Military Engineer Services Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Military Engineer Services - MES Tender
Security and Emergency Services
Eprocure
Opening Date28 Oct 2023
Closing Date18 Nov 2023
Tender Amount₹ 41,55,000
Costs
EMD
₹ 83,100Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_625536_1Bid Award Id
ViewTender No
80023-21/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply, Installation, Testing & Commissioning of Pressure gauge with switch contact having Range 0 to 400 Bar, Switching Point 270 Bar complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens
4
-
-
Supply, Installation, Testing & Commissioning of BRASS PNEUMATIC ACTUATOR, minimal pilot pressure- 8 Bar suitable for 300 Bar system) complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens
4
-
-
Supply, Installation, Testing & Commissioning of Manual Actuator with lever thread size M36x1.5 complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens
4
-
-
Supply, Installation, Testing & Commissioning of Pilot hose Flexible 800mm long , 4mm dia , working pressure 360 Bar complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
4
-
-
Supply, Installation, Testing & Commissioning of Pilot hose Flexible 1000mm long , 4mm dia , working pressure 360 Bar complete all as specified and directed . Make: Ceasefire/Fiwarec/Siemens /Rotarex
24
-
-
Supply, Installation, Testing & Commissioning of Adaptor for pilot line / Pilot Hose Adaptor complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
54
-
-
Supply, Installation, Testing & Commissioning of Bleed valve for use in pilot lines of fixed fire extinguishing systems complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
2
-
-
Supply, Installation, Testing & Commissioning of Screw Plug complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
4
-
-
Supply, Installation, Testing & Commissioning of Discharge Hose of suitable length, Nominal dia -12mm, Working Pressure 360 Bar complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
4
-
-
Supply, Installation, Testing & Commissioning of Check Valves for discharge hose pipe complete all as specified and directed . Make: Ceasefire/Fiwarec/Siemens /Rotarex
4
-
-
Supply, Installation, Testing & Commissioning of Discharge Nozzles designed to provide the proper flow rate and distribution of Gas to total flood a hazard area : 180 deg. / 360 deg ( 10NB to 50NB ) complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens /Rotarex
18
-
-
Supply, Installation, Testing & Commissioning of Manifold of suitable length (M.S. Seamless to ASTM A-106, SCH 160) 4 way - 2" BW x sch 160, ASTM A-106 Gr.B. including necessary fittings complete all as specified and directed . Make: Fabricated to specifications
1
-
-
Supply, Installation, Testing & Commissioning of Actuation System including the following:
a). 2kg M.S. Seamless Cylinder filled with CO2 gas along with wall/structure mountings.
b). Cylinder valve for CO2 (DN12) actuation cylinder
c). Manual Activation including mechanical box - 02 Nos, SS wire - 24 Mtrs, Aluminium Sleeve - 24 Mtrs, Corner Pulley - 12 Nos and End of Line - 4 Nos.
1
-
-
Supply, Installation, Testing & Commissioning of MS Seamless pipe schedule 80 of pipe size 25mm dia with all fittings/fixtures, nut bolts, U clamps etc including cutting, welding, moulding, drilling etc with supporting structure all as specified and directed.
15
-
-
Supply, Installation, Testing & Commissioning of MS Seamless pipe schedule 80 of pipe size 32mm dia with all fittings/fixtures, nut bolts, U clamps etc iincluding cutting, welding, moulding, drilling etc with supporting structure all as specified and directed.
15
-
-
Supply, Installation, Testing & Commissioning of MS Seamless pipe schedule 80 of pipe size 50mm dia with all fittings/fixtures, nut bolts, U clamps etc including cutting, welding, moulding, drilling etc with supporting structure all as specified and directed.
20
-
-
Material and labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as specified and directed.
6
-
-
Supply, Installation, Testing & Commissioning of 3 Zone Automatic Gas Extinguishing Panel, supports 3 conventional detection zones and 1 flooding/extinguishing zone. Designed and approved for EN 54-2, 4, & 13, EN12094-1 by BSI complete all as specified and directed. Make: CEASEFIRE/ADVANCE/LST
2
-
-
Supply, Installation, Testing & Commissioning of Manual Release Switch compatible with Rapid-Sense 3 Zone Automatic Gas Extinguishing Panel complete all as specified and directed.
2
-
-
Supply, Installation, Testing & Commissioning of Manual Abort Switch compatible with Rapid-Sense 3 Zone Automatic Gas Extinguishing Panel complete all as specified and directed
2
-
-
Supply, Installation, Testing & Commissioning of Conventional Rate of Rise Heat Detector, heat alarm threshold temperature 58°C, central LED for 360° status visibility complete all as specified and directed
9
-
-
Supply, Installation, Testing & Commissioning of A Conventional Detector Mounting Base associated with the CDX Range of Detectors and Beacons and is fully compatible with conventional fire alarm control panels complete all as specified and directed. Make: CEASEFIRE/ADVANCE/LST
18
-
-
Supply, Installation, Testing & Commissioning of Conventional Photoelectric Smoke Detector (White), fully compatible with the Conventional systems. A third terminal provides an integral remote indicator output complete all as specified and directed
9
-
-
Supply, Installation, Testing & Commissioning of Conventional Wall Sounder with Beacon, 3 level of volume adjustment, 32 recognised tones, 100 dB(A) output @1M, IP 65, EN 54-3, EN 54-23, LPCB complete all as specified and directed. Make: CEASEFIRE/ADVANCE/LST
2
-
-
Supply, Installation, Testing & Commissioning of Supply of 2C x 1.5 Sq.mm FRLS PVC insulated copper conductor armoured cable complete all as specified and directed. Make: POLYCAB/KEI/FINOLEX
225
-
-
Supply, Installation, Testing & Commissioning of Auto/Manual Selector Switch 24V DC operated, 1 input and 2 output, current rating 10A. Provided for changing the system operation from Main Cylinder (Auto Mode) and Standby Cylinder (Manual Mode) complete all as specified and directed
2
-
-
Supply, Installation, Testing & Commissioning of Non-Return Valve suitable for pilot line complete all as specified and directed
3
-
-
Supply, Installation, Testing & Commissioning of constant pressure regulator which is used to reduce the agent pressure comes out from high pressurecylinder which is filled at 300 or 200 bar complete all as specified and directed. Make: Ceasefire/Fiwarec/Siemens
4
-
-
Supply ,installation , testing and commissioning of single phase online Inverter/UPS of cap 4 KVA , sinewave technology, with FOUR Nos. tall tubular batteries of cap 12 volt,150 AH each including initial charging and filled with electrolyte ( 12 x 4 =48 volt ) complete with all safety measures, requisite copper cable connection and brass connectors complete all as specified and as directed. Make - Luminious , Model-Cruze,/Microtech
1
-
-
Final Testing , commissining and proper resetting the entire system after insttalation of all items for checking proper working of entire system . Testing should be in presence of user rep , Engr-in -Charge.Clearance certificate issued by fire safety officer of approved agencies or central govt/state govt is to be submitted by the contractor after testing.The charges/ fees for fire safety officer of central govt/state govt is to be born by contractor. Note :- 1. Layout plan of Gas suppression system showing all the items should be approved before starting the work. 2. If any additional items which are not included in the BOQ /CA ,and required for making proper functioning the rate for the same may be included in the quoted rate.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements