Military Engineer Services Tender

If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Aerospace and Defence
Eprocure
Opening Date28 Jun 2024
Closing Date3 Sep 2024
Tender Amount₹ 32,50,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
S & fix in renewal of MCB DP 40 to 63 Amp 240 Volts 'C' series 10 KA etc complete all as specified and directed.

23

-

-

... More
S&F in repair of MCB DB of sheet metal enclosure double door type, single pole and neutral 2 way with 200 Amp rated bus bar 240V the all incoming and outgoing wires shall be terminated with proper bottle thimbles and grouted in walls with PCC 1:2:4 type B1 using 20mm graded stone aggregate etc complete all as specified and directed.

23

-

-

... More
S&F in replacement of sub main wiring drawing in and including concealed rigid ERW stove enamelled steel conduit not less than 25mm dia medium grade with PVC cable FRLS 06 Sqmm nominal area 2run single core PVC insulated unsheathed cable with stranded copper conductor incl 06 Sqmm size PVC cable stranded copper conducter as earth continuity wire and connected to earth dolly with proper crimping of thimbles bottle type etc complete all as specified and directed.

250

-

-

... More
M&L for flame proof point wiring with FRLS PVC insulated PVC un-sheathed electric cable confirming to IS:694, 1100V grade AC single core having multi stranded FRLS copper conductor of size 4.0 Sqmm nominal cross sectional area for phase & neutral drawn in & including 1.6mm thick concealed ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 20 mm dia including flame proof fitting such as mild steel junction box, mild steel Coup-lings unions, bends, reducers, inspection elbow, sealing conduits, plugs etc conduit ISI marked in concealed wiring system & 4.0 Sqmm green PVC insulated unsheathed FRLS copper conductor as a earth wire connected to earth dolly by providing lugs complete for 3/5 pin 5/15, 20 Amp flame proof socket outlet and drawn in the same concealed conduit complete all as specified and directed. Note : Conduiting on the wall shall be concealed but if it is not posible to conceal the conduit on the RCC roof/crossing of column/beam then it shall be fixed on surface as per the condition of site etc complete all as specified and directed.

23

-

-

... More
Supply & fix flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, (2P+Earth) 250V complete all as specified & directed.

23

-

-

... More
Supply, installation, testiing commissioning and designing of 12.5 Mtr High Mast system, Mast Shaft shall be in two section, hot dip galvanised inside and outside in single dip, suitable for wind velocity as per IS 875 part 3 and Lantern carriage shall be of 40NB ERW class -B-MS pipe, diameter of lantern carriage ring of 600 mm internal dia, construction -12 arm welded, and provision for marking arrangement to include accesssories for high Mast including head frame, two point suspension system with steel wire rope of 6mm dia (7/19 construction ) double drum wrinch,galvanised lantern carriage arrengement suitable for 12 Nos luminaries LED types 150 watt,110 lux/watt,5700K, symetrically and lightening final. The mast shall have an internal type power tool mounted at the base compartment for its operation, the system shall comprises complete all as specified and directed with following accessories and technical parameter.

1

-

-

... More
(i) Foundation bolts manufactured from special steel alongwith nuts, washer, anchor plates and templates (ii) Twin dome LED aviation light 20 Watt each - 1 Set. (iii)Control panel housing suitable for control circuit including contactors, timers and suitable rating MCCBs/MCBs and 3 phase timer switch for automatic ON and OFF of the mast. It shall also have suitable control for operation of power tool. (iv) Construction of suitable shallow foundation of size as specified by manufacturer with 'M' -20 concrete for the High Mast cosidering the safe soil bearing capacity at site as 10 T/Sqm at minimum 2 Mtr depth with all materials and labours complete as per design given by highmast manufacturer including base foundation,nut bolts etc all as specified and directed. (v) Material of construction - BSEN 10025 or equivalent. (vi) Cross section of mast 20 side polygon. (vii) Length of Top section approx 8.250 mtr and bottom section 4.250 mtr. (viii) Base diameter 360 mm (Approx) and Top Dia 150mm (Approx). (ix) Joints shall be stress slip fit joints. (x) Length of overlap 1.5 times from the Dia of insertion. (xi) Thickness of Galvanisation average 70 Microns. (xii) Size of Door opening at base of Mast shall be not less than 1200mm x 250mm . (xiii) M.S. Base plate of size 540 mm dia and 25 mm thickness. (xiv) Dynamic loading as prevailing at site : - Max wind speed (IS-875-1987) - 180km/Hr, Nos of foundation bolts - 08 Nos of size as specified by manufacturar. (xv) Method of operation - Motor and manual both. (xvi) Power tool shall be of integral type, minimum capacity of motor- 1.5 HP of single speed Reversible type 3 phase 415 volts. (xvii) The top of the mast is to be covered to aviod water logging inside the structure.

-

-

-

... More
Note:- (i) Cost of equipment for loading/ unloading of high mast at site and erection is deemed to be included in the quoted rate. (ii) Cost of earth work and PCC work is deemed to included in above quoted rate and will be carried out as per manufacturer instructions. (iii) Cost of aviation light is deemed to be included in the rate quoted. (iv) Design and securing of housing for light tube done by contractor. Cost for same will be demeed to be included in quoted rate.

-

-

-

... More
Supply, laying, testing & commissioning for XLPE insulated, screened, PVC outdoor bedded/sheath and inner sheath, galvanized steel strip or wire aromoured cable of size 50 Sqmm 3.5 Core with stranded aluminum conductor suitable for rated voltage of 1100 Volt grade and laid in trenches/passing through pipe/ducts or on pole complete all as specified and directed.

200

-

-

... More
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide for laying of cables, erection of poles,struts, stays etc all as specified and as directed by Engr-In-Charge.

48.6

-

-

... More
Returning, filling in including spreading, levelling,watering and well ramming (Soil) in layers not exceeding 25 cm thick each , filling back in trenches after cables have been laid and tested, poles,stays,struts hane been erected and tested etc complete all as specified and directed.

29

-

-

... More
Removal of excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point etc complete all as specified and directed.

19.6

-

-

... More
M&L for clean dry sand laid in trenches/ducts for bedding and cushioning to cable, including spreading and levelling etc complete all as speccified and directed.

14.5

-

-

... More
M&L for laying in trenches burnt brick sub class 'B' for cable protection laid adjacent to each other length wise perpendicular to the central axis of cable complete all as specified and directed.

1440

-

-

... More
M&L for earthing complete with galvanised steel earth plate electorde of size 60cmx60cmx6.3 mm thick buried directly in ground vertically at a depth not less than 3.75 metre below from normal grond level with top edge of eath plate at a depth not less than 3.0 metre below normal ground level, earth plate surronded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of size 32x6 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts check nuts and washers made of galvanised iron and thimbles and protected by 40mm dia medium grade GI Pipe connected to main switch board or main control board or equipment and 20mm bore medium grade GI pipe for watering and including funnel, wire mesh, RCC pit cover in CC 1:2:4 type B1 reinforced with 8mm dia TMT bars @ 100mm C/C in both way and PCC chamber pit with PCC (1:3:6) Type C-2 (using 40mm graded stone aggregate), including necessary excavation and earth work in any type of soil including returning filling in exvavation and earth work and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009 (Part-1) complete all as specified and directed.

4

-

-

... More
S&F/Laying for 50 mm dia GI Tubing of light grade with all fittings and fixed complete to wall and ceiling or laid in floors complete all as specified and directed.

6

-

-

... More
Supply and fix LED flood light 150 watt warm white IP-66 symetrically and lightening final. Model No- BJFL150WLEDIWW or equivelant in CG/Bajaj/Philips

12

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.