Military Engineer Services Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Military Engineer Services - MES Tender
Paints and Enamels
Electrical and Electronics
Electrical Works
Eprocure
Opening Date2 Jan 2024
Closing Date5 Feb 2024
Tender Amount₹ 39,80,000
Costs
EMD
₹ 79,600Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_635485_1Bid Award Id
ViewTender No
CWE(AF)/CHK/EM/T-28 OF 2023-24Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Spring charging motor 24/240 Volt DC/AC for 11KV VCB, Bus Coupler of existing make, type, size & capacity with driving gear suitable for existing VCBs model complete all as specified and directed at site.
5
-
-
Spring charging motor 110/220 Volt DC/AC for 33KV VCB/SF-6 breaker of existing make, type, size & capacity complete all as specified and directed at site.
3
-
-
Spring charging motor 30/240 Volt DC/AC for 11KV & 33KV VCB of existing make, type, size & capacity complete suitable for existing VCBs complete all as specified and directed at site.
12
-
-
Open/Close auxiliary contacts switch suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
25
-
-
Plug-Socket connectors of electrical accessories suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
15
-
-
Door locking handle suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
20
-
-
Trolly alignment lever suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
20
-
-
Under voltage release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
15
-
-
Over voltage release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
15
-
-
Under/over frequency release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample.
10
-
-
Shunt trip closing coil assembly 110/220 volts, DC/AC. Make/Type- As per existing sample.
35
-
-
Shunt trip tripping coil assembly 110/220 volts, DC/AC. Make/Type- As per existing sample.
35
-
-
Shunt trip closing coil assembly 24-30/220 volts, DC/AC. Make/Type- As per existing sample.
30
-
-
Shunt trip tripping coil assembly 24-30/220 volts, DC/AC. Make/Type- As per existing sample.
30
-
-
Series trip coil 24-30/220 volts, DC/AC. Make/Type- As per existing sample.
15
-
-
Spring charging Motor Cut of switch. Make/Type- As per existing sample.
25
-
-
Ratchet wheel Assembly (small, large & middle gear assy). Make/Type- As per existing sample.
15
-
-
Manual spring charging gear assembly complete. Make/Type- As per existing sample.
15
-
-
Breaker IN/OUT handle. Make/Type- As per existing sample.
10
-
-
Local remote switch. Make/Type- As per existing sample.
10
-
-
Test/service position indicator. Make/Type- As per existing sample.
10
-
-
Breaker control switch. Make/Type- As per existing sample.
15
-
-
Mechanism charged/discharge indicator switch. Make/Type- As per existing sample.
15
-
-
Toggle ON/OFF switch for Heater & illumination circuit. Make/Type- As per existing sample.
20
-
-
Mechanical ON/OFF indication.
10
-
-
Door switch. Make/Type- As per existing sample.
20
-
-
Auto/Manual selection switch. Make/Type- As per existing sample.
12
-
-
Push button. Make/Type- As per existing sample.
25
-
-
ON/OFF Emergency trip push button. Make/Type- As per existing sample.
10
-
-
Indicator lamp LED type complete with holder to read RYB with necessary wiring complete.
25
-
-
Operation counter. Make/Type- As per existing sample.
10
-
-
Selector switch for voltmeter- 4 position (RY-YB-BR-OFF), 3 ways.
15
-
-
TNC control switch with pistol grip.
12
-
-
Spring charging handle.
6
-
-
VCB operating handle.
5
-
-
Terminal connectors.
25
-
-
Annunciator, 4 Window with existing dimension on panel for OC/EF/WTI/OTI/ Bucholz trip, with inbuilt PB of mute, ACK, Reset, Accept.
5
-
-
Master relay operating voltage 24V/110V DC or as per sample complete all as directed.
10
-
-
Spacer Heater. Make/Type- As per existing sample.
30
-
-
Thermostate 30-90 Deg.
30
-
-
Hooters. Make/Type- As per existing sample.
10
-
-
Terminal Block for CT wire.
20
-
-
Terminal Block for Remote feedback/within panel/board wire
20
-
-
NO/NC Contacts.
25
-
-
Bridge rectifier.
20
-
-
Auxiliary switch 7NO + 7NC.
10
-
-
"ZZ" micro switch.
10
-
-
Butterfly switch for motor cut off.
15
-
-
Motor cut off switch (Cherry).
15
-
-
Timer for spring charging motor.
