Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 90,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_MES_547382_1Bid Award Id
ViewTender No
GE (N) BKN TOKEN NO 47 /2022-2023Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
M&L sand filling under floors or in foundation including watering and consolidation complete all as specified.
214
-
-
M&L for Brick work with fly ash bricks old size straight or curved on plan exceeding 6m mean radius built in CM 1:6 complete all as specified and as directed by Engr-In-Charge.
108
-
-
M&L for 15mm thick Rendering in cement mortar 1: 4 on fair faces of brick work or concrete surfaces, finished fair and even complete.
250
-
-
M&L for 10mm thick Rendering in cement mortar 1: 6 on fair faces of brick work or concrete surfaces, finished fair and even complete.
150
-
-
M&L for Preparing new plastered or unplastered surfaces of walls and applying two coats of cement paint white or tinted over a coat of white wash complete.
250
-
-
M&L for Preparing new plastered or unplastered surfaces of walls and applying two coats ofoil bound distemper paint white or tinted over a coat of white wash complete.
150
-
-
M&L for Hardcore of broken brick bats, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface
30
-
-
M&L 75mm thick PCC 1:4:8 type D-2 using 40mm graded stone agregate as sub base of floors all as specified.
268
-
-
M&L 18-20 mm thick machine cut kota stone slab as in flooring, laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing over and including 20mm thick screed bed in cement and sand mortar 1:6 complete all as specified and as directed by Engineer-in-Charge.
268
-
-
M&L 18-20 mm thick machine cut kota stone slab as in skirting/dado etc laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing over and including 10mm thick screed bed in cement and sand mortar 1:4 complete all as specified and as directed by Engr-in-Charge.
10
-
-
S&F Mild steel joist , ISMB Sec for column , channel, angle, tee section, fixed independently without connecting plates etc. including welding as necessary confirming to Fe-290 Gde E-165
3200
-
-
M&L for preparation of new steel surface of any description n. exc 10cm width or girth and applying two coat of synthetic enamel paint over a coat of red oxide primer all as specified.
300
-
-
M&L mild Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to IS 1161- 1979 grade St-240, conforming to Fe- 290 Gde E-165 complete as directed by Engineer-in-Charge and all as specified.
3000
-
-
M&L Mild steel Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment conforming to Fe-290 Gde E-165 all as specified and as directed by Engineer-in-Charge.
350
-
-
M&L Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, length of bolt not exceeding 5 cm and dia of shank 5 to 10 mm complete all as specified and as directed by Engineer-in-Charge.
130
-
-
S & F Pre-painted galvatume aluminium zinc coating GI based plain steel sheet 0.50 mm thick of sand colour having tensile strength of 550 Mpa as in roof covering /cladding to wall Ridges , fixed with self tapping screwsSand Colour as complete all as specified.
40
-
-
S & F Pre-painted galvatume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of sand colour having tensile strength of 550 Mpa as in roof covering /cladding to wall, fixed with self tapping screws as Sand Colour complete all as specified.
300
-
-
S& F Mild steel work in wind ties for roof including cutting holes etc complete all as specified.
150
-
-
Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete.
73
-
-
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete.
132
-
-
M& L for 75mm thick PCC 1:3:6 type C-1 (Using 20mm gradede crushed stone aggregate) as in plinth protection finished even and smooth without using extra cement complete all as specified.
125
-
-
S&F Pressed steel frames for door with one or more rebates including necessary fixing lugs, hinges,lock strike plate of profile 125x60mm as specified
20
-
-
M&L MS work as in hold hast etc.
3
-
-
M&L for Cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregate as in filling in pressed steel frame chowkhats etc complete
0.28
-
-
S&F 2nd class hard wood 35mm thick Plain, framed, panelled shutters (any number of panels), with panels of timber flat on both sides (feather edged), or of veneered particle board medium density, wood partcile board with commercial face veneers.
0.29
-
-
M&L for painting to new wooden surface over 10cm width or girth with two coat of synthetic enamel paint over a coat of pink primer.all as specified.
20.8
-
-
S&F 100mm lomg butt hinges, cold rolled mild steel medium weight.
12
-
-
S&F Mild steel barrel tower bolt stove enameled black with bright bolt of length 200mm
8
-
-
S&F Mild steel sliding door bolts,plate type, stove enamelled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed 300mm long .
4
-
-
S&F 125mm long Mild steel pressed handles, oval type,stove enamelled black.
8
-
-
MS work as in framed work such as grills, gratting, guard bars, etc confirming to Fe-410-0
60
-
-
M&L Plain cement concrete (1:2:4) type B-0, 40 mm thick as in damp proof course to horizontal or vertical surfaces including necessary form work using water proofing compound as per manufacturer’s instructions complete all as specified and as directed.
30
-
-
S&F Steel window with side hung shutter incl.box type hinges with steel handle of MS flat 25x5mm and 2nos tower bolt of 100mm long fixed to shutter comp. With glazing bar dovtailed or welded including one shop coat of primer.
10
-
-
S&F Steel window with side hung shutter incl.box type hinges with steel handle of MS flat 25x5mm and 2nos tower bolt of 100mm long fixed to shutter comp. Without glazing bar dovtailed or welded including one shop coat of primer.
10
-
-
S&F 3mm thick Sheet glass , ordinary quality and glazing with oil putty in squares not exceeding 0.5 Sqm in each pane complete.
8
-
-
S&F stainless steel wire cloth, 0.56mm nominal dia of wire and average width of aperture 1.18mm, fixed with tinned tacks or galvanised wire staples complete.
8
-
-
Supply and fixing anodized snap grid frame work of size 605mm x 605 mm for false ceiling including necessary notching. The snap grid shall consist of anodized aluminium main & cross tee of size 36.5 x 25 x 1.4 mm weighing 0.24 Kg/RM and 23.5 x 26.4 x 1.40 mm weighing 0.191 Kg/RM respectively. The main and cross tee shall be jointed at junction crossing with anodized aluminum angle bracket of size 15mm x 15mm x 1.5 mm weighing 0.12 Kg/RM fixed with suitable MS bolts, nuts and washer. The snap grid (main/cross tee section) shall be supported at ends all along the wall with anodized aluminum angle of size 35 x 25 x 2 mm weighing 0.36 Kg/RM fixed to wall with suitable arrangement and providing 12 mm thick mineral fibre board fixed in grid support with 2.50 mm dia plain mild steel wire galvanised class 3 fixed in detached works etc to support snap grid, made of aluminum as per specification and providing two coats of synthetic enamel paint over a coat of pink primer including preparation to exposed surfaces complete all as specified and as directed by Engineer-in-Charge.Make of mineral fibre Board : Armstrong Ceiling Tiles.
30
-
-
M&L Point wiring with stranded copper conductor cable, 1100 volts grade (ISI marked) PVC insulated and unsheathed of size 1.5 Sq mm single core in and including new non-metallic rigid PVC concealed conduit, not less than 20 mm dia, medium duty ISI marked, including conduit fittings such as tees, bends etc terminating in and including new sunken box covered with and including 3 mm thick bakelite laminated sheet top cover of approved make for one fan or light or exhaust fan or bell/buzzer point controlled by one switch including provision of 1.5 Sqmm PVC insulated unsheathed copper conductor cable, multi stranded as earth wire to common earth & connecting to earth dolly complete all as specified and directed by Engineer-in-Charge.
16
-
-
All as per item No 41 here-in-before but socket point on the same board with other switches complete as specifed as directed by Engineer - In - Charge
8
-
-
All as per item No 41 here-in-before but socket point on the independent board with other switches complete as specifed as directed by Engineer - In - Charge
4
-
-
All as per item No 41 here-in-before but cable of 2.5 Sq mm for 15 Amp switch socket outlet on independent board
2
-
-
Switch piano flush type, Single pole 5 Amps, one way ISI marked, complete all as specified and as directed by Engineer-in-Charge
28
-
-
Ceiling rose PVC/poly carbonate insulated body three terminal ISI marked, complete all as specified and as directed by Engineer-in-Charge.
4
-
-
S&F Socket outlet flush type, 3 pin, 5 Amps, ISI marked, complete all as specified and as directed by Engineer-in-Charge.
