Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date2 Jan 2025
Closing Date29 Jan 2025
Tender Amount₹ 23,00,000
Costs
EMD
₹ 46,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_691391_1Bid Award Id
ViewTender No
CWE/NAVY/ARK/87708/E8 OF 2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Taking out burnt primary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 100 KVA to 160 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt primary including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 200KVA to 250 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt primary including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 315 KVA to 400 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt primary including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 500KVA to 630 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt secondary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 63 KVA ncluding new insulation complete all as specified and directed .
1
-
-
... More
Taking out burnt secondary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 100KVA to 160 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt secondary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 200KVA to 250 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt secondary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 315 KVA to 400 KVA including new insulation complete all as specified and directed
1
-
-
... More
Taking out burnt secondary winding including rewinding the same with super enamelled copper wire with existing gauge of capacity of transformer 500KVA to 630 KVA including new insulation complete all as specified and directed
1
-
-
... More
Material and labour for calibration of HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/type including relay,tripping mechanism etc as per standard/ specified / directed by OEM certified agency and submitting report all as specified and as directed.
10
-
-
... More
Material and labour for servicing, overhauling HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/type and checking door lock system, checking for phase sequence, mechanical and electrical interlocking system, complete wiring checking of relays, trip coil, spring charge motor, closing coil etc, tightening all the mechanical and electrical joints complete and writing with paint the Feeder name and checking the functionality in position after servicing complete all as specified and as directed.
Note:
(i) Quoted rate includes S&F all minor spares and wires required during servicing. (ii) Replacement of unserviceable major spare parts shall be measured and paid separately as supply only under relevant items here-in-after however fixing charges/labour cost for the spares to be included in the rate quoted for item No-15 .
10
-
-
... More
Supply only the following spare parts for HT VCB panel complete 11 KV 400-800 Amps, upto 500 MVA of various make/typeall as specified and as directed NOTE: labour cost for taking down old u/s item and fixing of following new items deemed to be included in Rate quoted for item No-14 here-in-before
-
-
-
... More
11kv tripping coil assy double trip 30v DC
2
-
-
... More
11kv Closing coil assy 30v DC
2
-
-
... More
11kv porcelain insulator
2
-
-
... More
11kv spring charging motor 230v AC
2
-
-
... More
Battery 2 volt 25 AH for battery bank of 110 volt 200 AH at 4 hanger
55
-
-
... More
Emergency push button
2
-
-
... More
Handle with locking arragement
4
-
-
... More
Thermostat
4
-
-
... More
Under voltage relay
2
-
-
... More
3 phase auxiliary relay 24/110/220v
2
-
-
... More
Supply and replacement of old and unserviceable phase indication lamps with LED 110 Volts suitable for HT VCBs as per site requirement complete all as specified and directed
8
-
-
... More
Material and labour for collecting the transformer oil from the transformers at site and sending the same to approved lab for testing of BDV and Acidity and submission of reports to Deptt including necessary T&P complete all as specified and directed.
25
-
-
... More
Material and labour for de-hydration and filteration of transformer oil through on load mobile stream liner transformer oil filteration plant at various site and various capacity installled at pole, floor, plinth mounted with all accessories connected to transformer to carrying out filteration of oil for desired dielectric strength all as per IS-335 i.e not less than 60 KVA at 2.5mm gap including testing after filtration complete all as specified and directed.
12000
-
-
... More
Supply , filling and topup of transformer oil of various capacity transformer pole mounted / floor mounted BDV should as per IS 335 complete all as specified and directed.
200
-
-
... More
Material and labour for disconecting the HT & LT supply from transformer, removing of top cover along with vent pipe joints, clean / flushing the core assembly by applying new oil through filteration plant and checking for loose connections, tap changer point HT / LT , connecting terminals and oil leakages at all joints, replacing of gaskets,oil seal HT & LT insulator bushings, HT terminal studs and acrylic sheet indicator along with rubber gasket after checking the insulation resistance value by 1000V megger and record the IR value of HT to earth and LT to earth, reconnect HT & LT supply line , commissioning in all respects complete all as specified and directed for the following transformers. Note :- Spares such as HT / LT insulator, bush, HT / LT terminal, brass studs , gasket, transformer oil for cleaning the core & shell shall be measured & paid separately under relevant items.
-
-
-
... More
Pole /Floor mounted 63 KVA Transformer.
2
-
-
... More
Floor mounted 100 KVA to 160 KVA Transformer
4
-
-
... More
Floor mounted 200 KVA to 250 KVA Transformer
2
-
-
... More
Floor mounted 315 KVA to 400 KVA Transformer
2
-
-
... More
Floor mounted 500 KVA to 630 KVA Transformer
4
-
-
... More
Supply and replacement of silica gel of superior quality of 5 to 10 mm grade complete all as specified and directed.
30
-
-
... More
Material and labour for Set of 3 HV rods along with oil gasket & oil seal and set of 4 LT terminal rod along with gasket and oil seal, transformer of capacity upto 160 KVA all as specified and directed
1
-
-
... More
Material and labour for Set of 3 HV rods along with oil gasket & oil seal and set of 4 LT terminal rod along with gasket and oil seal, transformer of capacity upto 400 KVA all as specified and directed .
1
-
-
... More
Material and labour for Set of 3 HV rods along with oil gasket & oil seal and set of 4 LT terminal rod along with gasket and oil seal, transformer of capacity 500 KVA to 630 KVA all as specified and directed
2
-
-
... More
Material and labour for replacement of breather assembly transparent PVC body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia as per site requirement/capacity of transformer upto 630 KVA complete all as specified and directed
4
-
-
... More
Material and labour for replacement of breather assembly transparent MS body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia as per site requirement /capacity of transformer upto 1000 KVA complete all as specified and directed .
2
-
-
... More
Supply and fix gun metal glob or gate valve iron wheel head , GM ISI marked suitable for for 25 mm dia bore of pipe screwed both ends for iron pipe or for socket or union of various capacity transformer drain valve complete all as specified and directed .
2
-
-
... More
Material and labour for replacement the explosion vent diaphragm suitable size as per sample complete all as specified and approved complete all as specified and directed .
2
-
-
... More
Material and labour to carry out test and identify exact location and nature of defect in 11 KV HT UG cable any size/type using cable fault locator/equipment including finding of cable route as per site requirement including transportation, testing after rectification and restoring of the supply in all respects and commissioning etc complete all as specified and as directed.
Note : Earth work, cable joints as per site requirement shall be measured and paid separately under relevant item of the schedule.
2
-
-
... More
Material and Labour for meggering existing HT UG cable of any size to find out fault for rectification from any location at NAS INS Rajali station after disconnection of cabel from both termination end including terminate both end after rectification of cable (Cable joint kit , excavation, relaying, will be measured and paid separately under relavant items) complete all as specified and as directed
8
-
-
... More
Taking up old /existing unserviceable defective HT 11000V UG Cable of size 185 sqmm 3 core from the existing trenches/ near panels and keep a side carefully and segrigating serviceable portion of cable for reuse / incorporating in the site complete all as specified and as directed.
Note Earth work shall be measured and paid separately.
100
-
-
... More
All as per item No 31 above but for 95 sqmm 3 core complete all as specified and as directed.
90
-
-
... More
Supply, laying, testing for replacement against unserviceable part of item No 31 here-in-before XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 185 sqmm 3 core complete all as specified and directed.
50
-
-
... More
Supply, laying, testing for replacement against unserviceable part of item No 32 here-in-before XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 95 sqmm 3 core complete all as specified and directed .
40
-
-
... More
Relaying of serviceable portion XLPE insulated 11000V HT heavy duty aluminium conductor, 11000 volts grade cable 185 sqmm 3 core size taken up from item 33 here-in-before all as per site requirement complete all as specified and directed
50
-
-
... More
Relaying of serviceable portion XLPE insulated 11000V HT heavy duty aluminium conductor, 11000 volts grade cable 95 sqmm 3 core size taken up from item 34 taking down here-in-before all as per site requirement complete all as specified and directed
50
-
-
... More
M&L for Cutting the existing road for 0.30M width , 0.60M depth for laying cable incl excavation in any type of soil, returning filling , removal and including Material and labour PCC 1:4:8 type D2 (40mm graded aggregate) of 15 cm thick for making good the disturbed road portion all as directed and specified. (Note:GI pipe with all fittings shall be measured and paid under the respective item)
4
-
-
... More
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for taking out /for laying under ground cables/pipes etc and getting out in soft/loose soil complete all as specified and directed
60
-
-
... More
Dismantling and taking down existing PCC cable cover from existing location of cable trench and keep it safe custody for refix the good conditional cable cover the same location complete all as specified and as directed.
550
-
-
... More
Supply and laying unreinforced pre cast concrete cable cover class HV type 1 flat size 300 x 180 x 40 mm for cable protection complete all as specified and as directed
350
-
-
... More
Relaying in trenches serviceable un-reinforced precast concrete cable cover, retrieved from site complete all as specified and as directed
200
-
-
... More
Spreading, leveling riddled earth as obtained in cable trenches all as specified and directed
13
-
-
... More
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed
36
-
-
... More
Removing excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed
24
-
-
... More
Material and labour for replacement of GI tube light grade 100 mm with all fittings complete for cable protection near poles,installations, trenches and road crossing complete including taking up old GI Pipe all as specified and directed
6
-
-
... More
Material and labour for galvanized iron tubing 50 mm bore light grade with all fitting laid in wall/floor/under road/culvert/on pole for protection of earth strip including taking down and providing fixing clamps, bolts and nuts of suitable size as required all as specified and as directed.
12
-
-
... More
Supply and fix replacement cable jointing kit for 11 KV grade (Earthed) cable for indoor type end termination through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sq mm including taking up old unserviceable cable, cutting/taking out joint etc complete all as specified and as directed
2
-
-
... More
Supply and fix replacement cable jointing kit for 11 KV grade (Earthed) cable for indoor type end termination through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sq mm including taking up old unserviceable cable, cutting/taking out joint etc complete all as specified and as directed
2
-
-
... More
Supply and fix replacement cable jointing kit for 11 KV grade (Earthed) cable for straight through heat shrink joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm including taking up old unserviceable cable, cutting/taking out joint etc complete all as specified and as directed
2
-
-
... More
Supply and fix in replacement cable jointing kit for 11 KV grade (Earthed) cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sq mm including taking up cable, cutting/taking out old unserviceable joint etc complete all as specified and as directed
2
-
-
... More
Servicing the 11 KV GOD by cleaning the contacts, disc / pin insulator with CTC and applying the petroleum jelly at the contact point / down rod links for smooth operation including replacing the rusted / corroded bolts & nuts and defective insulator of GOD as required at site.
Note :- (a) Insulator, male & female contacts ,copper strip shall be measured and paid separately as supply only. (b) labour cost for taking down old u/s component and fixing of following new items deemed to be included in quoted rate.
4
-
-
... More
Supply only Male / Moving contacts ( set of 3 Nos )
2
-
-
... More
Supply only Female / Fixed contacts ( set of 3 Nos )
2
-
-
... More
Supply only Copper tinned strip / Belt ( set of 3 Nos )
2
-
-
... More
Dismantling lightning arrestors of any type of any size and supply and fix 11 kv 65 KA polymer lightning arrester set of three pices including all accessories as per site requirement complete all as specified and directed each complete all as specified and directed
2
-
-
... More
Supply and fix on pole/buried in ground Earth continuity conductor GI strip 32mm x 6mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles.
12
-
-
... More
Material and labour for spray painting the following transformer complete by removing existing oil traces, paint by scraping and applying two coats of approved colour synthetic enamel paint and writing lettering SM / MES No and date of oil tested etc complete all as specified and directed
-
-
-
... More
Transformer of capacity upto 63 KVA 315 KVA
8
-
-
... More
Transformer of capacity 400 KVA to 630 KVA
12
-
-
... More
Transformer of capacity 800 KVA to 1000 KVA
2
-
-
... More
Surface dressing upto 15cm deep in and around transformer yard , four pole, two pole, three pole structure vicinity and clearing of vegetation/soil to a distance not exceeding 50m complete all as specified and as directed
2040
-
-
... More
Material and labour for loose filling and spreading with aggregates/broken stone or boulders 40mm gauge complete all as specified and as directed
14
-
-
... More
Material and labour for repairing the existing eart pit chamber, before removing the existing twisting earth pit sink into the ground, broken rcc cover etc. with replacement of new RCC cover of existing size and improve the earth value with added water and salt and findout the earth value using digital earth tester after disconnection of earth electrode from earth chamber for maintaining the record and fill the data in earth test register incl writing the earth value on earth pit with date of measurement complete all as specified and as directed
20
-
-
... More
Material and labour for Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 m deep below normal ground level, with top edge of the earth plate at a depth of not less than 1.5 mtr below ground connected to GI earth strip 32 x 6mm by means of GI bolts and nuts, washers and GI earth strip protected by GI pipe light grade 50mm bore upto 7.5 mtr and connecting to HT/ LT switch gear etc as per site requirement including necessary excavation, earth work in any type of soil, PCC 1:3:6 type C-1 earth chamber, 40mm thick RCC cover with 6mm dia MS bars 10cm C/C on both ways as reinforcement complete all as shown in electrical plate No 3 of MES Schedule Part 1 (2009) connected to earthing test points complete all as specified and as directed by Engineer-in-Charge. Note :- (i)Quoted rate deemed to include necessary earth work, PCC chamber, RCC cover, reinforcement, removal of surplus soil, site clearance etc. (ii) GI earth strip 32 x 6mm, GI tubing light grade 50mm dia upto 7.5 mtr deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 mtr the GI earth strip 32 x 6mm & GI pipe light grade 50mm dia shall be measured under relevant item of the schedule.
5
-
-
... More
Schedule of credit amount brought back from Ser Page No.32 - Rs.19,956.00 will be deducted from the above quoted amount to derive the contract sum. SIGNATURE OF CONTRACTOR
-
-
-