20
-
-
Drive link assembly with adjuster.
10
-
-
Big cam with main shaft with bearing & cover.
5
-
-
Trip /Close shaft assembly with springs & closing strips.
15
-
-
11KV, VCB Fixed contact suitable for 400Amp capacity. Make/Type- As per existing sample.
10
-
-
11KV, VCB moving contact suitable for 400Amp capacity. Make/Type- As per existing sample.
10
-
-
11KV, VCB Fixed contact suitable for 630Amp capacity. Make/Type- As per existing sample.
15
-
-
11KV, VCB moving contact suitable for 630Amp capacity. Make/Type- As per existing sample.
15
-
-
11KV, VCB Fixed contact suitable for 800Amp capacity. Make/Type- As per existing sample.
9
-
-
11KV, VCB moving contact suitable for 800Amp capacity. Make/Type- As per existing sample.
7
-
-
Spring for trip lever. Make/Type- As per existing sample.
20
-
-
Spout insulator incl hardware suitable for 11KV VCB of various capacity.
15
-
-
Spur gear of sizes as per sample suitable for upward or downward trolly movement mechanism with lock and bushing as required for 11KV VCB/OCB/bus coupler complete all as specified and directed by Engr-in-charge.
10
-
-
Trip shackle lever. Make/Type- As per existing sample.
10
-
-
Ratchet Pin suitable for HT VCB (As per sample) complete all as directed.
20
-
-
Insulated dust proof cover frame. Make/Type- As per existing sample.
10
-
-
Push Rod. Make/Type- As per existing sample.
10
-
-
Under voltage release mechanical override. Make/Type- As per existing sample.
6
-
-
Opening solenoid (MO3) device. Make/Type- As per existing sample.
5
-
-
Rack in out mechanical rod with handle. Make/Type- As per existing sample.
5
-
-
Trip Prop block Assy. Make/Type- As per existing sample.
6
-
-
Fuses holder suitable for cylindrical/DIN fuse.
20
-
-
HRC fuse (link type) having capacity 2 to 6 amp, 415 V, 80 KA.
15
-
-
HRC fuse (link type) having capacity 10 to 32 amp, 415 V, 80 KA.
15
-
-
11 KV, VCB, PT fuse 3.15 Amp complete as per sample.
15
-
-
Stud type terminals of 24V/110V DC suitable for 11KV VCB.
30
-
-
Antipumping Contactor 4NO+4NC, 24V/110V DC, 6 Amp.
30
-
-
Auxilary contactor for contact multiplication 4NO+4NC, 24V/110V, DC, 6 Amp.
12
-
-
Single Phase (red-Blue) busbar spout suitable for 400 amp to 1250 amps VCB including testing complete.Make and size - As per existing sample.
20
-
-
Single Phase (Yellow) busbar spout suitable for 400 amp to 1250 amps VCB including testing complete.Make and size - As per existing sample.
10
-
-
Testing and calibration of HT VCB 11 KV complete with primary and secondary test as required including checking of wiring of all electrical measuring instrument and resetting of relay and proper alignment mechanical system for smooth functioning and tripping at any type of fault developed in feeders complete all as specified and directed by Engr in Charge. Note :- Contractor will submit primary and secondary test record at the time of caliberation of HT OCB , VCB, SF-6 based panel, TR control panel by current injecting kit duly signed to Engineer In Charge. The rate quoted by tender shall deemed to include the cost of this provision incl T&P required for injecting regulated high current, HT megger and other sundary items as required in complaince with relevent IS/IEC codes complete all as directed.
30
-
-
S&F Vaccum interrupter bottle for vaccum circuit breaker of 400 Amps in HT panel 11000 volts grade incl taking out old interruter complete all as directed. Make : L&T/ABB/CG/Areva
3
-
-
All as per Srl item No 5.00 above but 630 Amps capacity.
6
-
-
All as per Srl item No 5.00 above but 800 Amps capacity.
6
-
-
S&F in replacement of indicators flush mounted, high intensity, clustered LED type, insulated from 30/220 V, DC/AC supply with appropriate coloured lens (Red, Green, Blue, Amber, White) complete all as specified and directed by Engr-in-Charge.
100
-
-
S&F in replacement Digital Multifuction meter (LCD) 3ph, 3W, IPM 110 V (L-L) 5A, Class 0.5 FM , Flush mounting 96x96mm CT/PT side programmable, Parameters - V, A, F, PF,kW, kVA, kVAR, kWh, Kvah and kVARh, THD, phase angles or power demand etc including fixing arrangment nuts,bolts, washers Hylem sheet, as required at site complete testing all as specified and directed. Make- L&T/ Schneider/ Siemens or equivalent as per Appx 'B' of Particular Specifications.
10
-
-
S & F in replacement MCB single pole 6 to 10 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed by Engr-in-Charge Make : Legrand/L&T/Siemens or equivalent as per Appx 'B' of Particular Specifications.
10
-
-
S & F in replacement of HT VCB Aluminium alloy bus bar air insulated, appropriate size and length with 11KV grade Polipro power line protector (sleeve) for designed to insulate bare busbar to prevent accidents due to electrocution/ ionisation. The protector should have excellent UV resistance, abrasion resistance, fire resistance properties, good dieelectric strength & maintenance free complete all as directed by Engr-in-Charge.
30
-
-
S&F in replacement of Bus Support insulators, non hygroscopic, track-resistant, high strength epoxy insulators complete all as specified and directed.
50
-
-
S & F in replacement of lugs, tinned copper, pre-insulated fork and pin type as applicable complete all as directed by Engr-in-Charge.
35
-
-
Supply, installation, testing and commissioning in replacement of 11KV Current Transformer with Indoor & Resin cast type single pole (Three core type) CTR-300-200/5+5A, STR - 18.4kA/1Sec, Class - 15VA/CL1.0+15VA/5P10 fixing on existing 11 KV panel including necessary connections, any modification required, addition/alteration required for fixing CT in existing 11 KV panel complete all as specified and as directed by Engr-in-Charge.
7
-
-
All as per Srl item No 14 above but CTR-200-100/5+5A, STR - 18.4kA/1Sec.
6
-
-
All as per Srl item No 14 above but CTR-100-80/5+5A, STR - 18.4kA/1Sec.
5
-
-
Supply, installation, testing and commissioning in replacement PT unit 3PH, Drawout type, VTR - 11000/110V AC, BA- 100VA/CL0.5 of breaker in VCB make Crompton for model- ALA/XLU including complete dismentling the complete voltage transformer from VCB including, nut bolts, washers, re-assembling the complete parts, complete testing for smooth operation, complete all as specified and as directed by Engr-in-Charge.
2
-
-
S & F in replacement of unsv defective protective relays with Digital protective Relay - 3 OC + 1 Earth fault 3 phase over current and earth fault (2 NO + 2 NC output contact) with high set, CT rating 5A, field selectable 20-110V, including addition/alteration including testing,calibration of relays and replaced control wring as required at site. Make- L&T - MC61AnX/ CGI14N or equivalent as per Appx 'B' of Particular Specifications.
12
-
-
S&F in replacement of float cum boost battery charger bank with panel made of 2mm CRCA sheet complete with maintenance free battery bank mounted on MS rack and provide with connector lead etc complete in respect with installed capacity 30 volt DC 15 Nos 2 volts 60Ah battery (Make Exide) including booster charger all as per standard specification and including DCDB for charger complete with DC Amps Meter Volt meter, switches ON/OFF, TRICKEL/BOOSTER complete all as specified and directed by Engr-in-Charge.
2
-
-
S&F in replacement of Batteries 12V of 150 AH maintenance free dry type (Make Exide) for booster battery charger including connection complete all as specified and directed.
4
-
-
M&L for wiring from battery charger to all connected 11KV VCB with 2.5 sqmm, 1100 volt grade multi strand flexible copper conducters and shall be properly bunched, tied, ferruled for proper indication and crimped with adequate size/types of lugs after wiring testing complete all as specified and directed.
225
-
-
Material and Labour for painting of HT switch gears VCBs outer surface and inner surface complete with synthetic enamel paint two coats by spray painting approved colour after cleaning of surface/rusted portion including sign writing i.e. MES/SM No Make/ Capacity 11000 Volts" and DANGER" including formation of Bone and Skull of appropriate size etc. complete all as directed by the Engineer-in-Charge.
50
-
-
Supply and fix in replacement Power Pack for 11 KV VCB suitable for incoming supply 220/30 volts AC/DC supply and output 30 volts DC supply all as per existing with wiring all connected VCB complete all as directed by Engr-in-Charge. Note : Battery backup of Power Pack shall be not less than 45 minute.
10
-
-
S&F PVC insulated and PVC sheathed cable galvanised steel stip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 Sqmm 12 core 1100 volt grade incl taking out old cable of any size and type complete all as directed.
100
-
-
All as per item No 24.00 here in before but 1.5 Sqmm 8 core 1100 volts grade.
50
-
-
S&F in repair GI nuts, bolts, off sizes complete with 3mm thick washers as per site requirement.
6
-
-
S & F in replacement of HT VCB copper alloy bus bar air insulated, appropriate size and length with 11KV grade Polipro power line protector (sleeve) for designed to insulate bare busbar to prevent accidents due to electrocution/ ionisation. The protector should have excellent UV resistance, abrasion resistance, fire resistance properties, good dieelectric strength & maintenance free complete all as directed by Engr-in-Charge.
50
-
-
S & F in replacement of 33KV single phase out door oil cooled CT of ratio 300/150 + 5 amps class 1.0 - 5P 10 burden 15 VA insulation level 70KV/170 KV as per IS : 2705.
2
-
-
Supply and fixing cable jointing kit termination outdoor type for HT 33KV grade cable for end termination joint complete with jointing material (Heat shrink type) and accessories suitable for XLPE armoured aluminium conductor cable of size 300 Sqmm, 3 core and testing after jointing complete. Make :- Reychem/ Denson or equivalent as per Appx 'B' of Particular Specifications.
4
-
-
M&L for detection of fault through fault locating high voltage mobile machine to locate the fault in 33/11 KV HT cable by giving high voltage surge and to find out exact location of fault all as directed by the Engineer-in-Charge at site. (Note : The Item includes transportation, charging machine upto detecting fault at a time)
10
-
-
S&F heat shrinkable straight through cable joint kit for XLPE (earthed) 11KV volt grade of size 120 to 185 Sqmm 3 core aluminium conductor cable complete incl taking out old jointing kit of any make and type all as specified and directed. Make :- Reychem/ Denson or equivalent as per Appx 'B' of Particular Specifications.
5
-
-
Supply and fixing cable jointing kit termination indoor type for HT 11KV grade cable for end termination joint complete with jointing material (Heat shrink type) and accessories suitable for XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm, 3 core cable and testing after jointing complete. Make :- Reychem/ Denson or equivalent as per Appx 'B' of Particular Specifications.
30
-
-
M&L for testing of 11KV cast rasin indoor type CT of any type and size with the help of high voltage testing kit complete all as directed by Engr-in-Charge.
15
-
-
Taking down/dismantling of CT from the VCB. Scraping, cleaning and preparation of old surfaces of the CT complete and M&L for coating "H" class insulation on the CT. After coating testing and reassembling complete all as directed by Engr-in-Charge.
10
-
-
Labour only for checking the serviceability of VCB/OCB/ACB/CT/PT panels or any connected electrical switch gear at 11 KV voltage level of any capacity including disconnecting HT/LT supply from any VCB & ACB if needed and testing of different spares / components / parts of panels of any description and in any position, checking functioning of relay, coils, switches, ratchet wheel assy, chrging motor, fuses contactors, MCCBs etc and their replacement if found to be unserviceable, regular cleaning of dust & dirt deposit due to natural effects, removal of carbon deposits it any or as direction of Engr-in-Charge. Replacement of un-serviceable/ damaged /broken part(s) either in single or in combination, re-assembling the panels and making the serviceable, fixing the VCB/ACB in position, connecting to electric supply and its testing on installation complete all as specified and directed by Engineer-in-Charge.
70
-
-
NOTE FOR ITEM NO 1.00 TO 35.00:- The above schedule is meant for maintenance of HV panels of AFS Kanpur. The contractor shall depute his representative to Engineer -in-charge or his representative (JE incharge of the contract) on daily basis to collect the complaints. There after contractor shall deploy sufficient manpower to attend the complaints on daily basis. The contractor shall arrange his resources accordingly. Non -compliance of the above on account of contractor's representative to Engineer incharge/JE or deployment of in-sufficient manpower to attend the complaints shall be bound to a penalty of Rs 1000/- per complaint per day after 02 Hrs of communication of complaint by any mode of communication (via SMS, telephone call, what's app etc to contractor/contractors rep) upto a max. of Rs 10000/- per day. Contractor must also mobilise/procure/arrange all tools & machinery like megger, earthing rod, protective gear, test lamp etc for expeditions & safe working compulsary.
-
-
-