Public Health Engineering Department Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 2,40,000Document Cost
₹ 1,000Tender Fee
₹ 1,000
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_PHCJA_176947_1Bid Award Id
ViewTender No
62/2019-20 cjjnTender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://https://phedwater.rajasthan.gov.in/phed
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Add 15% extra on depth more than 150 mtr for drilling beyond 150 mtr depth from ground level.
1
-
810.75
Construction of Tube Well up to 150 mtr. depth in all type of rocks by DTH system & over burden to accommodate casing pipe of following sizes in all types of soil & over burden including lowering of casing pipe, (if required) excluding cost of casing pipe, as per IS:2800 Part 1: 1991 and IS:2800 Part II: 1979 (both amended upto date) and technical specifications. The work would be completed after obtaining sand free water. The tube well should have a through out bore as per nominal dia of casing pipe.
Nominal Bore 150 mm Dia
1
-
576
Add 15% extra on depth more than 150 mtr for drilling beyond 150 mtr depth.
1
-
662.4
Supplying & Packing P-gravel suitable for slot size/mesh size as suggested in IS 2800 (Part-1) 1991 or as amended up to date.
1
-
3200
Labour charges for making slots on blank pipes made of ERW MS black pipe of following sizes, the slotting should be as per IS:8110-2000 or as amended up to date. 150 mm dia nominal bore.
1
-
180
Supply & Fixing tube well cover of MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug.
150 mm dia
1
-
600
Supply & Installation of 3 phase ISI marked submersible motor pump set of five star rating by BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect.
-
-
-
Up to 5.5 KW (7.5 HP) & head up to 120 mtr.
1
-
6920
Up to 5.5 KW (7.5 HP) & head above 120 mtr.
1
-
7760
7.5 KW (10 HP) & head up to 120 mtr.
1
-
4970
7.5 KW (10 HP) & head above 120 mtr.
1
-
6620
9.3 KW (12.5 HP) & head up to 120 mtr.
1
-
4460
9.3 KW (12.5 HP) & head above 120 mtr.
1
-
5550
11 KW (15 HP) & head up to 120 mtr.
1
-
4290
11 KW (15 HP) & head above 120 mtr.
1
-
4910
13 KW (17.5 HP) & head up to 120 mtr.
1
-
4250
13 KW (17.5 HP) & head above 120 mtr.
1
-
4610
Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc.
-
-
-
3 core 4.0 Sq.mm
1
-
137
3 core 10.0 Sq.mm
1
-
343
Providing & laying ISI marked GI Pipe “A” (light) class as per IS:1239 part I 2004 or amended up to date for casing pipe for submersible cable external/internal work 40 mm dia complete in all respect.
1
-
290
Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes
-
-
-
65 mm Dia
1
-
2160
80 mm Dia
1
-
2440
Providing, lowering, laying, aligning, fixing in position in pipe line, manually operated CI D/F sluice valve of approved make ( IS: 14846 maneded up to date) PN 1.0 class of following dia complete ( including jointing and jointing material) including all material, labour, testing and commissioning along with pipe line as per technical specification and as per direction of engineer. category "B" (makes/ vendors other than category "A" will be considerd in category "B") 80 mm Dia
1
-
4250
Providing & Lowering in tubewell ISI marked GI Pipe “B" (medium) class as per IS:1239 part I 2004 or amended up to date, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect.
-
-
-
32 mm dia
1
-
333
50 mm dia
1
-
515
Providing, installing, testing and commissioning of double flanged bulk flow meter with removable mechanism, of class B conforming to ISO 4064/1 or amended upto date of approved make including cost of all material and labour as per specifications with GI Box (sheet 16 SWG) suitable with locking arrangement of following dia.
50 MM DIA
1
-
11201
Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay, ampere meter with CTs, volt meter, phase preventor, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 guage M.S. Sheet with powder coating. Panel should be of minimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18" and double door including in built locking system. The legs should be embedded in M-15 cement concrete plat form.The size of CC plateform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for 440 Volt AC Supply.
-
-
-
Above 5 HP & upto 10 HP
1
-
18290
Above 10 HP & upto 15 HP
1
-
21240
Above 15 HP
1
-
24190
Providing & Fixing pump safety cage as per specifications or as directed by Engineer in charge.
1
-
825
Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended upto date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by butt fusion/ electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.
Supply up to 110 mm dia. in coil & above 110 mm dia straight length in 6 M.
-
-
-
PE-80 PN-6 (90 MM Dia)
1
-
243
PE-80 PN-10 (90 MM Dia)
1
-
341
Earth work in excavation in foundation trenches or drains including dressing of sides and ramming of bottoms, lift up to 1.5 mtrs. Including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed within a lead of 50 meter. All kind of soils
1
-
155
Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg. including all jointing material as per specification with safety cover.
1
-
800
Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required.
1
-
2800
Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to date of following sizes 150 mm dia NB(Thickness of pipe 5.0 mm & mass of tube 20.13 Kg/m)
1
-
1338
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements