Military Engineer Services Tender

If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date12 Jul 2024
Closing Date12 Sep 2024
Tender Amount₹ 48,59,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
One 2/3 pin 5 Amps socket outlet point on same board controlled by one switch.

145

-

-

... More
One 2/3 pin 5 Amps socket outlet point on independent board controlled by one switch.

150

-

-

... More
One bell point controlled by one way independent switch.

4

-

-

... More
All as per above item No 2 here in before but point wiring for 3/5 pin 16/20 Amps socket outlet independent using 2.5 Sqmm copper cable FRLSH for phase and neutral and 2.5 Sqmm as earth wire complete all as specified and directed.

75

-

-

... More
Supply and fixing modular switch, one way 10 Amps 1 module ISI marked 240 volts 50 Hz complete all as specified and directed.

977

-

-

... More
Supply and fixing modular switch, one way 20 Amps with LED indicator 1 module ISI marked 240 volts 50 Hz complete all as specified and directed.

75

-

-

... More
Supply and fixing modular 2/3 pin 10 Amp socket outlet 2 module ISI marked 240 volts 50 Hz complete all as specified and directed.

295

-

-

... More
Supply and fixing modular socket outlet 16/20 Amp 3/5 pin , 2 module ISI marked 240 volts 50 Hz complete all as specified and directed.

75

-

-

... More
Supply and fixing modular Fan step regulator 120W, 2 module ISI marked 240 volts 50 Hz complete all as specified and directed.

302

-

-

... More
Supply and fixing Metal flush mounting box of 1/2 Module complete all as specified and as directed.

20

-

-

... More
Supply and fixing Metal flush mounting box of 3 Module complete all as specified and as directed.

187

-

-

... More
Supply and fixing Metal flush mounting box of 4 Module complete all as specified and as directed.

90

-

-

... More
Supply and fixing Metal flush mounting box of 6 Module complete all as specified and as directed.

15

-

-

... More
Supply and fixing Metal flush mounting box of 8 Module complete all as specified and as directed.

70

-

-

... More
Supply and fixing Metal flush mounting box of 12 Module complete all as specified and as directed.

65

-

-

... More
Supply and fixing white colour blanking plate, one module complete all as specified and directed.

50

-

-

... More
Supply and fixing white colour cover plate with frame 2 module complete all as specified and directed.

20

-

-

... More
Supply and fixing white colour cover plate with frame 3 module complete all as specified and directed.

187

-

-

... More
Supply and fixing white colour cover plate with frame 4 module complete all as specified and directed.

90

-

-

... More
Supply and fixing white colour cover plate with frame 6 module complete all as specified and directed.

15

-

-

... More
Supply and fixing white colour cover plate with frame 8 module complete all as specified and directed.

70

-

-

... More
Supply and fixing white colour cover plate with frame 12 module complete all as specified and directed.Note applicable for item no 4 to 21- The colour of modular accessories shall be approved by AGE(I) in writing

65

-

-

... More
Supply and fixing ceiling rose surface type 65 mm x 50 mm, 2 to 3 terminal complete all as specified and directed.

682

-

-

... More
Material and labour for sub main wiring with Two runs of single core PVC FRLSH IS-694 cable with colour code unsheathed multi-stranded copper conductor of size 6 Sqmm and drawing through in concelead rigid non metallic PVC conduit pipe 20 mm dia medium grade heavy duty with all necessary fittings including one run of FRLSH insulated unsheathed stranded copper conductor cable of size 6 Sqmm as earth wire (green in colour) and connected to common earth dolly complete including taking down of old unserviceable sub main wiring complete all as specified and as directed. Note : (i) Three run of 6 sqmm cable and one run of PVC conduit pipe shall be measured against one unit. (ii) Cost of cutting /chasing/ plastering /colouring etc to match with disturbed surface shall deemed to be included in the quoted rate.(iii) Extra length of cable required for connection to DBs/MCBs shall deem to be included in unit rate quoted by contractor against the item (iv) Earth wire shall run inside the PVC conduit.

600

-

-

... More
Supply and fixing LED tube light fitting pre coated CRCA body heavy duty Industrial Batten with frame, driver etc in 20 W, 4 feet long including LED tube rod 20 watt self ballasted retrofit lamps with thermoplastic body 270 degree wide distribution CCT 6500 K white colour fixed on surface of wall / beam/ceiling etc incl making all electric connection using three core copper flexible cable white of size 23/0.0076 including taking down old unsv fitting complete as directed.

380

-

-

... More
Supply and fixing LED miror light fitting 8 Watt self ballasted LED batten, extruded thermoplastic body with PC diffuser in square shape, beam angle 120 degree wide distribution 3000 K with frame, driver etc fixed on surface of wall / beam/ceiling etc incl making all electric connection using three core copper flexible cable white of size 23/0.0076 including taking down old unsv fitting complete as directed.

10

-

-

... More
Taking down unserviceable main switches, DBs, bus bars chambers including all fittings and fixtures etc complete from existing main boards and removing from site all complete all as directed.

62

-

-

... More
Supply and fix sheet metal enclosure distribution board TPN, 4 poles ,double door, 4 way with 160 Amps rated copper bus bar vertical type including MCCB 4 pole 63 Amps 415 volts thermal magnetic base operated 16 KA as incomer with neutral link and maufacturer by OEM incl concealed in surface of wall and making all connection using gland , thimbles in required size complete all as specified and directed. Note : Cost of cutting /chasing/ plastering /colouring etc to match with disturbed surface shall deemed to be included in the quoted rate.

12

-

-

... More
Supply and fix sheet metal enclosure for MCB distribution board SPN, double door, 8 way with 200 Amp rated copper bus bar 230/240 Volts concealed in the surface of wall and making all connection using gland , thimbles in required size complete all as specified and directed. Note : Cost of cutting /chasing/ plastering /colouring etc to match with disturbed surface shall deemed to be included in the quoted rate.

10

-

-

... More
Supply and fix sheet metal enclosure for MCB distribution board SPN, double door, 6 way with 200 Amp rated copper bus bar 230/240 Volts concealed in the surface of wall and making all connection using gland , thimbles in required size complete all as specified and directed. Note : Cost of cutting /chasing/ plastering /colouring etc to match with disturbed surface shall deemed to be included in the quoted rate.

40

-

-

... More
Supply and fixing MCB , SPN 230/240 volts , 25-32 Amps , "C" Curve 10 KA complete all as specified and directed.

45

-

-

... More
Supply and fixing MCB , single pole 230/240 volts , 6-32 Amps , "C" Curve 10 KA complete all as specified and directed.

225

-

-

... More
Supply and fixing MCB , single pole 230/240 volts , 40-63 Amps , "C" Curve 10 KA complete all as specified and directed.

30

-

-

... More
M&L in replacement earthing complete with galvanized steel earth plate 600 x600 x 6 mm thick, buried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtrs below normal ground level, connected to galvanized GI wire 4 mm dia as earthing lead by means of bolts, nuts, check nuts & washers of galvanized iron or steel besides building at all joints including excavation and earth work, GI pipe light grade 40 mm bore for protection of GI strip from earth electrode and 15 MM as watering with wiremesh funnel charcoal dust, common salt, PCC (1:2:4) type B-1 using 20 MM graded stone aggregate for chamber and MS angle iron frame 40 x 40 x 3 MM and RCC cover 40 MM thick (1:2:4) type B-1 using 20 MM graded stone aggregate reinforced with 6 MM dia round bars @ 75 MM C/C both ways with MS handle 12 MM dia , PGI funnel and wire mesh , 20 MM bore GI Pipe light grade for watering complete all as shown in electrical plate No 3 of SSR Part-I (2010) and connected to earth test point including testing complete all as specified and directed. Note : Quoted rates shall be deemed to include the cost of GI wire upto 20.0 Mtr and required earth work..

6

-

-

... More
Material and labour for sub main wiring with two runs of single core PVC FRLSH IS-694 cable with colour code unsheathed multi-stranded copper conductor of size 10 Sqmm and drawing through in concelead rigid non metallic PVC conduit pipe 25 mm dia medium grade heavy duty with all necessary fittings including one run of FRLSH insulated unsheathed stranded copper conductor cable of size 10 Sqmm as earth wire (green in colour) and connected to common earth dolly complete including taking down of old unserviceable sub main wiring complete all as specified and as directed. Note : (i) Three run of 10 sqmm cable and one run of PVC conduit pipe shall be measured against one unit. (ii) Cost of cutting /chasing/ plastering /colouring etc to match with disturbed surface shall deemed to be included in the quoted rate.(iii) Extra length of cable required for connection to DBs/MCBs shall deem to be included in unit rate quoted by contractor against the item (iv) Earth wire shall run inside the PVC conduit.

250

-

-

... More
S&F in repair recess mounted LED fitting 40 watt LED luminiare size 2' x 2' with CRCA housing in white powder finish, high translucent PMMA diffuser provides soft glare free light suitable for surface/recess mounted openable cleanroom luminiare with IP 65 including LED 40 watt with all accessories, pre-wired connecting up complete with using three core copper flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-Charge.

20

-

-

... More
S&F in repair recess mounted LED downlight size 1' x 1' square shape capacity 18 watt with PDC aluminium body and high transmittance diffuser suitable for surface/recess mounted openable cleanroom luminiare with IP 65 including LED 18 watt complete with all accessories and connecting up with using three core copper flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-Charge.

10

-

-

... More
S & F in repair single pole and neutral enclosure with a two pin and earth plug and socket (MODULAR AC BOX) 4 module in sheet steel complete with single pole MCB 25 Amps 10 KA fixed properly on in concealed position all as directed by Engineer-in-Charge.

15

-

-

... More
Taking down old unsv ceiling fan/Exhaust fan, sealing cable end, dismantling blades and removing fan and blades and deposit to KV School store store yard. Note : Contractor should be deposit the handed over voucher to Engr-in-charge.

240

-

-

... More
Supply and fixing ceiling fan 1200 mm BLDC type, 5 star rated, with regulator enable motor power input 27 watt with 10% tolerance, motor insulation B type , 240 Volt, 50 Hz, speed 350 rpm, 230 CMM air delivery, service value minimium 8.1 with complete 3 blade, canopy, down rod, shackle, fan fixing clamp, with all accessories including Nuts, bolts, washer required with all accessories including connecting the same to ceiling rose with using flexible copper conductor 23/0.0076 complete all as specified and as directed. Note : Contractor shall be quote the rate inclusive of hanging clamp suitable for 40 mm GI pipe.

290

-

-

... More
Supply and fixing exhaust fan 300 mm sweep steel body heavy duty with louver mounting bracket ISI marked BEE 4 star rated energy saving less noise capacitor type including plastering, colour coating etc and all site required work for disturbed surface matching with existing and making electric connection using three core flexible copper conductor 23/0.0076 cable complete all as directed.

12

-

-

... More
Supply and fixing wall mounted fan heavy duty 300 mm sweep non capacitor bracket mounted type copper wound motor ISI marked BEE 4 star rated energy saving with fixing accessories complete making necessary electric connection complete all as directed.

6

-

-

... More
Supply and fixing modular bell switch, one way 10 Amps 1 way module complete all as specified and directed.

4

-

-

... More
Supply and fixing bell multi music AC 240 volts, single pole complete all as specified and directed.

4

-

-

... More
Excavation in trenches in soft/loose soil not exceeding 1.50 m wide and not exceeding 1.50 m in depth for laying of cables and getting out including trimming of sides complete all as specified and directed.

240

-

-

... More
Returing, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25 cm thick each layer compete all as specified and directed.

136

-

-

... More
Removal of surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.50 m above the starting point complete all as specified and directed.

104

-

-

... More
Material and labour for sand cushioning with a layer of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. Note: Punned thickness shall be measured for payment.

72

-

-

... More
Supply and laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other for cable protection complete all as specified and directed.

8

-

-

... More
Material & labour for cutting /boring to plinth protection/ hard standing / road etc in suitable depth to across the GI pipe size upto 80 mm dia of bore for drawn through XLPE under ground cable for giving mechanical protection to cable complete all as directed. (Note : Quoted rate shall include the cost of required material for repairing to disturbed surface complete all as per existing site and all as directed by Engineer-in-charge.

20

-

-

... More
Supply and laying 80 mm bore galvanized steel tubing "light grade" with all fittings,clamps, bolts, nuts and washers (ISI Marked) and fixing to the pole complete with all fittings, laid in trenches/fixed complete to wall and ceiling or laid in floors complete all as specified and directed.

40

-

-

... More
Supply, laying, jointing and testing underground cable of size 95 Sqmm 3.5 core, 1100 volts grade, XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with multi-stranded aluminium conductor laid in trenches, passing through pipe, ducts and making electrical connection with including suitable size lugs proper crimped by crimping tool, thimbles, glands, GI Nuts and bolts, washers, insulation tape etc complete all as specified and directed. Note: Excavation and earthwork, sand cushioning and bricks will be measured and paid separately under respective items.

230

-

-

... More
Supply, laying, jointing and testing underground cable of size 70 Sqmm 3.5 core, 1100 volts grade, XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with multi-stranded aluminium conductor laid in trenches, passing through pipe, ducts and making electrical connection with including suitable size lugs proper crimped by crimping tool, thimbles, glands, GI Nuts and bolts, washers, insulation tape etc complete all as specified and directed. Note: Excavation and earthwork, sand cushioning and bricks will be measured and paid separately under respective items .

240

-

-

... More
Supply, laying, jointing and testing underground cable of size 25 Sqmm 3.5 core, 1100 volts grade, XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with multi-stranded aluminium conductor laid in trenches, passing through pipe, ducts and making electrical connection with including suitable size lugs proper crimped by crimping tool, thimbles, glands, GI Nuts and bolts, washers, insulation tape etc complete all as specified and directed. Note: Excavation and earthwork, sand cushioning and bricks will be measured and paid separately under respective items .

430

-

-

... More
Supply, laying, jointing and testing underground cable of size 16 Sqmm 4 core, 1100 volts grade, XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with multi-stranded aluminium conductor laid in trenches, passing through pipe, ducts and making electrical connection with including suitable size lugs proper crimped by crimping tool, thimbles, glands, GI Nuts and bolts, washers, insulation tape etc complete all as specified and directed. Note: Excavation and earthwork, sand cushioning and bricks will be measured and paid separately under respective items.

550

-

-

... More
Supply, laying, jointing and testing underground cable of size 6 Sqmm 4 core, 1100 volts grade, XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with multi-stranded aluminium conductor laid in trenches, passing through pipe, ducts and making electrical connection with including suitable size lugs proper crimped by crimping tool, thimbles, glands, GI Nuts and bolts, washers, insulation tape etc complete all as specified and directed. Note: Excavation and earthwork, sand cushioning and bricks will be measured and paid separately under respective items .

300

-

-

... More
Supply, install, testing and commissioning of LT panel size 110 cm x 100 cm x 40 cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement incl inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired complete duly powder coated with comprising of the following :- INCOMING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 250 Amp ,415 Volt,35 KA, 4 pole Rated Ultimate Short circuit Breaking Capacity Ics 75%, at 415 V (kA rms) Vac (kA rms), frame AN type,Confirms to IS/IEC60947-2 -01 No (ii) Phase indicating lamp LED type with HRC fuse – 1 Set of three. (iii) ON/OFF indicating lamp on incomer feeder for status of feeder = 02 Nos (iv) Digital volt meter AC 0 to 500 volts with inbuilt selector switch duly provided with suitable size of copper insulated wire with universal coloured code of size 96x96mm-01No (v) Digital Amp meter AC up to 630 Amp with inbuilt selector switch and CT’s duly prewired with suitable size of copper insulated wire with universal colour code of size 96x96mm – 01 No. (vi) Aluminium bus bar 400 Amps capacity of suitable length insulated heavy heat shrinkable sleeves etc -04 Nos.

1

-

-

... More
OUTGOING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 200 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 35 KA, Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 01 Nos (ii) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 160 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 25 KA Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 03 Nos

-

-

-

... More
Supply, install, testing and commissioning of LT panel size 120 cm x 100 cm x 40 cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement incl inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired complete duly powder coated with comprising of the following :- INCOMING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 200 Amp ,415 Volt,35 KA, 4 pole Rated Ultimate Short circuit Breaking Capacity Ics 75%, at 415 V (kA rms) Vac (kA rms), frame AN type,Confirms to IS/IEC60947-2 -01 No (ii) S&F On load change over switch capacity 200 Amp, 4 pole, 415 V, , Size FR4, Type CO4-400, site convertible fuse version with open execution (Confirm to IEC 60947-3, IS/IEC 60947-3) complete terminal shrouds, source separator and phase gland box, Phase barriers, Handle with door interlock kit, with all fixing accessories suitable for horizontal as well as vertical mounting complete all as directed by Engr-in-Charge-01 no (iii) Phase indicating lamp LED type with HRC fuse – 1 Set of three. (iv) ON/OFF indicating lamp on incomer feeder for status of feeder = 02 Nos (v) Digital volt meter AC 0 to 500 volts with inbuilt selector switch duly provided with suitable size of copper insulated wire with universal coloured code of size 96x96mm-01No (vi) Digital Amp meter AC up to 630 Amp with inbuilt selector switch and CT’s duly prewired with suitable size of copper insulated wire with universal colour code of size 96x96mm – 01 No. (vii) Aluminium bus bar 400 Amps capacity of suitable length insulated heavy heat shrinkable sleeves etc -04 Nos.

1

-

-

... More
OUTGOING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 100 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 25 KA Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 02 Nos (ii) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 63 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 25 KA Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 02 Nos

-

-

-

... More
Supply, install, testing and commissioning of LT panel size 120 cm x 100 cm x 40 cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement incl inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired complete duly powder coated with comprising of the following :- INCOMING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 160 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short circuit Breaking Capacity Ics 75%, at 415 V (kA rms) Vac (kA rms), frame AN type,Confirms to IS/IEC60947-2 -01 No (ii) S&F On load change over switch capacity 160 Amp, 4 pole, 415 V, , Size FR4, Type CO4-400, site convertible fuse version with open execution (Confirm to IEC 60947-3, IS/IEC 60947-3) complete terminal shrouds, source separator and phase gland box, Phase barriers, Handle with door interlock kit, with all fixing accessories suitable for horizontal as well as vertical mounting complete all as directed by Engr-in-Charge-01 no (iii) Phase indicating lamp LED type with HRC fuse – 1 Set of three. (iv) ON/OFF indicating lamp on incomer feeder for status of feeder = 02 Nos (v) Digital volt meter AC 0 to 500 volts with inbuilt selector switch duly provided with suitable size of copper insulated wire with universal coloured code of size 96x96mm-01No (vi) Digital Amp meter AC up to 630 Amp with inbuilt selector switch and CT’s duly prewired with suitable size of copper insulated wire with universal colour code of size 96x96mm – 01 No. (vii) Aluminium bus bar 400 Amps capacity of suitable length insulated heavy heat shrinkable sleeves etc -04 Nos.

1

-

-

... More
OUTGOING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 63 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 25 KA Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 04 Nos

-

-

-

... More
Supply, install, testing and commissioning of LT panel size 120 cm x 100 cm x 40 cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement incl inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired complete duly powder coated with comprising of the following :- INCOMING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 160 Amp ,415 Volt,25 KA, 4 pole Rated Ultimate Short circuit Breaking Capacity Ics 75%, at 415 V (kA rms) Vac (kA rms), frame AN type,Confirms to IS/IEC60947-2 -01 No (ii) Phase indicating lamp LED type with HRC fuse – 1 Set of three. (iii) ON/OFF indicating lamp on incomer feeder for status of feeder = 02 Nos (iv) Digital volt meter AC 0 to 500 volts with inbuilt selector switch duly provided with suitable size of copper insulated wire with universal coloured code of size 96x96mm-01No (i) Digital Amp meter AC up to 630 Amp with inbuilt selector switch and CT’s duly prewired with suitable size of copper insulated wire with universal colour code of size 96x96mm – 01 No. (vi) Aluminium bus bar 400 Amps capacity of suitable length insulated heavy heat shrinkable sleeves etc -04 Nos.

1

-

-

... More
OUTGOING: (i) Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 63 Amps, Confirm to IS/IEC:60947-2, Rated Ultimate Shortcircuit Breaking Capacity 25 KA Icu at 415 V, Rated service short circuit Breaking capacity Ics=75% Icu at 415V (KA rms) complete all as specified and directed by Engineer-in-charge.- 04 Nos (ii)Supply and fix Digital timer switch with Timelite DBs outdoor type factory made powder coated all along internal and external surfaces, weather proof dust/water proof with IP 55 protection, consisting of 01 No AC contactor three phase 16 Amp capacity 25 KA, one digital Timer switch three nos MCB 16 Amp 10 KA toggle switch having both auto manual and by pass system - 01 No mounted on existing pole/panel with suitable size clamps all as specified and as directed by Engr-in-charge.

-

-

-

... More
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead using GI earth strip in size 32 x6 mm means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth strip protected by galvanized iron 40 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade with funnel including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete including taking out old unsv earthing all as directed by Engineer in Charge. (i) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I . (ii) Item includes the cost of 7.50m GI pipe and protection of earth strip. Any variation in length shall be paid separately under respective items hereinafter. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate. Note: Quoted rate shall be paid after getting resistance value satisfactorily (below 2.00 Ohm) and record will be submitted by the contractor.

3

-

-

... More
M&L for High mast steel tubular structure 15 metre long with Grade S-355 as per BS EN 10025 for shaft and gussets and grade FE-410 WA as per IS-2062 for 9 lantern symmetrically fitted along with their control gear and having three point suspension system with stainless steel wire rope of 6 mm dia 97/19 guage and double drum winch with luminaire mounting arm, pully assembly, LED dome aviation obstruction light with LED lamp, lightning arrester spike flange and door stiffness construction in two section longitudinal and welded in one section with thickness of sheet 3mm top and 4mm bottom and final including necessary excavation returning filling removal of soil from site all and PCC/RCC foundation of high mast light as per manufacturer design as spcified and comprising the following dimensions with the following accessories :- (a) Length of bottom section - 8.250 Mtrs (b) Length of top section -8.250 Mtrs (c) Base dia - 360 mm (approx) (d) Top dia -150 mm (approx) (e) Size of opening and door at base -1200x250 (close fitting door with suitable reinforcement to avoid Buckling at base of mast) (f)Lighting protection finial - G. single spike of length 1200 mm (g) Foundation depth - 1.5 Mtr below G.I (h) Nos of foundation bolts-08 Nos (h) PCD of foundation bolts - 460 mm (j) Diameter of foundation bolts - 30 mm (k) Length of foundation bolts - 850 mm (ii) size of base plate 520mm thick 25 mm dia complete all as specfied each set-01 Nos

1

-

-

... More
(iii) Lantern Carriage:- Lantern carriage ring with class BMS pipe/tube having sleeve on carriage ring 535 mm (ID) dia suitable to mount 09 Nos of lentern fitting symetrically -01 Nos. (iv) Winch :- Winch double drum type having operating speed 180 RPM and gear ratio 53 : 1 working operating manually/electrically with stainless steel wire rope 6mm dia too point suspension system including timble copper Talurit capacity 500 Kgs (per Drum) make lubrication arrangement self lubricant in permanent oil both bath type SAE-90/140 or equivalent each Job -01 No. (v) Stainless steel wire rope:- Diameter of SS rope 6 mm, AISI 304 grade, construction of SS rope 7/19 , stainless steel of centre core material DIN 3060, 4 Nos rope of 6 mm for Lantern Carriage, 2 Nos of 6 mm for Double drum Winch, breaking load capcity of SS wire rope are 2350 Kgs per SS rope. (vi) Trailing Cable :- Copper conductor cable PVC sheathed 1100 volt grade of size 4.00 Sq mm PVC insulataed from electrical box to street light fittings separately for nine fittings each Job -01 No. (vii) Push button control 415 Volt 3 phase 50HZ 1440 RPM single speed 1100 watt torque lifting capacity 750 Kgs adjustable mechanically tripping device complete all as specified. (viii) Power Tool:_ 1 HP integral model, single speed, reversible 415 volts/240 Volts with mechanical tripping facility.

-

-

-

... More
Supply,installation, testing and commisioning of factory made powder coated cubical outdoor LT feeder pillar box of size 900 x 750 x 300 mm confirming to IP-65, CPRI approved complete weather proof and vermin proof and the shell of 3.15 mm thick MS sheet with partitions and switch enclosure doors of 2 mm MS sheet with minimum clearance of 750 mm and canopy made out of 3.15 mm thick MS sheet all as per IS shall be available inside for easy access and working condition fixed on angle iron frame 50 x 50 x 6mm. Mounted on brick masonry pillars with a clearance of atleast 0.45 mtrs above GL on 100mm thick appron of PCC 1;4;8 type D-2 provided 1.0 mtr all around with a slight outward slope to avoid stagnation of water, marking to indentify incoming and outgoing circuits and earthing pillar box at two points out door feeder pillar box comprising of following :- (a) MCCB 63 Amp,4 pole 25 KA ,415 volt ICU 100% ICS with thermal based release = 02 Nos (01 Incomer, 01 spare) (b) Timer switch Analog outdoor type factory made powder coated all along internal and external surfaces, weather proof, dust and water proof with I P 55 protection, consisting of 01 No AC contactor 3 pahse 16 Amp capacity 10 KA, one digital Timer switch with 16 Amp three Nos MCB SP 10 Amp 10 KA having both auto manual and by pass system - 01 No mounted on existing panel with suitable size clamps complete all as specified and directed.

