Military Engineer Services Tender
... More
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date29 Nov 2024
Closing Date27 Dec 2024
Tender Amount₹ 47,96,000
Costs
EMD
₹ 96,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_686336_1Bid Award Id
ViewTender No
8460/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
BUS - BAR & INTERNAL CONNECTIONS:
The Bus Bar shall be made up of 04 Nos high grade Aluminium 500 A rated , duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulation of non- hygroscopic, non - combusitable , all internal connection from main bus-bars to swicth gears etc.
PROVISION FOR CABLE ENTRY:-
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cable with help of glands
Incoming:-
(a) MCCB 4 P (Lcs=100% ICU) with adjustable short circuit & adjustable overload setting for isolation , having breaking capacity 36 KA & of rating 250 Amps -02 Nos (1W + 1S)
Outgoing:-
(a) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 100 Amps - 04 Nos (3 W + 1S)
(b) MCB TPN 63A.-2 Nos (1W+1S)
INSTRUMENTATION SYSTEM
(a) Digital type Multi-Function meter with built in selector Switch with and 03 No's of CT's matching with the I/C breaker, Accuracy class - 1-3, phase, size 96 x 96 mm or any techo-commercially equivalent in secure / Elmeasure
(b) Indicator Lamp with integral circuit (230 / 240 V) & cluster LED (Red, Orange, Blue) - 01 Set
(c) Danger notice plate of size 20x15cm 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LTconforming to IS-2551 - 02 Nos (Front & Back)
(d) Door Opening Keys - 02 Nos
-
-
-
... More
Supply, install, testing & commissioning of Main LT control panel board "out-door type" of size 1200 mm (height) x 1500 mm (breadth) x 500 mm (depth) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & High grade aluminium bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories complete all as specified & as directed
2
-
-
... More
BUS - BAR & INTERNAL CONNECTIONS:
The Bus Bar shall be made up of 04 Nos high grade Aluminium 600 A rated , duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulation of non- hygroscopic, non - combusitable , all internal connection from main bus-bars to swicth gears etc.
PROVISION FOR CABLE ENTRY:-
The provision for cable entry / exit shall be provided in the bottom for both incoming & out-going cable with help of glands
Incoming:-
(a) MCCB 4 P (Lcs=100% ICU) with adjustable short circuit & adjustable overload setting for isolation , having breaking capacity 36 KA & of rating 320 Amps -01 Nos Outgoing:-
(a) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 100 Amps - 05 Nos (4 W + 1S)
(b) MCB TPN 63 A.-2 Nos
INSTRUMENTATION SYSTEM
(a) Digital type Multi-Function meter with built in selector Switch with and 03 No's of CT's matching with the I/C breaker, Accuracy class - 1-3, phase, size 96 x 96 mm or any techo-commercially equivalent in secure / Elmeasure
(b) Indicator Lamp with integral circuit (230 / 240 V) & cluster LED (Red, Orange, Blue) - 01 Set
(c) Danger notice plate of size 20x15cm 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LTconforming to IS-2551 - 02 Nos (Front & Back)
(d) Door Opening Keys - 02 Nos
-
-
-
... More
Supply, install, testing & commissioning of Main LT control panel board "out-door type" of size 1200 mm (height) x 1500 mm (breadth) x 500 mm (depth) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & High grade aluminium bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories complete all as specified & as directed
1
-
-
... More
BUS - BAR & INTERNAL CONNECTIONS:
The Bus Bar shall be made up of 04 Nos high grade Aluminium 600 A rated , duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulation of non- hygroscopic, non - combusitable , all internal connection from main bus-bars to swicth gears etc.
PROVISION FOR CABLE ENTRY:-
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cable with help of glands
Incoming:-
(a) MCCB 4 P (Lcs=100% ICU) with adjustable short circuit & adjustable overload setting for isolation , having breaking capacity 36 KA & of rating 320 Amps -01 Nos Outgoing:-
(a) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 100 Amps - 04 Nos (3 W + 1S)
(b) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 125 Amps - 01 Nos
(c) MCB TPN 32 A.-2 Nos
(d) Time Switch (Daily & Weekly Programmable Electronic type ) 415 V , 3 Phase of 20 A rating with Contactor - 01 Sets INSTRUMENTATION SYSTEM
(a) Digital type Multi-Function meter with built in selector Switch with and 03 No's of CT's matching with the I/C breaker, Accuracy class - 1-3, phase, size 96 x 96 mm or any techo-commercially equivalent in secure / Elmeasure
(b) Indicator Lamp with integral circuit (230 / 240 V) & cluster LED (Red, Orange, Blue) - 01 Set
(c) Danger notice plate of size 20x15cm 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LTconforming to IS-2551 - 02 Nos (Front & Back)
(d) Door Opening Keys - 02 Nos
-
-
-
... More
Supply, install, testing & commissioning of Main LT control panel board "out-door type" of size 1200 mm (height) x 1500 mm (breadth) x 500 mm (depth) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & High grade aluminium bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories complete all as specified & as directed
1
-
-
... More
BUS - BAR & INTERNAL CONNECTIONS:
The Bus Bar shall be made up of 04 Nos high grade Aluminium 500 A rated , duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulation of non- hygroscopic, non - combusitable , all internal connection from main bus-bars to swicth gears etc.
PROVISION FOR CABLE ENTRY:-
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cable with help of glands
Incoming:-
(a) MCCB 4 P (Lcs=100% ICU) with adjustable short circuit & adjustable overload setting for isolation , having breaking capacity 36 KA & of rating 250 Amps -01 Nos (b) Onload changeover switch -01 Nos, open-execution modular construction type , confirming to IS/IEC 60947, -3 rated current -250 Amps 415 volts , 4 pole, AC 23 A -01 Nos
Outgoing:-
(a) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 100 Amps - 04 Nos (3 W + 1S)
(c) MCB TPN 63 A.- 2 Nos
(d) Time Switch (Daily & Weekly Programmable Electronic type ) 415 V , 3 Phase of 20 A rating with Contactor - 01 Sets INSTRUMENTATION SYSTEM
(a) Digital type Multi-Function meter with built in selector Switch with and 03 No's of CT's matching with the I/C breaker, Accuracy class - 1-3, phase, size 96 x 96 mm or any techo-commercially equivalent in secure / Elmeasure
(b) Indicator Lamp with integral circuit (230 / 240 V) & cluster LED (Red, Orange, Blue) - 01 Set
(c) Danger notice plate of size 20x15cm 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LTconforming to IS-2551 - 02 Nos (Front & Back)
(d) Door Opening Keys - 02 Nos
-
-
-
... More
Supply, install, testing & commissioning of Main LT control panel board "out-door type" of size 1200 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & High grade aluminium bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories complete all as specified & as directed
1
-
-
... More
BUS - BAR & INTERNAL CONNECTIONS:
The Bus Bar shall be made up of 04 Nos high grade Aluminium 500 A rated , duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulation of non- hygroscopic, non - combusitable , all internal connection from main bus-bars to swicth gears etc.
PROVISION FOR CABLE ENTRY:-
The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cable with help of glands
Incoming:-
(a) MCCB 4 P (Lcs=100% ICU) with adjustable short circuit & adjustable overload setting for isolation , having breaking capacity 36 KA & of rating 160 Amps -01 Nos Outgoing:-
(a) MCCB 3 P ( lcs= 100%) with thermal magnetic release, adjustable short circuit & adjustable overload setting , suitable for isolation , having breaking capacity 25 kA & of rating 100 Amps - 02 Nos (c) MCB TPN 63 A.- 2 Nos
(d) Time Switch (Daily & Weekly Programmable Electronic type ) 415 V , 3 Phase of 20 A rating with Contactor - 01 Sets (e) Contactor MNX 40 , New Tech Isolater 40 A, ON /OFF Swicth Suitable for Motorized Exisiting High Mast Light INSTRUMENTATION SYSTEM
(a) Digital type Multi-Function meter with built in selector Switch with and 03 No's of CT's matching with the I/C breaker, Accuracy class - 1-3, phase, size 96 x 96 mm or any techo-commercially equivalent in secure / Elmeasure
(b) Indicator Lamp with integral circuit (230 / 240 V) & cluster LED (Red, Orange, Blue) - 01 Set (c) Danger notice plate of size 20x15cm 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LTconforming to IS-2551 - 02 Nos (Front & Back)
(d) Door Opening Keys - 02 Nos
-
-
-
... More
Supply, install, testing & commissioning of LT busbar junction box "out-door type" of size 750 mm (height) x 600 mm (breadth) x 300 mm (depth) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The box shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade aluminum bus-bar of rating 400A of length 600mm, min spacing of 80mm between the busbars & wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming cable rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including I/C & O/G cable opening on bottom & at both sides including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv LT panel of any size/type complete all as specified & as directed with & including the following accessories complete all as specified & as directed
2
-
-
... More
Notes for Item Nos 1 to 7 :-1) Design / drawing / BOM of LT Panel Shall be submitted by the contractor from OEM/ Auth Supplier & is to be got approved from the GE & Engr in charge before placing final order to the manufacturer .
2) Any item not included in the specification but technically requried for proper operation / functioning of LT panels is deemed to be included in the unit quoted rates.
-
-
-
... More
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground ( erath pit not less than 2.25 mtrs deep below ground level) with the top edge of the earth plate not less than 1.5 mtr below normal ground level,connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron or steel all shown in electrical plate No 3 connected to earthing test point on completeion with and including 40 mm bore medium grade GI protection pipe ( up to 7.5 mtrs long) for earth and 20 mm GI medium grade for watering including PCC Chamber pit & cover with suitable lifiting hooks , with funnel, wire mesh, common salt, charcoal filling, necessary excavation and earth work in any type of soil including testing on completion all as specified and directed .
24
-
-
... More
Note :-1) On completion of the complete work/job the Contr is to perform earth resistance tests for each earthing job in the presence of the Engr-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Dept till the results are satisfactory.
-
-
-
... More
S&F 32 x 6 mm galvanised iron strip as earth continuity conductor incl connection complete with the help of chromium plated washers, nuts etc. to Transformer Body/Neutal, Generator Body/Neutral etc.
30
-
-
... More
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed.
220
-
-
... More
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed.
350
-
-
... More
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed.
275
-
-
... More
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed.
150
-
-
... More
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4.0 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed.
200
-
-
... More
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for taking out/laying of UG Cables, GI Pipe etc. and getting out in hard dense soil complete all as specified and directed .
258.5
-
-
... More
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick with excavated soil complete all as specified and directed.
147.74
-
-
... More
Removing of excavated material (Soil) to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as speciofied and directed.
110.76
-
-
... More
M&L for providing sand cushioning for protection of UG cable in trenches with coarse Riddled Earth of approved quality as approved in writing by GE including filling, spreading and punning down to desired thickness complete and all as specified and directed by Engr-in-Charge.
79.05
-
-
... More
Supply and laying sub class "B" bricks in trenches for protection of UG Cable with width equal to length of bricks, laid dry & flat complete all as specified & as directed.
8130
-
-
... More
M&L for cutting the existing hardstanding/PCC/WBM road at a depth of not less than 60 cm & 30 cm in width for passing of HT cables through GI pipes, returning filling in, complete incl finishing the surfaces by providing cement concrete type B1 (1:2:4) with 20 mm graded aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified and as directed.
30
-
-
... More
NOTE for Item Nos 15 & 20 : Any damages made to the existing services of MES/WCB/TNEB/Other Depts like HT/LT UG cables, Water Supply/Sewage Pipe lines, OFC/BSNL/ITRC/Signal communication cables etc. during the excavation/boring/road cuting etc. progress of the work shall be made good with proper jointing kits etc. as per original to the entire satisfaction of Engr-In-Charge & GE & the cost of the same is deemed to be included in the unit quoted rates. Decision of the AO shall be final & binding.
-
-
-
... More
M&L for GI pipe light grade with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 100 mm complete all as specified and directed. Note : Wherever GI Protection pipes are to be placed/fitted above earths surface, cost of necessary clamping/fixing arrangements to the entire satisfaction of Engr-In-Charge is deemed to be included in the unit quoted rates.
30
-
-
... More
M&L for GI pipe light grade with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 80 mm complete all as specified and directed.
20
-
-
... More
M&L for GI pipe light grade with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 50 mm complete all as specified and directed.
20
-
-
... More
M&L for straight through joint, heat shrink type for LT UG Cable incl joint kits suitable for Aluminium conductor cable of size 25 to 50 Sqmm 4/3.5 core incl earthwork, taking down, preparation of damaged cable incl testing complete all as specified & as directed by the Engr-In-Charge.
4
-
-
... More
Description all as per Item Sl No 22 here in above but suitable for Aluminium conductor cable of size 70 to 120 Sqmm 3.5 core.
4
-
-
... More
Description all as per Item Sl No 22 here in above but suitable for Aluminium conductor cable of size 150 to 185 Sqmm 3.5 core.
4
-
-
... More
Description all as per Item Sl No 22 here in above but suitable for Aluminium conductor cable of size 240 to 300 Sqmm 3.5 core.
2
-
-
... More
Supply, installation, commissioning & testing of silent built in within an acoustic enclosure diesel engine driven generating set water cooled including customized AMF panel for standby power supply 415 volts, 03 Phase, 4 wire, 50 cycles/sec, 125 KVA (100.0 KW) at 0.8 power factor perfectly suitable for outdoor mounting (open to air) at an altitude of 1900.0 Mtr above MSL (Mean Sea Level) & suitable for starting at a temperature of - 3 degree C complete with alternator directly coupled to diesel engine, mounted on common base frame & complete with self starter, fuel tank capacity not less than 08 hours fuel requirement & battery as per OEM, battery leads, sound proof canopy, cold starting kit equivalent etc. & confirming to latest CPCB IV norms for noise and Exhaust Emission with features for automatic shutdown in the event of a circuit failure condition arising from low lube oil pressure, high engine temperature, over/under speed etc. with & including Microprocessor based genset controller with the following undermentioned features & all as specified & as directed :
1
-
-
... More
(a) Graphical LCD display.
(b) Operator interface.
(c) Suitable to provide a record of most recent fault conditions & fault history.
(d) Complete alternator data viz, voltage ph - ph, ph - neutral, current, KVA , KW, frequency, PF etc.
(e) Complete engine data viz, starting battery voltage, engine temp, engine runnning hours, engine oil pressure etc.
(f) Battery charging condition, fuel usage, AMF feature etc.
(g) Control incl provn of service adjustment & calibration of DG control functions.
GENSET SPECIFICATIONS :
NO OF PHASES : 03
POWER FACTOR : 0.8 (LAG)
FREQUENCY : 50 HZ
VOLTAGE : 415 V, 3 PH
Engine Specification:
Rating : 125 KVA / 100.0 KW
Aspiration : TA
No of cylinder : 04
RPM : 1500
-
-
-
... More
ALTERNATOR SPECIFICATIONS : MAKE : Mahindra / Stamford
IP PROTECTION : IP 23
INSULATION CLASS : H CLASS
CONFORMANCE STANDARDS :
IS 4722, IS 1460, ISO 8528, ISO 3046, IS 13018, IS/IEC 60034-1, IS 10002, BS 5514, CPCB-IV etc.
Make, Size & No of Battery : As per OEM.
The size/rating of all the connected accessories viz. Contactors, relays, timers, bus-bars, connecting cables etc. of the Suitable AMF Panel shall be as per OEM & in conformity with the I/C & O/G MCCBs duly provided with bypass system/arrangement complete.
-
-
-
... More
IMPORTANT NOTES : (i) Design/drawing/BOM of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/Panel board manufacturer/Auth supplier & is to be got approved from Engr-in-charge & GE before placing final order to the manufacturer.
(ii) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc. can be done for both SEB mains & DG mains.
(iii) The cost of periodical/routine servicing including minor repairs/replacement such as topping up of coolant, engine/lube oil, diesel as well as lube-oil filters including periodical checking of the complete DG set & AMF panel for the complete defect liability period from the authorized Service Dealer as & when required/due is deemed to be included in the unit quoted rates.
(iv) The complete installation, commissioning & testing of the DG Set & AMF Panel is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only.
(v) Anything missed out in the technical specifications but technically required for efficient working of the DG Set & AMF Panel is deemed to be included in the quoted rates.
(vi) Necessary PCC foundation/plinth shall be as per the recommendations of OEM & cost of the same is deemed to be included in the quoted rates.
(vii) The quoted rate shall be deemed to be include test run at site as specified in the PS in presence of rep of Accepting Officer, all testing arrangements / equipments, resistive load including FOL shall be made available by the contractor with out any extra cost
(viii) The distance between the DG Set & the AMF Panel is 20 Mtrs Approx& the cost of control cabling etc. from DG Set to the AMF Panel is deemed to be included in the unit quoted rates.
(ix) The DG Set & AMF Panel shall be completely suitable for switching ON the DG Set whenever EB Supply goes OFF & transfer the load to DG & vice-versa in the event of resumption of EB Supply.
-
-
-
... More
Disconnecting and taking out the existing DG set from its position and deposting it to MES AGE E/M store yard all as directed .Note :- The rate quoted by contractor is deemed to be included (a) T&P for shifiting to store yard (b) Making good the distrubed surface.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements