Military Engineer Services Tender

If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date10 Oct 2024
Closing Date7 Nov 2024
Tender Amount₹ 37,87,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(Description of serial item No. 2.00 contd....) (d) Complete trolley made out of MS sheet/channels/base plate/tyre rims shall be painted with 02 coats of syenthetic enamel paints (Light grey) shade over a coat of red oxide primer with spray gun including preparation of steel sufraces complete all as specified ad directed by Engineer-in-Charge. Note : (i) Transformer shall be mounted on the trolley as such necessary arrangment for mounting transformer and LT panel shall be made as per manufacturers's instructions. (ii) Design of trolley must be as per technical specification attached complete all as specified and directed. (iii) Contractor must submit drawing and technical details of trolley before placing the orders complete all as specified and directed. (iv) The technical specifications of trolley not specified above but required can be referred from the technical specifications attached here-in-after in particular specification.

-

-

-

... More
Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 150 Sqmm, 3 Core (ISI marked) fixed in poles/trolly mounted transformer complete all as specified & as directed.

80

-

-

... More
Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 400 Sqmm, 3 Core (ISI marked) fixed in poles/trolly mounted transformer complete all as specified & as directed.

80

-

-

... More
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm, complete all as specified & as directed.

6

-

-

... More
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 400 sqmm complete all as specified & as directed.

2

-

-

... More
Supply and fixing copper strip of size 32mm x 6mm thick, both side including drilling, bending, nuts, bolts and washers 04 Nos of appropriate size to transformer (hole size as per neutral terminal of the transformer) complete all as specified and as directed.

40

-

-

... More
Supply and fixing aluminium strip of size 25mm x 3mm thick, as roof conductor or down conductor or along the pole/pipe complete with saddles/insulators made out of porcelain or fibre and fixing screws complete all as specified and as directed.

40

-

-

... More
Supplying and laying synthetic Rubber insulated mats 2.5mm thick for voltage upto 11 KV for electrical purpose as per IS-15652-2006, (superseding IS-5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.

4

-

-

... More
Supplying and laying synthetic Rubber insulated mats 2.5mm thick for voltage upto 3.3 KV for electrical purpose as per IS-15652-2006, (superseding IS-5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.

2

-

-

... More
S&F double compression Brass cable gland (IP-66) for fixing armoured cable in panel of size 3.5 core 240 Sqmm to 300 Sqmm complete all as specified and directed.

4

-

-

... More
Supply , Install, Commissioning , and testing diesel engine driving generating set 62.5 KVA/ 50 KW output 415 volts AC ,3 phase 4 wire complete with integral acoustic sound proof (CPCB approved) within built of control pollution control board norms and control panel of the following:- (a) Diesel Engine:- Diesel Engine shall be water cooled , Multi cylinder in-line and maximum out put(BHP) as per manufacturer specification ,1500 rpm suitable to run 62.5 KVA Alternator with standard accessories such as start / stop switch, self starting system ,battery charging system with battery 12 volt ,88 AH ( dry and charged ) , oil temp gauge , rpm meter, hours meter, water temp gauge , oil pressure gauge, ammeter, high coolant temp gauge mounted on common base frame with silencer accessories and MS fuel tank for 12 hours continuous running fuel capacity built-in- the accoustic enclosure with vibration pads complete. (b) Alternator:- Alternator assembly, brushless, 415 V, AC, 50 Hz 3 phase, 4 wire type, confirming to BS5000/IS-4722 as per latest IS, rated, for continuous output of 62.5KVA / 50 KW, PF 0.8, 1500 RPM insulation class 'H' enclosure SPDP(IP 23) , self exiting and self regulated with AVR for +/- 1% voltage regulation coupled directly with prime mover with flexible coupling . (Note :-The Alternator is capable of developing rated output & able to take 10% overload for one hour at every 12 hrs of operation.)

1

-

-

... More
(Description of serial item No. 12.00 contd....) (c) Accoustic enclosure :- Accoustic enclosure should be made up of 1.2 mm Thick CRCA sheets and structural / sheet metal ,base frame . The walls of the enclosure shall be insulated with fire retardant foam so as to comply with the norms of 75 dBA at 1 mtr sound levels specified as per latest CPCB (testing as per ISO 8528). The enclosure should have following features. (i) Compact, modular construction and sleek design with low noise level 75 dBA, at a distance of 1 Meter from Canopy in free field conditions. (ii) Soundproof, weather-proof and environment friendly silent set. (iii) Steel outer construction with 1.2mm CRCA sheet with heavy-duty fabricated base frame and inbuilt fuel tank. (iv) Illumination arrangement inside the canopy. (v) Four point lifting for easy handling. (vi) CRCA should be powder coated with UV resistant power coating. (vii) Fuel filling point inside canopy.

-

-

-

... More
(Description of serial item No. 12.00 contd....) (d) Control Panel (AMF Panel) :- (i) Automatic main faliure contactor based of suitable cap, Control Panel fabricated out of sheet steel angle, iron structure, acid treated for anti-corrosion, floor mounting, cubicle pattern, powder coated dust and vermin proof, complete with internal wiring and with the followings: (ii) 1 x Genset Controller – Procom/ Depse (iii) 3 x Current Transformers of suitable rating – Kappa / Std. (iv) 2 x Indicating lamps “SET ON” / “LOAD ON” (v) 1 set TPN bus links from incoming and outgoing cable termination (vi) Digital combined volt , Amp, KW and Frequency meter (vii) 2 x Earth Studs (e) Material and Labour for making PCC Foundation of DG set size as per manufacture recommendation. Note :- (i) DG set should be sound proof as per latest policy. (ii) First filling of engine oil and fuel, coolant should be arranged by the contractor for testing of DG Set. (iii) Engine, alternator test certificate and warranty certificate shall be provided by the contractor. (iv) Engine operator / maintenance & spare manual shall be given to department. (v) OEM certificate shall be given by the contractor. (vi) Tools of DG set shall be supplied by the contractor.

