Military Engineer Services Tender
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Military Engineer Services - MES Tender
Civil And Construction
Eprocure
Opening Date3 Sep 2024
Closing Date7 Oct 2024
Tender Amount₹ 7,17,00,000
Costs
EMD
₹ 6,83,500Document Cost
₹ 3,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_670169_1Bid Award Id
ViewTender No
82493/E8 STP SulurTender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Particular specification 82493
BOQ Items
Note for 500KLD and 100KLD package type MBBR/ SBR STP
(i) The parameters of treated water shall be suitable for arboriculture .The actual raw water(sewage) parameters as per consultancy report is enclosed as Appx ’A’. However Contractor shall collect sample of raw water sewage in presence of GE to analysis of present characterestics of raw sewage and submit the test results to GE before design of STP.
(ii) Design and scheme for STP including electro-mechanical works and civil works shall be designed according to the actual sewage characterestics test results and vetted from IIT/NIT and the vetted design has to be submit for approval of accepting officer prior to execution. Quoted rates are deemed to be included for all these provisions for the entire completion of the project. Nothing extra shall be payable in this regard.
(iii) Collection sump and treated water tank shall be designed and vetted from IIT/NIT and the vetted design has to be submit for approval of accepting officer prior to execution. Quoted rates are deemed to be included for all these provisions for the entire completion of the project. Nothing extra shall be payable in this regard.
-
-
-
Note for 500KLD and 100KLD package type MBBR/ SBR STP Contd/- (iv) The characteristics of effluent after treatment shall conform to the following tolerance limits:
1. pH - 5.5-9
2. Total Suspended Solids 20mg/l 3. BOD (5 days) 10 mg/l
4. COD 50mg/l
5. Ammoniacal Nitrogen 5 mg/l
6. Total Nitrogen 10mg/l
7. Total Phosphorous 1mg/l
8. Oil & Grease 1mg/l
9. Fecal Coliform : Nil 10. Odour : No foul odour
11. Additional facilities required, if any, to achieve the standards laid down by the Sate Pollution Control Board shall also be made along with.
-
-
-
SCHEDULE 'A' PART -IB BUILDINGS/ STRUCTURES (TO BE QUOTED BY THE TENDERER)
(Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only. Bidder shall insert their rate in Green field under column 6)
-
-
-
Construction of Pumphouse building for STPs ( Pump room, Duty room, Verandha including toilet)in single storey with Permanent Specification with RCC M25 framed structure including foundation , fly ash brick masonry walls,ATT,RCC roof slab with PU based water proofing treatment, Aluminium Joinery, Steel rolling shutter, concealed electric and water supply etc complete all as specified and as shown on drawings No. WD/297/2024 sht No. 1/1
Note : - (i)The contractor should design the foundation according to the soil report, Super structure and structural drawings of the same shall be submitted after vetted from IIT/NIT along with design calculation sheet.
(ii) The pumphouse shall be desinged and built according to the architechtural drawings along with schedule of finishes.
(iv) Detailed yard stick along all connected documents shall be submitted before execution of the work for approval of accepting officer. Quoted rates are deemed to be included for all these provisions
2
-
-
GENERAL SUMMARY (Note : Schedule 'A' Part II to IX are prepriced by MES under Ser No. 16 to 20.Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only)
-
-
-
Total of Schedule ‘A’ Part II “SCREW PRESS SHED”
1
-
-
Total of Schedule ‘A’ Part III “ INTERNAL ELECTRIFICATION”
1
-
-
Total of Schedule ‘A’ Part IV “INTERNAL WATER SUPPLY”
1
-
-
Total of Schedule ‘A’ Part V “ PATH”
1
-
-
Total of Schedule ‘A’ Part VI “SEWAGE DISPOSAL”
1
-
-
Total of Schedule ‘A’ Part VII “FENCING/ GATE ”
1
-
-
Total of Schedule ‘A’ Part VIII “EXTERNAL WATER SUPPLY”
1
-
-
Total of Schedule ‘A’ Part IX “EXTERNAL ELECTRIC SUPPLY”
1
-
-
Sch 'A' Part- X- MISCELLANEOUS ITEMS (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only. Bidder shall insert their rate in Green field under column 6)
-
-
-
SEWAGE DISPOSAL
-
-
-
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil complete all as specified and as directed.
4712.49
-
-
Excavating in trenches, exc 1.5 m wide and n exc 3.0m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil complete all as specified and as directed.
1231.99
-
-
Excavating in trenches, exc 3 m wide and n exc 4.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil complete all as specified and as directed.
230.47
-
-
Excavating in trenches, exc 3 m wide and n exc 4.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any soft/disentigrated rock complete all as specified and as directed.
10
-
-
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
3559.56
-
-
Removing excavated material exc. 1.50 km but n exc. 5 km and depositing out side MoD land complete all as specified and as directed.
2323.82
-
-
Removing excavated material (Rock) exc. 1.50 km but n exc. 5 km and depositing out side MoD land complete all as specified and as directed.
10
-
-
S & F DWCPE (SN8) 150 (ID) diameter pipes laid in trenches and jointed as specified
2602
-
-
S & F DWCPE (SN8) 250 (ID) diameter pipes laid in trenches and jointed as specified
1876
-
-
S & F DWCPE (SN8) 150 (ID) diameter elbows laid in trenches and jointed as specified
19
-
-
SCADA SYSTEM FOR NEW STPs AND OLD EXISTING (02 Nos) STPs
-
-
-
Supply, Installation, Testing and Commissioning of Indoor type PLC (CPRI approved) (Programmable Logic Controller) based Slave Monitoring / Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 02 Nos submersible pumps ,04 centrifugal pumps,06 Nos Motorized actuator, 02 Nos Ultra Sonic Level Sensor.
The panel shall consist of the following equipments; (i) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC . (ii) 7" LCD HMI (iii) Transformer with regulated output voltage of 230V +/-5%, (iv) SMPS of Suitable rating (v) Set of Control Relays and suitable MCB (vi) Audio visual generator (vii) Suitable No. of LED Indicators for easy visualisation (viii) Selecetor Swtiches (ix) Push Buttons / Illuminated Push Buttons
(x) 0.5 sqmm multistrand internal wiring with ferruling and suitable lugs. (xi) Ethernet Card 6020 (xii) Media Converter (xiii) Ethernet Switch
(xiv) LIU(Light Interface Unit)box patch chord and mounting accessories with following specification. Communication: Primary- OFC, Stand by: GPRS Location:- STP/GULMOHAR STP/Kiran Area /Near Play Ground
4
-
-
Supply, Installation, Testing and Commissioning of Indoor type PLC (CPRI approved) (Programmable Logic Controller) based Slave Monitoring / Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 02 Nos submersible pumps , 02 Nos Motorized actuator, 01 Nos Ultra Sonic Level Sensor.
The panel shall consist of the following equipments; (i) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC . (ii) 7" LCD HMI (iii) Transformer with regulated output voltage of 230V +/-5%, (iv) SMPS of Suitable rating (v) Set of Control Relays and suitable MCB (vi) Audio visual generator (vii) Suitable No. of LED Indicators for easy visualisation (viii) Selecetor Swtiches (ix) Push Buttons / Illuminated Push Buttons
(x) 0.5 sqmm multistrand internal wiring with ferruling and suitable lugs. (xi) Ethernet Card 6020 (xii) Media Converter (xiii) Ethernet Switch
(xiv) LIU(Light Interface Unit)box patch chord and mounting accessories with following specification. Communication: Primary- OFC, Stand by: GPRS Location:- OLD KALPA,NEWKALPA,MEHRA,GULMOHAR/Near Guard /Near Play Ground-02Nos
7
-
-
Supply, Installing,Testing and Commissioning of Ultrasonic Level Transmitter Range : 0-5 metres Accuracy : 0.5 % minimum Supply Voltage : 24V dc Output : 4-20 mA
14
-
-
Supply, Installation, Testing and Commissioning of Motor Actuated Ball Valve/ butterfly valve(with wheel for manual operation) consisting of suitable single phase Actuator and ball valve/ butterfly valve of size 50 mm dia with appropriate bracket/mounting arrangement including two nos.limit switches for open and closed condition and splash proof enclosure complete all as specified and directed. Specification supply and fixing eatures Input Voltage:230V, A.C. Designed line pressure:10kg/sq cm. Material of Ball:Stainless Steel Limit switches:02Nos For open and close status Mounting:Direct on valves
6
-
-
Supply, Installation, Testing and Commissioning of Motor Actuated Ball Valve/ butterfly valve (with wheel for manual operation) consisting of suitable single phase Actuator and ball valve/ butterfly valve of size 100 mm dia with appropriate bracket/mounting arrangement including two nos.limit switches for open and closed condition and splash proof enclosure complete all as specified and directed. Specification supply and fixing eatures Input Voltage:230V, A.C. Designed line pressure:10kg/sq cm. Material of Ball:Stainless Steel Limit switches:02Nos For open and close status Mounting:Direct on valves
18
-
-
Supply, Installation, Testing and Commissioning of Motor Actuated Ball Valve / butterfly valve (with wheel for manual operation) consisting of suitable single phase Actuator and ball valve/ butterfly valve of size 150 mm dia with appropriate bracket/mounting arrangement including two nos.limit switches for open and closed condition and splash proof enclosure complete all as specified and directed. Specification supply and fixing eatures Input Voltage:230V, A.C. Designed line pressure:10kg/sq cm. Material of Ball:Stainless Steel Limit switches:02Nos For open and close status Mounting:Direct on valves
14
-
-
Supplying and fixing 4 x 1.5 sq. mm. PVC insulated and PVC sheathed amoured copper cable etc as reqd complete all as specified and as directed.
350
-
-
Supplying and fixing 6 x 1.5 sq. mm. PVC insulated and PVC sheathed amoured copper cable etc as reqd complete all as specified and as directed.
450
-
-
Upgradation of Existing SCADA software including creating SCADA screens and soft keys for remote monitorng and operation SPS and STP Panels complete all as specified and as directed.
1
-
-
Supply and fixing in repairs 6F HDPE sheathed armoured uni-tube SM optical Fibre cable with central loose tube with jelly compound and high quality electro chromium coated corrugated steel type laid over head on existing available supports all as specified and directed
2910
-
-
Supply, Installation, Testing and Commissioning of GPRS communication Modem along with suitable external antenna of suitable gain, patch chord and mounting accessories with following specification. The cost shall include the cost of communication for a period of 12 months from the date of completion of work.
11
-
-
Supply and fixing LED Monitor UA 43AU8000KLXL(UHD)-LED UHD
2
-
-
Supply and fixing VG CRYSTAL UP TO 43' LED MONITOR
2
-
-
RE USE OF TREATED WATER
-
-
-
Supply and install test and commissioning of Monoblock pumps set suitable for 415 Volt , 3 Phase system having capacity 5 HP with chrome steel impeller (1W+1S) complete all as directed. (Location : Near Kiran Sub Station)
2
-
-
Supply and install test and commissioning of Monoblock pumps set suitable for 415 Volt , 3 Phase system having capacity 15 HP with chrome steel impeller (1W+1S) complete all as directed. (Location : Near Play Ground)
2
-
-
Supply and install test and commissioning of Monoblock pumps set suitable for 415 Volt , 3 Phase system having capacity 10 HP with chrome steel impeller (1W+1S) complete all as directed. (Location : Near PS)
2
-
-
Supply and lay 110mm dia Unplasticiscd PVC pipes of pressure rating 10 kgf/cm2 ,class 'B' laid in trenches complete all as specified and as directed.
4755
-
-
Supply and lay 75mm dia Unplasticiscd PVC pipes of pressure rating 10 kgf/cm2 ,class 'B' laid in trenches complete all as specified and as directed.