12
-
-
S&F Switch piano flush type, Single pole 15 Amps, one way ISI marked, complete all as specified and as directed by Engineer-in-Charge
2
-
-
S&F Socket outlet flush type, 3 pin, 15 Amps, ISI marked, complete all as specified and as directed by Engineer-in-Charge.
2
-
-
S&F Lamp holder insulated body with LED Bulb 9 watt back plate for conduit/casing capping fittings complete all as specified and as directed by Engineer-in-Charge.
4
-
-
S&F Decorative ultra slim linear LED lightening fixture, Eco friendly energy efficent 18/20 Watt complete all as specified and directed by engineer-in-charge.
4
-
-
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 63 Amps. In metal box of suitablecomplete all as specified and directed by engineer-in-charge.
2
-
-
S&F Sheet metal enclosure for distribution boards, suitable for fixing MCBs 240 volts with 200 Amps rated bus bar, SPN, 8 ways double door , supplied and fixed in repair, including making good the disturbed surface of wall, complete all as specified and as directed by Engineer-in-Charge. Make - Legrand/ GE/Seimens/L&T/Schneider/Indo Asian/C & S/Strandard/BCH/HPL
2
-
-
S&F MCB single pole, 240 volts of rating 6-32 Amps, breaking capacity of 10 KA complete all as specified and as directed by Engineer-in-Charge Make :- Schneider/ HPL/Legrand/ GE/ Seimens/L&T/Indo sian/C&S/Havells/BCH/ABB
12
-
-
S&F MCB suitable for 6 to 32 Amps, 240 Volt AC supply single pole and neutral with over load and short circuit protection having rupturing capacity not less than 10 KA complete all as specified and as directed by Engineer-in-Charge. Make :- Legrand/ GE/ Seimens/L&T/Indo Asian/C&S/ABB/BCH /Havells
2
-
-
Supply and fixing Street light bracket in replacement, made of GI pipe 40mm bore, light grade not less than 1.2 m long bent to shape including fixing with 2 nos suitable size of MS flat iron clamps, nuts, bolts and washers and making connections all as directed by the Engineer-in-Charge.Make of GI pipe : Jindal/Surya/Prakash
4
-
-
Suppy and Fixing LED based street light, housing made up of LM6 pressure die cast aluminium alloy with effectie thermal management, sturdiness. The fixture should have a minimum system efficiency of more than 100 lumen/watt and a minimum system lumen output of not less than 7000 lumens and maximum system wattage 70 Watts. The fixture shall have a correlated colour temperature of al least 5700K and CRI f minimum 70. The fixture shall be designed for a system life of 50,000 hours @ 70% lumen maintenance ingress protection of IP66 (lamp and gear compartment and mechanical inpact resistance raiting of IK=08. The fixture driver should have an operating voltage range of 140-270 V & potted type for humming free operation, driver should be wthstand up to 440v for 8hrs, two surge proection not less than 5KV one on driver and one external surge protection, PF0.95 and THD10% and have double phase protection. LED light fitting should be suitable for ambient temperature from (-) 10C to (+) 50 C. The fixture should comply with the parameters IEC 60598 and LED should comply to IEC 61000-3-2 ed. 3.2 per harmonics IEC 61347-2-3,2006 in configuration with IEC 61347-1 ed 2.0,2007 for electrical safety LM 79 and for LED LM 80 test report needs to be submitted from the house NABL accreditation laboratory. Make:- CG/Phillips/Wipro
8
-
-
M&L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including GI pipe 20 mm dia light grade for watering and bringing the same upto 30 cm above normal ground level with plug at top including pipe fittings etc complete and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 3 SSR Part-I.
2
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps, making electrical connections of incoming and out going cables with suitable thimbles compirising of the following:- ( For Rajana)
1
-
-
Incoming MCCB 4P 125 Amps, 35 kA-01 Nos
-
-
-
Outgoing MCCB 4P 63 Amps, 35 kA -04 Nos
-
-
-
Outgoing MCCB 4P 32 Amps, 35 kA -02 Nos
-
-
-
MCB SPN, 32 Amps -01 Nos
-
-
-
Star delta Starter 20 HP-01 Nos
-
-
-
Star delta Starter 15 HP-02 Nos
-
-
-
DOL Starter 3/5 HP-02 Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 160 A, 4P-01 Nos
-
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following :- ( for East Camp)
1
-
-
Incoming MCCB 4P 125 Amps, 35 kA-01 Nos
-
-
-
Outgoing MCCB 4P 63 Amps, 35 kA -02 Nos
-
-
-
Outgoing MCCB 4P 32 Amps, 16 kA -02 Nos
-
-
-
MCB SPN, 32 Amps -02 Nos
-
-
-
Star delta Starter 15 HP-02 Nos
-
-
-
DOL Starter 3/5 HP-02 Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 100 A, 4P-01 No
-
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following ( West Camp Phase-I )
1
-
-
Incoming MCCB 4P 160 Amps, 35 kA-01 Nos
-
-
-
Outgoing MCCB 4P 100 Amps, 35 kA -04 Nos
-
-
-
MCB SPN, 63 Amps -03 Nos
-
-
-
Star delta Starter 40 HP -04Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 160 A, 4P-01 Nos
-
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following ( West Camp Phase-II )
1
-
-
Incoming MCCB 4P 125 Amps, 35 kA-01 Nos
-
-
-
Outgoing MCCB 4P 63 Amps, 35 kA -04 Nos
-
-
-
Outgoing MCCB 4P 32 Amps, 35 kA -02 Nos
-
-
-
MCB SPN, 32 Amps -01 Nos
-
-
-
Star delta Starter 20 HP-01 Nos
-
-
-
Star delta Starter 15 HP-02 Nos
-
-
-
DOL Starter 3/5 HP-02 Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 160 A, 4P-01 Nos
-
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following ( West Camp Alpha Cul )
1
-
-
MCCB 4P 63 Amps, 35 kA-01 Nos
-
-
-
MCCB 3P 32 Amps, 10 kA-4 Nos
-
-
-
MCB SPN, 32 Amps-01
-
-
-
DOL Starter 3/5 HP-04 Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 63 A, 4P-01 Nos
-
-
-
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50*50*6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following ( West Camp Bravo,charlie and Delta Cul )
1
-
-
MCCB 4P 63 Amps, 35 kA-01 Nos
-
-
-
MCCB 3P 32 Amps, 10 kA-4 Nos
-
-
-
MCB SPN, 32 Amps-01
-
-
-
DOL Starter 3/5 HP-04 Nos
-
-
-
Digital Voltmeter with built in selector switch 0-500 volts -1 No
-
-
-
Digital Ampmeter with built in selector switch 0-250 Amps with Suitable CTs -1 No
-
-
-
LED indicating Lamps ( R,Y,B) one set-01
-
-
-
Onload Change Over switch 63 A, 4P-01 Nos
-
-
-
Taking down old unsv LT panel
6
-
-
Taking down old unsv Copper conductor wire of any size complete all as specified
317
-
-
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 16 sq mm ,4 core, 1100 Volts grade.
90
-
-
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 10 sq mm ,4 core, 1100 Volts grade.
95
-
-
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 6 sq mm ,4 core, 1100 Volts grade.
132
-
-
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed.
Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
16
-
-
Supply& fix in replacement , laying, jointing, testing and commissioning LT XLPE insulated, PVC sheathed armoured heavy duty electric cables LT 1100 volt grades with aluminium stranded conductor passing through pipes, in duct, on poles,in trenches, under road etc complete all as specified and directed of following :-
-
-
-
(a) 50 Sqmm 3.5 core
90
-
-
(b) 70 Sqmm 3.5 core
58
-
-
(c) 35 Sqmm 3.5 core
80
-
-
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
65
-
-
All as per serial item No. 1 here-in-before but depth exc 1.5m and not exc 3m.
45
-
-
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of under ground electric cable complete all as specified and as directed.
Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
24
-
-
M&L for sub class ‘B’ (old size) clay bricks laid flat and dry abutting each other with gap between adjacent bricks not exc. 10mm for protection of underground electric cable in such a way that the length of brick is at right angle to the central axis of cable complete all as specified and as directed.