-

-

-

... More
M&L for fabrication of moveable trolley made out of mild steel for mounting of 62.5 KVA DG Set, Feeder pillar box along with LT cable complete with 'I' - Hooks for hanging cables and moving arrangements so as to move the trolley both ways at 180 degree complete to move from one place to another and comprising of following components as appended below:- (a) Fabrication of chasis of movable trolley made out of 6mm thick MS base plate of size 4m x 2.6m x 1.2m (LWH) welded on (ISMC) heavy duty channel of size not less than MC 100mm of length 4 RM - 02 Nos and of same size for length 2.6 mtr 07 No along with 04 Nos outer cover with tube inner including rubber flap of size 7.50, 16 ply with steel rim of load capacity 5.0 Tonne and heavy duty excel of suitable size of suitable length - 02 Nos for 04 Nos Wheels ,eye hook provision for transporting trolly with the help of tractor/other vehicles from one place to another place and four column/pillers for standing the trolly free from wheels. (b) Moveable trolley enclosure made out of MS plate of size 6mm thick duly welded all around the base platform of trolley of minimum height 1.2 meter, base frame made out of angle iron of size 50x50x6 mm and vertical supports 40x40x6mm (2 end supports and 1 middle supports in each direction and to be provided all around) including wire mesh of size 10SWG fixed with MS flat iron of size 25mmx4mm with suitable size of nuts bolts and washers including Provn of door opening at front of the trolley of suitable size using angle iron of size 40x40x6mm including locking and suitable steps for operation & maintenance purpose , hinges, welding etc complete with back open-able shutter duly hinged (heavy duty ).

1

-

-

... More
(Description of serial item No. 13.00 contd....) (c) Suspension system of trolley made out of loaded leaf springs (step made patterns) - (04 Nos) made out of E-N 180 steel flat of suitable size with varying length starts from 1.06 RM (Total flats 06 Nos/Per sheel) including cutting, welding grinding at the time of fabrication of jobs complete. (d) Complete trolley made out of MS sheet/channels/base plate/tyre rims shall be painted with 02 coats of syenthetic enamel paints (olive green) shade over a coat of red oxide primer with spray gun including preparation of steel sufraces complete all as specified ad directed by Engineer-in-Charge. Note : (i) DG Set shall be mounted on the trolley as such necessary arrangment for mounting DG set and LT panel shall be made as per manufacturers's instructions. (ii) Design of trolley must be as per technical specification attached complete all as specified and directed. (iii) Contractor must submit drawing and technical details of trolley before placing the orders complete all as specified and directed. (iv) The technical specifications of trolley not specified above but required can be referred from the technical specifications attached here-in-after in particular specification.

-

-

-

... More
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.

14

-

-

... More
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.

9

-

-

... More
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.

5

-

-

... More
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of under ground electric cable complete all as specified and as directed. Notes :-(i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.

4

-

-

... More
M&L for sub class ‘B’ (old size) burnt clay bricks laid flat and dry abutting each other with gap between adjacent bricks not exc. 10mm for protection of underground electric cable in such a way that the length of brick is at right angle to the central axis of cable complete all as specified and as directed.

0.4

-

-

... More
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 70 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified and directed. Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.

150

-

-

... More
M&L for cable jointing kit for 1100 Volts grade cable for oudoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm complete all as specified & as directed.

6

-

-

... More
M&L for Earthing to Transformer/ equipments/ panels etc with & including galvanised mild steel earth plate electrode of size 60cm x 60cm x 6mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.

5

-

-

... More
Supply, installing, commissioning and testing LT panel board (otdoor type) cubical type made out of CRCA sheet 3.15 mm thick dust and vermin proof and angle iron of size 50x50x6 mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded stone aggregated thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with copper bus bar of capacity 200 Amps, TPN, three phase, 04 wire (In separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the follwoing:- (a) MCCB 125 Amp, 50 Hz, 415 V,4 Pole,thermal magnetic release with rupturing capacity 16 KA. -01 Nos (b) MCCB 63 Amp, 50 Hz, 415 V,4 Pole,thermal magnetic release with rupturing capacity 16 KA. -03 Nos (02 working + 01 standby)

1

-

-

... More
(Description of serial item No. 22.00 contd....) (c) MCB 4 pole 63 Amps, 10 KA. Fixed type - 03 Nos (02 Working + 01 Stand by) (b) MCB 4 pole 40 Amps, 10 KA. Fixed type - 03 Nos (02 Working + 01 Stand by) (e) Digital Voltmeter 0-500 Volts-01 No (f) Digital Ameter 0-100 Amps Volts-01 No (g) Selector switch and indicator lamp (h) Internal wiring with multistranded copper conductor cable/ PVC Insulated aluminium Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (j) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (k) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 160 Amps. Note : Foundation/platform shall be in PCC 1:2:4 type B1 using 20mm graded crushed stone aggregate (Foundation not less than 450mm above the ground level and not less than 300mm below the ground level) including necessary form work & 10mm thick cement plaster on exposed surfaces in CM 1:4 duly applied with three coats of white wash and quoted rate shall deemed inclusive of same.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.