1888
-
-
Supply, install, testing and commissioning of outdoor type Factory fabricated motor starter panel CPRI approved suitable for 3 phase 415V, 50Hz system made out of CRCA sheet 3.15 mm with suitable neoprene rubber gasket to make it completely, dust and vermin proof, front openable type alongwith locking arrangement having angle iron base frame and legs of suitable size, PCC (1:3:6) bedding for grouting of base complete all as specified and directed. The panel shall comprise the following accessories and specifications :-
(a) MCCB 4 pole, 25 Amps, 16 KA - 01 No (Incoming)
(b) DOL starter suitable for 5 HP Centrufugal pump set incl timer- 02 Set
(c) Motor protection relay - 01 Set
(d) Single phase preventor - 01 Set
(e) Phase indicating LED lamps RYB - 01 Set
(f) Panel mounted multifunction meter including CTs of suitable ratio - 01 Set
(g) ON/ OFF push button alongwith indication light - 01 Set
(h) Electrolytic high conductivity insulated copper bus bar of suitable capacity - 01 Set
(j) Pump 1 & 2 Selector switch
(k) Auto mannual selector switch -01 No (l) Earthing terminals - 02 Nos
1
-
-
Supply, install, testing and commissioning of outdoor type Factory fabricated motor starter panel CPRI approved suitable for 3 phase 415V, 50Hz system made out of CRCA sheet 3.15 mm with suitable neoprene rubber gasket to make it completely, dust and vermin proof, front openable type alongwith locking arrangement having angle iron base frame and legs of suitable size, PCC (1:3:6) bedding for grouting of base complete all as specified and directed. The panel shall comprise the following accessories and specifications :-
(a) MCCB 4 pole, 32 Amps, 16 KA - 01 No (Incoming)
(b) DOL starter suitable for 10 HP Centrifugal pump set incl timer- 02 Set
(c) Motor protection relay - 01 Set
(d) Single phase preventor - 01 Set
(e) Phase indicating LED lamps RYB - 01 Set
(f) Panel mounted multifunction meter including CTs of suitable ratio - 01 Set
(g) ON/ OFF push button alongwith indication light - 01 Set
(h) Electrolytic high conductivity insulated copper bus bar of suitable capacity - 01 Set
(j) Pump 1 & 2 Selector switch
(k) Auto mannual selector switch -01 No (l) Earthing terminals - 02 Nos
1
-
-
Supply, install, testing and commissioning of outdoor type Factory fabricated motor starter panel suitable CPRI approved for 3 phase 415V, 50Hz system made out of CRCA sheet 3.15 mm with suitable neoprene rubber gasket to make it completely, dust and vermin proof, front openable type alongwith locking arrangement having angle iron base frame and legs of suitable size, PCC (1:3:6) bedding for grouting of base complete all as specified and directed. The panel shall comprise the following accessories and specifications :-
(a) MCCB 4 pole, 40 Amps, 16 KA - 01 No (Incoming)
(b) DOL starter suitable for 15 HP Centrifugal motor pump set incl timer- 02 Set
(c) Motor protection relay - 01 Set
(d) Single phase preventor - 01 Set
(e) Phase indicating LED lamps RYB - 01 Set
(f) Panel mounted multifunction meter including CTs of suitable ratio - 01 Set
(g) ON/ OFF push button alongwith indication light - 01 Set
(h) Electrolytic high conductivity insulated copper bus bar of suitable capacity - 01 Set
(j) Pump 1 & 2 Selector switch
(k) Auto mannual selector switch -01 No (l) Earthing terminals - 02 Nos
1
-
-
S&F of 100 mm MS flange, bolt, nut, waser & gasket
18
-
-
S&F of pressure gauge 4" dia MOC - SS Glycerine filled - Diaphragm type Bottom entry 1/2 " PSB
6
-
-
Supply and Fix of Electromagnetic flow meter Size: 80 NB as per manufacturer's design including all necessary fittings complete all as specified and as directed.
2
-
-
Construction of Valve Chamber of following internal size suitable for Sluice Valve, with 150 mm thick PCC 1:4:8, Type D2, using 40mm graded aggregate for foundation, 200 mm thick Brickwork with old size Fly Ash Bricks in Cement Mortar 1:6, 40 mm thick PCC, 1:2:4, Type B1, using 20mm graded aggregate Coping, rendering in CM 1:4, 15 mm thick including provision of Mild Steel Sheet Cover 3 mm thick with 40 X 40 X 6 mm size Angle Iron frame work embedded in concrete with suitable hinges and locking arrangements including two coat of synthetic enamel black paint over a coat of red oxide zinc chrome primer to steel surfaces and including necessary earth work excavation in any type of soil etc., removal of surplus soil off the premises complete all as specified. (a) 900X 900 X 900mm type 'C'
4
-
-
Same as iten No. 54 above but Size 600 X 600 X 600 mm type 'B'
6
-
-
DG SET
-
-
-
Supply and installation of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation etc 58.5 KVA for STP 500 KLD
1
-
-
Supply and installation of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation etc 25 KVA for STP 100 KLD
1
-
-
EXTERNAL ELECTRIC SUPPLY
-
-
-
Riddling Sand obtained from excavation for cable protection 8cm under the cable and 15cm above the cable in trench and get the thick layer of 18cm after ramming complete all as specified and directed. Note :- In case sufficient sand not obtained from excavation, the required additional qty obtain from out side MD land as directed by the Engineer-in-Charge. The rate is deemed to be included the above provision.
50
-
-
Supply, Install, testing and commissioning of LT panel CPRI approved cubical type of suitable size, 415 volt, factory made dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick except inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, including aluminium bus bar of 250 Amps capacity,4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be mounted on angle iron frame and legs (vertical height of legs not less than 45 cm except in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable ,including danger notice sticker ,comprising the following accessory including testing complete all as specified. (a) MCCB 100 Amps 25 kA, 4 pole, Icu=100% Ics - 01 No. (Incomer)
(b) MCCB 63 Amps 16 kA, 3P, Icu=100% Ics - 01 Nos. (Outgoing for STP)
(c ) MCCB 40 Amps 16 kA, 3P, Icu=100% Ics - 01 Nos. (Treated Pump)
(d) MCB 6-32 Amps 10 kA, SP, Icu=100% Ics - 2 Nos. (Opertator Room & Street Light) (e) R,Y,B Indicators -01 Set
(f) Digital Amp meter (0-200) Amp incl necessary CTs (set of three) - 1 sets
(g) Digital volt meter (0-500 Volts) - 01 No. (h) Energy meter - 1 No.
1
-
-
Supply, Install, testing and commissioning of LT panel CPRI approved cubical type of suitable size, 415 volt, factory made dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick except inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, including aluminium bus bar of 200 Amps capacity,4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be mounted on angle iron frame and legs (vertical height of legs not less than 45 cm except in PCC) made from angle of size 50x50x6 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate)complete including all connection/ control wiring with suitable size of copper conductor cable ,including danger notice sticker ,comprising the following accessory including testing complete all as specified. (a) MCCB 63 Amps 25 kA, 4 pole, Icu=100% Ics - 01 No. (Incomer)
(b) MCCB 40 Amps 16 kA, 3P, Icu=100% Ics - 02 Nos. (Outgoing for STP & Treated Pump)
(c ) MCB 6-32 Amps 10 kA, SPN, Icu=100% Ics - 2 Nos. (Street Light & Operator Room) (d) R,Y,B Indicators -01 Set
(e) Digital Amp meter (0-200) Amp incl necessary CTs (set of three) - 1 sets
(f) Digital volt meter (0-500 Volts) - 01 No. (g) Energy meter - 1 No.
1
-
-
Supply and fixng factory made street pole mounted junction box made out of one piece ,2 mm thick polycarbonate FRP box ,totally enclosed,weather proof,frount openable ,water proof,power coated finish on outside & inside surfaces (of Approed Shade) moulded SMC IP65 protection having aluminium bus bars 100 Amp single phase and neutral with one No MCB SPN 6 Amp for street light, cable entry from bottom, maintenance free size 300x200x100 mm fixing on pole with MS flat 25x3mm clamp including nut bolts front openable all as specified and directed by Engineer-in-Charge.
8
-
-
Supply and fixing 2.5 sqmm PVC insulated & sheathed cable three core Copper conductor cable from SMC Box to street light fittings
64
-
-
S/F street light bracket made to shape at required angle made out of 40mm dia ( light grade ) GI tubing of length not less than 1.5m long suitable for fixing /holding street light fittings including mild steel flate iron 50 x 6 mm clamp 02 Nos with bolts, nuts and washer complete all as directed by Engr-in-Charge.
8
-
-
Material and labour earthing with GI earth plate electrode of size 60x60cmx3.15mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to GI strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI Mediam grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, earth work in any type of soil, all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.
26
-
-
Supply and fix sheet metal enclosure powder coated MCB DB 6 way double door with 200 Amps rated Bus bar complete all as specifed and as directed.
2
-
-
Misc items for Shifting of existing cables and pipe lines
-
-
-
Material and labour for taking down HT cable,11 KV, XLPE insulated of size 185Sqmm 3 core with aluminium conductor including shifting to other location and relaying and re- routing the same cable in trenches tghrough pipes etc complete all as specifed and as directed.
Note :-
The unit rate deemed to be included for excavation for taking down existing cable, shifting of cable as directed by engineer in charge and relaying cable including required excavation, sand cushioning/ cable protection etc complete all as specifed and as directed.
65
-
-
Material and labour for taking down LT cable,1.1 KV, XLPE insulated of size 50 Sqmmto 185 sqmm 3.5 core with aluminium conductor including shifting to other location and relaying and re- routing the same cable in trenches tghrough pipes etc complete all as specifed and as directed.
Note :-
The unit rate deemed to be included for excavation for taking down existing cable, shifting of cable as directed by engineer in charge and relaying cable including required excavation, sand cushioning/ cable protection etc complete all as specifed and as directed.
65
-
-
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specifed and as directed.
4
-
-
Material and labour for out door type straight through cable jointing kit (heat shrinkable) suitable for XLPE underground aluminium conductor cable , 1.1 KV (Earthed) grade of cross sectional araea 185 Sqmm to 240 Sqmm 3.5 core complete all as specifed and as directed.
5
-
-
Material and labour for out door type straight through cable jointing kit (heat shrinkable) suitable for XLPE underground aluminium conductor cable , 1.1 KV (Earthed) grade of cross sectional araea 50 Sqmm to 120 Sqmm 3.5 core complete all as specifed and as directed.
5
-
-
Material and labour for taking downGI/CI/DI pipe line any size and shifting to other location and relaying and re- routing the same pipe in trenches etc complete all as specifed and as directed.
Note :-
The unit rate deemed to be included for excavation for taking down existing pipe, shifting of pipe as directed by engineer in charge and relaying pipe including required excavation, specals etc complete all as specifed and as directed.
60
-
-
STP
-
-
-
Supply, install, testing and commissioning of Non clog vertical submersible pump sets 415V, three phase with chrome steel impeller non clog of discharge capacity flow 480 LPM and Head 12m with all necessary accessories and fittings to pass 40mm size particles including supply installation with guide rail and lifting chain cables earthing testing complete with necessary pressure gauges, electrically actuated valve complete. Each pump set shall be automatically operated vide an ultrasonic level sensor including automatic starter panel board double door type of suitable capacity, front mounted including PCC foundation, angle iron of suitable size for legs and frame with mounting arrangements with min height of 450 mm above GL complete all as directed. (01 Working+01 Stand by).
2
-
-
Supply, install, testing and commissioning of Non clog vertical submersible pump sets 415V, three phase with chrome steel impeller non clog of discharge capacity flow 1250 LPM and Head 12m with all necessary accessories and fittings to pass 40mm size particles including supply installation with guide rail and lifting chain cables earthing testing complete with necessary pressure gauges, electrically actuated valve complete. Each pump set shall be automatically operated vide an ultrasonic level sensor including automatic starter panel board double door type of suitable capacity, front mounted including PCC foundation, angle iron of suitable size for legs and frame with mounting arrangements with min height of 450 mm above GL complete all as directed (01 Working + 01 Stand by).
2
-
-
Supply and laying in trenches Pipe ductile Iron, S/S Class “K-9” of size 100mm (4”) dia in standard length, with inside cement motor lining and black bitumen external coating conforming to IS including push on rubber gasket joints including testing complete with all fittings all as specified and directed. Note : DI fittings will be measured and paid separately vide relevant items.
20
-
-
M&L for DI fittings such as bends (any type, radius and angle), Tapers any type (straight, bend, increasing, decreasing or double socket etc), Tee pieces single branch, Y junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs upto 100mm bore.
60
-
-
S&F Valves sluice flanged of class PN 1.6 of size 100mm all as specified and directed.
4
-
-
S&F Valve reflex/Non return valve with by-pass arrangement complete of sizw 100mm dia for pumping lines all as specified.
4
-
-
Supply and fix Outdoor Type LT Panel Board with incoming 4 pole MCB 25 A and outgoing MCB TP of Cap 10 A- 2 Nos DOL starter – 2 Nos for 2 HP Pump sets and Aluminum busbar 50 Amps rating complete all as directed.
2
-
-
Supply and fix Outdoor Type LT Panel Board with incoming 4 pole MCB 25 A and outgoing MCB TP of Cap 10 A- 2 Nos DOL starter – 2 Nos for 2 HP Pump sets and Aluminum busbar 50 Amps rating complete all as directed.
2
-
-
Supply and fix MCCB 4 pole 32A, 25KA, 415 Volt on existing LT panel all as directed and specified.
2
-
-
STP Manning and Operation
-
-
-
Outsourcing of services required for manning and operation of STP 100KLD and 500KLD during First year of DLP after completion of work under Phase -I, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during Second year of DLP after completion of work under Phase -I, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during FIRST year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during SECOND year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of SSTP 100 KLD and 500 KLD during THIRD year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLDD during FOURTH year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during FIFTH year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during SIXTH year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during SEVENTH year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Outsourcing of services required for manning and operation of STP 100 KLD and 500 KLD during EIGHTH year after DLP after completion of work under Phase -II, by employing one FGM (Skilled) per shift of 08 hours in a day for 02 Shifts, 16 hrs per day including sundays and holidays with all necesary tools , protective equipmets etc to carryout the work complete all as specified and as directed by Engineer-in- Charge.
12
-
-
Note for item No. 86 to 96:- The Manning and Operation comprises of the following works:-
(a) Operation of sewage pump sets as directed by the engineer in charge and operating Diesel Gen sets 25 KVA and 50 KVA during electric supply failiuer.
(b) Maintaining Log book for Pump sets
(c) Carrying out minor repairs Viz, replacing blow out fuses, recharging MCCBs, priming of pumps, minor repair to pipe line complete all as specified and directed by Engineer-in-Charge.
(d) Necessary tools , uniform and other accessories required for the smooth functioning of installation shall be provided by the contractor and the rate for the same shall be deemed to be included in the quoted rates
(e)Assurance of proper operation of all units of STP
(f) Checking of all electro mechanical systems daily inorder to ensure proper working condition
-
-
-
Supply,install and testing of Centrifugal Monoblock pump set suitable for 415 V ,3 phase system and discharge of treated water 12 LPS, Head-27Mtr and suitable size suction and delivery,PCC foundation all as specified and directed. ( For flushing of toilet with treated water and arboriculture) Make : Kirloskar Model KDI-830+ or equivalent make of V Guard/CRI
-
-
-