If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Military Engineer Services - MES Tender

Works
Machinery and Tools
Eprocure
Opening Date16 Jan 2025
Closing Date6 Feb 2025
Tender Amount₹ 40,60,000 
Notes
Download

Costs

Summary

Repair To Pump Set Water Supply Installation And Allied Work And Repair Maint Of Internal Electrification With Fitting And Fixture Of

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M&L for dismantling of old GI earth strip and deposited to MES Store yard complete all as specified and directed.

90

-

-

... More
M&L for transportation of induction motor of capacity 75 HP to work shop for repair & rewinding with super enamelled copper winding wire of existing gauge and weight, varnishing and drying complete. Reassembling, bringing back to the installation, making the same functional after re-fixing at the existing location, testing after proper alignment the motor on full load complete all as specified and directed. (Note :- The cost of bearing is deemed included in this items nothing shall be paid extra )

1

-

-

... More
All as per item No 5.00 but of capacity 50 to 60 HP complete all as specified and directed.

1

-

-

... More
All as per item No 5.00 but of capacity 25 to 12.5 HP complete all as specified and directed.

5

-

-

... More
All as per item No 5.00 but of capacity 10 to 7.5 HP complete all as specified and directed.

4

-

-

... More
All as per item No 5.00 but of capacity 5 to 1 HP complete all as specified and directed.

5

-

-

... More
M&L for Transportation Centrifugal Pump of capacity (coupled with 75 HP/60 HP 3 phase elect motor) capacity 40,000 GPH, 60 Mtr head) to work shop for repair/Service, repair the unserviceable pump by insertion of graphite packing,rubber gasket,brass bush,gland plate, studs and greasing etc, including replacement of unserviceable spare parts and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed. Note: spares to be replaced included in item rate nothing shall be paid extra in this account.

3

-

-

... More
Disconnecting and taking up self priming centrifugal pump (coupled with 25 HP 3 phase elect motor) capacity 180000 LPH, 20 Mtr head, 1410 RPM, SP6L from the existing foundation. Service/repair the unserviceable pump including necessary facing, grinding, turning, filling and replacement of bearings with greasing, resetting and machining of shaft, replacement of gun metal bearing bush, sleeves and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up centrifugal pump (coupled with 20 HP 3 phase elect motor) capacity 50 LPS, 19 Mtr head, 1450 RPM, type-BCP100x260 from the existing foundation. Service/repair the unserviceable pump by facing, grinding, turning, replacement of bearings with greasing, resetting and machining of shaft , gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

2

-

-

... More
Disconnecting and taking up centrifugal pump (coupled with 15HP 3 phase elect motor) capacity14.81 LPS, 34Mtr head, from the existing foundation. Service the unserviceable pump by facing, grinding, turning, replacement of bearings with greasing, resetting and machining of shaft , gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

2

-

-

... More
Disconnecting and taking up monoblock pumpset (prime mover 20 HP 3 phase elect motor) capacity 39200 GPH, 19 Mtr head, 2900 RPM, type-MEGA from the existing foundation. Repair the unserviceable pump by facing, grinding, turning, replacement of bearing with greasing, resetting and machining of shaft, gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up monoblock pumpset (prime mover 20 HP 3 phase elect motor) capacity 29.7 LPS, 30 Mtr head, 2900 RPM, type-KDS2050 from the existing foundation. Repair the unserviceable pump by facing, grinding, turning,replacement of bearing with greasing, resetting and machining of shaft , gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up monoblock pumpset (prime mover 15 HP 3 phase elect motor) capacity 24.3 LPS/23.7LPS, 29.5 Mtr head, type-KDS1537 from the existing foundation. Repair the unserviceable pump by facing, grinding, turning,replacement of bearing with greasing, resetting and machining of shaft , gun metal bearing bush, and studs.Reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up monoblock pumpset (prime mover 12.5 HP 3 phase elect motor) capacity 25 LPS, 25 meter head, 2900 RPM, type-KDS-1331 from the existing foundation. Repair the unserviceable pump by facing, grinding, turning, insertion of graphite packing, replacement of bearing,greasing, resetting and machining of shaft, gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up pumpset (prime mover 7.5 HP 3 phase elect motor) from the existing foundation. Repair the unserviceable pump by facing, grinding, turning, insertion of graphite packing, replacement of bearing,greasing, resetting and machining of shaft, bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up monoblock pumpset (prime mover 5 HP 3 phase elect motor from the existing foundation. Repair the unserviceable pump by facing, grinding, turning, insertion of graphite packing, replacement of bearing,greasing, resetting and machining of shaft, gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

2

-

-

... More
M&L servicing of pumpsets 2HP to 3HP alongwith motor (any type) including replacement of suitable mechanical seal and packings, coupling repairs, replacment to bearings, resetting and machining of shaft, bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

3

-

-

... More
Supply only cast iron impeller for pumping set suitable for upto 5 HP to 25 HP complete all as specified and directed by Engineer-in-charge .

2

-

-

... More
S&F in replacement, MCCB 4 pole, 415V, adjustable 100 Amps with breaking capacity 16 KA complete all as specified and directed.

2

-

-

... More
S&F in replacement, MCCB 4 pole, 415V, adjustable 250 Amps with breaking capacity 25 KA complete all as specified and directed.

1

-

-

... More
S&F in replacement, MCCB 4 pole, 415V, adjustable 63 Amps with breaking capacity 16 KA complete all as specified and directed.

2

-

-

... More
S&F in replacement, MCCB 3 pole, 415V, adjustable 160 Amps with breaking capacity 16 KA complete all as specified and directed.

1

-

-

... More
S&F in replacement digital voltmeter of range 0-500 Volts complete all as specified and as directed.

3

-

-

... More
S&F in replacement digital ampere meters 0-250 Amps with CT complete all as specified and as directed. (Note :- Old unserviceable Ampere meter to be deposited in MES Yard)

3

-

-

... More
S&F in replacement, 3 pole AC power contactors, 415 volt rating coil, freedom series, suitable for 60 KW/75 HP (Rating 85-100 Amps), 3 phase electric motor starter complete all as specified and directed.

2

-

-

... More
S&F in replacement, 4 pole AC power contactors, 415 volt rating coil, NHD series, suitable for 20 HP(Rating 28-42 Amps), 3 phase electric motor starter complete all as specified and directed. (Note :- Old unserviceable item to be deposited in MES Yard)

2

-

-

... More
S&F in replacement, pnematic timer block "ON/OFF" delay site selectable (1NO+1NC) (0.1 to 180 sec) complete all as specified and directed.

2

-

-

... More
S&F in replacement, Oil immersed Fully automatic star-delta starter with bi-metalic relay suitable for 400V,3 Phase AC,50 Hz, 25 to 10 HP Electric Motor including initial fill of starter oil and making elect connection and testing Type-KF-40 complete all as specified and directed.

2

-

-

... More
S&F in replacement, direct on line citation motor starter 415V coil suitable for 7.5-5 HP, suitable size of overload relay , complete with SS enclosure complete all as specified and directed.

3

-

-

... More
S&F in replacement, direct on line citation motor starter 415V coil suitable for 1--3 HP, suitable size of overload relay , complete with SS enclosure complete all as specified and directed.

3

-

-

... More
S&F in replacement, auto switch single phase preventer for star delta and DOL starter as recommended by OEM complete all as specified and directed.

3

-

-

... More
S&F in replacement timer block suitable for L&T ML6 to ML-3 FASD starter as recommended by OEM complete all as specified and as directed.

5

-

-

... More
S&F in replacement of power contactor, AC-1 rating,32 amps to 9 Amps, 3 Pole, AC control with Auxiliary contacts 1 NO + 1 NC, suitable for coil voltage 110 V, 220, 240 & 415 volts, 50 Hz complete all as specified and as directed.

4

-

-

... More
S&F in replacement of thermal over load relay adjustment range 45-70 amps with relay mounting block, all electrical control wiring complete all as specified & as directed.

2

-

-

... More
S&F in replacement of thermal over load relay adjustment range 28-42 Amps, 20-32 amps with relay mounting block, all electrical control wiring complete all as specified and directed.

2

-

-

... More
S&F in replacement of thermal over load relay adjustment range 9-14 Amps, 6-10 Amps & 4- 6.5 amps with relay mounting block, all electrical control wiring complete all as specified and directed.

7

-

-

... More
S&F in replacement, mild steel coupling and supply and fix mild steel coupling complete of make-Unique/Power/ Supreme alongwith alignment of shafts complete all as specified and directed.

8

-

-

... More
Supply only copper thimbles 6 to 35 sqmm complete all as specified and directed.

40

-

-

... More
Supply only Polypropylene rope approx 22 mm dia, suitable for handling heavy equipments of weight upto 500 kg complete all as specified and directed.

50

-

-

... More
S&F FRP roofing sheets including all joinery items complete all as specified and directed.

15

-

-

... More
S&F, in replacement, MS work of required size with all additional joinery items and colour on all complete all as specified and directed.

100

-

-

... More
Taking down Old unservicable LT cable of any size and type and deposited it to MES Yard complete all as specified and directed.

120

-

-

... More
Supply and lay in replacement jointing and testing and commissioning in replacement of 35 Sqmm x 3.5 core XLPE insulated, screened , PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor & PVC sheathed LT cable 1100 V grade conforming to IS-7098,Part-I laid in trenches/ducts/fixed on poles wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed.

120

-

-

... More
Excavation in trenches not exceeding 1.5 mtr wide and not ecxceeding 1.5 mtr depth for laying of cables including taking up or down the LT cable complete all as specified and directed.

32.4

-

-

... More
Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25cm complete all as specified and directed.

19.55

-

-

... More
Removal of Excavated material n exceeding 50 mtr and depositing where complete all as specified and directed.

12.85

-

-

... More
Supply and filling in Sand for Cable protection complete all as specified and directed.

9.72

-

-

... More
Supply and laying un reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches complete all as specified and directed.

640

-

-

... More
S&F in replacement of electric terminal box with cover suitable for motor of any capacity complete all as specified and directed.

2

-

-

... More
S&F in replacement of motor cooling fan including nuts and bolts suitable for motor of any capacity complete all as specified.

1

-

-

... More
M&L for complete removal of existing paint of Elect motor with pump of capacity 5 HP to 75 Hp including base frame and applying two coats of spray paint using synthetic enamel paint over a coat of red oxide primer, marking of SM/MES No on equiptment complete all as specified and directed.

25

-

-

... More
Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI strip 25X4mm (upto the body of equipment) by means of GI bolts/nuts/washers, protected by 40 mm bore GI light grade pipe. Earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15 cm thick all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, RCC cover in 1:2:4 type B1using 20mm graded crushed stone aggregate and reinfircement (TMT) with 8mm dia @ 100 c/c bothways & frame, PCC (1:3:6) type C2 (using 20 mm graded crushed stone aggregate) as in earthing pit including necessary excavation & earth work, complete all as specified & shown in electrical plate No. 3 of MES schedule Part-I. Note:(i) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate. (ii) PCC chamber shall be construced at least 1.50 m away from the earth electrode and pipe for watering shall be provided in slanting manner.

10

-

-

... More
M&L repair to manual mobile floor crane at clear water complex for pumpset lifting including greasing, oiling, hydraulic lift repair etc complete all as specified and as directed.

1

-

-

... More
Supply only nuts , bolts with washers of various sizes required at site complete all as specified and directed.

30

-

-

... More
S&F in replacement three phase off load changeover 415 V 400 amps complete with suitable outdoor panel IP 65 protection made out of CRCA mild steel sheet, thickness 2.25 mm single door with lock arrangement and grouting on ground including all necessary electrical connections with accessories complete all as specified and as directed. (Note :- Old unserviceable Changeover to be deposited in MES Yard)

1

-

-

... More
S&F in replacement PVC reflux valve 40 mm to 80 mm dia complete all asspecified and directed.

2

-

-

... More
Supply & fixing, testing & commissioning of 100 mm dia Burden type, Stainless Steel dial type pressure gauge (in Pump Room) including brass isolation valve and pipe having caliberation of 0-100 Kg/cm2 complete all as specified and directed. (Note - Cost is deemed included for suitable size of boring in existing pipeline if required and plugging existing bore)

16

-

-

... More
S&F in replacement of energy meter with Multifunction LCD Meter Accuracy Class 1 as per IEC 62053-21 with RS485 showing V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events (High-Low), Neutral Current, k factor, Maximum Demand with Real Time Clock (RTC) and Events (high-low) with time stamp complete all as specified and directed. (Note :- Old unserviceable meter to be deposited in MES store Yard)

1

-

-

... More
M&L for general periodical servicing of twin lobe air blower of flow rate 220 m3/hr to 350 m3/hr coupled with 12.5 HP 3 Phase induction motor by replacement of lub oil, air filter , fan belts, unserviceable spares, testing and making alignment of V belt complete all specified and directed. Note : (a) Cost of grease shall deemed to be included in quoted rate (b) Spares included in this item nothing shall be paid extra in this account.

4

-

-

... More
Supply and fixing Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volt Conforming to IS 694 of size 50 sqmm complete all as specified and directed. (Note :- Old unserviceable PVC cable to be deposited in MES store yard)

60

-

-

... More
M&L for taking out defective submersible pump set of capacity upto 20 HP Capacity from bore well after disconnecting electrical connections,lifting the submersible pump from bore well including all accessories like column pipe etc, transportation to workshop for repair, dismantling the pump set for detection of repair such as rewinding of motor, replacement of iron stainer, gun metal bushes stainless steel sleeve, impeller key, thrust bearing, replacement of unserviceable nut-bolts, washer, lugs, terminal plate, reassembling, lowering of pump & strainer in well in its original position, making proper electrical connections, commissioning & testing complete all as specified and directed. Note : - (i) Cost for transportaion to workshop carry back to site after repair is inlcuded in the unit rate of item quoted by contractor and nothing extra shall be paid on this acount. (ii) Rewinding of submersible motor shall be paid separetly against respective items as "Supply only". (iii) Lathe work and grinding of shaft if required included in this item rate nothing shall be paid extra in this account. (iv) Cost of new nuts, bolts, washers, lugs and terminal plate required to be replaced is included in the unit rate of item quoted by the contractor and nothing extra shall be paid on this account. (v) Old burnt copper coil winding , gun metal bush, bearing to be deposited in MES Store, cost of transporation is deemed included in this rate.

2

-

-

... More
M&L for rewinding of motor of submersible pump set of capacity 20 HP with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and greasing of bearings, bushes, water seal, motor coupling and other connected parts and making necessary hook/clamp arrangement or body for attachning PVC rope complete all as specified and directed.

1

-

-

... More
M&L for rewinding of motor of submersible pump set of capacity 5 Hp to 7.5 HP with super enamelled copper winding wire of existing gauge including varnishing, baking, cotton tape and greasing of bearings, bushes, water seal, motor coupling and other connected parts and making necessary hook/clamp arrangement or body for attachning PVC rope complete all as specified and directed.

1

-

-

... More
M&L for disconnection electric connection, taking down the induction motor 25 HP to 50 HP from foundation and transportation to work shop for repair , greasing & varnishing the winding and drying complete. Reassembling, bringing back to the installation, making the same functional after re-fixing at the existing location, testing after proper alignment the motor on full load complete all as specified and directed. (Note :- The cost of bearing is deemed included in this items nothing shall be paid extra )

2

-

-

... More
Disconnecting and taking up centrifugal pump (coupled with 50 HP 3 phase elect motor) capacity 84 LPS, 23 Mtr head, 1450 RPM, type-SHM-150x32N from the existing foundation. Service/repair the unserviceable pump by facing, grinding, turning, replacement of bearings with greasing, resetting and machining of shaft , gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Disconnecting and taking up non clog centrifugal pump (coupled with 25 HP 3 phase elect motor) capacity 60 LPS, 18 Mtr head, 1450 RPM, type-BCP125x100 from the existing foundation. Service/repair the unserviceable pump by facing, grinding, turning, replacement of bearings with greasing, resetting and machining of shaft , gun metal bearing bush, and studs and reassembling and fixing to its original position, making mechanical connections and testing pumping set complete all as specified and directed.

1

-

-

... More
Supply and fixing insulating rubber mating chequare plate made out having electrical resistance as per IS 15652 : 2006 of size 1000mmx2000mm with thickness 2.5 mm suitable for use 11 KV working voltage,dielectric strength 40 kv with working temperature up to 50 degree centrigate complete all as specified and as directed.

8

-

-

... More
S&F Fully automatic soft starter in replacement of star delta starter, suitable for 50 to 75 HP pumpset ,3 phase 415 volt, 50 Hz as per sample, including making electrical connection and mounting of starter in electrical panel complete all as specified and as directed. (Note :- Unserviceable starter to be deposited in MES Store Yard)

4

-

-

... More
S&F in replacement of Galvanised iron strip 32 x 6mm buried in ground or on wall using insulator( clamped using proper nut and bolts) complete all as specified directed.

65

-

-

... More
M&L replacement of glands in sluice valves of various sizes & pumpsets of any capacity as specified and directed.

40

-

-

... More
M&L for danger notice sticker for LT panel, with letters, figures and conventional skull and bones in signal red colour of approved size for LT 18x10 cm , complete all as specifed and directed.

30

-

-

... More
Taking down carefully aluminium point wiring (light, fan, socket or power, bell complete fitting such as sockets, ceiling roses, pendants, batten holders, regulators and making good the disturbed surfaces of wall, floors, ceiling in CM 1:3 etc complete all as specified and directed.

390

-

-

... More
M & L for concealed conduit point wiring complete for light on independent /combine board with cable 1.5 sqmm (Nominal area) FRLSH PVC insulated multistranded unsheathed copper conductor, drawn in and including PVC Concealed conduit pipe medium grade 20 mm dia, pipe hooks , elbows, modular juction covers and junction boxes , after cutting in wall chasing for conduits and sinking's for modular sunken cast iron/ pressed steel terminal boxes thickness & deep as per recommended by OEM including modular cover plate and frame for mounting, switches, sockets,fan regulator and making the good disturbed surfaces of wall in CM 1:3 with white wash or existing colour including provision of continuous earth continuity conductor 1.5 sqmm FRLSH copper PVC insulated cable and connected to common earth dolly for one light/ fan point controlled by one switch,complete all as specified and direced.

210

-

-

... More
All as per Srl item No 76 here in before but for one switch socket combination 5/6 amp on independent board complete all as specified and directed.

50

-

-

... More
All as per Srl item No 76 here in before but for one three pin socket outlet 5 Amp on same board with other switches complete all as specified and directed.

30

-

-

... More
All as per Srl item No. 76 here in before but for one switch socket combinationt 6 pin 5/ 15 Amps on independent board with copper conductor 2.5 Sqmm complete all as specified and directed.

50

-

-

... More
All as Srl item No. 76 here in before but for one light point controlled by two 2 ways switches complete all as specified and directed.

20

-

-

... More
All as per Srl item No. 76 here in before but for call bell point complete all as specified and directed.

30

-

-

... More
M & L for concealed existing conduit point wiring complete for light/ fan on independent /combine board with cable 1.5 sqmm (Nominal area) FRLSH PVC insulated multistranded unsheathed copper conductor, drawn in PVC existing concealed conduit pipe medium grade 20 mm dia, pipe hooks , elbows, modular juction covers and junction boxes , after cutting in wall chasing for conduits and sinking's for modular sunken cast iron/ pressed steel terminal boxes thickness & deep as per recommended by OEM including modular cover plate and frame for mounting, switches, sockets,fan regulator and making the good disturbed surfaces of wall in CM 1:3 with white wash or existing colour including provision of continuous earth continuity conductor 1.5 sqmm FRLSH copper PVC insulated cable and connected to common earth dolly for one light/ fan point controlled by one switch,complete all as specified and direced.