1

-

-

... More
Supply and fixing High performance floodlight luminiare 200 watt with pressure die-cast housing toughened glass and secondary lens optics with IP 66 ingress protection, efficiency 120 lm/W complete with all fixing accessories all as specified and directed by Engineer-in-Charge.

9

-

-

... More
S&F in repair LED Bollard (garden light) 10 watt in inverted pyramid tripod type LED Bollard with soft 360 light, IP 65 protection, resistant to corrosion with better optic for uniform distribution complete with all accessories prewired and connecting up with using three core copper flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-Charge.

10

-

-

... More
M&L for GI Tubing 40 mm bore medium grade including necessary fittings, erected on wall for fixing of ceiling fan complete with wall cutting and finishing with after fixing of pipe complete all as directed by Engr-in-Charge.

120

-

-

... More
Taking down XLPE cable of various sizes on wall and refixing the same in PVC Cassing caping size100 x 50 mm ISI marked trunking type with elbow, tee, etc along with all fixing accessories complete all as directed by Engr-in-Charge.Note : Contractor shall be quote the rate including PVC Cassing caping 100 x 50 mm ISI mark trunk type with all accessories.

450

-

-

... More
S&F of steel tubular swaged poles 9.00 mtrs long type 410 SP-31 confirming to IS - 2713 Prt I to III 1980 complete with cast iron base plate, nuts, bolts finial taper plug including PCC foundation in (1:3:6) type C-2 using 40mm graded stone aggregate and PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in coping for poles including necessary form work(straight curve) and finishing to all exposed surfaces of concrete including necessary earth work and excavation including applying two coat of aluminum paint over a coat of red oxide primer on pole and painting 03 Nos band/ strip with black, yellow, synthetic enamel paint in alternate layer and pole numbers (30 cm wide each at distance of 30 cm from plinth block including writing numbers with white paint above 1.5 Mtr above ground level over black painted surfaces complete all as specified and directed. Note : Earth work, cement concrete will be incuded in quoted unit rate

2

-

-

... More
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete including all accessories complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F LT cable junction box dust and water proof made out of PVC non metallic sheet FRP type, factory made out of PVC non metalic sheet FRP type, factory made, size of box 250mm x 200 mm x 100 mm deep with swivelling cover and locking clamp, MS clamps and nuts, bolts, for fixing the box on steel tubular pole, consisting of aluminium bus bar strip 150mm x 30 mm x 3 mm - 04 nos mounted on pole and provision of incoming and outgoing PVC insulated cable with grommets including inbuilt 6 Amp MCB SP 10 KA-01 No comlete all as specified and directed.

2

-

-

... More
S&F bracket for street light fittings made out of 32 mm dia "medium grade" galvanized steel (GI) tubing of 1.5 m long, bent to required shape (having an angle 120 degree) including necessary FI clamp (02 Nos of size 40 x 5 mm) nuts, bolts and washers and fixing to the pole complete after taking down old unserviceable bracket from the pole complete all as specified and directed.

2

-

-

... More
S&F LED board of size 26'X3'X4'' (L x W x H) made out of 24 guage GI sheet and front with acrylic sheet total enclosed with computerised letter writings of size not less than 100 mm as decided by Engr-in-charge and inside with 10*20w LED tube light complete with time control switch , MCB and battery back up with timer and synchronised motor board should be fix on 40mm dia medium grade GI pipe of 4' height (min 06 nos) (3' from the bottom of the board and 1' embedded with PCC on top of roof),fixed in PCC 1:2:4 type B-1 using 20mm graded agg of size 450*450*600mm (min 06 nos) with complete wiring of 2 sqmm 3 core copper sheathed cable 10 meter long including service connection from the pole by means of 25mm dia light grade pipe to the board. The cable inside the board shall run in PVC reinforced flexible conduit including PCC work for fixing of board on bldg roof. The details to be written with computerised writing complete all as specified and as directed by Engr-in-Charge.

1

-

-

... More
M & L providing PCC 1:4:8 type D-2 (Using 40 mm graded stone aggregate) as in foundation of size 150 mm x 150 mm cross section, planting depth 0.30 Mtr for concrete encasing the pole upto GL and including form work finished even and fair complete all as specified and directed.

2.4

-

-

... More
M & L providing PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) for plinth block/Coller above GL 150 mm high of size 150 mm x 150 mm and including form work finished even and smooth with using extra cement complete all as specified and directed.

0.6

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.