Bhabha Atomic Research Centre Tender
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Bhabha Atomic Research Centre - BARC Tender
Electrical Goods and Equipments
Electrical and Electronics
Eprocure
Opening Date13 Aug 2024
Closing Date9 Sep 2024
Tender Amount₹ 9,26,23,349
Costs
EMD
₹ 18,52,467Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_BARC_820558_1Bid Award Id
ViewTender No
BARC/NRB/FRFCF/ELE/ETR081/2024Tender Authority
Bhabha Atomic Research Centre ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
3/3.5/4Core X above 120 & up to 240 sqmm
1500
-
-
3/3.5/4Core X above 240 & up to 400 sqmm
100
-
-
End Termination of the following size Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineerin- Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
-
-
-
4C x 2.5 Sq.mm including cable gland earthing
44
-
-
4C x 6/10 Sq.mm including cable gland earthing
12
-
-
End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches / Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
-
-
-
4 Core X 16 Sqmm
124
-
-
3.5/4 C x 35 sq.mm
124
-
-
3.5/4C x 50/70 sq.mm
72
-
-
3.5 x 95/120 sq.mm
34
-
-
3.5 x 185 sq.mm
32
-
-
3.5 x 240 sq.mm
16
-
-
3.5 x 300 sq.mm
4
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Ladder type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 600mm width x 100 mm depth x 2.0 mm thickness
345
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Ladder type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 450mm width x 100 mm depth x 2.0 mm thickness
415
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Ladder type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 300mm width x 100 mm depth x 2.0 mm thickness
580
-
-
Fabrication, assembling and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Ladder type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension:150mm width x 100 mm depth x 2.0 mm thickness
50
-
-
Fabrication, assembling and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 600mm width x 100 mm depth x 2.0 mm thickness
160
-
-
Fabrication, assembling and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 450mm width x 100 mm depth x 2.0 mm thickness
275
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension:300mm width x 100 mm depth x 2.0 mm thickness
855
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 150mm width x 100 mm depth x 2.0 mm thickness
720
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension:300mm width x 100 mm depth x 2.0 mm thickness
2250
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 150mm width x 100 mm depth x 2.0 mm thickness
275
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 600mm cable tray Cover with 2.0 mm thickness
160
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 450mm cable tray Cover with 2.0 mm thickness
275
-
-
Fabrication, assembling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 300mm cable tray Cover with 2.0 mm thickness
3105
-
-
Fabrication, assembling and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work.
Dimension: 150mm type cable tray Cover with 2.0 mm thickness
1000
-
-
Fabrication, supply and Installation of GI: MS fabrication With hot dipped galvanising Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.
134262
-
-
Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. 25 X 6 mm GI flat
3000
-
-
Design,supply,installation, testing and commissioning of following 415 V Indoor Power cum Motor Control Centre panel (PMCC) with drawout type ACB / MCCB's modules with associated accessories as per the specifications and scope of work.
-
-
-
Power cum Motor Control Centre panel (PMCC) - 1 (800A ACB I/C-1No, O/G MCCBs 16A-3Nos, 32A-5Nos ,63A-4Nos, 250A-3Nos, 400A-1Nos)
1
-
-
Power cum Motor Control Centre panel (PMCC) - 2 (1250A ACB I/C-1No, O/G MCCBs 16A-5Nos, 32A-8Nos ,63A-3Nos,125A-5Nos, 250A-3Nos, 400A-2Nos)
1
-
-
Power cum Motor Control Centre panel (PMCC) - 3 (800A ACB I/C-1No, O/G MCCBs 16A-8Nos, 32A-12Nos ,63A-4Nos,125A-3Nos, 250A-4Nos)
1
-
-
Power cum Motor Control Centre panel (PMCC) - 4 (630A MCCB I/C-1No, O/G MCCBs 16A-15Nos, 32A-4Nos ,63A-1Nos, 125A-5Nos, 250A-1Nos)
1
-
-
Power cum Motor Control Centre panel (EPMCC) - 1 (1000A ACB I/C-1No, O/G MCCBs 16A-1Nos, 32A-10Nos ,150A-4Nos, 250A-1Nos, 630A-1Nos)
1
-
-
Power cum Motor Control Centre panel (EPMCC) - 2 (800A ACB I/C-1No, O/G MCCBs 32A-2Nos, 125A-2Nos, 150A-4Nos, 250A-1Nos, 630A-1Nos)
1
-
-
Design,supply,installation, testing and commissioning of following 415V Indoor Motor Control Centres (MCC) panel with panel drawout type MCCB's modules with associated accessories as per the specifications ,SLD and scope of work.
-
-
-
Motor Control Centre panel (EMCC) - 1 (630A MCCB I/C-1No, O/G MCCBs 32A-4Nos ,63A-2Nos, 125A-5Nos, MPCBs 16A-2Nos, 63A-3Nos, 125A-2Nos)
1
-
-
Motor Control Centre panel (EMCC) - 2 (630A MCCB I/C-1No, O/G MCCBs 32A-4Nos ,63A-2Nos, 125A-2Nos, MPCBs 16A-1Nos, 63A-4Nos, 125A-2Nos)
1
-
-
Motor Control Centre panel (EMCC) - 3 (630A MCCB I/C-1No, O/G MCCBs 400A-4Nos, MPCBs 125A-5Nos)
1
-
-
Design,supply,installation, testing and commissioning of the following 415V Indoor Main Lighting cum Power Panel (MLPP) with drawout type MCCB's module with associated accessories as per the specifications,SLD and scope of work.
-
-
-
Main Lighting cum Power Panel (MLPP) - 1 (400A MCCBs I/C-1No, O/G MCCBs 80A-16Nos, 100A-13Nos, 125A-3Nos)
1
-
-
Main Lighting cum Power Panel (EMLPP) - 1 (125A MCCBs I/C-1No, O/G MCCBs 80A-13Nos, 100A-6Nos)
1
-
-
Design,supply,installation, testing and commissioning of 415 V Indoor 90kW heavy duty Variable Frequency Drive (VFD) panel (MCC-2) with associated accessories as per the specifications and SLD. (630A MCCBs I/C-1No, O/G MCCBs 250A & 90kW Heavy duty VFD-5Nos)
1
-
-
Design,supply,installation, testing and commissioning of the following lighting transformer and associated accessories as per the specifications and scope of work.
-
-
-
200kVA Lighting transformer
1
-
-
75kVA Lighting transformer
1
-
-
Design,supply,installation, testing and commissioning of the 415 V Indoor standalone starter panel and associated accessories as per the specifications and scope of work.
-
-
-
Direct On Line starter panel ( Type-1) for 2.5kW motor
1
-
-
Direct On Line starter panel ( Type-2) for 5 kW motor
2
-
-
Direct On Line starter panel ( Type-3) for 5.5 kW motor
2
-
-
Star-Delta Starter panel(Type-4) for 30kW motor
3
-
-
Design,supply,installation, testing and commissioning of the 415 V Indoor standalone 45kW heavy dutyVariable Frequency Drive (VFD) panel with Star Delta Starter bypass with associated accessories as per the specifications and SLD
2
-
-
Supply and installation of Surface/Flush mounting Powder Coated TPN 250A,3ph,415V,50Hz, 12Way DB with 1no of I/C-4P,250A MCCB, 12 No's of O/G's-4P,63A MCB and 4P 63A RCCB with all acccessories as per the scope of work.
6
-
-
Supply and installation of local push button station and associated accessories as per the specifications and scope of work.
33
-
-
Supply, cleaning the floor, proper pasting and installation of 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kV for 3 minutes, AC dielectric strength 30kV RMS Insulating Mat confirming to IS:15652 as per specification.
215
-
-
Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting with 1 coat primer & 2 coats synthetic enamel paint including supply of required, fasteners, nuts, washers, etc.
250
-
-
Fabrication,supply, installation of the copper bonded steel round conductor of 10mm diameter having coating thickness of 250μm for lightning protection system in built-in trenches/ walls/column/floor/ slab including clamp and other fixing assessories as per the tender specification
3900
-
-
Fabrication, supply, installation of the copper bonded steel round conductor of 18mm diameter having coating thickness of 250μm lightning protection system in built-in trenches/ walls/column/floor/ slab including clamp and other fixing assessories as per the tender specification
100
-
-
Fabrication, supply, installation of the copper bonded steel round conductor of 18mm diameter having coating thickness of 250μm for lightning protection system including excavation and refilling as per the tender specification
100
-
-
Jointing of 10mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Straight type Joint complete with all supply components like mould, powder, control unit and accessories as per the scope of work and drawings.
45
-
-
Jointing of 10 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Cross type Joint complete with all supply components like mould, powder, control unit and accessories as per the scope of work and drawings.
110
-
-
Jointing of 10 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the T- type Joint complete with all components and accessories as per the scope of work and drawings.
237
-
-
Supply and erection of copper test link for termination of 10mm size and 18mm size copper bonded steel conductors at 1500mm above finished ground level as per tender specification
48
-
-
Supply installation and testing of Maintenance free earthing system (1x10feetx5/8inch copperb bonded steel rod, 22 kg Ground Enhancing Material (GEM) ) as per IS: 3043 including RCC Chamber and RCC cover slab as per Drawing No. IGC/ESD/5060/1008/1 enclosed.
48
-
-
Excavation of soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. And initial lift upto 1.5 Mtrs. including neat banking as per detailed specification.
150
-
-
Supply & Installation of Following Size of Copper Earthing Conductor direct in ground including excavation, and back filling the trench as per detailed specification. 185 Sq.mm multi Stranded tinned copper conductor (Excavation)
1500
-
-
Supply and installation of Following Size of Copper Earthing Conductor in Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per detailed specification. Size: 185 Sq.mm multi Stranded tinned copper conductor (inbuilt)
100
-
-
Supply and installation of Following Size of Copper Earthing Conductor in Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per detailed specification. Size: 95 Sq.mm multi Stranded tinned copper conductor
500
-
-
Supply,Jointing of 185 Sq.mm tinned, stranded copper conductor by exothermic welding (CAD welding) of the Straight type Joint complete with all components and accessories as per the scope of work ,drawings and as directed by the Engineer-In-Charge.
56
-
-
Supply, Jointing of 185 Sq.mm tinned, stranded copper conductor by exothermic welding (CAD welding) of the T- type Joint complete with all components and accessories as per the scope of work, drawings and as directed by the Engineer-In-Charge.
135
-
-
Supply and installation of the following sizes copper wires in built in trench as per the detailed specification. Size:- 8SWG copper wire
400
-
-
Supply and installation of the following sizes copper wires in built in trench as per the detailed specification. Size:- 6SWG copper wire
150
-
-
Supply, installation and testing of Copper Plate Earth Electrode as per IS: 3043 including Excavation, RCC Chamber and RCC cover slab as per Drawing Nos. IGC/ESD/5060/1001/1 & IGC/ESD/5060/1008/1 are enclosed. (50 Kg.each Bentonite & Charcoal shall be provided for each earth pit).
14
-
-
End Termination of the 185sq.mm stranded tinned Copper conductor of annealed, tinned, stranded Copper conductor including supply of copper crimping lugs etc.
80
-
-
End Termination of the 95sq.mm stranded tinned Copper conductor of annealed, tinned, stranded Copper conductor including supply of copper crimping lugs etc.
30
-
-