600

-

-

... More
All as per Srl item no 82 here in before but for one switch socket combination 5/6 Amps on independent board complete all as specified and directed.

80

-

-

... More
All as per Srl item No 82 here in before but for one three pin socket outlet 5 Amp on same board with other switches complete all as specified and directed.

60

-

-

... More
All as per Srl item No. 82 here in before but for one socket outlet 3 pin 15 Amps on independent board with 2.5 Sqmm copper cable complete all as specified and directed.

60

-

-

... More
All as per Srl item No. 82 here in before but for one light point controlled by two 2 ways switches complete all as specified and directed.

30

-

-

... More
All as per Srl item No. 82 here in before but for call bell point complete all as specified and directed.

20

-

-

... More
M & L modular switch 5/6 Amps single pole one way,one module complete all as specified and directed.

900

-

-

... More
M & L of module switch 1 way 16 A, 1 module complete all as specified & directed.

110

-

-

... More
M & L modular switch 5/6 Amps single pole two ways complete all as specified and directed.

100

-

-

... More
M & L of modular socket, 6/16 Amps, 2/3 pin combined 2 module complete all as specified and directed.

110

-

-

... More
M & L modular socket outlet 5 pin 5 Amps flush type complete all as specified and directed.

130

-

-

... More
M & L modular bell push 5 Amp complete all as specified and directed.

30

-

-

... More
Taking down old unsv industrial metal clad plug socket and replace with new industrial socket metal clad plug and socket with MCBs single pole 20 Amp complete all as specified and directed.

30

-

-

... More
Taking down old unsv fan regulator and replace with new modular type fan regulator not less than 120 watt for ceiling fan 1200/1400mm sweep complete all as specified and directed.

80

-

-

... More
Taking down old unsv T/L fitting, bulkhead, angle holder etc of any type and capacity and deposite to MES store yard complete all as specified and directed.

500

-

-

... More
Fixing only new angle holder issued from MES store yard against items obtained dismantling complete all as specified and directed.

80

-

-

... More
Fixing only new security light fitting any watt, any type with all necessary wiring from ceiling rose to existing light fitting issued from MES store yard against items obtained from dismantling with all necessary acessories complete all as specified and directed.

50

-

-

... More
Fixing only light fitting with new LED batten 20 watt with all necessary wiring from ceiling rose to existing light fitting issued from MES store yard against items obtained from dismantling with all other accessories ceiling rose/connector complete all as specified and directed.

250

-

-

... More
Fixing only new bulk head fitting 10 watt issued from MES store yard against items obtained from dismantling complete all as specified and directed.

60

-

-

... More
Fixing only new mirror light fitting 10 watt issued from MES store yard against items obtained from dismantling complete all as specified directed.

60

-

-

... More
Taking down old unsv Decorative wall light and replace with new Decorative wall light fixture made up of Polycarbonate, suitable for 9 W LED lamp B22 base complete all as specified and directed.

30

-

-

... More
Taking down old unsv LED Bedside Light and replace with new LED Bedside Light (White,3000k) 3 Watt, with flexible arm suitable for reading complete all as specified and directed.

30

-

-

... More
S & F sensor based LED batten 20 watt having extruded aluminium housing with microwave motion technology for providing an energy efficient soluion with aluminium housing and integrated electronic driver complete all as specified and directed.

150

-

-

... More
S & F in replacement of sub-main wiring with two single core cables PVC insulated and un-sheathed 6 sqmm (Nominal Area) FRLSH stranded copper conductor drawn in existing PVC conduict including 6.00 Sq mm (Nominal Area) copper cable as earth continuity conductor including necessary connections, PVC flexible pipes are used in pannel board while connecting the cable complete all as specified and directed.. (Note : PVC cable and PVC conduit shall be ISI marked)

500

-

-

... More
S & F in replacement of sub-main wiring with PVC insulated and un-sheathed 4 x 6.00 sqmm (Nominal Area) FRLSH stranded copper conductor drawn in and including PVC "medium quality" conduit as per size required including 2 x 6 Sqmm (Nominal area) copper cable as earth contiunity conductor after chasing in wall and making good the disturbed surfaces and white wash or existing colour , necessary junction box and covers including necessary connections, PVC flexible pipes are used in pannel board while connecting the cable complete all as specified and directed. (Note : PVC cable and PVC conduit shall be ISI marked) Note :- 4 lengths of 6 Sqmm cable and one length of 2x6 Sqmm earth cable along with PVC conduit will be measured as one running length

300

-

-

... More
S & F in replacement of sub-main wiring with two single core cables PVC insulated and un-sheathed 4 sqmm (Nominal Area) FRLSH stranded copper conductor drawn in and including steel dia 25mm “medium quality” conduit including 4.00 Sq mm (Nominal Area) copper cable as earth continuity conductor after chasing in wall and making good the disturbed surfaces and white wash or existing colour , necessary junction box and covers including necessary connections, PVC flexible pipes are used in pannel board while connecting the cable complete all as specified and directed.

300

-

-

... More
Taking down old unsv DB and replace with new sheet metal enclosure for double door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted SP & N 8 ways, 240 Volts, ISI marked 200 amps bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed.

40

-

-

... More
Taking down old unsv DB and replace with new sheet metal enclosure for double door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted SP & N 12 ways, 240 Volts, ISI marked 200 amps bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed.

20

-

-

... More
Taking down old unsv DB and replace with new sheet metal enclosure for double door DBs made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted VTP & N 4 ways, 415 Volts, ISI marked 200 amps bus bar stove enameled dust and vermin proof suitable for incorporation MCCB and isolators etc including fixing in Wall with Cement mortar complete all as specified and directed by Engineer - in - Charge.

15

-

-

... More
Taking down old unsv MCCB TPN and replace with new MCCB TPN 63 Amps with breaking capcity 25kA ,Fixed TM and 415 volts AC Supply ISI marked complete all as specified and directed.

10

-

-

... More
Taking down old unsv MCCB TPN and replace with new MCCB TP&N 40 Amps with breaking capcity 16kA ,Fixed TM and 415 volts AC Supply ISI marked complete all as specified and directed.

5

-

-

... More
Refixing only serviceable MCB ‘B’ series type and fixing only new MCB ‘B’ series type issued from MES store yard against unsv item obtained from SL item no 33-38 suitable for 240 volts, AC supply 5 to 30 Amps , single pole with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed.

440

-

-

... More
Refixing only serviceable MCB ‘c’ series type and fixing only with new MCB ‘c’ series type issued from MES store yard against unsv item obtained from SL item no 33-38, suitable for 240 volts, AC supply 5 to 30 Amps, S P & N with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed.

40

-

-

... More
Refixing only serviceable MCB ‘c’ series type and fixing only with new MCB ‘c’ series type issued from MES store yard against unsv item obtained from SL item no 33-38 suitable for 240 volts, AC supply 40 to 63 Amps, S P & N with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed.

20

-

-

... More
M & L for Earthing complete with GI earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of plate not less than 1.5 Mtr below ground level , connecting to GI earth lead 4 mm dia GI earth wire ,by means of bolts,nuts and washers of GI and protection by provision of GI medium grade pipe 15 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20 mm grade stone aggregate with 40 mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 gs /Sqmm ) and frame of angle iron 25mmX25mmX6mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape ,GI light grade 20mm bore pipe for watering perforated at the bottom 1.75 meter long placed ontop edge of earth plate common salt and charcoal filling test point made out of 40 mmX 8 mm FI with fixing arrangement ,funnel, wire mesh and earth work inhard dense soil ,returning filling in and removal of surplus soil to a distance not exceeding 50 mtrs all as per electric plate no.3 of SSR part 1 and connecting to earth test point including taking out unserviceable earthing with all acessories all as specified or indicated including testing on completion all as specified and directed. Note: Destruction of old earthing pit and connected items retrived from site will deposite in MES store yard.

30

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.