Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 42,600Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_MES_561035_1Bid Award Id
ViewTender No
CA No. CWE BKN-Token No. 32/2022-2023Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Removing excavated material/soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed .
36.84
-
-
M&L for plain cement concrete 1:4:8 type D-2 using 40mm graded crushed stone aggregate as in foundations of poles/struts, filling and mass concrete complete all as specified and as directed.
Note : Volume of pole/struts embedded in concrete shall be deducted for payment purpose.
14.04
-
-
M&L for plain cement concrete 1:3:6 type C-1 using 20mm graded crushed stone aggregate as in filling and mass concrete, foundations of stays, coping, bed concrete of pole, pedestal of poles and the like including use and waste of form work (straight or curved), all exposed surface of concrete finished even & smooth without using extra cement, complete all as specified & as directed.
Note : Volume of pole/struts embedded in concrete shall be deducted for payment purpose.
12.91
-
-
Dismantling of old existing pre-stressed concrete HT poles of any description and depositing to MES Store yard complete all as specified and directed. Note :- Excavation and earthwork including taking out pole form foundation, removing, breaking existing PCC and refilling after erection and disposal of soil and rubbish shall be deemed to be included in the unit rate quoted for this item and shall not be measured separately.
11
-
-
S&F pre-stressed concrete pole 11 metre long of cross section 152mm x 152mm at the top and 152mm x 260mm at bottom, class 9, complying with requirements of IS-1678-1998 with & including two coats of synthetic enamel paint in alternate black and yellow strips 30 cm each upto 1.5 metre height from PCC coping/pedestal and marking pole number in letters & figures of size not less than 8cm height, complete all as specified & as directed
Note :- Excavation, earthwork, PCC in foundation & coping shall be measured and paid for separately.
11
-
-
Supply and fixing steel tubular pole, swaged type, 11 metre long, type 410 SP-55, with mild steel base plate, finial taper plug, bolts, nuts & screws including drilling of necessary holes, with & including two coats of synthetic enamel paint in alternate black and yellow strips 30 cm each upto 1.5 metre height from PCC coping and applying two coats of aluminium paint over a coat of aluminium red oxide primer to remaining portion of pole and marking pole number in letters & figures of size not less than 8cm height complete all as specified & as directed.
Note :- Excavation, earthwork, PCC in foundation & coping shall be measured and paid for separately.
2
-
-
Dismantling old unserviceable insulators of any type any size including MS spindle GI washers nuts etc complete all as specified and directed.
96
-
-
S&F Disc type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 145 mm height, 255 mm dia ball and socket type for working pressure 11000 Volts grade, complete all as specified and as directed .
48
-
-
S&F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for working pressure 11000 Volts grade, complete all as specified and as directed.
48
-
-
Dismantling of existing unserviceable HT over head line aluminium conductor and earth wire , steel reinforced ACSR conductors of any size/ type/capacity from existing overhead lines on HT lattice towers/steel tubular poles/PCC poles (of any height) complete complete all as specified and as directed.
10
-
-
M&L for Aluminium Conductor Steel Reinforced (ACSR) of any size as directed including stringing for overhead line on HT poles including jointing with & including aluminium binding wire 2mm dia, jumpers, line tapes, conducting jelly etc, complete all as specified and as directed.
Notes: (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.
(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors for payment purpose.
(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra shall be added for sag, jointing, jumpers etc.
(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS Code.
10
-
-
Dismantling old stay assembly complete with stay bow, stay strand of any size, loop insulator etc complete all as specified and directed.
10
-
-
S&F Stay assembly complete with 20mm dia, 1800mm long GI stay rod, with threaded ends and GI nuts, two number thimbles, MS galvanized clamps made out of 40mmx6mm flat iron including MS galvanized nuts, bolts and washers, 300mm x 300mm x 6mm MS galvanized stay plate, stay bow, galvanized stay strand 7/4 mm including shackle insulator and stay clamp, with & including painting of exposed MS work with two coats of aluminium paint over a coat of red oxide zinc chromate primer, all as shown in electrical plate No 1 of MES Schedule Part-I, complete all as specified and as directed.
