Military Engineer Services Tender

If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date6 Sep 2024
Closing Date4 Oct 2024
Tender Amount₹ 60,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M&L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm and after punning down sand cushioning will be 18 cm complete all as specified and directed . Note : 18 cm thick only will be considered for payment purpose.

40.16

-

-

... More
M&L for precast concrete cover class HV type 1, flat size 300mmx180mmx40mm laid in trenches for cable protection complete all as specified and directed .

2752

-

-

... More
Re-Laying only old but serviceable precast concrete cover class HV type, flat size 300 mm X 180 mm X 40 mm in trenches for cable protection with cable cover retrieved from srl No 1 here in before complete all as specified and directed .

600

-

-

... More
Supply, laying testing and commissioning in replacement trenches /passing through pipes/ on poles etc cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with stranded aluminium conductor, 11000 volts, grade of size of cable 120 sq mm 3 core suitable for earthed system including taking out unserviceable cable complete all as specified and directed . Note :- ( Excavation & Earth work, Sand cushioning and precast concrete cover shall be measured and paid separately under relevant items of Sch. ‘A’).

200

-

-

... More
All as per item No.7 here in before but size 95 sqmm 3 core complete all as specified and directed .

550

-

-

... More
M&L for defect rectification HT 11 KV cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc.including and additional excavation in normal alluvial strata required for exposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 185 Sq mm 3 core. The fault locating equipments will be brought to site within an hours of instruction from Engineer-in-Charge

8

-

-

... More
Supply and jointing straight through heat shrink type joint complete with jointing material suitable for HT 11KV XLPE cable of size 240- 300 Sq mm 3 core complete all as specified and as directed .

5

-

-

... More
All as per item No 10 here in before but suitable for cable size 150- 185 Sq mm complete all as specified and directed .

5

-

-

... More
All as per item No 10 here in before but suitable for cable size 95 -120Sq mm complete all as specified and directed .

10

-

-

... More
Supply and jointing heat shrinkable end termination outdoor joint with jointing material suitable for HT 11KV XLPE cable of size 240 to 300 Sq mm 3 core complete all as specified and as directed .

4

-

-

... More
All same as per item No 13 here in before but for size 120-185 Sq mm complete all as specified and directed .

4

-

-

... More
All same as per item No 13 here in before but for size 95-120 Sq mm complete all as specified and directed .

4

-

-

... More
Supply and jointing heat shrinkable end termination indoor joint with jointing material suitable for HT 11 KV XLPE cable of size 240-300 sqmm 3 core complete all as specified and as directed .

4

-

-

... More
All same as per item No 16 here in before but for size 120-185 Sq mm complete all as specified and directed .

2

-

-

... More
All same as per item No 16 here in before but for size 50-95 Sq mm complete all as specified and directed .

2

-

-

... More
Taking out trolley of VCB 630/800 Amps 11 KV from the cabinet and opening top cover, de-carbonizing moving and fixed contacts if required, lubricating, inspecting the wiring of Micro processor EF/OC relay, tripping coil electrical and checking for manual/auto tripping system complete and placing back the breaker trolley in its original position all as specified and as directed by Engr-in-Charge. Note: (i) The various unsv items required to be replaced shall be paid seperately under item No. 20 to 26 (II) (ii) Calibration of relays shall be paid seperately under item No. 19

10

-

-

... More
Supply and fixing for replacement of fixed contact block complete suitable for 630 Amps, 11 KV HT VCBs all as specified and directed .

6

-

-

... More
Supply and fixing for replacement of moving contact block complete suitable for 630 Amps 11 KV HT VCBs all as specified and directed .

6

-

-

... More
Supply and fixing for replacement of mechanical castle interlock assembly with key suitable for HT 11 KV VCB of rating 630 Amps complete all as specified and directed .

6

-

-

... More
Supply and fixing for replacement of closing coil assembly 230 volts AC/ 24 volts DC, all as specified and directed .

6

-

-

... More
Supply and fixing for replacement of Tripping coil with plunger assembly 230 volts AC/24V DC, all as specified and directed .

5

-

-

... More
Supply and fixing for replacement of closing coil plunger with 24 volts DC, all as specified and directed .

5

-

-

... More
Supply and fixing for replacement of spout bushing 11 KV for VCB all as specified and directed .

6

-

-

... More
M & L for callibration of microproccessor E/F and O/C relay of VCB complete and calibrating with portable relay test kit to set time and fault level and adjustment of setting with according to load & time with main grid of Sekhawati/ Khyber line for proper functioning complete all as specified and directed by Engr-in-Charge.

15

-

-

... More
Supply and fix in replacment of Vaccum interruptor type WL-33379 (4 inch dia) suitable for HT VCB 630 Amps all as specified and directed .

4

-

-

... More
S & F in replacement trip push button suitable for HT 11 KV VCB complete all as specified and directed.

6

-

-

... More
S & F in replacement of indicator lamp LED with holder (R/Y/B in colour) complete all as specified and as directed by Engr-in-Charge.

15

-

-

... More
S & F in replacement of CT operated digital ampere meter 0 to 200 Amps flush pattern square type suitable to mounted on existing HT panel complete all as specified & directed.

5

-

-

... More
S & F in replacement of selector switch suitable for voltmeter/amp meter complete all as specified and as directed by Engr-in-Charge.

5

-

-

... More
S & F in replacement of shunt trip coil 30 volts DC for HT VCB all as specified and directed .

6

-

-

... More
Supply & Fixing in replacement motor and gear assembly 110 volts AC/24V DC UMG-14 type all as specified and directed .

6

-

-

... More
Supply & Fix in replacement of isolating contact assembly suitable for 630 Amps HT VCBs all as specified and directed .

4

-

-

... More
Supplying, installation, testing and commissioning of DC Auxiliary Supply battery charger panel for 11 KV substation equipment haveing DC-24V. DC Battery charger panel with input voltage 230V AC + 10%, 50 HZ + 5% outputwith 24V. DC/20Amp FCBC battery charger panel with enclosure of repeated make with 2 Nos. cells of 12V/120AH SMF VRLA battery bank of exide/Amoron/Panasonic make icluding dismantling of old existing panel etc. as required complete all as specified and directed .

2

-

-

... More
Supply installationsand testing as in replacement of voltage transformer (PT) 3 phase, resin type of oil fired 3 limb indoor type primary voltage 11 KV and secondary voltage 110 volts type VA class complete all as specified and directed .

3

-

-

... More
Supply & Fix in replacement Digital protective 3 phase over current and earth fault relay for HT 11 KV VCB panel with high set and RS-485 MC61C complete with connection and testing on full load all as specified and directed .

3

-

-

... More
Supply & Fix in replacement of Digital protective 3 phase over current and earth fault relay with high set with CT rating 5A 2 NO+2NC model MC61A complete for HT 11 KV VCB panel and connection and testing on full load all as specified and directed .

4

-

-

... More
Supply & Fix in replacement of Master trip relay suitable for working voltage 30 Volt DC and connecting the circuit with existing over current and earth fault relays complete all as specified and directed by Engr-in-charge.

8

-

-

... More
S & F in replacement of volt meter 0-15 KV PT operated anlog type of size 150mmx150mm meter suitable to mount on existing HT panel all as specified and directed .

25

-

-

... More
S&F in replacement of maintenance free fully charged Nickle cadmium battery 42 Ah, 12 volts complete all as specified and as directed .

20

-

-

... More
Opening the front and rear cabinate of the RMU 3way/5 way 630/800 Amps 11 KV de-carbonizing moving and fixed contacts if required, lubricating, checking the pressure of SF-6 gas, inspecting the wiring of micro processor EF/OC relay, tripping coil electrical and checking for manual/auto tripping system complete and placing the SF-6 VCB and isolating unit in its original position all as specified and as directed by Engr-in-Charge.

20

-

-

... More
Supply and fixing plug in type voltage presence indicator system (VPIS) type WIM for 11 KV, RMU complete all as specified and directed .Make:

10

-

-

... More
Supply and fixing SF-6 Ring Main unit fuse 11 KV by opening fuse canisters of RMU positioned behind interlocking cover complete all as specified and directed .

10

-

-

... More
Supply and fixing terminal contact piece with silicone coupling for SF-6 Ring Main unit 11 KV by opening the terminal cover complete all as specified and directed .

10

-

-

... More
Supply and fixing pressure indicator manometer for SF-6 Ring Main unit 11 KV by opening the front cover complete all as specified and directed .

5

-

-

... More
Supply and fixing ring type current transformer 100/1 Amps for SF-6 Ring Main unit 11 KV by opening the cable compartment cover of fixed the CT on cable elbow plug/T plug complete all as specified and directed .

6

-

-

... More
Supply and fixing ring type current transformer 50/1 Amps for SF-6 Ring Main unit 11 KV by opening the cable compartment cover of fixed the CT on cable elbow plug/T plug complete all as specified and directed .

6

-

-

... More
Supply and fixing SF-6 gas in safe ring/safe plus by SF-6 gas bottle by removing front cover and on screw manometer and reduction valve and maintained the pressure 14 bar obslute complete all as specified and directed .

1

-

-

... More
Supply and fixing Trifurcation boot 11 KV capacity for cable termination joint of RMU incoming and outgoing terminals including taking out old defective trifurcation boot complete all as specified and directed .

15

-

-

... More
Supply and fixing HT bushing with gaskit for SF-6 Ring main unit 11 KV complete all as specified and directed .

6

-

-

... More
Callibration of microproccessor E/F and O/C relay of RMU complete and calibrating with portable relay test kit to set time and fault level and adjustment of setting with according to load & time with main Tech area power house incl replacement of relay battery for proper functioning complete all as specified and directed by Engr-in-Charge.

12

-

-

... More
Supply & Fix in replacement of earth fault protection and indicator relay for Ring main unit including callibrating the relay with existing load and tripping timming complete Make :Crompton Model EMG-1 complete all as specified and directed by Engr-in-Charge.

5

-

-

... More
Disconnecting HT/LT sides of defective transformer indoor/outdoor installed on 2/4 pole structure/PCC foundation of any capacity up to 800KVA and then drainage of complete transformer oil. Opening of top cover with due care and removal of all HT/LT winding connections from bushing and then lifting of core by means of tripod and chain pulley with due care for inspection and ascertain it’s serviceability state after keeping it aside. Removal of all sludge and unwanted material from tank and core, lowering of core assembly after carrying out required repairs to the winding and core. In case the repairs which are not possible at site then the transformer has to be taken to the work shop for repairs all as specified and directed . Note :- the following items will be measured and paid separately under relevant items of the Sch ‘A’ (i)The cost of transportation. (ii)The cost of rewinding HT/LT coils (iii) The cost of dehydration/filtration’ (iv) The cost of transformer oil toping up /replaced any spares required for making transformer serviceable.

3

-

-

... More
Material and labour for replacement of worn out HT copper coils (limb) made out of super enameled insulated copper wire all as per existing size and shape including all insulating, requisite insulating paper/material in each layer of binding, varnishing and baking in vacuum furnace complete all as specified and directed by Engineer in charge.

420

-

-

... More
Material and labour for replacement of worn out LT copper coils made out of super enameled insulated copper strip all as per existing size and shape including all insulating, binding, varnishing and baking in vacuum furnace complete all as specified and directed by Engineer in Charge.

320

-

-

... More
Material & labour for replacement of worn out bushing rod made out of copper/brass with heavy duty double nuts and one washer at both ends suitable for HT side all as exiting size, shape and length suitable for transformers of capacity 100 to 400 KVA all as specified and directed .

12

-

-

... More
All as per item No. 58 here in before but the transformer of capacity 500 to 800 KVA all as specified and directed .

12

-

-

... More
Material and labour for replacement of worn out bushing rod made out of copper/brass with heavy duty double nuts and one washer at both ends suitable for LT side all as exiting size, shape and length suitable for transformer of capacity 100 to 400 KVA all as specified and directed .

