Military Engineer Services Tender
View complete overview of Uttarakhand MES Tender
Military Engineer Services - MES Tender
Civil And Construction
Pipe Line Project
Eprocure
Opening Date2 Feb 2022
Closing Date2 Mar 2022
Tender Amount₹ 27,05,304
Costs
EMD
₹ 60,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_MES_505291_1Bid Award Id
ViewTender No
8392/130/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
REPAIR MAINT AND REPLACEMENT OF OVERHEAD LINES UNDER GROUND CABLES AND ALLIED WORKS AT ROORKEE AND PURKAZI UNDER GE ROORKEE
REPAIR MAINT AND REPLACEMENT OF OVERHEAD LINES UNDER GROUND CABLES AND ALLIED WORKS AT ROORKEE AND PURKAZI UNDER GE ROORKEE
REPAIR MAINT AND REPLACEMENT OF OVERHEAD LINES UNDER GROUND CABLES AND ALLIED WORKS AT ROORKEE AND PURKAZI UNDER GE ROORKEE
BOQ Items
M&L for plain cement concrete (1:2:4) type B1 (using 20mm graded stone aggregate) as in coping of new or existing poles / stays / struts etc including necessary form work and finishing fair and even complete all as specified and directed.
5
-
-
Taking down old unserviceable 80mm dia bore galvanized iron pipes and S&F new 80mm dia bore galvanized iron pipes, light grade, laid in trenches / road crossings or across the nallah or fixed to wall / pole with & including mild steel clamps, screws, nuts, bolts & washers etc complete all as specified and directed.
30
-
-
Taking down old unserviceable 40mm dia bore galvanized iron pipes and S&F new 40mm dia bore galvanized iron pipes, light grade, laid in trenches / road crossings or across the nallah or fixed to wall / pole with & including mild steel clamps, screws, nuts, bolts & washers etc complete all as specified and directed.
24
-
-
Taking down old unserviceable 32mm dia bore galvanized iron pipes and S&F new 32mm dia bore galvanized iron pipes, light grade, laid in trenches / road crossings or across the nallah or fixed to wall / pole with & including mild steel clamps, screws, nuts, bolts & washers etc complete all as specified and directed. Note for Sl item Nos 5 to 7:- The quoted rate is deemed to be included for necessary earth work, road cutting etc
36
-
-
Taking down or up old unserviceable cable and Supply, laying & testing new XLPE insulated armoured heavy duty electric cable 3.5 core 95 Sqmm size with aluminium conductor, 1100 Volt grade, laid in trenches or fixed to walls / poles complete all as specified and directed.
200
-
-
All as per Sl item No. 8.00 but cable 3.5 core 70 Sqmm size
300
-
-
All as per Sl item No. 8.00 but cable 3.5 core 50 Sqmm size
350
-
-
All as per Sl item No. 8.00 but cable 3.5 core 35 Sqmm size
300
-
-
All as per Sl item No. 8.00 but cable 4 core 25 Sqmm size
200
-
-
All as per Sl item No. 8.00 but cable 4 core 16 Sqmmsize
350
-
-
All as per Sl item No. 8.00 but cable 4 core 10 Sqmm size
350
-
-
All as per Sl item No. 8.00 but cable 2 core 10 Sqmm size
600
-
-
Excavation in trenches in soft/loose soil n.exc 1.5 m wide and n.exc 1.5 m in depth as in foundations of poles/stays/struts, trenches for laying of pipes / cables etc and getting out, forming bottom surfaces to required level complete all as specified and directed.
600
-
-
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm thick with soil obtained from excavation complete all as specified and directed.
400
-
-
Removing surplus spoil to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mr above the starting point complete all as specified and directed.
200
-
-
Supply and laying neat dry river sand in trenches for cushioning to cables in two layers, Ist layer of 8 cm thickness laid before laying of cable and IInd layer of 15 cm thicness laid after laying of cable (total 23 cm) and punning properly around the cable complete all as specified and directed.
Note:- Thickness of sand cushioning shall be taken as 18 cm after punning for payment purpose.
140
-
-
Supply and laying old size sub class 'B' bricks in trenches for cable protection as cable cover, laid dry, flat adjacent to each other across the length of cable complete all as specified and directed by Engineer-in-charge.
18
-
-
Labour only for stretching, tightening, fixing and connecting existing HT/LT over head line with 2 ACSR conductors with or without GI wire of any size and type, approximate span/length between two poles 45 to 50 m complete all as directed by Engineer-in-charge.
50
-
-
All as per Sl item No. 21.00 but HT/LT over head line with 5 conductors with or without GI wire.
80
-
-
All as per Sl item No. 21.00 but HT/LT over head line with 6 conductors with or without GI wire.
60
-
-
Taking down unserviceable pin type insulator and providing new pin type 100mm height, 65 mm dia for 1100 Volt grade, porcelain vitreous white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut complete all as specified.
5
-
-
Taking down unserviceable shackle type insulator and providing new shackle type 90mm dia and 75mm height porcelain, vitreous white, brown or green insulator working under 1100 Volts including 12mm dia bolt, straps made of flat iron 31x3mm, washers & nuts complete all as specified and directed.
5
-
-
Taking down unserviceable stay assembly and S&F new stay assembly comprising MS stay plate of size 23cmx23cmx6mm thick, stay rod 20mm dia 215cm long with nuts, MS/GI stay bow 40cm long with 2 Nos GI thimbles, 7/4mm size galvanized stay wire of suitable length, loop insulation of size 65x90mm with 16mm dia hole and other accessories including all necessary earth work, PCC foundation for fixing stay assembly in position as shown in Plate No. 1 of SSR Part-I complete all as specified and directed by Engineer-in-charge.
Note:- MS clamps shall be measured and paid for separately under respective item of Schedule 'A'.
3
-
-
M&L for cutting and cleaning away all grass, vegetation, saplings, shrubs, undergrowth roots and trees up to 50 cm girth from the area surrounding of E/M installations, under HT & LT over head lines, 4/2 pole structures, transforemers, installations, yards, valve chamers and removing the rubbish upto a distance of 50 m outside the periphery of the area under clearance and dressing the area etc complete all as specified and directed by Engineer-in-charge.
3000
-
-
Dismanting unserviceable mild steel work of any description and S&F new mild steel work as in cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated including preparing surfaces and applying two coats of synthetic enamel paint over one coat of redoxide primer complete all as specified and directed.
1
-
-
Disconnecting existing electric panel (Indoor or Outdoor type) and replacing the following unserviceable accessories with new accessories including making incoming / outgoing electric connections with & including copper wire of suitable size complete all as specified and directed by Engineer-in-Charge:-
-
-
-
MCCB rating 250 Amps, FP, breaking capacity 36 kA
2
-
-
MCCB rating 200 Amps, FP, breaking capacity 36 kA
2
-
-
MCCB rating 160 Amps, FP, breaking capacity 36 kA
3
-
-
MCCB rating 125 Amps, FP, breaking capacity 25 kA
3
-
-
MCCB rating 100 Amps, FP, breaking capacity 25 kA
4
-
-
MCCB rating 63 Amps, FP, breaking capacity 16 kA
4
-
-
MCCB rating 100 Amps, TP, breaking capacity 16 kA
3
-
-
MCCB rating 400 Amps, FP, 36/35kA, 415 Volts, thermal magnitc adjustable type including over load and short circuit protection
1
-
-
Digital Voltmeter of rating 0-500 Volts, square type of size 96mmx96mm
2
-
-
Digital Ammeter of rating 0-600 Amps, square type of size 96mmx96mm
2
-
-
Selector switch rotary type as per existing size and make
3
-
-
LED Indicator assembly (Set of 3) with red / yellow / blue colours
36
-
-
Current transformer (CT) (Set of 3) copper wound ratio 100/5 Amps
3
-
-
Current transformer (CT) (Set of 3) copper wound ratio 200/5 Amps
3
-
-
Disconnection all incoming and outgoing electrical connections from existing indoor LT Panel and dismatling/taking down unserviceable Onload Change Over switch of any of capacity and S&F new Onload Change Over switch of 400 Amps capacity, 415 Volts, 50 Hz, conforming to IEC: 60947-3, with rotating handle and connecting all incoming and outgoing electrical connections to existing indoor LT Panel complete all as specified and directed.
1
-
-
Disconnection all incoming and outgoing electrical connections from existing indoor LT Panel and dismatling/taking down unserviceable Onload Change Over switch of any of capacity and S&F new Onload Change Over switch of 200 Amps capacity, 415 Volts, 50 Hz, conforming to IEC:60947-3, with rotating handle and connecting all incoming and outgoing electrical connection to existing indoor LT Panel complete all as specified and directed.
1
-
-
Removing unserviceable LT line spacer of any description and S&F new rigid PVC spacers suitable for 4 Lines of LT 1100 Volts complete all as specified and directed by Engineer-in-charge.
10
-
-
All as per Sl Item No. 32.00 but line spacer suitable for 3 Lines.
15
-
-
All as per Sl Item No. 32.00 but line spacer suitable for 2 Lines.
20
-
-
Dismantling existing unserviceable earthing of any description and M&L for new earthing with galvanized steel plate electrode of size 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 m below normal ground level with top edge of the earth plate at a depth not less than 1.50 m below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers of 15 cm thickness and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized iron pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6) type C1 in chamber of size not less than 300x300x300mm (internal diamentions), RCC (1:2:4) type B-1, reinforced with 8 mm dia TMT steel bars @ 15 cm c/c both ways for cover with angle iron 40X40X5mm frame etc complete all as specified and directed by Engineer-in-Charge.
Note: The unit rate includes earthing wire and protection pipe upto maximum 7.5 metre from earth plate, earth point / test point and chamber shall be made 0.50 mtr away from the earthing pit.
5
-
-
All as per Sl Item No. 35.00 but earthing with Copper electrode of size 600mmx600mmx3mm thick and copper strip 25mmx3mm thick.
2
-
-
Disconnecting all electrical connections and taking down unserviceable bus-bar chamber of any description and S&F new bus-bar chamber made out of sheet metal enclosure 200 Amps powder coated independent for five connections, copper bus-bar suitable for 200 Amps current rating mounted on wall and connecting to all incoming and outgoing electrical connections complete all as specified and directed by Engineer-in-Charge.
1
-
-
Disconnecting all electrical connections and taking down unserviceable distribution board of any description and S&F new TPN DB - VTPN 4 way, IP 43, IK 09 with 250 Amps bus-bar for independent mounting on wall duly flush mounted complete all as specified and directed.
3
-
-
Taking down unserviceable MCB of any description and S&F new MCB TP 63 Amps, 415 Volts, 'C' curve including all necessary connections complete all as specified and directed by Engineer-in-charge.
3
-
-
Taking down unserviceable MCB of any description and S&F new MCB SP 6 to 32 Amps, 415 Volts, 'C' curve including all necessary connections complete all as specified and directed by Engineer-in-charge.
36
-
-
M&L for preparation of old painted steel and iron surfaces of HT electric pole 11 m long in existing position and applying two coats of aluminium paint on all exposed surfaces including cross arms, brackets etc with and including marking 300mm wide strips / bands 3 Nos with post-office red & navy blue colour paint alternatively starting from top of coping, writing Pole No. with black paint in 2.5 cm high figures inside 3" dia circle complete all as directed by Engineer-in-Charge.
Note :
(i) All necessary safety measures shall be taken by the contractor.
(ii) The cost of necessary scafolding, ladders etc shall be deemed included in quoted rates.
50
-
-
All as per Sl item No. 41.00 but LT electric pole 9 long.
200
-
-
Taking down existing unserviceable junction box of any type and description and S&F new PVC Junction box of size 255x355x122 mm with aluminium bus bars 04 Nos, one No. MCB SP 6 Amps capacity and fixed on pole with the help of MS clamp made of FI 40mmx5mm with nuts & bolts and making hole in existing pole of suitable size to take out connections to fittings (if required at site) including provn of cable glands for incoming and outgoing cables complete all as specified and directed.
50
-
-
Excavation in trenches n.exc. 1.50 m wide and n.exc. 1.50 m in depth in any type of soil for findingout cable fault in underground cables including relaying of sand cushioning & old bricks, returning, filling and levelling with excavated soil after rectification of the fault complete all as specified and directed.
800
-
-
M&L for overhauling of outdoor type LT panel / feeder pillar box of any size & make including insulating to bus bars with shrinkable PVC sleeves of red, yellow, blue and black colours, replacement of worn out / us cables as per existing gauge, door rubber beadings, nuts, bolts washers, hinges, thimbles, lugs, cable glands & welding work etc as required to make functional to the system and testing on load complete all as specified and as directed at site by Engineer-in-Charge.
Note:- Spare parts required for replacement such as MCB or any switch gears etc) shall be measured & paid for separately under respective items of Schedule 'A'.
5
-
-
All as per Srl item No. 45.00 but indoor type LT Panel / feeder box.
2
-
-
M&L for preparing old painted internal & external surfaces of indoor/outdoor type LT panel / feeder pillar box of size not more than 1.8 m height and applying two coats of synthetic enamel paint of approved quality, writing of bus bars & outgoing / incoming locations with white paint upto 2” (50mm) size complete all as specified and directed by Engineerr-in-Charge.
10
-
-
Disconnecting & dismantling old unserviceable LT panel /feeder pillar box with all accessories and S&F new feeder pillar bus-bar box of size 600x450x550mm of outdoor type, double door, both sides openable, locking arrangement, kiosk type, powder coated, 3.15mm thick MS sheet water proof hinged, having 4 Nos aluminium bus-bar of 400 Amps duly colour coded mounted on porcelain insulator with provn of 06 Nos outgoings including MCCB 200 Amps, 4 pole, 36 kA 01 No, LED indicator (RYB), 08 Nos holes in bottom for inlet and outlet cables with suitable size of cable gland and mild steel stand for mounting of panel board made of angle iron of size 50 mm X 50 mm X 6 mm, 1.05 metre high (450mm below ground level and 600mm above ground) grouted in & including cement concrete (1:2:4) type B1 and connecting the panel with earthing complete all as specified and directed by Engineer-in-Charge.
Note:-
(i) Feeder pillar box shall be fabricated from CPRI approved and shall be from approved list of manufaturer only and depth of panel not less than 55 cm.
(ii) Electric connection between MCCB and bus-bar shall be made with aluminium strip links duly colour coded.
2
-
-
Taking down old sub main wiring of any description and S&F new sub main wiring with two runs of single core (FRLS) PVC insulated and unsheathed multistranded, copper conductor cable of size 6.0 Sqmm LT, 1100Volt grade, drawn through and including PVC non metallic conduit of 20mm dia or other appropriate dia with all accessories and fittings and one run of 6.0 Sqmm single core multi stranded copper conductor cable as earth continuity conductor. Two runs of cable one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length, Cable required for connection to DBs shall be deemed to be included in quoted rates and shall not be measured separately complete all as specified and directed. Note :- (i) Two runs of 6.0 Sqmm cable & one run of earth wire and one run of PVC non metallic conduit shall be measured as one run length.
(ii) Cable required for connection to DBs shall be deemed to be included in unit rate and shall not be measured separately. (iii) Earth wire shall run inside the conduit pipe.
(iv) Extra length of cable required for connection to MCBs shall be deemed to be included in unit rate.
100
-
-
M&L for boring horizontal holes under road, pavement, hard standing by trenchless technology using GI Pipe of any dia and necessary machine suitable for 0.4 mpa working pressure complete all as directed by Engineer-in-Charge. Note :- GI pipe shall be measeured and paid for saperately under respective item of Schedule 'A'
30
-
-
Labour only for repairing/ maint of LT over head lines and routine maintenance of electric supply / current leakage / under ground LT cables, checking and removing vegitation growth/trimming branches over and around of LT OH lines, repair / maint of LT feeder pillar boxes, MCCBs / Timer switch, protection devices and other electrical accessories in day to day maintenance and making it serviceable in all respects with & including small length of wires (not more than 50cm) & adhesive cable and other connected minor accessories complete all as directed by Engineer-in-Charge.
1800
-
-
Note:- (a) The contractor's representative will report to Engineer-in-Charge / JE EM I/C Ext Electric Supply with one Electrician and one Helper/Mazdoor daily in forenoon and afternoon to collect routine/urgent works related to Ext Elecctric Supply till completion of the contract. The work shall be attended by the contractor immediately. (b) The contractor will ensure availability of manpower equipped with all sort of petty items such as insulation tape, Jumpers, insulators, nuts, bolts, washers etc required to accomplish the job. The contractor will also ensure availability of every type of requiste T&P and Mobile phone to his trades men. The cost of all these items is deemed to be included in quoted rates.
(c) All routine/urgent jobs recived on job slip will be repaired & got signed by the user's and will be deposited to JE E/M within 24hrs. In case of any delay in attending the complaint more than 24hrs after handing over of routine/urgent works, the contractor shall be liable to pay the penalty of Rs. 250/- per day for each pending complaint.
-
-
-
S&F in replacement LED bulb 45/50 watts suitable for B-22 / E-27 type base, 5700K complete all as specified and directed. Make: Syska Cat Part No. SSK-RB-4501 B22 & E27 BULB or Havells Cat Part No. LED FLORIDA ULTRA 50W or Philips Cat Part No. TFORCE CORE 37W/4000LM B22
40
-
-
S&F in replacement lamp holder B-22 base with & including LED bulb 30/40 watts suitable for B-22 / E27 type base, 5700K, fxed to post-top lantern fittings complete all as specified and directed. Make: Syska Cat Part No. SSK-HPB-40W or Havells Cat Part No. LED FLORIDA ULTRA 30W or Philips Cat Part No. TFORCE CORE 47W/5000LM E-27
60
-
-
Taking down carefully old unserviceable security light fittings from pole and S&F new security light fittings LED 25 watt with secondary lens luminaries IP 66, 5700K with inbuilt surg diverter and all accessories complete all as directed by Engineer-in-Charge. Make : Syska Cat Part No. SSK-SLF-CF-25W-WL or Havells Cat Part No. ENDURAPEARLSL25WLED757SASYTOPCMP or Crompton Cat Part No. TRP-400-25-57-SL-LM-NSR.
20
-
-
Taking down carefully old unserviceable security light fittings from pole and S&F new security light fittings LED 45 watt with secondary lens luminaries IP 66, 5700K, with inbuilt surg diverter and all accessories complete all as directed by Engineer-in-Charge. Make : Syska Cat Part No. SSK-SLF-CF-45W-WL or Havells Cat Part No. ENDURAPEARLNEOSL45WLED757PASYTOPC or Crompton Cat Part No. TRP-409-45-57-SL-NS-GL-NSG.
60
-
-
Taking down carefully old unserviceable security light fittings and S&F new security light fittings suitable for LED 60 watt with lens and all accessories complete all as directed by Engineer-in-Charge. Make: Syska Cat part No. SSK-SLF-CF-60W-WL or Havells Cat Part No. ENDURAPEARLNEOSL60WLED757PASYTOPC or Crompton Cat Part No. TRP-409-60-57-SL-GL-NSG.
50
-
-
Taking down carefully old unserviceable security light fittings and S&F new security light fittings suitable for LED 90 watt with lens and all accessories complete all as directed by Engineer-in-Charge. Make : Syska Cat Part No. SSK-SLF-CF-90W-WL or Havells Cat Part No. ENDURAPEARLPLUSSL90WLED757PASYTOP CASTHO or Crompton Cat Part No. TRP-411-90-57-SL-GL-NSG.
40
-
-
Taking down carefully old unserviceable light fittings and S&F new Flood light fittings suitable for LED 120 watt IP 66 with lens and all accessories complete all as directed by Engineer-in-Charge. Make: Syska Cat Part No. SSK-FLN-120W or Havells Cat Part No. JETAIRISFLS 120WLED757APWBLT G or Crompton Cat Part No. LFLN-120-WW/60-M.
20
-
-
Taking down carefully old unserviceable light fittings and S&F new Flood light fittings suitable for LED 200 watt IP 66 with lens and all accessories complete all as directed by Engineer-in-Charge. Make: Syska Cat Part No. SSK-FLN-200W or Bajaj Cat Part No. BJFL 200W LED I or Crompton Cat Part No. LFLN-200-WW/60-M
9
-
-
Taking down carefully old unserviceable light fittings S&F new LED Highbay light fitting 100 watt capacity with PDC aluminium with reflactor including making electrical connection from ceiling rose to light fitting complete all as directed by Engineer-in-Charge. Make: Syska Cat Part No. SSK-HBG-100W or Havells Cat Part No. SAUCERGENXPROHBP100WLED757P60DBOLT G or Crompton Cat Part No. LHB11-100-CDL/60-HPM.
Note for Item No. 54 to 60:- (i) The quoted rate is deemed to be included for installation of light fitting at any height including High mast lights, Tower lights, Indoor sports complex lights etc. (ii) All necessary T&P, ladders, temporary scaffolding etc and safety equipmentsshall be deemed to included in the quoted rates.
8
-
-
Taking down old unserviceable brackets of any size and description and M&L for new bracket made out of 1.50 m long 40mm dia bore GI tubing, light grade including fixing with 2 Nos MS clamps made out of flat iron 50mmx5mm thick and 4 Nos 12mm dia 75mm long bolts, nuts & flat washer (3mm thick) 01 No for each clamp including two coats of aluminium paint over one coat of red oxide primer to GI pipe, MS clamps & bracket etc complete all as specified and directed.
20
-
-
S&F in replacement three core 1.5 Sqmm PVC Insulated cable with multi stranded copper conductor for making connection from junction box to light fitting with copper lugs of suitable size complete all as specified and directed.
500
-
-
S&F in replacement three core 2.5 Sqmm PVC Insulated cable with multi stranded copper conductor for making connection from junction box to light fitting with copper lugs of suitable size complete all as specified and directed.
200
-
-
Supply only PVC electric cable with insulated aluminium conductor (stranded) with inner sheathing of PVC tape and overall PVC sheathed 1100 volts grade, heavy duty, 6 Sqmm 2 core, weather proof flat with all accessories complete all as specified and directed.
300
-
-
All as per Sl Item No. 64.00 but cable of size 10 Sqmm 2 core.
500
-
-
All as per Sl Item No. 64.00 but cable of size 16 Sqmm 2 core.
200
-
-