Note : Excavation & earthwork and PCC shall be measured & paid for separately under respective items of this Schedule.
10
-
-
Dismantling old unserviceable MS Work such as cross arms, MS clamp, supports of any size and shape, nuts, bolts, washer etc complete all as specified and directed.
24
-
-
S&F cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections conforming to Grade E-165 (Fe 290) including nuts, bolts, washers, welding, bending cold or hot, drilled holes for bolts, in any shape or size as directed with & including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces complete all as specified and as directed .
Note: - (i) Sizes, sections & types of members and shape of the cross arms etc shall be as required at site and all as directed. (ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account. (iii) Weight of paint shall not be considered for payment purpose and quoted rate shall deemed to be included this aspect.
24
-
-
Dismantling old/ unserviceable earth wire or conductor, service feeder or distributor span complete all as specified and directed.
0.5
-
-
S&F Switch air break, gang operated outdoor, Horizontal operated type, HT 11 KV, Triple pole, 200 Amps, 3 insulator per phase, tilting/rocking horizontal type, rotating type contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, complete all as specified and as directed.
10
-
-
S&F Switch air break, gang operated outdoor, Horizontal operated type, HT 11 KV, Triple pole, 200 Amps, 3 insulator per phase, tilting/rocking horizontal type, with fixed type contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, complete all as specified and as directed.
6
-
-
S&F Anti-climbing device, spikes type fabricated out of MS bars (round, square and flat) conforming to Grade E-165 (Fe 290) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole, with & including two coats of aluminium paint over a coat of red oxide zinc chrome primer, complete all as specified & directed.
2.6
-
-
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized iron earth wire 4 mm dia as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted to earth plate at one end and other end of earth wire connected to transformer / GOD / Panel / equipment body / test point, GI earth wire encased in and including 15mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing.
Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
28
-
-
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed.
Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
4
-
-
Supply and fixing AMF Panel Box cubical type of comprising size (Panel box size) with bus bar chamber having 4 wire, 415 volts, factory made dust proof varmin proof for out door use made out CRCA sheet 2mm thick powder coated, machine pressed, front openable double door with provision of rubber beadings and locking system, danger notice board in front and rear sides including insulated copper bus bar of 400 Amps capacity, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x6mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) complete including all connections/ control wiring incoming /out going with suitable size of copper conductor cable, foundation is not less than 30cm below ground level and not less 45cm above ground level, legs of panel will be grouted in centre of PCC foundation centre place will be open for connection of under ground cables, as per epoxy powder coated after 7 tank pre treatment process & accessories, door hinges and clips locks hardware 7 accessories, door hinges 7 clips locks, air louvers, neoprene rubber gaskets, trasparent polycarbonated sheet/ MS sheet covering and MS angle work with suitable size wire & accessories, PVC wires ferrule thimble 7 other accessories, PVC channels, terminal strips, end plate, drawing material for wiring, buttons, tie sticker complete all as specified and directed including provision of following for 62.5 KVA DG Set :-
INCOMING FEEDER
(a) MCCB 400 Amps, 36 kA, 4 Pole, Thermal Magnetic type- 02 No
(b) MFM - 01 No
(c) Indicator Set RYB, “LED” type - 04 Nos
(d) CTs 400/5 Amps - 03 Nos (Description of serial item No. 24.00 contd…)
1
-
-
Description of serial item No. 24.00 contd…
OUTGOING
(a) MCB, 6 to 32 Amps, Single Pole, 240 Volts, 10 kA, ‘C’ Curve - 04 Nos
(b) MCB, 20 Amps, Double Pole, 240 Volts, 10 kA, ‘C’ Curve - 01 Nos
(c) Battery Charging unit 24 volts, 10 Amps
(d) SM 500 relay - 02 Nos
(e) Engine star relay 12 volts, DC-01 No
(f) CTs 400/5 Amps -01 set (Set of three)
(g) On load Changover switch 160 Amp, 415 Volt, 4 Pole, - 02 Nos
(h) Power Contactor capacity 160 Amp, 4 Pole, 415 Volt, type MCX32, - 02 Nos
(j) Indicator “LED” light for main & DG - 02 Nos
(k) Indicator “LED” light for battery charger - 01 No
(l) Auxilary Contactor - 02 Nos
(m) 14 Pin relay with base 24 volts - 01 No
(n) Auto/ Manual swithc - 01 No
(o) Start / stop push button - 02 Nos
Notes :- (i) The rates of PCC shall be included in quoted rate of this item. Nothing extra shall be paid for separately. (ii) The contractor shall produce and get the detailed drawings of LT Panel approved from GE before fabrication and placing the order to the approved manufacturer. (iii) The quoted rate shall deemed to include supply & provision of built in flush type locks (with 02 keys) of superior quality as directed by Engineer in Charge. (iv) Cost of any minor addition/alteration where required at site (the decision of GE will be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
-
-
-
Supply and fixing AMF Panel Box cubical type of comprising size (Panel box size) with bus bar chamber having 4 wire, 415 volts, factory made dust proof varmin proof for out door use made out CRCA sheet 2mm thick powder coated, machine pressed, front openable double door with provision of rubber beadings and locking system, danger notice board in front and rear sides including insulated copper bus bar of 400 Amps capacity, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x6mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) complete including all connections/ control wiring incoming /out going with suitable size of copper conductor cable, foundation is not less than 30cm below ground level and not less 45cm above ground level, legs of panel will be grouted in centre of PCC foundation centre place will be open for connection of under ground cables, as per epoxy powder coated after 7 tank pre treatment process & accessories, door hinges and clips locks hardware 7 accessories, door hinges 7 clips locks, air louvers, neoprene rubber gaskets, trasparent polycarbonated sheet/ MS sheet covering and MS angle work with suitable size wire & accessories, PVC wires ferrule thimble 7 other accessories, PVC channels, terminal strips, end plate, drawing material for wiring, buttons, tie sticker complete all as specified and directed including provision of following for 45 KVA DG Set :-
INCOMING FEEDER
(a) MCCB 250 Amps, 36 kA, 4 Pole, Thermal Magnetic type- 02 No
(b) MFM - 01 No
(c) Indicator Set RYB, “LED” type - 04 Nos
(d) CTs 400/5 Amps - 03 Nos (Description of serial item No. 25.00 contd…)
1
-
-
Description of serial item No. 25.00 contd…
OUTGOING
(a) MCB, 6 to 32 Amps, Single Pole, 240 Volts, 10 kA, ‘C’ Curve - 04 Nos
(b) MCB, 20 Amps, Double Pole, 240 Volts, 10 kA, ‘C’ Curve - 01 Nos
(c) Battery Charging unit 24 volts, 10 Amps
(d) Power Contactor capacity 130 Amp, 3 Pole, 415 Volt, MCX32 - 02 Nos
(e) On load Changover switch 125 Amp, 415 Volt, 4 Pole, - 02 Nos
(f) Engine star relay 12 volts, DC-01 No
(g) CTs 400/5 Amps -01 set (Set of three)
(h) Indicator “LED” light for main & DG - 01 No
(j) Indicator “LED” light for battery charger - 01 No
(k) Auxilary Contactor - 02 Nos
(l) 14 Pin relay with base 24 volts - 01 No
(m) Auto/ Manual swithc - 01 No
(n) Start / stop push button - 02 Nos
(o) SM 500 relay - 02 Nos
Notes :- (i) The rates of PCC shall be included in quoted rate of this item. Nothing extra shall be paid for separately. (ii) The contractor shall produce and get the detailed drawings of LT Panel approved from GE before fabrication and placing the order to the approved manufacturer. (iii) The quoted rate shall deemed to include supply & provision of built in flush type locks (with 02 keys) of superior quality as directed by Engineer in Charge. (iv) Cost of any minor addition/alteration where required at site (the decision of GE will be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
-
-
-
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 95 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified.
Notes :-
(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
70
-
-
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 70 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified.
Notes :-
(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
100
-
-
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 50 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified.
Notes :-
(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
(ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
100
-
-
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of under ground electric cable complete all as specified and as directed.
Notes :- (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used.
(ii) For the purpose of payment, only punned thickness shall be measured.
10
-
-
M&L for sub class ‘B’ (old size) burnt clay bricks laid flat and dry abutting each other with gap between adjacent bricks not exc. 10mm for protection of underground electric cable in such a way that the length of brick is at right angle to the central axis of cable complete all as specified and as directed.
1
-
-
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm to 95 sqmm complete all as specified & as directed.
12
-
-
S&F MCB, 6 to 32 Amps, SPN, 240 Volts, 10 kA, ‘C’ Curve, with over load and short circuit protection, ISI marked, fixed, complete all as specified and as directed.
2
-
-
S&F sheet metal enclosure for distribution boards flushed in wall, double door type (IP-43 IK 09 with metal door), suitable for fixing MCBs, 415 Volts with 200 Amps rated bus bar, load line DB fitted with bus bar neutral links blank plates, SPN, 2 way, suitable for 3 Pole / 4 Pole ‘A’ frame MCBs, fitted with and accessories, complete all as specified and as directed.
Note : Cost of cutting/leaving forming chases for sinking for DB and making good in CM 1:4 shall deemed to be included in quoted rate of this item.
3
-
-
S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 230 Volt, 10 kA, ‘C’ Curve, fixed, complete all as specified and as directed.
2
-
-
Supply, installation, fixing, commissioning of hi wall Split type, Air conditioning unit indoor/ outdoor, electric driven single phase of capacity 1.5 TR (3 Star rated, BEE) complete with cordless remote control unit and inbuilt air ioniser and plasma filter for better indoor air quality, suitable for wall mounted single phase 230/250 volts AC including breaking necessary for fixing indoor and outdoor unit and making good to distrubed surfaces with cement mortar to match with existing colour surface after commissioning making connection between indoor and outdoor unit with copper tubing with proper insulation and making connection unplasticised PVC pipe medium duty 20mm dia for draining out condensed water all as required including necessary connections complete all as specified & directed.
Note:- (i) Cost of copper tubing for indoor and outdoor unit deemed shall be including quoted rates as per OM. Make : Hitach/Dainen/Llyod
(ii) Cost of bracket, drain pipe, cutting chases/cutting holes etc in walls/floors including making good in cement mortar 1:4 and other necessary arrangement for fixing indoor & outdoor unit & other minor extras shall be deemed included in quoted rate of this item.
2
-
-
Supply, installation, voltage stabilizer for automatic operation single phase naturally air cooled indoor type copper wound and designed for input variation between 170 volts to 250 volts with output voltage stabilized at 230 volts with accuracy of ± 2.5% of capacity 4 KVA with mounting bracket with time delay relay complete all as specified and directed.
2
-
-
M&L for sub main wiring with two runs of 4 sqmm (nominal area) size main cable & one run of 4 sqmm size earth continuity conductor, single core, PVC insulated, unsheathed, FRLS with multi-stranded copper conductor, 1100 Volts grade, ISI marked cables, drawn through & including suitable size of heavy duty non-metallic rigid PVC concealed conduit ISI marked not less than 25mm dia & conduit fittings/accessories, fixed concealed in wall/ceiling complete all as specifid and directed.
Notes :- (i) 02 runs of 4 sqmm size main cable, 01 run of 4 sqmm size earth continuity conductor cable & conduit with accessories shall be measured as one run length for payment purpose. (ii) Cost of cutting/leaving forming chases for conduits and making good in CM 1:4 shall deemed to be included in quoted rate of this item.
30
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements