Military Engineer Services Tender
... More
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date7 Mar 2019
Closing Date27 Mar 2019
Tender Amount₹ 18,86,605 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 43,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Repairs Maintenance Of Ht Em Equipments And Allied Works In The Area Of Age Em Under Ge Sri Ganganagar (4th Call)
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_MES_207065_4Bid Award Id
ViewTender No
CWE SGNR-31 OF 2018-19Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
400 KVA to 630 KVA, 3.15 MVA & 1.6 MVA
4
-
-
... More
M&L for replacement of insulation material such as gasket(cork sheet for top cover), LT terminal box, LV & HV bushing washer, paper insulation for coil for following transformer : -
-
-
-
... More
63 KVA to 100 KVA
4
-
-
... More
200 KVA to 315 KVA
4
-
-
... More
400 KVA to 630 KVA, 3.15 MVA & 1.6 MVA
4
-
-
... More
M&L for reconnecting the following transformer after complete repairs including installation & testing the transformer as per relevant IS provisions complete all as specified and directed by Engineer-in-Charge : -
-
-
-
... More
63 KVA to 100 KVA
4
-
-
... More
200 KVA to 315 KVA
4
-
-
... More
400 KVA to 630 KVA, 3.15 MVA & 1.6 MVA
4
-
-
... More
Supply and filling of fresh transformer oil confirming to IS 335 having di electric strength not less than 30 KV in existing transformers installed at different locations complete all as specified and directed by Engineer-in-Charge.
Make : Sheetal N-68/Power oil/Castrol with test certificate.
1500
-
-
... More
M & L for HT/LT coils, 33KV/11 KV, 440Volts fabricated out of new aluminium wire/strip of suitable gauge with proper insulation, varnish etc suitable for indoor/outdoor type transformer complete all as specified and directed by Engineer-in-Charge.
100
-
-
... More
M & L for HT/LT coils 33KV / 11 KV/440V fabricated out of new copper wire/strip of suitable gauge with proper insulation, varnish etc suitable for indoor/outdoor type transformer complete all as specified and directed by Engineer-in-Charge.
300
-
-
... More
S & F in replacement of transformer bushing of HT side (set of 03) with porcelain, brass rod, bolts, washers and packing sheet suitable for transformer complete all as specified and directed by Engineer-in-Charge.
-
-
-
... More
25 KVA to 630 KVA (11 KV)
12
-
-
... More
3.15 MVA (33 KV) & 1.6 MVA
2
-
-
... More
Supply & fixing in replacement of transformer bushing of LT side (Set of 04) with porcelain, brass rod bolts washers and packing sheet suitable for transformer complete all as specified and directed by Engineer-in-Charge.
-
-
-
... More
63 KVA to 100 KVA (0.433KV)
8
-
-
... More
200 KVA to 315 KVA (0.433KV)
8
-
-
... More
400 KVA to 630 KVA (0.433KV)
8
-
-
... More
3.15 MVA (11 KV)
2
-
-
... More
Dehydration and filtration of existing transformer oil using centrifugal plant to eliminate foreign particles and to improve di-electric strength not less than 40 KV in 25mm electrode gap and to bring the acidity within the permissible limit complete all as specified and directed by Engineer - in - Charge.
10000
-
-
... More
M & L for preparation of existing painted external surface of transformer of following capacities and applying two coats of synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
-
-
-
... More
63 KVA to 100 KVA
2
-
-
... More
200 KVA to 315 KVA
2
-
-
... More
400 KVA to 630 KVA
2
-
-
... More
Taking out existing silica gel and providing new silica gel complete all as specified and directed by Engineer-in-Charge.
10
-
-
... More
Supply and fixing in replacement of Air breather asembly with silica gel for transformer ranging from 25 KVA to 630KVA complete all as specified and directed by Engineer-in-Charge.
10
-
-
... More
Supply & fixing aluminium strip 25 x 3 mm thick fixed in ducts/on wall/in trenches/floor etc and jointing for interconnection of earthing fixed to equipment, test point including drilling holes and jointing with aluminium nuts, bolts and washers complete all as specified and directed by Engineer-in-Charge.
50
-
-
... More
Supply and fixing in replacement of transformer temperature gauge heavy duty 0-150 degre centigrade of size 96mm dial type for 100 KVA to 400 KVA transformer having brass sensor complete all as specified and directed by Engineer-in-Charge
Make - Scientific/H Guru/Tapan
5
-
-
... More
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 11KV under ground earthed system 3 core XLPE cable of size 95Sqmm including making connections complete all as specified and directed by Engineer-in-Charge. (Make : Raychem / M Seal / 3M)
8
-
-
... More
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 11KV under ground earthed system 3 core XLPE cable of size 185 Sqmm including making connections complete all as specified and directed by Engineer-in-Charge. (Make : Raychem / M Seal / 3M)
5
-
-
... More
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 11KV under ground earthed system 3 core XLPE cable of size 240 Sqmm including making connections complete all as specified and directed by Engineer-in-Charge. (Make : Raychem / M Seal / 3M)
6
-
-
... More
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 32mm x 6mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat iron and perforated water pipe 20mm dia GI medium grade of length 2.25 metre and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 6mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. complete all as specified and directed by Engr-in-charge.
Notes :- (i) GI strip upto earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover
20
-
-
... More
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed layer of charcoal dust and common salt, connected to earth lead of GI wire 4 mm dia (8 SWG) by means of bolts, nuts and washers of the earth wire galvanised iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia and water pipe 20mm dia GI light grade with funnel & wiremesh, PCC chamber in cement concrete (1:2:4) type B1 including 40mm thick pre-cast RCC (1:2:4) type B0 cover and 40x40x6mm angle iron frame on top of pit cover and excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. complete all as specified and directed by Engr-in-charge.
Notes :- (i) GI wire upto earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1 metre away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 Kg for each earth pit cover.
6
-
-
... More
Cutting/ trimming of tree branches not exc 10cm girth touching/approaching the LT/HT overhead lines upto 3 metre width on each side with hacksaw/axe to clear the LT/HT line including disposal of trimmed branches 100 Metre away inside the cantonment area & clearing site complete all as specified and directed by Engineer-in-Charge.
500
-
-
... More
M&L for opening the joints of HT / LT overhead conductor from the end of poles, stretching the overhead aluminum conductor with chain pulley and other T&P machineries, refixing the overhead conductor at the same place such that sagging of conductor is not more than 3% complete all as specified and directed by Engineer-in-Charge. Note : Length of each OH conductor to be measured.
2
-
-
... More
Supply and fix in repalacement pin insulator of size 150mm height, 150 mm dia porcelain vitreous white, brown or green insulator suitable for 11 KV grade including one galvanized mild steel spindles two GI washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
20
-
-
... More
Supply and fix in replacement disc insulators, vitreous porcelain 145 mm high and 255 mm dia ball and socket type, white, brown or green of two in series assembly for tension with tension clamps for conductor working pressure 11000 volts grade complete all as specified and directed by Engineer-in-Charge. .
30
-
-
... More
Supplying and fix in replacemnet of air break gang operated switch, triple pole, 11 KV (outdoor type) mechanically operated, suitable for horizontal or vertical mounting fixed type complete with 12 insulators and steel frame, with operating mechanism worked from ground level with fixed contacts of phosphorous bronze and moving control of copper, for current rating upto 200 Amps including GI pipe heavy duty of required size and with locking arrangement including Godrej (Freedom) 50mm pad lock with two keys with fuse mounts, fuse carriers and HT fuse elements having 200 amp rating suitable for HT 11 KV, 50 Hz, AC supply including necessary electric connections, mild steel ISMC-75 of required length fixed with mild steel clamps made out of 50mm x 6 mm flat iron,nut,bolts and washers of required size for fixing GOD complete and painting structural steel surface with 2 coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
5
-
-
... More
Supplying and fix in replacemnet of air break gang operated switch, triple pole, 11 KV (outdoor type) mechanically operated, suitable for horizontal or vertical mounting fixed type complete with 12 insulators and steel frame, with operating mechanism worked from ground level with fixed contacts of phosphorous bronze and moving control of copper, for current rating upto 400 Amps including GI pipe heavy duty of required size and with locking arrangement including Godrej (Freedom) 50mm pad lock with two keys with fuse mounts, fuse carriers and HT fuse elements having 400 amp rating suitable for HT 11 KV, 50 Hz, AC supply including necessary electric connections, mild steel ISMC-75 of required length fixed with mild steel clamps made out of 50mm x 6 mm flat iron,nut,bolts and washers of required size for fixing GOD complete and painting structural steel surface with 2 coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
4
-
-
... More
Supplying and fix in replacemnet of air break gang operated switch, triple pole, 33 KV (outdoor type) mechanically operated, suitable for horizontal or vertical mounting fixed type complete with 12 insulators and steel frame, with operating mechanism worked from ground level with fixed contacts of phosphorous bronze and moving control of copper, for current rating upto 630 Amps including GI pipe heavy duty of required size and with locking arrangement including Godrej (Freedom) 65mm pad lock with two keys with fuse mounts, fuse carriers and HT fuse elements having 630 Amp rating suitable for HT 33 KV, 50 Hz, AC supply including necessary electric connections, mild steel ISMC-75 of required length fixed with mild steel clamps made out of 50mm x 6 mm flat iron,nut,bolts and washers of required size for fixing GOD complete and painting structural steel surface with 2 coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S & F in replacement lightning arrester expulsion type conforming to IS-3070 Part-II 1989 as amended upto date suitable for 33 KV earth system having discharged current rating 5 KA high current impulse with stand 65 KA for OH 33 KV line including bracket clamps nuts, washers and connecting to earth as specified and directed by Engineer-in-Charge.
1
-
-
... More
S & F in replacement lightning arrester expulsion type conforming to IS-3070 Part-II 1989 as amended upto date suitable for 11 KV earth system having discharged current rating 5 KA high current impulse with stand 65 KA for OH 11 KV line including bracket clamps nuts, washers and connecting to earth as specified and directed by Engineer-in-Charge.
3
-
-
... More
S & F in replacement of pre-stressed cement concrete pole, 11 metre long of cross section 152mm x 152mm at top and 152mm x 260mm at bottom, class 9, complying with requirements of IS-1678-1998 erecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and white colour up to 1.5 metre height from top of PCC pedestal/coping of poles and writing/ numbering of poles with synthetic enamel paint white in 80mm high letters over 150mm x 200mm black or yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. Note : PCC for foundation and earth work shall be measured and paid for separately. Volume of pole embeded in PCC shall be deducted for payment purpose.
3
-
-
... More
S & F in replacement pre-stressed cement concrete pole, 9 metre long of cross section 102mm x 152mm at top and 102mm x 289mm at bottom, class 10, complying with requirements of IS-1678-1998 errecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and white colour upto 1.5 metre height from top of PCC pedestal/coping of poles and writing/ numbering of poles with synthetic enamel paint Black in 80mm high letters over 150mm x 200mm yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
Note :- PCC for foundation, cross arms and earth work shall be measured and paid for separately. Volume of pole embeded in PCC shall be deducted for payment purpose.
3
-
-
... More
Supplying and fixing in replacement cross arms, bracings, stiffeners, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, binding cold or hot, drilling holes for bolts, in any shape or size as indicated or directed complete all as specified and directed by Engr-in-Charge.
Note :Exposed steel surface shall be treated with two coats of aluminium paint over a coat of red oxide primer and unexposed surface of steel sections shall be applied one coat of red oxide primer. The quoted rate shall be deemed inclusive of the above provn.
1
-
-
... More
Supply, laying, jointing testing and commissioning in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade of cross-sectional area 185 Sqmm, 3 core, IS 7098 marked, suitable for HT 11 KV(E) system , laid in trenches / ducts / encased in GI pipe / fixed to pole complete all as specified and directed by Engineer-in-Charge.
50
-
-
... More
Supply, laying, jointing testing and commissioning in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade of cross-sectional area 95 Sqmm, 3 core, IS 7098 marked, suitable for HT 11 KV(E) system , laid in trenches / ducts / encased in GI pipe / fixed to pole complete all as specified and directed by Engineer-in-Charge.
Note for Ser item Nos 32 & 33 : Excavation and earth work, brick protection, sand cushioning and GI protection pipes shall be measured and paid separately under respective item of BOQ
100
-
-
... More
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out complete all as specified and directed by Engineer-in-Charge.
50
-
-
... More
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
30
-
-
... More
Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-charge .
18
-
-
... More
M & L for sand cushioning with dry coarse sand to under ground cable below and around after laying the cable jently punning down complete all as specified and directed by Engineer-in-Charge.
Note : Thickness after punning shall be considered for payment.
12
-
-
... More
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 33KV under ground earthed system 3 core XLPE armoured aluminium conductor cable of size 185 Sqmm including making connections complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
Maintenance and complete overhauling of 11 KV VCB rating upto 800 Amp suitable for rupturing capacity 350 MVA and remote control switch including dismantling of operating mechanism parts, well cleaning with petrol & CRC-226 and replacing moving parts including reassembling of parts after well cleaning of complete panel board, main bus bar, de-carbonizing all joints bus bar, CTs & PTs and spouts metal parts and making VCB perfect operating in manual and electric mode including all routine and preventive maintenance complete all as specified and directed by Engineer-in-Charge. Notes: 1. Replacement of certain spare parts required for repair shall be measured and paid separately under respective items of BOQ and shall be procured from approved OEM of suitable capacity under this item.
7
-
-
... More
Supply only microprocessor based relay in replacement of IDMT current relay including testing, setting of relay for proper tripping according to load all as specified and directed by Engineer-in-Charge.
Make : CG14N of Crompton & Greaves or equivalent
2
-
-
... More
Supply only terminal bushing assembly (spout bushing) 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only Tulip contact (isolating contact 630 A) 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only circuit spout RYB (bus bar insulators) 61mm for 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only vaccum interpreter chamber for 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only spring charging gear for 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only operating gear mech 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only trip shaft for 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only Tripping coil assembly 230 V AC for 11 KV complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply only Closing coil assembly 230 V AC for 11 KV complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply only trip roller for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
3
-
-
... More
Supply only vaccum interupter bottles for 11 KV VCB complete all as specified and directed by Engineer-in-Charge. Make : Crompton & Greaves
3
-
-
... More
Supply only Trip cross locking assembly for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply only Auxiliary Contactor 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply only Auxiliary switch 4 pole for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply only spring charging motor for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Make : Crompton & Greaves
3
-
-
... More
Supply and fixing Digital Voltmeter of range 0-12 KV with built in selector switch suitable for 110 V AC of square size 96x 96 mm dial with shrouded terminals complete all as specified and directed by Engineer-in-Charge.
5
-
-
... More
Supply and fixing Digital Ammeter of range 0-400 A with built in selector switch dial graduated scale of square size 96x 96 mm dial with shrouded terminals complete all as specified and directed by Engineer-in-Charge.
6
-
-
... More
S& F in replacement of handle for manual charging of Spring charging mechanism of VCBs consisting of gears grooves complete all as specified and directed by Engineer-in-Charge. Make : CROMPTON & GREAVES
2
-
-
... More
M&L for surface dressing not exceeding 15cm deep in soft/ loose soil including cutting of grass roots, bushes if any and filling of lower portion with soil obtained from dressing complete all as specified and directed by Engineer-in-Charge.
600
-
-
... More
M&L for graded gravel/coarse stone aggregate 20 to 40 mm spread and levelled in layers complete all as specified and directed by Engineer-in-Charge.
Note : Deduction @15% Shall be made for bulkage for payment purpose.
5
-
-
... More
M & L for PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation for poles, stays & mass concrete including necessary form work and fair finishing complete all as specified and directed by Engineer-in-charge
5
-
-
... More
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge
1
-
-
... More
Supply and fixing in replacement stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1.8 metre long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.
Note : PCC for foundation and earth work shall be measured and paid for separately.
5
-
-
... More
Supply, fixing & stretching in replacement aluminium conductor steel, reinforced (ACSR) of any size fixed on HT/LT poles fixed on insulators and binding with & including binding wire 14 SWG complete all as specified and directed by Engineer-in-Charge. Note : The weight of binding wire shall not be considered for payment.
1
-
-
... More
Supply & fix continuous earth wire/guard cradle hexagonal rectangular, fabricated out of 3.15 or 4mm dia galvanized steel wire including mild steel wire of 1.63mm dia complete all as specified Note For payment purpose weight of 3.15 or 4 mm dia galvanized wire shall only be measured and paid.
0.25
-
-
... More
Supply and fix in replacement shackle type insulators, vitreous porcelain white, brown or green for working pressure 11000 Volts grade of 150mm height and 150mm dia including galvanized mild steel straps of 38mm x 5mm size 20mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge
20
-
-
... More
Supply and fix in replacement of GI pipe 100 mm bore light grade for protection of cable including provision of clamps, nut, bolts etc required for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete all as specified and directred by Engineer-in-Charge.
10
-
-
... More
Supply and fix in replacement of GI pipe 50 mm bore light grade for protection of cable including provision of clamps, nut, bolts etc required for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete all as specified and directred by Engineer-in-Charge. Note for Srl Item No 67 & 68: (i) Excavation & earth work shall be measured and paid separately under respective item of this Schedule.
10
-
-
... More
M & L for boring hole across the Road/plinth/hard standing by trench less technology method suitable for 100mm bore pipe for 0.4 mpa working pressure for cable passing without damaging Road / Plinth /Floor complete all as specified and directed.
10
-
-
... More
S & lay un-reinforced precast concrete cable cover class HVP, type-1, with peak, size 300mm x 180mm x 40mm laid flat length of cover across the length of cable complete all as specified and directed by Engineer-in-Charge.
830
-
-
... More
Disconnecting and taking down old unserviceable burnt out fixed female contact from the existing position and supply and fix new female contact of hard drawn strip of air break switch 11000 Volts grade upto 400 Amps capacity out door type fixed with suitable size of nuts bolts and washers etc. and applying pertoleum jelly for smooth operation including testing complete all as specified and directed by Engineer-in-Charge. Make : JAYSHREE / VERSTEC / JSI
21
-
-
... More
Disconnecting and taking down old unserviceable burnt out moving male contact from existing position and supply and fix new moving male contact of hard drawn strip of air break switch 11000 Volts grade upto 400 Amps capacity out door type fixed with suitable size of nuts bolts and washers etc. and applying pertoleum jelly for smooth operation including testing complete all as specified and directed by Engineer-in-Charge. Make : JAYSHREE / VERSTEC / JSI
21
-
-
... More
Disconnecting the electric supply and taking down the unserviceable HT jumpers of bus bar / two / four pole structure and out point and supply and fix new HT jumpers of any length with suitable size of ACSR conductor and lugs PGI clamps and testing complete all as specified and directed by Engineer-in-Charge.
40
-
-
... More
Cutting the burnt out portion of the HT 11 KV grade underground XLPE cable of size 90 / 120 Sqmm 3 Core, supply and jointing HT cable straight through joint (Heat Shrinkable) 11 KV grade of size 120 Sqmm 3 Core including testing complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
Cutting the burnt out portion of the HT 11 KV grade underground XLPE cable of size 150 / 185 Sqmm 3 Core, supply and jointing HT cable straight through joint (Heat Shrinkable) 11 KV grade of size 120 Sqmm 3 core including testing complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
M&L for site clearance around 3 Mtrs of 4 pole structure including surface dressing not exceeding averaging 15 Cm deep in soft / loose soil and getting out including cutting of grass roots, bushes, tree branches and tree not exceeding 15 Cm girth, if any and filling of lower portion with soil obtained from cutting or dressing complete all as specified and directed by Engineer-in-Charge.
10
-
-
... More
M&L for site clearance around 3 Mtrs of 2 pole structure incuding surface dressing not exceeding averaging 15 Cm deep in soft / loose soil and getting out including cutting of grass roots, bushes, tree branches and tree not exceeding 15 Cm girth, if any and filling of lower portion with soil obtained from cutting or dressing complete all as specified and directed by Engineer-in-Charge.
14
-
-
... More
M&L for site clearance around 3 Mtrs of transformer plateform / 3 Mtrs around of fencing of transformer plateform, including surface dressing not exceeding averaging 15 Cm deep in soft / loose soil and getting out including cutting of grass roots, bushes, tree branches and tree not exceeding 15 Cm girth, if any and filling of lower portion with soil obtained from cutting or dressing complete all as specified and directed by Engineer-in-Charge. -----------------------------------------------------------------------------------------
Note : A sum of Rs. 1,54,705.00/- will be deducted on account of credit for dismantled/ demolished / taken down material. Please refer details on Srl Page No. 29 & 30 (Schedule of Credit) of Tender documents
22
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements