Military Engineer Services Tender

Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Eprocure
Opening Date31 Aug 2024
Closing Date28 Sep 2024
Tender Amount₹ 38,70,000 
Notes
Download

Costs

Summary

Provn Of Lightning Protection System At Ashoka Block Valmiki Library Ranjith Block Qm Store At

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Air terminal Adaptor made up of Brass/SS for the connectivity of Air terminal & the Mast, with suitable terminal clamp made up of SS. Make ERICO Cat Part No: INTCPT-ADM3/4UNC or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

7

-

-

... More
Base/ side Bracket to hold the Air terminal mast with suitable fixing accessories, Guy wire support and all required fixing equipment's. Make ERICO Cat Part No: IGUYKIT4MGRIP or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

7

-

-

... More
Supply and installion of Monkey Protection for the supporting mast and Guy wire to avoid physical damage of Monkey. The mokey protection made up of 304 SS protector length of 1 Meter for mast and 1 meter for 3nos Guy wire. ( PART NO. MONKEY - CUP SS -1M ).

7

-

-

... More
S & F 2 runs of 8 mm Copper Bonded Steel Round Conductor, minimum copper bonding shall be 254 microns having continuous coin form, the conductor core shall consist of low-carbon steel grade for improved flexibility. The copper surface of the conductor should provide high conductivity and corrosion resistance properties, well‐suited as a lightning protection conductor in accordance with IEC 62305‐3 Edition 2.0 standard. Make ERICO Cat Part No: CBSC - 8MM or techno-commercially equivalent of SEIMENS/ HARGERcomplete all as specified and as directed by Engr-in-Charge. Note: 2 runs of 8 mm Copper Bonded Steel Conductor shall be measured and paid as one unit length.

300

-

-

... More
S & F Clamp Holder made up of 304 grade SS with SS bolt and nut at every 1 m distance of round conductor. The clamp should be suitable for double run of Copper bonded Steel round conductor size of 8-mm. Make ERICO Cat Part No: CBSC-8 SADDLE or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

300

-

-

... More
Supply, Installation, Commissioning and Testing of Maintenance Free Radial Earthing system comprising of the following:

-

-

-

... More
Copper Bonded Steel Earth Rod of size 5 feet x 5/8 inch diameter of 3 Nos, earthing system required excavation of 300 mm width x 450 mm depth x 5000 mm length in two different directions, 2 radials should be 10 meters apart, Auger 3 Nos hole of diameter 4 inch and 4 feet depth in the soil, Placing the Earth rods in to the augured hole, hammering the rods to 1 feet depth, Readymade PVC Heavy duty earth chamber (250 mm Dia , 260 mm Height) two numbers per one earthing system with minimum 5 ton load bearing capacity, removing excavated material. Make ERICO Cat Part No: CODE74071020 or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge. Brief features/ specifications of CBSE Rod is as follows: a) The outer surface must be molecularly bonded with uniform layer of 250 micron Copper, 99.9% pure electrolytic copper coating. b) Nickel interface must be provided between the copper and steel to avoid the galvanic corrosion. c) Must be capable of withstanding fusing current of 20 KA. d) Earth rod must be in compliance with IEC 62305- 2 e) Tensile strength greater than 80000 PSI on 12 mm. f) High resistance to corrosion..

21

-

-

... More
Ground Enhancement Material (GEM) , Per Bag -11.33 Kgs ,Conforming to IEC 62561-7 Standard, , Premixing the GEM into slurry form using water( not more than 5 L to 6 L per bag), Pouring the GEM mixture in the augured hole and filling. Make ERICO Cat Part No: GEM 25A- 25-1lb or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge. Brief features/ specifications of the same is as follows: a) Must be carbon based superior conductive material. b) Resistivity must be less than 2 Ω-cm. c) Must not cause corrosion to copper when in contact. d) Must not expand or experience any shrinkage once set. e) Must not depend on the continuous presence of water / moisture / salt to maintain its conductivity f) Must not decompose or leach out with time g) Must not contain hazardous chemicals as per IEC 62561-7 standard. h) Flexural and possess compressive strength as per relevant standard. j) Sulphur content must be less than 2%.

28

-

-

... More
Cadweld Materials for Connections between Ground Rod with CBSC conductor by Exothermic reaction. Connections to be made with a semi-permanent graphite mould, which shall hold the conductors to be welded. Weld metal must be a mixture of copper oxide and aluminium. Make ERICO Cat Part No: 150 PLUS F20 or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

35

-

-

... More
8 mm Copper Bonded Steel Round Conductor, minimum copper bonding shall be 254 microns having continuous coin form, the conductor core consists of a low-carbon steel grade for improved flexibility. The copper surface of the conductor should provide high conductivity and corrosion resistance properties, well‐suited as a lightning protection conductor in accordance with the IEC 62305‐3 Edition 2.0 standard. Including excavation depth 30 cm for laying round conductor, removing excavated material, return filling. Make ERICO Cat Part No: CBSC - 8MM or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

140

-

-

... More
IMPORTANT NOTES FOR SL ITEM NOS 1 To 5 : 1) The complete work of the lightning protection system is to be got done from the OEM or their authorized sister concern/ channel partner only. 2) Any items missed out in the technical specification, but technically required for efficient working of the system is deemed to be included in the unit quote rates. 3) The contractor/firm is required to visit the site prior to quoting of the subject items/ work so as to ascertain the actual ground requirements. Any further query at a later date shall not be entertained & responsibility of the same shall rest on the contractor/ firm. 4) Comparative analysis in respect of the items wherever techno-commercially equivalent w.r.t the given Cat/Part/Model ref concerned is to be submitted to the Engr-in-Charge & GE for approval. 5) The cost of making good the disturbed surfaces (Walls, Roofs, Pavement etc) is deemed to be included in the unit quoted rate of relevant items. 6) Purchase Vouchers & Manufacturers test certificates to be submitted in original to the Engr-in-Charge. 7) Design/Drawing/BOM/Technical Specifications of the complete lightning protection system showing the layout including dimensions is to be obtained from OEM strictly keeping in view the actual ground requirements & the same is to be got approved from Engr-in-Charge & GE before placing final order to the OEM. 8) The contractor should submit a detailed Report of Test results (Air terminal, Lightning Event Counter and Grounding ) from OEM after completion of work and same is to be certified from Engr-in-Charge & GE. 9) Repair/ Servicing / Preventive & Breakdown maintenance of the complete lightning protection system is to be got done from the OEM/ Sister Concern/ Channel partner only by the contractor for the entire defect liability period i.e two years from the certified date of completion & the cost of the same is deemed to be included in the unit quote rates. 10) Testing at an interval of 6 months of the entire lightning protection system is to be got done from the OEM/ Sister Concern/ Channel Partner only by the contractor & report submitted accordingly to the Engr-in-Charge for the entire defect liability period & and the cost of the same is deemed to be included in the unit quote rates.

-

-

-

... More
S&F Lightning Event Counter, Installed on down conductor, Non resettable mechanical counter, Non electronic without battery or external power source, IP67 enclosure, Triggering impulse 2 KA, 8/20 micro second, Warning sticker should be provided near to the Down conductor in a visible place. Make ERICO Cat Part No: LEC-IV or techno-commercially equivalent of SEIMENS/ HARGER complete all as specified and as directed by Engr-in-Charge.

7

-

-

... More
Removing of Existing Lightning Protection system Coventional type and unload the down conductors from the Building Ashoka , Ranjith Block, Valmiki Libaray complete all necessary connection etc all as specified and directed by the Engr-in-charge.

3

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.