Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 59,980Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_MES_395910_1Bid Award Id
ViewTender No
83902Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Overhauling and servicing 33 KV VCB including disassembling of operating mechanism parts, spring, charging mechanism, well cleaning with cleaning agent & CRC -226 and replacing unserviceable parts/ accessories, oiling and greasing of moving parts, dismantling, checking and well cleaning of pole, insulator, checking of vaccume, interrupters, links, gas drive insulator and fibre reinforced plastic frame around the vaccume interrupters including routine and periodical test complete all as specified and directed.
1
-
-
... More
Supply, installation of spring charging motor operated with 220-230 volt 50 HZ ,140 RPM, suitable for operation of 33 kv oudoor VCB from indoor 33 kv control panel through NTC switch complete testing of all parameters of the operating relays(OT, WT, VTA, etc) complete all as specified and as directed.
1
-
-
... More
Supply, installation, testing commissioning of IDMT CGI14N over current & earth fault protection relay operated with 18-52 volt DC supply integrated with microprocessor technology, IDMT function, digital conversion of the measured value, LCD display, password protection, recording of 10 last fault record, breaker failure protection, programming through 6 button key pad complete with all accessories
1
-
-
... More
Supply and fix in replacement of ECO watt+750/12 volt 230v, 50 Hz UPS battery charging commences even at as low as 110 V main AC including integent thermal management sys to keep sys cool and shut down the sys during over temperature condition, high charging current with with 3 selectable current setting for quick charging of the battery including indication (main available, eco mode, ups mode, battery charging, low battery, over load) with alarm including battery 12 volt 120 AH with SMPS complete all accessories and connection complete all as specified and directed
1
-
-
... More
Supply and fix in replacement HT 33 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 insulators of rating upto 200 Amps
1
-
-
... More
S & F in replacement post type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 260mm height, 140 mm dia for 33000 volts grade complete all as specified and directed.
10
-
-
... More
S & F in replacement Disc type insulator, porcelain, vitreous ball and socket type, white, brown or green, Single disc assembly for tension with tension clamps for conductors, working pressure 33000 volts grade complete all as specified and directed.
9
-
-
... More
Supply and fix in replacement Power pack with Input voltage 110 Volt AC and output Voltage 110 Volt DC with minimum 30 minute battery back up suitable for HT 11 KV VCB complete all as specified and directed.
1
-
-
... More
Supply and fix in replacement moving contact blade for air break switch GOD for 11 KV complete all as specified and directed.
24
-
-
... More
Supply and fix in replacement Fixed contact jaw for air break switch GOD for 11 KV complete all as specified and directed.
24
-
-
... More
Supply and fix in replacement tinned copper flexible jumper 200 Amp for air break switch GOD for 11 KV complete all as specified and directed.
24
-
-
... More
Supply and fix in replacement MS jumper carrier for air break switch GOD for 11 KV complete all as specified and directed.
24
-
-
... More
Supply and fix in repair fixed back connector for air break switch GOD for 11 KV complete all as specified and directed.
24
-
-
... More
Dismantling of HT unserviceable pre-stressed concrete poles of any size and shape including taking out of embedded portion of poles from concrete after necessary demolition of concrete foundation and disposal of the same all as specified and directed. (Note:- Demolition of concrete, excavation, earthwork, cement concrete work etc. shall be measured and paid separately under relevant item of this schedule)
9
-
-
... More
Dismantling cross-arms of MS channel or angle sections etc. complete and serviceable materials keep In safe custody for re-use and unserviceable removing from the site(s) complete all as specified and directed.
16
-
-
... More
Dismantling insulators of any type, any size from HT poles and serviceable insulator keep in safe custody for re-use and unserviceable insulators removing from the Site(s), complete all as specified and as directed.
350
-
-
... More
Dismantling of HT stay assembly of any description and removed from the site(s) complete all as specified and directed. (Note:- Demolition of concrete, excavation shall be measured and paid separately under relevant item of this schedule)
8
-
-
... More
Dismantling of ACSR conductors from poles of any size & capacity and serviceable materials keep in safe custody for re-use and unserviceable materials removing from the Site(s), complete all as specified and as directed.
15
-
-
... More
Dismantling earth wire, guarding cradle or disturbed span serviceable materials keep in safe custody for re-use and removing unserviceable materials from the Site(s) complete all as specified and as directed.
4
-
-
... More
Dismantling of HT Lightning Arresters any type/size of any capacity with all fittings complete all as specified and directed.
10
-
-
... More
Excavating in trenches, for foundation of poles, stays or for laying of cables, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in soft/loose soil complete all as specified and as directed.
142
-
-
... More
All as per item No 24.00 here in before but exceeding 1.5 mtr in depth & not exceeding 3 mtr.
1
-
-
... More
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed.
110
-
-
... More
Removing excavated material (soil) n.exc.50m and depositing where directed at a level n.exc. 1.5m above the starting point complete all as specified and directed.
32
-
-
... More
M & L for plain cement concrete type C2 1:3:6 (40mm graded aggregate) for foundation of poles, stay assembly, struts, etc. complete all as specified and as directed.
8
-
-
... More
M & L for plain cement concrete type B1 (1:2:4) (20mm graded stone aggregate) as in coping of poles including necessary form work complete all as specified and as directed.
1
-
-
... More
Supply, erecting & fixing Prestressed concrete pole, 11.0 metres long. 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 specifications, complete all as specified & directed. (Note:- Excavation & earthwork, cement concrete, etc. will be measured and paid separately under relevant Items of this Schedule)
9
-
-
... More
M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including two coats of aluminium paint over a coat of red oxide zinc chrome primer including preparation of surfaces complete all as specified & as directed.
6
-
-
... More
Fixing only serviceable Cross arms, bracings, supports, clamps and back plates etc. as obtained from Srl item No 18.00 here-in-before including two coats of aluminium paint over a coat of red oxide zinc chrome primer after necessary preparation of surfaces complete all as specified & as directed.
10
-
-
... More
S & F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed.
165
-
-
... More
Fixing only serviceable pin type insulator as obtained from serial item No 19.00 here in before complete all as specified and directed.
85
-
-
... More
S & F Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, Single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts grade complete all as specified and directed.
50
-
-
... More
Fixing only serviceable Disc type insulator as obtained from srl item No 19.00 here in before complete all as specified and directed.
50
-
-
... More
M & L stay assembly complete with all accessories such as mild steel galvanized flat iron stay clamp, 7/4 mild steel galvanized stay wire, mild steel galvanized stay bow, thimbles, 20mm dia mild steel galvanized stay rod and mild steel galvanized stay-plate all as shown in electrical plate No 1 of SSR Part-I complete all as specified and as directed. (Note: Excavation, earthwork, cement concrete work shall be measured and paid separately under relevant Items of this schedule)
8
-
-
... More
M & L for Galvanised stay strand, size 7/4mm including dismantling unserviceable stay wire complete all as specified and directed.
0.5
-
-
... More
M & L for aluminium conductor, steel reinforced (ACSR) of any size as approved on HT/LT Poles including straining, binding to insulators with copper binding wire with connectors, etc, providing PVC sleeves for jumpers as in OH conductors complete all as specified and as directed.
8
-
-
... More
Refixing and tightening of serviceable ACSR conductor for overhead lines of any size on LT poles including provisioning of necessary copper binding wire, connectors, PVC sleeves for jumpers etc as obtained from srl item No 15.00 here-in-before complete all as specified and as directed.
7
-
-
... More
M & L for Galvanised steel continuous earth wire 4mm dia complete all as specified and directed.
2
-
-
... More
M & L for Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 4mm dia complete all as specified and directed.
1
-
-
... More
Fixing only serviceable Cradles, made of galvanised steel wire of any size as obtained from serial Item No 22.00 here in before complete all as specified and directed.
1
-
-
... More
M & L for fixing and connection of lightening arresters non linear resistor type complete with all fittings, transmission class, discharge capacity 10 Kilo Amp of rating 11 KV complete all as specified and as directed.
10
-
-
... More
Trimming of tree branches around the overhead conductor, poles & stays (not less than 3 metre) to clear the approach of overhead lines including removing of nest, wild grass creepers, unwanted vegetation, etc from pole/ stay including cleaning of creepers climbed on poles and angles, channels and disposed off from site complete all as specified & directed by Engr-in-Charge.
550
-
-
... More
Surface dressing of installation area by removing of grass, creepers, etc from the roof of the building, in fencing and surrounding area of installation building complete all as specified and directed.
1150
-
-
... More
Opening top cover from transformer of capacity 50 KVA to 500 KVA at site for replacement of old unserviceable spares/components & reassembling & testing complete all as specified and as directed by Engr-in-Charge. (Note:- Unserviceable spare/components parts shall be measured and paid separately here-in-after under item No 48 to 61 as supply only rates)
9
-
-
... More
Supply only LT Bush insulators as per existing size and shape for 350 to 500 KVA capacity transformers.
5
-
-
... More
Supply onlyLT Bush insulators as per existing size and shape for 200 to 300 KVA capacity transformers.
7
-
-
... More
Supply only LT Bush insulators as per existing size and shape for 50 to 150 KVA capacity transformers.
7
-
-
... More
Supply only LT stud (metal parts) as per existing size and shape for 350 to 500 KVA capacity transformers.
6
-
-
... More
Supply only LT stud (metal parts) as per existing size and shape for 200 to 300 KVA capacity transformers.
7
-
-
... More
Supply only LT stud (metal parts) as per existing size and shape for 50 to 150 KVA capacity transformers.
5
-
-
... More
Supply only gasket (set of four) for LT bushing as per existing size & shape complete for the 350 to 500 KVA capacity transformers.
5
-
-
... More
Supply only gasket (set of four) for LT bushing as per existing size & shape complete for 200 to 300 KVA capacity transformers.
6
-
-
... More
Supply only gasket (set of four) for LT bushing as per existing size & shape complete for 50 to 150 KVA capacity transformers.
5
-
-
... More
Supply only top cover gasket set as per existing size and shape complete for 350 to 500 KVA capacity transformers.
6
-
-
... More
Supply only top cover gasket set as per existing size and shape complete for 200 to 300 KVA capacity transformers.
7
-
-
... More
Supply only top cover gasket set as per existing size and shape complete for 50 to 150 KVA capacity transformers.
6
-
-
... More
Supply of temperature gauge of range 0 to 200oC for indication of temperature rise in transformer oil for transformers upto 500 KVA capacity.
6
-
-
... More
Supply only breather for transformer up to 500 KVA capacity complete all as specified and directed.
8
-
-
... More
M & L for preparation of old painted steel or iron surfaces of 50 KVA to 100 KVA transformer by scrapping with steel wire brush/scrapper emery paper etc and applying two coats of synthetic enamel smoke grey paint over a coat of red oxide primer (painting shall be done by spray machine) including writing of SM No, MES No etc. at prominent place/location of transformer with black synthetic enamel thick paint in white back ground complete all as specified and directed
(Note:- Necessary shut down of power supply should be granted from the Engr-in-Charge by the contractor before proceeding the work, also electric supply should be restored as early as possible after completion of the work)
9
-
-
... More
All as per ser item No. 62 here-in-before but transformer capacity 125 KVA to 200 KVA
3
-
-
... More
All as per ser item No. 62 here-in-before but transformer capacity 250 KVA to 500 KVA
2
-
-
... More
M & L for preparation of old painted rusted steel/iron surfaces of any description exc. 10cm in width or girth at different location and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer complete all as specified and directed.
150
-
-
... More
Supply, filling & toping up new transformer oil conforming to for filling/toping up oil of transformer up to desired level complete all as specified and as directed. (Note: Dielectric strength of oil should not be less than 50 KV complete all as specified and directed.) Make:- Gulg/ Power Oil or equivalent as approved by GE.
1400
-
-
... More
Dehydration and filtration of existing transformer oil of transformer at different location in site with filtration machine and heating system to get Di-electric strength of oil 45KV minimum without disturbing the power supply system complete all as specified and as directed.
2600
-
-
... More
M&L Earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick buried directly in ground preferably vertically in ground with top edge not less than 1.25 mtr deep below normal ground level connected with and including galvanised iron wire 4 mm dia as earthing lead by means of nuts bolts and washers of galvanized iron protected by 15mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe, including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size, charcoal and salt in alternate layers necessary excavation and earth work in soft/loose soil all as shown in Electric plate No. 3 of SSR part-I and testing on completion complete all as specified and as directed.
8
-
-
... More
M & L earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick, burried directly in ground (earth pit not less then 2.25m deep bellow ground level) with top edge of the plate not less then 1.5m deep below normal ground level connected to galvanised iron strip of 32 x 6mm earth lead by means of bolt, nuts, washers of galvanised steel earth strip protected by and including GI pipe 40mm dia bore (light grade) and connected to main test point as directed and including concrete pit in PCC(1:3:6)type C-1 precast RCC(1:1.5:3)type A-1 cover slab 54 x 5 cm reinforced with 4mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8mm dia TMT bar embedded in precast cover slab funnel wire mens 20mm bore GI pipe (medium grade) for watering charcoal and salt in altenate layers, including necessary excavation and earth work in any type of soil complete all as shown on electrical plate No. 3 of SSR part-I complete all as specified.
7
-
-
... More
M & L for filling of clean dry coarse sand all-round the transformer platform and cable duct after cleaning grass/small bushes, etc. including removal of old dirty sand complete all as specified and directed.
6
-
-
... More
M & L for filling of gravels of size 20 to 40mm all-round the transformer platform over sand filling complete all as specified and directed. (Note:- Sand filling shall be measured & paid separately here-in-before)
41
-
-
... More
S & F drop out expulsion fuse assembly single pole 25 to 50 Amp capacity, 11000 Volts grade after taking out old unserviceable one complete all as specified and directed.
8
-
-
... More
Supply, jointing and testing cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old one complete all as specified and directed.
8
-
-
... More
Supply, jointing and testing cable jointing kit for 11 KV grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old one complete all as specified and directed.
6
-
-
... More
All as per item no 74.00 as above but cable size 120 to 185 Sqmm
4
-
-
... More
Supply, jointing and testing cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including taking out old one complete all as specified and directed.
4
-
-
... More
Disconnection of HT/LT connection, earthing lead and taking down carefully defective Transformer of capacity of 50 to 500 KVA, 11 KV/440Volt from 2/4 pole structure/Platform including transportation to factory workshop and draining out existing transformer oil, opening the top cover of the transformer, by removing nut, bolts, washer etc and lifting the core and winding by using triploid and chain pulley after removing LT/HT spindle with bushing and cleaning the yoke and winding/core and spindle bushing the same winding/core and spindle bushing and replace the worn out nut, bolts, washer gaskets etc with provision of cork sheets of 6mm thick (best quality) and filling the transformer oil which was removed earlier, through stream line filter after dehydration and back to site after necessary repair & lifting of Transformer to its original position including necessary testing complete all as specified and directed.
5
-
-
... More
Material and labour for rewinding of HT coil of transformer any capacity using proper size DPC copper wire and HT insulation material suitable for working voltage 11 KV complete all as specified and directed.
210
-
-
... More
Re-insulation of HT coil of transformer any capacity using proper size DPC Copper wire and HT insulation material suitable for working voltage 11 KV complete all as specified and directed.
80
-
-
... More
Material & Labour for rewinding of LT coil of transformer any capacity using proper size DPC copper wire and HT insulating material suitable for working voltage 11 KV complete all as specified and directed.
140
-
-
... More
Re-insulation of LT coil of transformer any capacity using proper size DPC Copper wire and HT insulation material suitable for working voltage 11 KV complete all as specified and directed.
80
-
-
... More
Material and labour for rewinding of LT coil of Servo Voltage Stabilizer any capacity using proper size DPC copper wire and LT insulation material suitable for working voltage 440Volt complete all as specified and directed.
50
-
-
... More
Re-insulation of LT coil of Servo Voltage Stabilizer any capacity using proper size DPC Copper wire and LT insulation material suitable for working voltage 440 V complete all as specified and directed.
100
-
-
... More
Material & Labour for off load tap changer switch suitable for transformer of capacity 63 to 200 KVA complete all as specified and directed.
5
-
-
... More
Material & Labour for off load tap changer switch suitable for transformer of capacity 250 to 500 KVA complete all as specified and directed.
2
-
-
... More
Material & Labour for 32 mm dia gunmetal drain valve of transformer as per existing one complete all as specified and directed.
5
-
-
... More
All as per serial item No 86.00 above but 25mm dia.
5
-
-
... More
All as per serial item No 86.00 above but 20mm dia.
5
-
-
... More
Material & Labour for HV bushing with brass terminal (metal parts) with nuts and washer and sheet gasket suitable for transformer of capacity 50 to 500 KVA complete all as specified and directed.
9
-
-
... More
Dismantling air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism complete all as specified and directed.
14
-
-
... More
Material & Labour for switches air break, gang operated, triple pole, 11000 Volts grade and current rating upto 200 Amps, mechanically operated, mounted on insulator and steel frame with operating mechanism worked from ground level complete all as specified and directed.
14
-
-
... More
Taking out old unserviceable HT cables including protection pipes/bricks or precast concrete cable cover etc of any description from trenches/poles/transformers of any size and unserviceable materials removing from site all as specified and as directed. (Note:- Excavation & earthwork shall be measured & paid separately here-in-before)
400
-
-
... More
Supply, Laying, Jointing, commissioning & testing HT UG cable of size 95 Sqmm 3 core, 11000 Volts , aluminium conductor, XLPE insulated, earthed, screened, PVC bedded, armoured heavy duty electric cable conforming to IS-7098 (part-II) 1985 with latest amendments drawn through pipe or laid in trenches, fixed on poles etc. complete all as specified and as directed.
210
-
-
... More
All as ser per item no 93.00 above above but size of cable 120 Sqmm 3 core
190
-
-
... More
Laying only old serviceable 40 to 50 mm thick roughly hammer dressed stone 25 to 30 cm wide and no less than 60 cm long, laid dry and abutting each other with gap adjacent slab not exc.10 mm for protection of UG cable complete all as directed
52.5
-
-
... More
M & L for 40 to 50 mm thick roughly hammer dressed stone 25 to 30 cm wide and no less than 60 cm long, laid dry and abutting each other with gap adjacent slab not exc.10 mm for protection of UG cable complete all as directed
35
-
-
... More
Supply and spreading clean dry( tibba) sand in trenches for cushioning all as specified for cable protection complete all as directed.
28
-
-
... More
Material & Labour for 80 mm dia GI pipe ‘light grade’ with all fittings for protection of cable laid on road crossing, drain crossing, laid in floor or fixed to iron structures/poles complete all as specified and directed.
45
-
-
... More
Demolition of plain cement concrete of any description and in any position not otherwise specifically provided for complete all as specified and as directed.
8
-
-
... More
Supply and install test and commissioning of factory made powder coated cubical panel board of size 0.90 mtr x 0.60 mtr x 0.60 mtr 3 phase and wire out door type front and rear door made out of 3.15 mm sheet PGI sheet, including 200 Amps capacity Aluminium Busbar for junction box of HT connection and mounted and MS angle iron frame of size 50 x50 x 6mm grounted in PCC type B2 above ground level. complete all as specified and directed.
4
-
-
... More
Preparation of old painted surfaces and removing dust and other deposited material by scraping from PCC poles of upto 11.00 metre length, cross arms brackets and applying 2 coats of aluminium paint to all steel surfaces, including MS clamps, cable protection pipe bracket fitted with street light fittings etc and including Zebra colour of painting from 1.5 mtr height from the top of caping/ bottom of pole as per site condition and numbering of poles complete all as specified and as directed by Engr-in –charge. (Note:- Zebra colour will be applied by synthetic enamel paint of black/yellow colour as approved in alternate layer of 30 cm height of each layer)
280
-
-
... More
All as per ser item no 101 above here-in-before but 2/3 pole structure complete all as specified and directed.
6
-
-
... More
All as per ser item no 101 above here-in-before but 4 pole structure complete all as specified and directed.
15
-
-