Military Engineer Services Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date20 Sep 2024
Closing Date11 Oct 2024
Tender Amount₹ 48,20,000
Costs
EMD
₹ 96,400Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_673555_2Bid Award Id
ViewTender No
GE/EM/LKO/HOSP/T-64 OF 2024-2025Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
All as per item No 01 above but LT UG cable of size 25 Sqmm 4 core.
200
-
-
... More
All as per item No 01 above but LT UG cable of size 50 Sqmm 3.5 core.
350
-
-
... More
All as per item No 01 above but LT UG cable of size 95 Sqmm 3.5 core.
300
-
-
... More
All as per item No 01 above but LT UG cable of size 150 Sqmm 3.5 core.
320
-
-
... More
All as per item No 01 above but LT UG cable of size 185 Sqmm 3.5 core.
200
-
-
... More
All as per item No 01 above but LT UG cable of size 240 Sqmm 3.5 core.
250
-
-
... More
Supply, fix, testing and commissioning of LT panel board , CPRI approved, confirming to IS 5039, of size 1.5 metre x 1.0 metre x 0.50 meter, out door type, factory made, pedestal type, outer fabricated out of 3.15 mm CRCA sheet and inner CRCA sheet 2 mm thick and slopy roof, overall powder coated of approved shade, locking arrangement comprise 50 mm size brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder, fixing of panel 45 cm above nearest road level by providing 90 cm long angle iron of size 50 x 50 x 6 mm welded on all the for corner, including connection all exisiting cable with MCCB terminal all as specified and directed by EIC at the site requirment complete including the following component:-
7
-
-
... More
A- Incoming
(i) MCCB 4P 250 Amps, 25 kA - 01 Nos. B- Outgiong
(i) MCCBs 4P Thermal magnatic & fixed type 160 Amps, 25 kA -02 Nos
(ii) MCCBs 4P Thermal magnitic & fixed type 100 Amps, 25 KA -2 Nos
-
-
-
... More
C- Accessories
(i) Aluminium bus bar rating 400 Amps - 04 Nos. (ii) Digital Volt meter 0-500V with selector switch-01 No, (iii) Digital Amp meter 0-300 amp with CT and selector switch-01 No, (iv) Indicating lamp-01 Set (LED Type) set of three
-
-
-
... More
D- Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
-
-
-
... More
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
-
-
-
... More
Supply, fix, testing & commisioning LT bus bar panel, CPRI approved, confirming to IS 5039, of size 1 metre x 1.0 metre x 0.50 metre, out door type, factory made, pedastal type outer fabricated out of 3.15 mm CRCA sheet and inner CRCA sheet 2 mm thick, and slopy roof overall powder coated of approved shade, locking arrangement comprise 50 mm size brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 45 cm above nearest road level by providing 90 cm long angle iron of size 50 x 50 x 6 mm welded on all the for corner, including connection all exisiting cable with with MCCB terminal all as specified and directed by EIC at the site requirment complete including the following component:-
10
-
-
... More
A- Incoming
(i) MCCB 4P 125 Amps , 16 kA - 01 Nos. B- Accessories
(i) Aluminium bus bar rating 200 Amps -04 Nos .
(ii) Digital Volt meter 0-500V with selector switch-01 No,
(iii) Digital Amp meter 0-300 amp with CT and selector switch-01 No
(iv) Indicating lamp-01 Set (LED Type)
-
-
-
... More
C- Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
-
-
-
... More
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
-
-
-
... More
Supply, fix, testing & commissioning of LT panel board CPRI approved, confirming to IS 5039, of size 1.5 metre x 1.0 metre x 0.50 metre, out door type, factory made, pedestal type, outer fabricated out of 3.15 mm thick CRCA sheet and inner 2 mm thick CRCA sheet, and slopy roof, overall powder coated of approved shade, locking arrangement comprise 50 mm size brass pad lock with duplicate keys two, earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 45 cm above nearest road level by providing 90 cm long angle iron of size 50 x 50 x 6 mm welded on all the for corner, including connection all exisiting cable with MCCB terminal all as specified and directed by EIC at the site requirment complete including the following component:-
1
-
-
... More
A- incoming
(i) MCCB 630 Amps, 4Pole 36 Ka -01 Nos. B- Outgiong
(i) MCCBs 4P Thermal magnatic & fixed type 400 Amps, 25 KA -02 Nos.
(ii) MCCBs 4P Thermal magnitic & fixed type 250 Amps, 25 KA -2 Nos.
(iii) MCCBs 4P Thermal magnitic & fixed type 100 Amps, 25 KA -2 Nos.
(iv) Change Over switch of capacity 800 Amps 415 Volts 4 ploe - 01 Nos.
-
-
-
... More
C- Accessories
(i) Aluminium bus bar rating 1000 Amps - 04 Nos.
(ii) Digital Volt meter 0-500V with selector switch-01 No.
(iii) Digital Amp meter 0-700 amp with CT and selector switch-01 No.
(iv) Indicating lamp-01 Set (LED Type) set of three.
-
-
-
... More
D- Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
-
-
-
... More
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
-
-
-
... More
S&F Cable jointing kit suitable for 1100 Volt LT grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 25 -50 Sqmm complete all as specified and all as directed.
15
-
-
... More
S&F Cable jointing kit suitable for 1100 Volt LT grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 70 - 95 Sqmm complete all as specified and all as directed.
13
-
-
... More
S&F Cable jointing kit suitable for 1100 Volt LT grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 120 - 150 Sqmm complete all as specified and all as directed.
14
-
-
... More
S&F Cable jointing kit suitable for 1100 Volt LT grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armored aluminium conductor cable of size 185 - 240 Sqmm complete all as specified and all as directed.
10
-
-
... More
Material and labour for renewal of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanized steel strip of size 32 x 6 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 40 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.
18
-
-
... More
Taking down Old Unsv ACSR Conductor from LT Poles including Insulator clamps nut bolts and service connections complete all as specified and directed.
1600
-
-
... More
Excavation in trenches in soft / loose soil not exceeding 1.5 M wide and not exceeding 1.5 M in depth and getting out, including trimming the sides including forming bottom surface to required levels for laying of cables complete all as specified and directed.
480
-
-
... More
Returning, filling in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick after laying of cable complete all as specified and directed.
230
-
-
... More
Removing surplus excavated material (soil) to a distance not exceeding 50M and depositing where directed at a level not exceeding 1.5 meter above the starting point complete all as specified and directed.
250
-
-
... More
M&L for providing dry river sand as in sand cushioning below and above cable thickness as specified in SSR to under ground cable including punning down of sand in layer all as specified and directed by Engg-in-Charge. Note: for measurement purpose punned thickness of sand will be consider.
172
-
-
... More
Supply and Laying of bricks well burnt sub class B (old size) laid flat for cable protection width equal to the length of bricks complete all as specified and directed by Engineer-in-Charge.
20
-
-
... More
M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge.
50
-
-
... More
M&L for 80 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge.
50
-
-
... More
M&L for 100 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge.
50
-
-
... More
Deployment of tools & manpower for Boring of hole under road / pavement / hard standing or any other situation by manual means suitable for passing of 40 to 100 mm bore pipe and making good both ends all specified and directed
30
-
-
... More
Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete with fitting such as switches, sockets ceiling rose sketch light fittings etc, and making good the disturbed surface of walls and floors etc as directed.
527
-
-
... More
Material & Labour for conceled point wiring for one light / Fan point controlled by one, one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable 1100 volts grade ISI marked drawn through and including concealed PVC conduit not less than 20 mm dia, including all accessories like bend, tees, junction boxes etc. including 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable of green colour as a earth wire connected to common earth dolly, etc including pressed steel terminal box of suitable size with laminated white top sheet cover of 3.00 mm thick complete.
175
-
-
... More
All as per Item No 29 above but for one 5 pin 5 Amp socket outlet point on an independent board.
40
-
-
... More
All as per Item No 29 above but for one 5 pin 5 Amp socket outlet point on the same board with other switch.
12
-
-
... More
All as per item No 29 above but wiring with 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable and 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable as earth wire connected to common earth dolly for 15 Amps multipurpose socket outlet on independent board, controlled with one way switch.
55
-
-
... More
Material & Labour for point wiring for one light / Fan point controlled by one, one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable 1100 volts grade ISI marked drawn through and including surface type caping & casing not less than 25 mm wide, including all accessories like bend, tees, junction boxes etc. including 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable of green colour as a earth wire connected to common earth dolly, etc including pressed steel terminal box of suitable size with laminated white top sheet cover of 3.00 mm thick complete.
145
-
-
... More
All as per Item No 33 above but for one 5 pin 5 Amp socket outlet point on an independent board.
40
-
-
... More
All as per Item No 33 above but for one 5 pin 5 Amp socket outlet point on the same board with other switch.
10
-
-
... More
All as per item No 33 above but wiring with 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable and 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable as earth wire connected to common earth dolly for 15 Amps multipurpose socket outlet on independent board, controlled with one way switch.
50
-
-
... More
M&L for Switch Piano type, white polycarbonate body, single pole, one way 6 amp, 230 V, including connecting complete.
477
-
-
... More
M&L for Switch Piano type, white polycarbonate body, single pole, one way 15 amp, 230 V, including connecting complete.
105
-
-
... More
M & L for socket outlet white polycarbonate body, 6A / 15 A - 230 V, 2/3 pin combined, including connecting complete.
105
-
-
... More
M & L for socket outlet white polycarbonate body, 6A - 230 V, 2/3 pin combined, including connecting complete.
102
-
-
... More
M&L for Ceiling rose ceiling rose, 3 phase white polycarbonate body 6 Amps, 250 Volts AC, including connecting complete.
320
-
-
... More
Supply & fix fan regulator electronic step type for ceiling fan fixed, in existing board and connecting as directed, after dismantling and removing unserviceable regulator.
18
-
-
... More
S&F in replacement distribution board VTPN, 4 way, double door suitable for 4 pole MCCB, TPN, 125 Amps 01 No, as incoming, MCB SP 32 amps 04 Nos & MCB SP 63 Amps 08 Nos as outgoing, 200 Amps rated Busbar, inter connection link, cable ties, earth bar etc including necessary civil works and electrical connections with suitable lugs / spreader links complete all as specified and directed by Engr-in-charge. Note: Quoted rates shall be deem to including cost of MCCB & MCB
3
-
-
... More
S&F in repair Distribution board made out of sheet metal enclosure (CRCA sheet) dust and vermin proof SPN 12 way with 200 Amps rated copper bus bar neutral bar, earth bar IP 43 protection, single pole and neutral 230 Volts, double door type, fixed flush to wall complete all as specified and directed.
10
-
-
... More
Supply and fix MCB’s single pole 6-32 Amps, 230 Volts with ‘C’ curve, fixed in sheet metal board complete including connecting.
100
-
-
... More
Supply and fix MCB’s single pole & neutral 63 Amps, 230 Volts with ‘C’ curve, fixed in sheet metal board complete including connecting.
10
-
-
... More
Material & Labour for sub main wiring with 2 run single core multistranded copper conductor cable, of size 4.00 Sqmm, PVC insulated, unsheathed, fire retardant low smoke, drawn through and including heavy duty rigid PVC conduit not less than 20 mm dia with all necessary fitting and including one run single core multistranded copper conductor cable, of size 4.00 Sqmm, PVC insulated, unsheathed, fire retardant low smoke as earth wire in green colour, fixed on wall / ceiling, including taking down old sub main wiring complete. Note: (i) 2 Runs of main cable and one run earth wire with conduit will be measured as one Unit for payment.
170
-
-
... More
Material & Labour for sub main wiring with 2 run single core multistranded copper conductor cable, of size 6.00 Sqmm, PVC insulated, unsheathed, fire retardant low smoke, drawn through and including heavy duty rigid PVC conduit not less than 20 mm dia with all necessary fitting and including one run single core multistranded copper conductor cable, of size 6.00 Sqmm, PVC insulated, unsheathed, fire retardant low smoke as earth wire in green colour, fixed on wall / ceiling, including taking down old sub main wiring complete. Note: (i) 2 Runs of main cable and one run earth wire with conduit will be measured as one Unit for payment.
180
-
-
... More
S&F in replacement 1100V grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connection, one twin core cable flat or circular strande 10 Sqmm aluminiuam conductor complete all as specified and as directed.
120
-
-
... More
S&F in replacement of sheet metal enclosures with socket plug top and MCBs with a two pin and earth plug and socket complete with including one single pole MCB 20 Amps all as per specified and directed
20
-
-
... More
Supply and fix in replacement of wall / surface mounting luminaires integrated LED Batten 20 W, 6000 K, 100 lumens / watt, 230V , 4 feet long with frosted PMMA/PC diffuser & integrated electronic driver complete including Electrical connection with PVC three core copper flexible wire & all necessary fixing arrangements all as per specified and directed by Engr-in-charge.
180
-
-
... More
S&F in replacement of LED Building security light 35 Watt with high power LED source (110 lumen/watt) PDC housing, IP65 and IK 07 with 4 KV inbuilt surge protection potted driver including Electrical connection with PVC three core copper flexible wire & all necessary fixing accessories such as bracket of GI pipe light grade 40 mm dia 0.60 mtr long bend to shape as per suitable size along with all accessories, fixed on wall including bolts & nuts.
25
-
-
... More
Supply and fix in repairs, Recess type LED llight fittings of size 2 X 2 feet, 36 watt LED made of CRCA powder quoted finish with fully covered by PMMA Acrylic Lumio Diffuser, LED Used shall be SMD type and fixture including cutting and making false ceiling of any pattern / mtrl proper fixing of light in falce ceiling , electrical connection up to 15 feet height of various ward and dept all as specified and directed.
30
-
-
... More
S&F ceiling fan 1200mm sweep, BEE star rated, bldc motor, AC single phase, 230/240 volts white colour complete with fan motor, blade, down rod, canopy and provn of connection with three core flexible copper wire cable of size 1.50sqmm from ceiling rose to fan complete all as specified and directed.
10
-
-
... More
Supply and fix heavy duty metal body exhaust fan single phase 230 / 240 volt of size 300 mm sweep including holes of suitable size, grouting of nuts and bolt etc and making good to match the existing surface including louvers and making connetion with twisted copper flexible wire 23/0.076mm, including disconnecting and taking down old unserviceable exhaust fan and deposited in AGE E/M (W) store yard for BER action complete all as specified and directed.
5
-
-
... More
Material and labour for renewal earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanized steel wire 4 mm dia by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 15 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.
5
-
-
... More
Disconnecting of ceiling fans / exhaust fan of any size from ceiling rose / connector for cleaning, servicing /oiling and greasing of fan by using appropriate grade of oil / grease and replacing defective parts such as bush bearing , split pin rubber bush, capacitor etc and rehanging the same after proper cleaning and making connection with ceiling fan / connector with flexible wire of size 23 / 0076 copper conductor multi stranded as directed by Engr-in-Charge.
25
-
-
Evaluation Notes How It Works ?