10

-

-

... More
All as per item No. 60 here in before but the transformer of capacity 500 to 800 KVA all as specified and directed .

10

-

-

... More
Disconnecting HT/LT sides of defective transformer indoor/outdoor installed PCC foundation of any capacity up to 500KVA and then drainage of transformer oil. upto bushing Opening of top cover and find out leakage/sepage of transformer oil from body / fins carrying out required repairs such as replacement of top gasket, HT/LT bushing, bushing gaskets/tap changer and rifillig the transformer oil after repair complete all as specified and directed . Note :- Cost of bushing, top cover gasket and tap changer will be measured and paid separately under relevant items of the Sch ‘A’

6

-

-

... More
Material and labour for replacement of worn out rubberized cork sheet 4mm thick for transformer top cover all as required at site and as directed by engineer in charge suitable for transformers of capacity 100 to 400 KVA all as specified and directed .

5

-

-

... More
All as per item No. 63 above but the transformer of capacity 500 to 800 KVA all as specified and directed .

5

-

-

... More
Dehydration/filtration of transformer oil by means centrifuging machine electrically operated to remove moisture and chemical contains of oil at site of installation of transformer in running condition including testing of transformer oil before and after filtration by means of oil testing machine, keeping the electrodes at 2.5 mm gap and to achieve die electric strength of filtered oil 60 KV and above complete all as specified and directed by Engineer in charge.

12000

-

-

... More
Transportation of transformer to workshop from site of installation for repairs including loading and unloading of transformer, and reinstalled the transformer at site from where it was taken for repairs including connecting all HT/LT connections complete all as specified and directed by Engineer in charge.

4

-

-

... More
Supply and topping up/replaced of transformer oil conforming to IS : 335 and with stand dielectric strength of 60 KV (when tested with 2.5 Gap electrode) in transformer complete all as specified and directed by Engineer in charge.

1600

-

-

... More
Preparation of old surface of transformer for painting externally including fins/radiators removal of all rust/oil/grease and unwanted material and then two coats of synthetic enamel paint by means of spray gun at site of installation of transformer including writing SM No. & Cap of transformer complete all as specified and directed by Engineer- in- Charge suitable for transformers of capacity 100 to 400 KVA all as specified and directed .

25

-

-

... More
All as per item No. 68 here in before but the transformer of capacity 500 to 800 KVA all as specified and directed .

13

-

-

... More
Material and labour for replacement of worn out breather with silica gel all as per existing sample suitable for transformers of capacity 100 to 400 KVA. Make: Jaypuri Brother /Pactil all as specified and directed .

30

-

-

... More
All as per item No. 70 here in before but the transformer of capacity 500 to 800 KVA all as specified and directed .

20

-

-

... More
Material and labour for replacement of worn out off load tap changer set and connecting with existing windig to match the ratio of tap position all as per existing sample suitable for transformers of capacity 100 to 400 KVA all as specified and directed .

7

-

-

... More
All as per item No. 72 here in before but the transformer of capacity 500 to 800 KVA all as specified and directed .

6

-

-

... More
Material and labour for oil temperature gauge suitable for transformers all as per existing shape and size for any make and model transformers all as specified and directed incl taking out old gauge all as specified and directed .

4

-

-

... More
Supply, installation, commissioning and testing of air break switch gang operated HT 11 KV triple pole outdoor type with 12 insulator 200 Amps rating with drop out fuse assly with fuse carrier and the fuse element mounted on insulator and steel frame mechanically operated with operating mechanism consisting of operating rod of 25mm bore light grade GI pipe of suitable length operative from ground level and with locking arrangement with MS flat iron clamp 50 x 6 mm including MS channel of suitable size and length to fixing GOD including nuts, bolts and washers all as specified and directed (25mm GI pipe shall be mesured seperately)

14

-

-

... More
Dismantling and opening of existing servo voltage stablizer 100 KVA to 250 kVA with disconnection of all incomming and outgoing connection with taking proper safety measure , drain out insulating oil if reqd and servicing of stabilizer inluding greasing of the machanical gear, servicing of motor with replacement of mechenical parts , replacement of all wiring and PCB circuits for maintaining input variation between 340 V to 460 V with output voltage stablized at 415 with accuracy +(-) 2.5% and speed of correction 8 V per Second replacing the digital voltmeter and Ammeter, auto adjustment setting complete . Note:- The rate quoted against this item shall include:- (i) Testing and adjusting of springs, contacts, all control circuits . (ii) The cost of any minor parts such as springs, nuts, bolts, terminal blocks etc which are not included in the Sch 'A' item above (iii) Any brazing and welding if need to the control system or the body

2

-

-

... More
Supply only Micro processor based control card suitable for 150 to 180 KVA Make- Volina/AE/Vinitek

2

-

-

... More
Dimmer stat unit 200 Amps suitable for 180 KVA Servo stablizers existing make and model Make- Volina/AE/Vinitek

2

-

-

... More
Electronic circuit card (PCB)suitable for 180 KVA Servo stablizers Make- Volina/AE/Vinitek

2

-

-

... More
Material and labour for in replacement of spreading/ levelling coarse broken stone aggregate of 40 mm size evenly in Switch Yard and surroundings of transformer complete all as specified and directed.

50

-

-

... More
Supply and fixing cable route indicator made out of pcc 1:2:4 of size length 30 cm , width/thickness- 15 cm and Height -100cm reinforeced with 8 mm dia at 8 cms centre to centre on LT cable 1 mtr depth grouted in the ground with suitable PCC work with writing MES HT cable joint complete all as directed.

50

-

-

... More
Supply and fixing Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed.

45

-

-

... More
M & L for earthing complete with copper earth plate electric 60 cm x 60 cm x 3.15mm buried directly and vertically in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to Copper strip 20 x 3 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and including necessary earth work execution in any type of latent rock, PCC 1:3:6 type C2 chamber and chamber cover 50mm (PCC 1:2:4) with 8 mm dia CTD reinforcement watering pipe 20mm dia GI, protection pipe for copper strip 40mm dia GI light grade, salt, coal, magnesium sulphate and water funnel etc complete all as per electrical plate No 4 of SSR Part I complete all as spd and directed by Engr-in-Charge .

16

-

-

... More
M&L for earthing in replacement of with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip 32x6mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge.

15

-

-

... More
M&L for preparation of old painted for chain link/Barbed wire fencing/gate/angle iron/PCC post of sub station (outer exposed surface) painting starts from above ground level including MS channel / angle iron and GI bracket/clamps with bolts, nuts and applying two coat of aluminium paint / snowcem including writing substation details with black colur of existing size letters all as specified and as directed.

60

-

-

... More
Cutting existing road / foot path bituminous macadam and PCC on foot path for laying protection pipe for cable and making good the disturbed surfaces of road/ foot path to match with the existing surface all as required , specified , and directed at site by Enge-in-charge. Note: PCC wil be measured and paid seperately

3

-

-

... More
Dismantling posts or struts (wood steel or RCC) any section including taking out embeded portion of concrete and making good disturbed in ground

40

-

-

... More
Dismantling old chain link/barbed fencing of any size or mesh

150

-

-

... More
Dismanlting wrought iron or mild steel work of any description not otherwise provided for

2

-

-

... More
Framed brackets of angles or tees with web and flanges cut to shape, drilled and ountersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under 'Structural Steel')

250

-

-

... More
M&L for synthetic enamel paint over a coat of red oxide primer. Preparation of new surfaces of steel and iron surfaces of any description over 10cm in width or grith.not otherwise described.

10

-

-

... More
Supply and fixing chain link fencing 4mm dia galvanised steel wire 150x100mm mesh, made upto including wire mesh any size etc. including provision of binding wire.

150

-

-

... More
S&F mild steel chequered/MS plates 5 mm thick or over in thickness avilable size duly painted with two coat of black bituminous paint over one coat of red oxide primer and cut to shape for cable duct complete.

7

-

-

... More
S&F in replacement of 2.5 mm thick insulated synthetic mat conforming to IS 15652 : 2006 and meeting the requirements of IS : 5216 (Part 1.2 & 3), IS 8437, IFC-479 Pub-1, alongwith suitable adhesive/chemical bound, PU resin, waterproofing compound and sealing material as per in service recommendation of IS : 15652 Class-B suitable for working voltage up to 11 KV with trolley movement complete all as specified and as directed .

14

-

-

... More
Removing of old paint by removers scrubing from HT steel poles 11 mtr, cross arms clamps etc for painting and M &L for painting with one coat of superior quality aluminum paint on exposed surface of poles including clamps and cross arms mounted on the poles and MS sections as under making black strip upto1.5 Mtr height from ground level and writing pole Nos etc. written on it with black synthetic enamel paint compete all as specified and directed

90

-

-

... More
Supply and fixing of smart intergaded smart bright , all in one solar street light with infra Red Remote 24 Watt with built in mono crystaline panel, Lithium ferro phospate ( Lite PO 4 ) Battery, MPPT charge controllaer and PIP Sensor with colour tempreture 6000-6500 K complete all as specified and directed.

5

-

-

... More
Supply and fixing LED street light 70 watt 230 V AC out-door type with high pressure die cast aluminium hosing and heat resistant complete with driver , lamp bracket with impact and corrosion ressistant including thermal management in multiple optics complete with IP 65/66 protection , fixed to pole or wall of building with and incuding suitable bracket made out of 32 mm dia GI light grade pipe, 1.20 M long bend to shape by cutting and welding as required and directed and fixed with two Nos of FI clamps 35 x 6 mm to be lightened with suitable size of bolts , nuts and washers and including painted with two coat of aluminium paint over a coat of red oxide primer and including connecting the fitting to electric source with and including twin twisted copper flexible wire of size 2.5 Sqmm three core with flexible PVC conduit including all acessories and fixing arrangement for fixing complete all as specified and directed

50

-

-

... More
Triming of tree branches upto 150 mm thick and around 01 mtr HT/LT OH line complete all as specified and directed

310

-

-

... More
Supplying and fixing MCCB, 630 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 50 KA with adjustable load setting, thermal magnetic release complete all as directed.

2

-

-

... More
Supplying and fixing MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 KA with adjustable load setting, thermal magnetic release complete all as directed.

3

-

-

... More
Supplying and fixing MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 35/36 KA with adjustable load setting , thermal magnetic release complete all as directed.

6

-

-

... More
M&L for stay assembly complete comprising of 7/3.15mm galvanized stay stranded wire of required length to pole with and including flat iron clamp bolt, nuts and washers etc. including galvanized 14mm dia 400mm long stay bow with 20mm dia 215 cm and long stay rod with threaded ends G.I. nuts and washers galvanized steel plate of size 300x300x 6mm thick , 2 Nos thimble, MS clamps made out of 50 x6 mm flat iron loop insulator 90mmx140mm dia hole, 25mm porcelain complete all as specified and shown in electrical plate No. 1 of SSr Part-I including earth work, PCC complete all specified and directed.

25

-

-

... More
M & L for surface dressing n.exc 15cm deep in sooft/ loose soil complete all as specified and directed.

768

-

-

... More
M&L for 25 mm thick sand cushion layer for laying complete all as specified and directed.

20

-

-

... More
Material supplied only nominal size 20 mm graded coarse aggregate complete all as specified and directed.

20

-

-

... More
M&L for 100 mm thick Cement concrete type C-2, 1:3:6 (using 40 mm graded stone aggregate) in sub base of flooring/ hard standing finishing surface even and rough using broom finish complete all as specified and directed.

190

-

-

... More
M&L for Providing and laying 60mm thick factory made chamfered edge cement concrete coloured paver block of M-35 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of coarse sand,compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand;complete all as specified and directed.

190

-

-

... More
M&L for providing PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in coping, bands, benching and other similar works including use and waste of necessary form work complete all as specified and directed.

3

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.