroscopic , non combustible, track resistant high strength DMC material interconnection all
Contd..
5
-
-
... More
incomings & outgoings.
ii) Red, Yellow ,Blue Phase indicating lights LED Type 220 V AC-1 Set (Set of Three)
INCOMING SUPPLY:-
i) MCCB 4P 100 Amps 16 KA, 415 Volts, 50Hz- 01 No -
OUTGOING SUPPLY:-
i) MCB SPN 6-32 Amps 240 Volts, 50Hz, ruptiring capacity 10 KA = 06 Nos ii) MCB SP 6-32 Amps 240 Volts, 50Hz, ruptiring capacity 10 KA = 01 Nos, iiI) Space required for 06 Nos smart Pre-paid Energy meter single Phase, AC 240V, 10-60 Amps iv) DMC Connector 2 way 100 Amps for outgoing submain supply-07 Nos
v) Panel wiring for control circuit with copper flexible 1.5 Sqmm & power wiring minimum 4 Sqmm flexible .
Contd...
-
-
-
... More
Notes:-
1. The panel manufacturer should have following certification:-
i) CPRI certificate Degree of protection IP-54 (should have IEC:61439-1-2 & IEC: 60529 tests)
ii) CPRI certificate short circuit with stand strength should be 50 KA RMS for 1 Sec with initial peak of 105 KA.
iii) CPRI certificate rated current not less than 5000A. 2. Drawing of panel board/meter box should be got approved from GE (MES) Clement Town, Dehradun before fabrication.
3. Panel board should be fully seperate compartment for 6Nos SMART Pre-paid meter,mcb tpn etc in accordance to form 4b of IEC 61439-1- 2 5.While replacing the existing LT meter box/panel board All serviceable items of Panel ie. ,MCBs etc should be deposited into MES store yard based on inventory prepared by joint inspection of engr in charge & contractor all as specified and directed by engr in charge.
.
-
-
-
... More
Supply, installing, testing and commissioning factory made and tested LT Panel indoor type wall mounted, of size not less than 900X700X250mm in repair suitable for 415 Volts 3 Phase and neutral, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated electrolyted Aluminium bus bars TPN of capacity 200 Amps rating insulated on DMC insulators with bus bar chamber, front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLSH cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens gray RAL-7035 shade. The scope of work also comprising of the following :- (a) BUS BAR CHAMBER :- i) 200 Amps 3 Strips and Neutral Strip 100 Amps, Aluminium Conductor with current density 0.8/sqmm color coded heat shrinkable sleave and shall be mounted on non hygroscopic , non combustible, track resistant high strength DMC material interconnection of all .
Contd....
2
-
-
... More
all incomings & outgoings.
ii) Red, Yellow Blue Phase indicating lights LED Type 220 V AC-1 Set (Set of Three)
INCOMING SUPPLY:-
i) MCCB 4P 63 Amps 16 KA, 415 Volts, 50Hz- 01 No OUTGOING SUPPLY:-
i) MCB SPN 6-32 Amps 415 Volts, 50Hz, ruptiring capacity 10 KA = 4 Nos, ii) MCB SP 6-32 Amps 415 Volts, 50Hz, ruptiring capacity 10 KA = 01 Nos, iii) Space required for 04 Nos Pre-paid Energy meter three Phase, AC 415 V, 10-60 Amps iv) DMC Connector 2 way 100 Amps for outgoing submain supply-05 Nos
v) Panel wiring for control circuit with copper flexible 1.5 Sqmm & power wiring minimum 4 Sqmm flexible .
Contd....
-
-
-
... More
Notes:-
1. The panel manufacturer should have following certification:-
i) CPRI certificate Degree of protection IP-54 (should have IEC:61439-1-2 & IEC: 60529 tests)
ii) CPRI certificate short circuit with stand strength should be 50 KA RMS for 1 Sec with initial peak of 105 KA.
iii) CPRI certificate rated current not less than 5000A.
2. Drawing of panel board/meter box should be got approved from GE (MES) Clement Town, Dehradun before fabrication.
3. Panel board should be fully seperate compartment for 4 Nos Pre-paid meter,mcb tpn etc in accordance to form 4b of IEC 61439-1- 2 4.While replacing the existing LT meter box/panel board All serviceable items of Panel ie.,MCBs etc should be deposited into MES store yard based on inventory prepared by joint inspection of engr in charge & contractor all as specified and directed by engr in charge.
Contd....
-
-
-
... More
Material & labour for sub main wiring with 1100 volt grade two single core PVC insulated and unsheathed cable with stranded copper conductor (FRLSH) of following sizes drawn into and including electrical grade PVC conduit not less than 25 mm dia with all accessories fixed concealed including chase cutting in brick/ stone masonry for fixing conduit and making good the disturb surfaces of wall as per existing including multi - stranded copper conductor as earth wire in green colour complete all as specified and directed.
-
-
-
... More
(a) 2 run of 4.0 Sqmm cable and 1 run of 4.0 sqmm cable connected to common earth dolly (Note :- Two runs of 4.0 sqmm (FRLSH) and one run of 4.0 sqmm (FRLSH) copper conductor shall be measured as one unit length.)
400
-
-
... More
(b) 2 run of 6.0 Sqmm cable and 1 run of 6.0 sqmm cable connected to common earth dolly (Note :- Two runs of 6.0 sqmm (FRLSH) and one run of 6.0 sqmm (FRLSH) copper conductor shall be measured as one unit length.)
52
-
-
... More
Dismantling and taking down u/s sub-main wiring/service wire of any size including wooden batten / PVC Conduit etc and making good the disturbed surfaces of wall/floor to match with the existing wall/floor etc. complete all as specified & as directed. Note :- If the contractor fail to make good the disturbed surface of wall/floor etc and do not match with the existing surface of wall/floor to the entire satisfaction of Engr-in-Charge a recovery @ of Rs. 50/- per RM will be made from payment due to the Contractor. In case of any dispute the decision of accepting officer will be final and binding.
652
-
-
... More
Supply and fixing sub main wiring two run of single core 4.00 sq mm PVC insulated unsheathed stranded copper conductor cable ( FRLSH ) ISI Marked ,1100Volts grade drawn in existing PVC conduit along with one run of 4.00 Sq mm PVC insulated unsheathed copper conductor cable (FRLSH) as earth wire and wire connected with main earth dolly including cutting chasing and making good disturbed portion all as specified and as directed
200
-
-
... More
Taking down old u/s LT Cable & M& L for laying and passing through pipes LT XLPE PVC insulated steel armoured aluminum stranded conductor LT UG cable (confirming to IS7098) ISI marked in trench/ducts/through GI pipes under roads heavy duty electric cable with aluminium conductor 1100 Volts grade,cross sectional area 25 Sqmm, 3.5 core complete all as directed.
450
-
-
... More
Excavation in trenches in any type of soil and not exc 1.5 m wide and n.exc 1.5 m in depth for laying GI tubing for connect to near by pipe line or laying underground cable and GI tubing (where provide for protection of cable) and getting out trimming the sides,forming bottom surface to required level in any type of soil complete etc all as specified and directed.
70
-
-
... More
M&L for sand cushioning for under ground cable with layer of fine dry sand 80 mm thick before laying of cable and 150 mm thick after laying of cable in trench complete all as specified and as directed.Note: Punned (consolidated) thickness of sand will be measured and paid.
28
-
-
... More
Supply and laying , nominal size of traditional / conventional burnt bricks sub class "B" as cable cover, flat, of size 230mmX 114mmX 76mm , complete all as specified & as directed.
3150
-
-
... More
Returning , filling in including spreading leveling, watering and well ramming in layers not exceeding 25 cm thick with excavated soil complete all as specified and directed.
34
-
-
... More
Removing excavated material (surplus soil) to a distance not exceeding 50 mtrs and depositing where directed at a level not exc 1.5m above the starting point all as specified and directed.
36
-
-
... More
Material & labour for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground. ( earth pit not less than 2.25 mtr depth below ground level at any type of strata ) with top edge of the earth plate not less than 1.5mtr below normal ground level connected by 4 mm GI wire as earth lead by means of brass nuts and bolt,thimbles check nuts, washers including concrete chamber of PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320x320x80mm size (1:2:4) Type B1 using 20mm graded stone aggregate rainforced with XPM and charcoal, dust and common salt all as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified including and provision of GI wire upto 7.5 mtrs long with 15 mm dia light grade Gi pipe protection and watering pipe of GI 20 mm bore, medium grade, including all exavation and earth work and connecting the earthing strip to panel, including testing on completion complete
14
-
-
... More
all as specified and directed by Engr-in-charge. Note:- (i) RCC pit cover shall be precast of RCC(1:2:4) type B1, 80mm thick rainforced with XPM weighting not less than 4kg/sqm in lieu of CI cover.
(ii) Cost of additional GI wire more than 7.5 mtrs will be measured and paid seperately under relevant items.
-
-
-
... More
Provision for comprehensive operation including periodic charges of telecom operator, smart meter billing from completion of work till the completion of defect liability period of 2 years complete all as specified and directed.
27672
-
-
... More
Comprehensive operation and maintenance of system including Project implementation & management, all expenditure including periodic charges of telecom operator, smart meter billing and maintenance, after completion of defect liability period till completion for 08 years extendable to further 2 years after manual agreement complete all as specified and directed."
110688
-
-
... More
Note for item No 31 & 32: Penalty Clause:-
(a) Any defect/ malfunctioning in meter will have to be resolved within 24 hours failing which payment for that particular meter for concerned month shall not be made to the contractor.
(b) In case issue is not resolved for 48 hours, penal recovery double rate quoted shall be made from contractor's due.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%