Military Engineer Services Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date2 May 2024
Closing Date28 May 2024
Tender Amount₹ 36,00,000
Costs
EMD
₹ 72,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_652041_1Bid Award Id
ViewTender No
8179/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
S & F in repair selector switch 3 way for checking of Amps in 3 phase at different position in existing panels complete all as specified and directed by Engr-in-charge .
10
-
-
... More
S & F in repair of Multifunctional meter with all acccessories ie CT etc for measuring Volt, Amps, frequency and power factor digital type and fixing the same in existing panel by modification to existing space of volt meter/Ameter by cutting welding and cover the blank space by existing colour MS sheet and making good to disturbed surface complete all as specified and directed.
4
-
-
... More
S & F in repair of Ammeter 0-600 Amps with selector switch complete all as specified and directed.
2
-
-
... More
S&F in repair loop-in-loop out box of size 30x20x20cm made out from 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door and locking arrangements with slanting cover on top and provision of 4 Nos aluminium bus bar of size 25mm x 2mm-4 Nos fixed on insulator and one MCB of capacity 6 Amps complete fixed on pole with and including suitable size MS flat iron clamps, nuts,bolts & washers etc complete all as specified and directed
30
-
-
... More
Supply and installing commissioning and testing cubical type LT Panel outdoor type of 1.50 x 1.40 x 0.60 mtr CPRI certified factory made cubical type weather and vermin proof fixed on and including ventilation and louvers arrangement PCC 1:2:4 type B-2 using 40 mm graded stone aggregate as in foundation of required/suitable size and as directed at site with angle iron frame of size 50x50x6mm, 3 phase 4 wire 415 volts 50 HZ fabricated out of 3.15 mm thick MS sheet including two coats of synthetic enameled paint over a coat of primer red oxide and keeping adequate working space inside of the box (outer width of the box not less than 45cm and gap between bus bar not less than one inch) and double door handle including locking arrangement including taking out old LT Panel from existing site as directed before manufacturing the panel. The drawing of the feeder pillar box will be approved by Engr-in-Charge and the same have the following electric controls :-
2
-
-
... More
Incoming :- (i) Insulated epoxy coated high conductivity aluminium bus bar 500 Amps of suitable size for phase and neutral complete all as specified and directed. (ii) MCCB 400 Amp 36 KA, 4 pole, 415 volts 50 Hz – 01 No (iii) Digital type Volt meter (0-500) volts with selector switches. (iv) Digital Amp meter with suitable resin cast CT and selector switch – 01 (At main out going) (v) LED Indicating lamp assembly R,Y,B Phase – 03 Set
Outgoing :-
(i) MCCB 250 Amp 36KA, 4 pole, 415 volts 50 Hz- 01 Nos (ii) MCCB 100 Amps 16 KA, 4 pole 415 Volt 50Hz - 04 No
-
-
-
... More
Supply and installing commissioning and testing cubical type LT Panel outdoor type of 1.50 x 1.40 x 0.60 mtr CPRI certified factory made cubical type weather and vermin proof fixed on and including ventilation and louvers arrangement PCC 1:2:4 type B-2 using 40 mm graded stone aggregate as in foundation of required/suitable size and as directed at site with angle iron frame of size 50x50x6mm, 3 phase 4 wire 415 volts 50 HZ fabricated out of 3.15 mm thick MS sheet including two coats of synthetic enameled paint over a coat of primer red oxide and keeping adequate working space inside of the box (outer width of the box not less than 45cm and gap between bus bar not less than one inch) and double door handle including locking arrangement including taking out old LT Panel from existing site as directed before manufacturing the panel. The drawing of the feeder pillar box will be approved by Engr-in-Charge and the same have the following electric controls :-
2
-
-
... More
Incoming :- (i) Insulated epoxy coated high conductivity aluminium bus bar 400 Amps of suitable size for phase and neutral complete all as specified and directed. (ii) MCCB 250 Amp 36 KA, 4 pole, 415 volts 50 Hz – 01 No (iii) Digital type Volt meter (0-500) volts with selector switches. (iv) Digital Amp meter with suitable resin cast CT and selector switch – 01 (At main out going) (v) LED Indicating lamp assembly R,Y,B Phase – 03 Set
Outgoing :-
(i) MCCB 125 Amp 25KA, 4 pole, 415 volts 50 Hz – 02 Nos
(ii) MCCB 100 Amp 25 KA 4 pole 415 Volts - 50Hz - 01No
-
-
-
... More
M&L for preparing old painted surface of LT Panel board indoor/outdoor type of any size by cleaning removing of the old paint by scraping with wire brush/sand paper etc and including minor repair to panel in different location where required with arc/gas welding with replacement of hinges and place the door in original position denting/patching of broken/rusted surfaces etc and apply two coat of synthetic enamel paint by spray painting on inside/ outside surface of panel,all as specified and directed by Engr-in- charge.
320
-
-
... More
S&F in repair MCCB 415 Volts 4 pole 630 Amps 50 Hz 50 KA alongwith spreader terminal with adjustable thermal & magnetic setting setting including lugs/thimbles of suitable size in existing panels complete all as specified and directed by Engr-in-Charge.
Note :- Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
1
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 500 Amps 4 pole 50 Hz 415 V, 50 KA
2
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 400 Amps 4 pole 50 Hz 415 V, 36 KA
14
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 250 Amps 4 pole 50 Hz 415 V, 36 KA
12
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 200 Amps 4 pole 50 Hz 415 V, 36 KA
8
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 160 Amps 4 pole 50 Hz 415 V, 36 KA
6
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 125 Amps 4 pole 50 Hz 415 V, 16 KA
8
-
-
... More
All as per Item Ser No 13 here-in-before but of MCCB 100 Amps 4 pole 50 Hz 415 V, 16 KA
10
-
-
... More
S&F in replacement Isolator 4 pole 100 Amps, 415 Volts complete all as specified and directed by Engr-in-Charge.
5
-
-
... More
All as per Item Ser No 20 here-in-before but 63 Amps, complete all as specified and directed by Engr-in-Charge.
2
-
-
... More
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed.
399.6
-
-
... More
Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed.
254.19
-
-
... More
Removing of excavated soft/loose soil not exc 50 m & depositing where as directed at a level n.exc 1.5 m above from starting point completed all as specified and directed.
145.41
-
-
... More
Taking out old defective cable from trenches/ floor/road/wall/pipe/pole /service connections of any size , testing with LT magger , seggregating the serviceable part of cables and store for relaying complete all as specified & directed. Note : Excavation and earth work will be paid and measured separately in relevant item.
1850
-
-
... More
Supply and laying in replacement of XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor 1100 volt grade, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe of cross sectional area 240 Sq mm 3.5 core all as specified and directed. Note :- Rate deemed to be inclusive of connection including cable glands and lugs.
50
-
-
... More
All as per Ser item No 25 here-in-before but 185 Sq mm 3.5 core
150
-
-
... More
All as per Ser item No 25 here-in-before but 150 Sq mm 3.5 core
200
-
-
... More
All as per Ser item No 25 here-in-before but 120 Sq mm 3.5 core
250
-
-
... More
All as per Ser item No 25 here-in-before but 95 Sq mm 3.5 core
600
-
-
... More
All as per Ser item No 25 here-in-before but 25 Sq mm 4 core.
400
-
-
... More
Relaying only serviceable LT UG Cable obtained from Srl item No 24 of any size and discription including necessary cable lugs. Note :- All relevent items like excavation, earth work tc shall be paid and measured seperately.
200
-
-
... More
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches, punning complete all as specified and directed Note:- Punning thickness of 18 cm will be considered for payment.
119.88
-
-
... More
M & L for brick protection to cable using old size sub class 'B' bricks, laid flat/lengthwise perpendicular to the axis of cable all as specified & directed.
7.3
-
-
... More
Relaying of Old brick recovered from item No 30 or during excavation for protection of cable all as specified & directed.
4.5
-
-
... More
M&L Cutting of floor/wall/road/footpath for removal of LT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed.
40
-
-
... More
M&L for Boring of holes under road /pavement/hard standing or any other situation by mannual means for 100/80 mm bore at the depth not less than 1 mtr below ground level for crossing the cable and making good both the ends all as specified and directed. Note :- GI pipe shall be measure and paid separately under respective item.
20
-
-
... More
M&L for PCC (1:3:6) type C2 using (40 mm graded aggregate in foundation, filing and mass concrete complete all as specified and directed.
2
-
-
... More
S & F in replacement GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. (a) 50 mm dia
20
-
-
... More
ditto but of size 80 mm dia
20
-
-
... More
ditto but of size 100 mm dia
10
-
-
... More
M&L for earthing complete with galvanised iron steel earth plate of size 600 x 600 x 3.15 mm thick burried directly in ground (earth pit not less 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below ground level connected to thick electrode and 32x6 mm GI strip as earthing by means of nuts bolts check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore (medium grade) and connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1 precast RCC cover slab 54 x 54 cm x 5 cm with reinforcement with 8 mm TMT bars @ 150 C/C with one handle and funnel for watering charcoal or coke and salt in alternate layers & necessary earth work in soft/loose soil complete all as shwon in electrical plate No 5 of SSR Part-I including testing on completion all as specified and directed.
12
-
-
... More
Dismantling and taking down of LED/Street light/ Bollard Light of any cap any size any make complete all as specified and as dierected.
60
-
-
... More
S&F in replacement light fitting Energy saving, exclusive innovative designed, long life versatile pressure die cast aluminium IP-66 (surface mounting lense type SMD LED) flood light luminaire with high power LED 180 Watt complete all as specified and as dierected.
35
-
-
... More
All as per Item Ser No 45 but rectangular flood light LED 120W (with surface mounting lense type SMD LED) complete all as specified and as dierected.
25
-
-
... More
Supply ,fixing ,commisioning and testing of Nature timer switch control Street Lights complete with MCB, Power and Panel duly complete with wiring 12KW3P, three phase, max load 12KW complete all as specified and directed.
2
-
-
... More
Lopping / prooning of tree branches upto the extend to obtain clearance all around the LT/HT over head lines conductor upto 3 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed. Note:- (a) Tools & plants including safety measures equipments like belt, ladder & ropes etc shall be arranged by the contractor at own cost.(b) Contractor supervisor will take proper shut down before starting the work and clear it before resuming power supply, however full assistance will be provided by MES Staff.
20
-
-
... More
M&L for spraying chemical (Roundup) on area to remove unwanted vegitation / grass at E/M installations / 2 pole/ 4 pole structures complete all as specified and directed. Note : Labour and equipments to spray chemical on required area are inclusive in quoted rate.
10
-
-
... More
S&F in replacement electric shock treatment chart of size approx 3ft x 2ft & 6 mm thick plywood with teak wood frame and covered with glass complete all as specified and directed.
2
-
-
... More
S&F in replacement of notice board of size approx 4 ft x 3 ft duly fixed with 6 Nos clips for display of instructions with aluminum frame including covered with plastic laminated sheet complete all as specified and directed.
2
-
-
... More
S&F in replacement 1100 volts grade PVC insulated aluminium conductor screened served with inner sheathed in service connection flat twin core cable of size 10 sqmm complete all as specified and directed.
900
-
-
... More
All as per Ser item No 52 here-in-before but 06 sqmm complete all as specified and directed
1000
-
-
... More
Supply and fixing cable twin core PVC insulated and unsheathed multistranded aluminium conductor of size 2.50 Sqmm complete all as specified and directed.
600
-
-
... More
S&F in repair off load change over switch three phase, Four pole with enclosure capacity 400 Amps with side handle operated complete all as specified and directed by Engineer-in-charge.
2
-
-
... More
All as per Ser item No 55 here-in-before but capacity 200 Amps complete all as specified and directed
4
-
-
... More
All as per Ser item No 55 here-in-before but capacity 100 Amps complete all as specified and directed
4
-
-
... More
S&F in repair ON load change over switch three phase, Four pole with enclosure capacity 400 Amps with Front handle operated complete all as specified and directed by Engineer-in-charge.
2
-
-
... More
Supply, fixing, testing and commissioning of Heat shrinkable type end termination jointing kit suitable for LT cable of size 35 Sqmm to 70 Sqmm, 3.5 to 4 core, XLPE insulated, PVC sheathed armoured 1100 volts grade.
10
-
-
... More
All as per item No. 59 above but 95 to 120 Sqmm.end termination jointing kit
5
-
-
... More
All as per item No. 59 above but 150 to 185 Sqmm.end termination jointing kit
3
-
-
... More
Supply, fixing, testing and commissioning of heat shrinkable type straight through jointing kit suitable for LT cable of size 35 Sqmm to 70 Sqmm, 3.5 to 4 core, XLPE insulated, PVC sheathed armoured 1100 volts grade.
6
-
-
... More
All as per item No 62 above but 95 to 120 Sqmm.
6
-
-
... More
All as per item No 62 above but 150 to 185 Sqmm.
10
-
-
... More
Note : (i) Complaints pertaining to LT External Electric Supply shall be resolved by the contractor immediatelly after getting complaints. In case of failure on the part of contractor to resolve to the complaints within stipulated time, a penalty of Rs 1000/- per day per complaint shall be imposed from the contractor.(ii) A register shall be maintained to record all orders & instructions and their complaints and is to be signed by the contractor/his representative and the Engineer-in-charge/JE E/M concerned.(iii) Work done register to be maintained by the contrator. A separate Docket complaints slip book shall maintained by the contractor to note the complaints/jobs and get it signed by the user after completion of work and submits to the JE-in-Charge. (ii). Tenderers may note that amount as given in schedule of credit will be deducted from the total amount to worked out the net contract sum at the time of Acceptance of tender.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements