Military Engineer Services Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date16 Oct 2024
Closing Date6 Nov 2024
Tender Amount₹ 37,67,700
Costs
EMD
₹ 75,400Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_679702_1Bid Award Id
ViewTender No
9734/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Re-laying of old serviceable bricks as in cable protection cover, laid flat and dry in trenches over the cable length of brick laid prependicular to the direction of cable complete all as specified and as directed. Note:- Old serviceable bricks obtained from item here-in-before shall be used under this item.
2
-
-
... More
M&L for local sand coushioning with dry and clean over and under the cable for protection of cable , 80 mm sand laid before laying the cable 150 mm sand after laying the cable and filling the sand in cable duct of inside the sub station building complete all as specified and as directed.
24
-
-
... More
S & F in repair of double wall corrugated pipes with sockets as per IS 16025 Part 24 of following sizes-
-
-
-
... More
DWC pipe (6mtr length) of 63 mm of outer dia and 50 mm inner dia complete all as specified and directed.
1250
-
-
... More
DWC pipe (6mtr length) of 120 mm of outer dia and 102.5 mm inner dia complete all as specified and directed.
450
-
-
... More
Taking out old serviceable/unserviceable LT UG cables of size 10 to 95 Sq mm 3.5/4 Core from trenches, poles/walls/ducts and floor including taking out old unserviceable/serviceable bricks covers/GI pipe of any size from trenches for removing or re-laying (after necessary repair/jointing) the cable complete all as specified and as directed.
1825
-
-
... More
Taking out old serviceable/unserviceable LT/HT UG cables of size 120 to 400 Sq mm 3/3.5/4 Core from trenches, poles/walls/ducts and floor including taking out old unserviceable/serviceable bricks covers/GI pipe of any size from trenches for removing or re-laying (after necessary repair/jointing) the cable complete all as specified and as directed.
450
-
-
... More
Laying only and connection of serviceable XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of following sizes laid in trenches or fixed on walls/floor/pole complete all as specified and as directed.
-
-
-
... More
10 sqmm to 70 Sqmm 3.5/4 core complete all as specified and as directed.
210
-
-
... More
95 sqmm to 400 Sqmm 3.5/4 core complete all as specified and as directed.
240
-
-
... More
Supply and Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of the following sizes laid in trenches or fixed on wall/floor/poles complete all as specified and as directed :-
-
-
-
... More
10 Sq mm 4 core complete all as specified and as directed.
510
-
-
... More
25 Sq mm 3.5 core complete all as specified and as directed.
505
-
-
... More
50 Sq mm 3.5 core complete all as specified and as directed.
350
-
-
... More
70 Sq mm 3.5 core complete all as specified and as directed.
250
-
-
... More
95 Sq mm 3.5 core complete all as specified and as directed.
210
-
-
... More
M&L for drilling suitable dia horizontal bore holes for insertion/ laying of 80 mm bore GI tubing of any description below/under existing road surfaces / floors at a level not less than 0.60 mtr etc with using mechanical / or manual devices as required at site including making good the disturbed surfaces to match with the existing after laying pipes complete all as specified and directed by Engineer-in-Charge. Note : (i) Cost of equipment tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor at no extra cost to the Govt.
30
-
-
... More
M & L in replacement for HDPE pipe double wall corrugated 40 mm inner dia with all fitting laid in bore holes/trenches/drian/culvert or fixed along with pole/wall etc complete all as specified and as directed.
30
-
-
... More
M&L for dismantling the cable connection of four pole ACB of capacity upto 1250 Amp, 415V 50Hz of as per existing make, strip opening the ACB, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance:- (a) Cleaning the insulation parts including bushing with with CTC solution. (b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer’s instructional manual. (c) Check the bolts,nuts,washers,cotter pins and all terminal connections are in place and tightening and replacement of the worn out parts. (d) Check arc chutes for damage. (e) Clean and lubricate the operating mechanism with a non-hardening grease for the wearing surfaces, Adjust breaker operating mechanism all as per manufacturer’s instructional manual. (f) Checking/inspecting shunt trip coil for serviceability and replacing the same if required. (g) checking control device free for operation. (j) Check after servicing the circuit breaker to verify the contacts move to fully opened and fully closed positions, that ther is an absence of friction and that the electrical operation is functional. Note: The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like shunt release & trip coil etc will be measured & paid separately under relevant schedule items.
4
-
-
... More
Supply only spring charging motor suitable for ACB of 630 A to 1250 Amps as all per existing complete all as specified and as directed.
2
-
-
... More
Supply only arcing contacts (fixed/moving) suitable for ACB of 630 A to !250 Amps as all per existing complete all as specified and as directed.
1
-
-
... More
Supply only arc chutes (for 415 V) suitable for ACB of 630 A to !250 Amps as all per existing complete all as specified and as directed.
1
-
-
... More
Supply only shunt release (240/415V AC) or suitable for ACB of 630 A to 250 Amps as all per existing complete all as specified and as directed.
1
-
-
... More
Supply only cluster contact suitable for ACB of 630 A to 250 Amps as all per existing complete all as specified and as directed.
1
-
-
... More
Supply only trip coil or suitable for ACB of 630 A to 250 Amps as all per existing complete all as specified and as directed.
3
-
-
... More
M & L for fault detection through machine to detect and rectify underground LT cable fault including disconnecting the cable and rectify the fault including necessery earth work and reconnected to the existing postion complete all as specified and directed. Notes for item 20 : (i) All T&P and other acceseries required for checking and finding of fault in cable shall be provided by the Contractor (ii) Charges/rent of the fault locating mobile machine, operator, engineer, electricians etc shall be deemed to included rate quoted by Contractor.
8
-
-
... More
Supply and fixing MCCB thermal magnetic adjustable type 80 to 100 % of the following sizes on existing LT panel board including dismantling and taking out of old unserviceable MCCB from the LT panel board complete all as specified and as directed
-
-
-
... More
MCCB 4 pole , 630 amp rating of 36 KA.
3
-
-
... More
MCCB 4 pole , 400 amp rating of 36 KA.
4
-
-
... More
MCCB 4 pole , 250 amp rating of 25 KA.
5
-
-
... More
MCCB 4 pole , 200 amp rating of 25 KA.
5
-
-
... More
MCCB 4 pole , 160 amp rating of 16 KA.
5
-
-
... More
MCCB 4 pole , 125 amp rating of 16 KA.
6
-
-
... More
MCCB 4 pole , 100 amp rating of 16 KA.
6
-
-
... More
M&L for straight through jointing kit suitable for LT 1100 volts cable (earthed) for out door , heat shrinkable type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable complete all as specified and directed of the following sizes :-
-
-
-
... More
25 to 50 Sqmm 3.5 core.
5
-
-
... More
70 to 120 Sqmm 3.5 core.
5
-
-
... More
150 to 240 Sqmm 3.5 core.
2
-
-
... More
M&L for End jointing kit suitable for LT 1100 volts cable (earthed) for out door , heat shrinkable type complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable complete all as specified and directed of the following sizes :-
-
-
-
... More
25 to 70 Sqmm 3.5 core.
10
-
-
... More
95 to 185 Sqmm 3.5 core.
15
-
-
... More
240 to 400 Sqmm 3.5 core.
10
-
-
... More
Supply, installation, testing and commissioning in replacement of feeder pillar box, kisok outdoor type floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3.15 mm thick outer cell and 2mm thick ineer cell, MS sheet CRCA sheet on angle iron 50x50x6 mm frame of size suitable to incorporate following accessories with front and rear opening doors, fully compartment wise , having seven tank treatment process with thickness not less than 60microns with paint shade RAL 7035 provided with suitable gasket to make it dust/vermin proof, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on pcc foundation of size as required or approved by manufacurers in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by Engr-in-charge including earth work complete comprising of following:-
1
-
-
... More
INCOMING (a) MCCB capacity 630 amp, 4 pole, 415V, 36 KA , Ics=Icu=100% Thermal magnetic adjustable type , - 1 No.
(b) Busbar chamber comprising 4 Nos made of aluminium strip of capacity 900 Amps with PVC insulated & PVC sheathed with colour coding.
(c) Multifunction digital panel meter with LCD display flush mounting type of size 96x96 mm, accuracy class 1, suitable for CTs with secondary current 5A-01 Nos.
(d) Indicator lamp LED based (RYB) - 01 Nos.
OUTGOING
(a) MCCB capacity 400 amp, 4 pole, 415V, 36 KAThermal magnetic adjustable type complete with spreader links - 01 No.
(b) MCCB capacity 200 amp, 4 pole, 415V, 25 KA Thermal magnetic adjustable type complete with spreader links - 01 No.
(c) MCCB capacity 160 amp, 4 pole, 415V, 16 KA Thermal magnetic adjustable type complete with spreader links - 01 No.
(d) Spare - 01 No All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for circuitss as per standard engineering practice and required at site.
-
-
-
... More
Supply, installation, testing and commissioning in replacement of feeder pillar box, kisok outdoor type floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3.15 mm thick outer cell and 2mm thick ineer cell, MS sheet CRCA sheet on angle iron 50x50x6 mm frame of size suitable to incorporate following accessories with front and rear opening doors, fully compartment wise , having seven tank treatment process with thickness not less than 60microns with paint shade RAL 7035 provided with suitable gasket to make it dust/vermin proof, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on pcc foundation of size as required or approved by manufacurers in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by Engr-in-charge including earth work complete comprising of following:-
1
-
-
... More
INCOMING (a) MCCB capacity 630 amp, 4 pole, 415V, 36 KA , Ics=Icu=100% Thermal magnetic adjustable type , - 1 No.
(b) Busbar chamber comprising 4 Nos made of aluminium strip of capacity 900 Amps with PVC insulated & PVC sheathed with colour coding.
(c) Multifunction digital panel meter with LCD display flush mounting type of size 96x96 mm, accuracy class 1, suitable for CTs with secondary current 5A-01 Nos.
(d) Indicator lamp LED based (RYB) - 01 Nos.
OUTGOING
(a) MCCB capacity 320 amp, 4 pole, 415V, 36 KA Thermal magnetic adjustable type complete with spreader links - 01Nos.
(b) MCCB capacity 200 amp, 4 pole, 415V, 25 KA Thermal magnetic adjustable type complete with spreader links - 02 Nos. (c) MCCB capacity 100 amp, 4 pole, 415V, 16 KA Thermal magnetic adjustable type complete with spreader links - 01 Nos. All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for circuitss as per standard engineering practice and required at site.
-
-
-
... More
Supply, installation, testing and commissioning in replacement of feeder pillar box, kisok indoor type floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 2 mm thick MS sheet CRCA sheet on angle iron 50x50x6 mm frame of size suitable to incorporate following accessories with front and rear opening doors, fully compartment wise , having seven tank treatment process with thickness not less than 60microns with paint shade RAL 7035 provided with suitable gasket to make it dust/vermin proof, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on pcc foundation of size as required or approved by manufacurers in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by Engr-in-charge including earth work complete comprising of following:-
1
-
-
... More
INCOMING (a) MCCB capacity 400 amp, 4 pole, 415V, 36 KA , Ics=Icu=100% Thermal magnetic adjustable type , - 1 No.
(b) Busbar chamber comprising 4 Nos made of aluminium strip of capacity 600 Amps with PVC insulated & PVC sheathed with colour coding.
(c) Multifunction digital panel meter with LCD display flush mounting type of size 96x96 mm, accuracy class 1, suitable for CTs with secondary current 5A-01 Nos
(d) Indicator lamp LED based (RYB) - 01 Nos.
OUTGOING
(a) MCCB capacity 200 amp, 4 pole, 415V, 36 KA Thermal magnetic adjustable type complete with spreader links - 01Nos.
(b) MCCB capacity 160 amp, 4 pole, 415V, 25 KA Thermal magnetic adjustable type complete with spreader links - 01 Nos.
(c) MCCB capacity 100 amp, 4 pole, 415V, 16 KA Thermal magnetic adjustable type complete with spreader links - 03 Nos. All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for circuitss as per standard engineering practice and required at site.
-
-
-
... More
Supply & fixing in replacement of 400 Amp aluminium busbar outdoor type floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3.15 mm thick outer cell and 2mm thick ineer cell, MS sheet CRCA sheet on angle iron 50x50x6 mm frame of size suitable to incorporate following accessories with front and rear opening doors, having seven tank treatment process with thickness not less than 60microns with paint shade RAL 7035 provided with suitable gasket to make it dust/vermin proof, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on pcc foundation of size as required or approved by manufacurers in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by Engr-in-charge including earth work complete .
6
-
-
... More
Supply & fixing in replacement of 200 Amp aluminium busbar outdoor type floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3.15 mm thick outer cell and 2mm thick ineer cell, MS sheet CRCA sheet on angle iron 50x50x6 mm frame of size suitable to incorporate following accessories with front and rear opening doors, having seven tank treatment process with thickness not less than 60microns with paint shade RAL 7035 provided with suitable gasket to make it dust/vermin proof, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on pcc foundation of size as required or approved by manufacurers in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by Engr-in-charge including earth work complete .
5
-
-
... More
Supply, heating and filling/topping up/replacement of transformer insulating oil EHV grade having dielectric strength not less than 60 KV (R.M.S) at 2.5 mm gap high viscosity in transformer confirming to IS-335 of 1983 complete all as specified and directed.
800
-
-
... More
M&L for disconnecting all incoming and outgoing electric connection of stabilizer upto 250 KVA,opening from top including taking out transformer oil for repair of stablizer and repouring after repair including taking out U/S parts and replaced with new parts under following items -
4
-
-
... More
Supply only following parts for replacement of stablizer parts-
-
-
-
... More
(a) Push button switch
2
-
-
... More
(b) Auto manual switch
2
-
-
... More
(c) DPDT switch
2
-
-
... More
(d) micro switch
2
-
-
... More
(e) Panel lamp
2
-
-
... More
(f) Potentiometer
2
-
-
... More
(g) Voltmeter (Digital/Analog)
2
-
-
... More
(h) Amp meter with C.T. (Digital/Analog)
2
-
-
... More
(j) Electronicc circuit card (P.C.B)
2
-
-
... More
(k) Micro processor based control card for each phase
2
-
-
... More
(l) Trigger Transformer
2
-
-
... More
(m) Servo motor 10 K.G torque
2
-
-
... More
(n) R.C. network for 10KG motor
6
-
-
... More
(o) Service charges upto 150 KVA per unit
2
-
-
... More
M & L for shifting of servo voltage stablizer upto 250 KVA by disconnecting incoming and outgoings and dismantled from existing postion and re-located at new position by connecting incoming and outgoings with all connected accessories complete.
4
-
-
... More
Servicing of LT panel board to check the main incoming LT MCCB , and replace the unserviceable parts and ensure the performance of panel, check the incoming and outgoing MCCBs terminals and removing unserviceable MCCBs, burnt busbars, unserviceable indicator lamps, unserviceable Ammeter, unserviceable Volt meter and fixing proper hanging front and rear openings replace burnt thimples with new, ensure that there is no loose connection on panel, providing cable glands including taking out cable from tenches/loop and reconnect in same after repair for as per required quantity and marking locations of out going feeder complete all as specified and as directed. Note :- Spare parts shall be paid separately as supply only under respective items.
5
-
-
... More
Supply only of multifunction meter suitable for measuring volt, Ampere, Power factor,frequency fixed in existing LT Panel based including connection etc complete all as specified and directed.
5
-
-
... More
Servicing of static frequency convertor panel to check the main incoming and replace the unserviceable minor parts and ensure the performance of panel, check the fuses, capacitor serviceability and replace burnt parts with new, ensure that there is no loose connection in panel, providing proper connection including checking the serviceablity capacitor bank, control card, RC network etc complete all as specified and as directed. Note- Spare parts shall be renewed and paid separately under respective items.
1
-
-
... More
Supply only IGBT module.
4
-
-
... More
Supply only 3300mfd 350 volts capacitor bank.
8
-
-
... More
Supply only 3 phase control card.
1
-
-
... More
Supply only driver card.
1
-
-
... More
Supply only RC network.
1
-
-
... More
Supply only 3 phase DC card.
1
-
-
... More
Servicing of APFC panel to check the main incoming LT MCCB, and replace the unserviceable parts and ensure the performance of panel, check the fuses, capacitor serviceability and replace burnt parts with new, ensure that there is no loose connection in panel, providing proper connection including taking out cable from trenches/loop and reconnect in same after repair for as per required quantity complete all as specified and as directed. Note- Spare parts shall be paid separately as supply only under respective items.
4
-
-
... More
Supply only HRC fuse link of capacity 2A to 32A.
8
-
-
... More
Supply only HRC fuse link of capacity 40A to 63A.
8
-
-
... More
Supply only capacitor of size 10 to 20 KVAR, 440V.
15
-
-
... More
Supply only relay of capacity 40A.
4
-
-
... More
Material & labour for replacement only earthing with galvanised steel earth plate electrode 60cm x 60cm x 6.00mm thick burried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip of 32x6 mm as earthin lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by medium 40 mm dia GI pipe connected to main switch board or main control board or equipment and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, 40mm thick RCC pit cover reinforced with 8mm dia TMT bar at 75c/c both ways and lifting arrangement by providing handles (02 Nos) of 12mm dia MS round bar and PCC chamber pit with PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) including excavation and earth work in soft/loose soil, returning, filling in with excavated soil and disposal of surplus spoil to a distance not exceeding 50m and shown in electrical Plate No 3 of SSR 2009 (Part-I) complete all as specified and directed.
18
-
-
... More
Supply and fixing in repair of LED road way light fitting luminaires ,comprising of epoxy powder coated housing ,enclosed with glass cover in frame , IP-65, 60 watt LED with 110LM/W complete all as specified and directed.
25
-
-
... More
Supply and fixing in repair of LED road way light fitting luminaires ,comprising of epoxy powder coated housing ,enclosed with glass cover in frame , IP-66, 90 watt LED with SPD 10 KV , efficiency 110LM/W complete all as specified and directed.
10
-
-
... More
S&F in repair for pole factory made, dust proof, vermin proof , out door type Polycarbonate boxs not less in size 200x300x105 incl MCB SP 6 Amps,, 4 nos aluminium bus bar, insulator,GI nut, bolts and washers and aluminum lugs etc with and including FI clamp made out of 30 mmx 3 mm , nut and bolts complete all as specified and directed.
35
-
-
... More
S&F in repair Street light bracket made out of 32 mm dia GI light grade pipe 1.2 mtr long bend to shape 120 degree and duly fixed alongwith existing pole/bldg with the help of 2 Nos of MS clamp of sizes 32x3 mm including suitable size of bolt ,nuts, and washers complete all as specified and directed.
35
-
-
... More
M & L in replacement for twin core aluminium conductor 2.5 sqmm PVC insulated , shethed wire complete all as specified and directed.
350
-
-
... More
S&F in replacement rigid GI conduit 20 mm dia and duly fixed alongwith existing pole/bldg with the help of 2 Nos of MS clamp of sizes 32x3 mm including suitable size of bolt ,nuts, and washers complete all as directed by EIC.
210
-
-
... More
M&L for PCC (1:2:4) type B1 using 20 mm gradded stone aggregate for coping of poles, panel board etc complete all as specified and as directed.
3
-
-
... More
Supply, erecting and fixing in repair true vertical position, steel tubular swaged pole (410 SP-31), 09 meter long, complete with cast iron base plate, pole cap/finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be painted with two coats of aluminium paint over a coat of red oxide primer including painting blue(sky blue) strips of 15 cm width in alternate layers up to 1.2 mtr above the ground level complete all as specified and directed.
Note : Excavation, Earth work and PCC etc shall be measured and paid separately.
10
-
-
... More
Preparation of surface of LT steel poles 9 meter long, cross arms clamps etc for painting and M &L for painting with one coat of superior quality aluminum paint on exposed surface of poles and street light bracket mounted on the poles,junction box etc and making black strip upto1.5 Mtr height from ground level and writing pole Nos etc. written on it with black synthetic enamel paint compete all as specified and directed
150
-
-
... More
M&L for spray painting of feeder pillar boxes complete with existing colour one coat of primer and two coat of synthetic enamel paint by spray painting to achiev smooth and uniform finish incl removal of existing paint,filling up cavities and writing of MES no with black paint complete all as specified and directed
10
-
-
Evaluation Notes How It Works ?