Military Engineer Services Tender

If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Military Engineer Services - MES Tender

Works
Civil And Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date24 Jan 2023
Closing Date15 Feb 2023
Tender Amount₹ 24,75,577 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-charge .

365

-

10

... More
M & L for sand cushioning with dry coarse canal sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.

275.4

-

10

... More
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable complete all as specified and directed by Engineer-in-Charge.

29.56

-

10

... More
Supplying, laying, jointing and testing and commissioning of 25 sq mm, 4 core PVC insulated, screened, PVC bedded galvanized steel strip or wire armoured electric power cable heavy duty multi stranded aluminum conductor & PVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. Note: Excavation, earth work, sand cushioning and brick protection required for item shall be measured and paid separately under respective items of BOQ

1200

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 10 Sqmm, 2 core complete all as specified and directed by Engineer-in-Charge

500

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 16 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge

700

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 50 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

300

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 70 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

300

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 95 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

300

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 120 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

200

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 150 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

200

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 185 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

200

-

10

... More
All as per Srl item No 7 here-in-before but cable of cross sectional area 240 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge

100

-

10

... More
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of earth plate at a depth of not less than 1.5 meter below ground level, earth plate surrounded by 15cm thick and packed layer of charcoal dust and common salt, connected to earth lead of GI wire 4 mm dia. by means of bolts, nuts and washers of the earth wire galvanized iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanized iron pipe light grade 40mm dia. up to earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat iron and perforated water pipe 20mm dia. GI medium grade of length 2.25 meter and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 6mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. Complete all as specified and directed by Engr-in-charge. Notes: - (i) GI strip up to earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 meter away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover

8

-

10

... More
M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of earth plate at a depth not less than 1.5 meter below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 32mm x 6mm thick as earth lead by means of bolts, nuts and washers of galvanized iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanized iron pipe light grade 40mm dia. up to earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat iron and perforated water pipe 20mm dia. GI medium grade of length 2.25 meter and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 6mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. Complete all as specified and directed by Engr-in-charge. Notes: - (i) GI strip up to earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 meter away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover

8

-

10

... More
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc as required for 32x6mm galvanized iron strip complete all as specified and directed by Engr-in-charge.

20

-

10

... More
Supplying, erecting in true vertical position in replacement of 9 meter long ,PCC pole ,102mmX172mm at top and 12mmX279mm at bottom complete with cast iron base plate, finial taper plug, bolts nuts and screws including painting with two coat of synthetic enamel paint black and white in alternate strips 30cm each up to 1.5 meter height from top of PCC coping and remaining portion of pole shall be painted with two coats of aluminum paint including writing pole No. with black synthetic enamel paint over 15 cm dia. yellow round base prepared with synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. NOTE: - Excavation, earth work and concrete work for embedding poles shall be measured and paid separately.

5

-

10

... More
Supplying, erecting in true vertical position in replacement of 9 meter long ,type 410 SP- 31 steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts nuts and screws including painting with two coat of synthetic enamel paint black and white in alternate strips 30cm each up to 1.5 meter height from top of PCC coping and remaining portion of pole shall be painted with two coats of aluminum paint including writing pole No. with black synthetic enamel paint over 15 cm dia. yellow round base prepared with synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. NOTE: - Excavation, earth work and concrete work for embedding poles shall be measured and paid separately.

8

-

10

... More
Supply and fixing new generation energy saving & environmental friendly long life versatile pressure die-cast aluminum IP-66 road way luminaries 45 watt LED with high power LEDs as light source and electronic driver including testing complete all as specified and directed by Engineer-in-Charge

5

-

10

... More
Supply and fixing new generation energy saving & environmental friendly long life versatile pressure die-cast aluminum IP-66 road way luminaries 70 watt LED with high power LEDs as light source and electronic driver including testing complete all as specified and directed by Engineer-in-Charge

5

-

10

... More
M & L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation for poles, stays & mass concrete complete all as specified and directed by Engineer-in-charge

6

-

10

... More
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in pedestal coping of poles etc including weathering, slightly rounded or chamfered angle and necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge

1

-

10

... More
M&L for surface excavation not exceeding 30 cm deep and averaging 15cm deep in soft/ loose soil and getting out including cutting of grass roots, bushes if any and filling of lower portion with soil obtained from cutting or dressing complete all as specified and directed by Engineer-in-Charge.

500

-

10

... More
Dismantling insulators of any type and make including clamps from poles complete all as specified and directed by Engineer-in-Charge.

30

-

10

... More
Dismantling and taking down cross arm of MS channel or angle section etc distance as directed complete all as specified and directed by Engineer-in-Charge.

1

-

10

... More
Dismantling and taking down ACSR conductor of any size complete all as specified and directed by Engineer-in-Charge.

1

-

10

... More
Dismantling of stay assembly complete all as specified and directed by Engineer-in-Charge

10

-

10

... More
Dismantling and taking out PCC poles of any size etc complete all as specified and directed by Engineer-in-Charge.

8

-

10

... More
Dismantling and taking out steel poles of any size etc complete all as specified and directed by Engineer-in-Charge.

8

-

10

... More
M & L for cutting road /plinth /hard standing for laying of pipe for passing cable through road without damaging Road / Plinth /Floor including making good with bitumen ready mix material as per existing specifications complete all as specified and directed by Engineer-in-Charge.

10

-

10

... More
S&F street light timer switch i.e. nature switch which works on the basis of measurement of lux level of infra red rays along with enclosure box having dust and termite proof, outdoor type mounted on electric panel or on pole single phase with contactor, MCB rating 40 Amps with load bearing capacity of 5 KW complete all as specified and directed by Engineer-in-Charge. Make - Indo Asian Cat No TL032ASO/ Havells Cat No. IHXTSS01060A /Sandeep 02ES5KWIP

1

-

10

... More
S&F street light timer switch i.e. nature switch which works on the basis of measurement of lux level of infra red rays along with enclosure box having dust and termite proof, outdoor type mounted on electric panel or on pole three phase with contactor, MCB rating 20 Amps with load bearing capacity of 5 KW complete all as specified and directed by Engineer-in-Charge. Make - Indo Asian Cat No TL032ASO/ Havells Cat No. IHXTSS01060A /Swadeep 02EC5KW3P

1

-

10

... More
Supplying and fixing in replacement air break gang operated switch, triple pole, 11 KV (outdoor type) mechanically operated, suitable for vertical mounting fixed type complete with 3 Nos silicon rubber polymeric insulators and steel frame, with operating mechanism worked from ground level with fixed contacts of phosphorous bronze and moving control of copper, for current rating upto 400 Amps including GI pipe heavy duty of required size and with locking arrangement including Godrej (Freedom) 65mm pad lock with two keys with fuse mounts, fuse carriers and HT fuse elements having 400 amp rating conforming to CPRI approval and IEC 61109 suitable for HT 11 KV, 50 Hz, AC supply including necessary electric connections, mild steel ISMC-75 of required length fixed with mild steel clamps made out of 50mm x 6 mm flat iron,nut,bolts and washers of required size for fixing GOD complete and painting structural steel with 2 coat of synthetic enamel paint over a coat of red oxide primer on steel surfaces, complete (Set of three) all as specified and directed by Engineer-in-Charge.

1

-

10

... More
Supplying and fixing cross arms, bracings, stiffeners, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, binding cold or hot, drilling holes for bolts, in any shape or size as indicated or directed complete all as specified and directed by Engr-in-Charge.Note: Exposed steel surface shall be treated with two coats of aluminum paint over a coat of red oxide primer and unexposed surface of steel sections shall be applied one coat of red oxide primer.

1

-

10

... More
Supply & Fix aluminium conductor steel, reinforced (ACSR) of any size fixed on HT/LT poles fixed on insulators and binding with & including binding wire 14 SWG complete all as specified and directed by Engineer-in-Charge. Note : The weight of binding wire shall not be considered for payment.

0.75

-

10

... More
Supply and fix shackle type insulators, vitreous porcelain white, brown or green for working pressure 1100 volts grade of 100 mm height and 115 mm dia including galvanized mild steel straps of 31mm x 5mm size,14mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge.

40

-

10

... More
Supply and fix stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1.8 metre long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge. Note : Excavation, earthwork and PCC in foundation will be included under respective items of BOQ.

10

-

10

... More
Supply & fix continuous earth wire/guard cradle hexagonal rectangular, fabricated out of 3.15 or 4mm dia galvanized steel wire including mild steel wire of 1.63mm dia complete all as specified and directed by Engineer-in-Charge. Note For payment purpose weight of 3.15 or 4 mm dia galvanized wire shall only be taken and clips & clamps eye hooks shall be measured and paid for separately.

0.25

-

10

... More
M&L for opening the joints of HT / LT overhead conductor from the end of poles, re-stretching the overhead aluminum conductor with chain pulley and other T&P machineries, refixing the overhead conductor at the same place such that sagging of conductor is not more than 3% complete all as specified and directed by Engineer-in-Charge.

300

-

10

... More
Cutting/ trimming of tree branches not exc 10cm girth touching/approaching the LT/HT overhead lines with hack saw/axe to clear the LT/HT line upto 3 metre on each side (Horizontal and / or vertical) including disposal of trimmed branches 2 KM away inside the cantonment area & clearing site complete all as specified and directed by Engineer-in-Charge. Note :- 3 metre width on each side of LT/HT line shall be cleared and each span having not less than 3/5 conductors and min30-40 m pole to pole distance.

300

-

10

... More
Supply and fix GI pipe 100 mm bore light grade for protection of cable including provision of clamps, nut, bolts etc required for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete all as specified and directed by Engineer-in-Charge. NOTE: Clamps & nut bolt required for fixing included in item rate. Excavation & earth work shall be measured and paid separately under respective item of this BOQ

40

-

10

... More
All as Item No 44 above but 50 mm dia pipe complete all as specified and directed by Engineer-in-Charge.

40

-

10

... More
Laying only existing surface cable( LT/XPLE/PVC cable) to undergroundof size ranging 10 Sqmm 2 core to 16 Sqmm 4 core including disconnecting it and reconnecting using lugs cable and gland etc all as specified and directed by the Engineer-in-Charge. Note Excavation, earth work, and protective work shall be measured and paid separately under respective items

250

-

10

... More
Laying only existing surface cable ( LT/XPLE/PVC cable) to underground of size ranging 25 Sqmm 4 core to 120 Sqmm 3.5 core including disconnecting it and reconnecting using lugs cable and gland all as specified and directed by the Engineer-in-Charge. Note Excavation, earth work, and protective work shall be measured and paid separately under respective items

250

-

10

... More
S&F on pole / wall /in panel , Sheet metal enclosure Bus bar chamber consisting 4 pole 400 Amp 415 volts ,copper bus bar suitable for connecting cable as a junction including connecting of existing cables with suitable sizes aluminum thimbles all as specified & directed by Engineer-in-Charge.

4

-

10

... More
Description all as per srl item No 48 but capacity 200 Amp 4 pole 415 volt complete all as specified and directed by Engineer-in-Charge

4

-

10

... More
Description all as per srl item No 48but capacity 100 Amp 4 pole 415 volt complete all as specified and directed by Engineer-in-Charge

5

-

10

... More
Supply and fix in replacement Hot moulded (FRP) junction box of size 240mm x 160130mm x 110 mm for street light pole with locking arrangement with 32 Amps, 4 way heavy duty terminal block suitable connection for three phase incoming cable three phase outgoing cable and single phase connection for light fittings with control MCB SP 2.5 Amps 01 Nos enclosed in thermoplastic box in closed shock proof safe IP 65, weather, vermin proof, dust and water proof complete with two number cable entry gland of standard size with suitable size mild steel clamps of size 25x3mm with nut and bolt to fix on pole complete all as specified and directed by Engineer-in-Charge

20

-

10

... More
S&F with alternation and modification for smooth functioning of MCCBs door for closingin replacement of MCCB400 Amp, Four pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 36 KA complete all as specified & directed by Engineer-in-Charge.

4

-

10

... More
S&F with alternation and modification for smooth functioning of MCCBs door for closingin replacement of MCCB 315 /350Amp, Four pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 36 KA complete all as specified & directed by Engineer-in-Charge.

4

-

10

... More
S&F in replacement of MCCB, with alternation and modification in the Panel so that after installation of MCCB, panel door of MCCB will closed wihout any hindernance, MCCB 250 Amp, Four pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 36 KA complete all as specified & directed by Engineer-in-Charge.Make: Indo Asian/Havells/Schenider

4

-

10

... More
S&F with alternation and modification for smooth functioning of MCCBs door for closingin replacement of MCCB 200 Amp, four pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 36 KA complete all as specified & directed by Engineer-in-Charge.Make: Indo Asian/Havells/Schenider

6

-

10

... More
S&F with alternation and modification for smooth functioning of MCCBs door for closingin replacement of MCCB 125 Amp, Three pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 16KA complete all as specified & directed by Engineer-in-Charge.Make: Indo Asian/Havells/Schenider

8

-

10

... More
S&F with alternation and modification for smooth functioning of MCCBs door for closingin replacement of MCCB 63 Amp, three pole, 415 Volts with adjustable thermal and adjustable magnetic setting with breaking capacity not less than 16 KA complete all as specified & directed by Engineer-in-Charge.Make: Indo Asian/Havells/Schenider

8

-

10

... More
Disconnection & removing and reneual of all LT connection from panel including ACB,unserviceable CTs, any type of Busbar aluminium /copper,supporting insulator,lugs.removing unsv insulation ,cable glands,MCCBs,volt meter, ameters,pilot lamp,selector switch,bakonite insulation of as measuring instrumentation,nuts,bolts, fabrication materials,CRCA sheet as per required , etc all accessories of unsv of panel a ,connectors etc. excavation works ,returning and filling for cables and panel are also including this rate complete all as specified and directed by Engineer-in-Charge.

12

-

10

... More
Supply and fix copper busbar as per existing size of bus bar including mounted on saddle /porcelain insulator with screwing and making hole and connection for cables,MCCBs etc after testing of completion of works

20

-

10

... More
Supply and fix Aluminium busbar as per existing size of bus bar including mounted on saddle /porcelain insulator with screwing and making hole and connection for cables,MCCBs etc after testing of completion of works complete all as specified and directed by Engineer-in-Charge

20

-

10

... More
Disconecting all electric connections of APFC panel and removing the damaged/unserviceble components, Cleaning, trouble shooting, programing of APFC relay, tightning of of all terminals and overhauling the APFC panels,Maintaining the Power Factor .99 at APFC panel & callibration after fixing all as specified and directed by Engr-in-Charge.Note :- (i) The new spare parts required for replacement shall be measured and paid separately. (ii) Relevent T&P and testing equipments/tools and minor accessories are arranged by the contractor and included in the unit rate of item.

6

-

10

... More
Supplying ,installation ,testing and commissionng of 8 step APFC relay complete all as specified and directed by Engineer-in-Charge. Make- EPCOS,L & T,Schnider,Siemens

4

-

10

... More
Supplying ,installation ,testing and commissioning of 12step APFC relay complete all as specified and directed by Engineer-in-Charge. Make EPCOS,L & T,Schnider,Siemens

2

-

10

... More
S & F for SPREADER LINKS T P 400 AMP complete all as specified and directed by Engineer-in-Charge

2

-

10

... More
Supplying ,installation ,testing & commissioning of 3 pole MCB 6 to 32 Amp complete all as specified and directed by Engineer-in-Charge. Make10 KA L & T/SIEMNS/SCHNIDER

2

-

10

... More
Supplying ,installation ,testing & commissioning of 3 pole MCB 40 to 63 Amp 10 KA complete all as specified and directed by Engineer-in-Charge. Make10 KA L & T/SIEMNS/SCHNIDER

4

-

10

... More
Supplying ,installation ,testing & commissioning of single pole MCB 6 Amp 10 KA complete all as specified and directed by Engineer-in-Charge. Make10 KA L & T/SIEMNS/SCHNIDER

21

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 5 KVAr. Make-EPCOS,L & T,Schnider,Siemens

1

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 10 KVAr complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T,Schnider,Siemens

1

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 15 KVAr. Make-EPCOS,L & T,Schnider,Siemens

12

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 20 KVAr. Make-EPCOS,L & T,Schnider,Siemens

3

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 25KVAr complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T,Schnider,Siemens

6

-

10

... More
Supplying ,installation ,testing & commissioning of capacitor duty contactor 30 KVAr complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T,Schnider,Siemens

6

-

10

... More
Supplying ,installation ,testing & commissioning of AC 3 Duty Power contactors 50 A complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T,Schnider,Siemens

4

-

10

... More
Supplying ,installation ,testing & commissioning of AC 3 Duty Power contactors 16 A WITH ADD ON 4 NO+4 N C complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T, Schnider,Siemens

3

-

10

... More
Supplying ,installation ,testing & commissioning of AC 3 Duty Power contactors 70 A complete all as specified and directed by Engineer-in-Charge. Make-EPCOS,L & T,Schnider,Siemens

6

-

10

... More
Supplying ,installation ,testing & commissioning of class 1 accuracy current transformer 200/5 TO 400/5 complete all as specified and directed by Engineer-in-Charge. Make-RISHABH/A E/KAPPA

11

-

10

... More
Supply & fitting of multy stranded FRLS wire for control wiring in panel board 1.5sqmm complete all as specified and directed by Engineer-in-Charge. Make-HAVELLS/PHENOLEX/RR KABEL

100

-

10

... More
Supply & fitting of multy stranded FRLS wire for power & control wiring in panel board 4 sqmm complete all as specified and directed by Engineer-in-Charge. Make-HAVELLS/PHENOLEX/RR KABEL

100

-

10

... More
Supply & fitting of multy stranded FRLS wire for power & control wiring in panel board 6 sqmm Make-HAVELLS/PHENOLEX/RR KABEL

90

-

10

... More
Supply & fitting of multy stranded FRLS wire for power & control wiring in panel board 10 sqmm complete all as specified and directed by Engineer-in-Charge. Make-HAVELLS/PHENOLEX/RR KABEL

25

-

10

... More
Supply & fitting of multy stranded FRLS wire for power & control wiring in panel board 16 sqmm complete all as specified and directed by Engineer-in-Charge. Make-HAVELLS/PHENOLEX/RR KABEL

4

-

10

... More
Supplying ,installation ,testing and commissioning of Heavy duty 440 V0lts cylindrical power capacitors complete all as specified and directed by Engineer-in-Charge. Make EPCOS,L & T,Schnider,Siemens

40

-

10

... More
Supplying ,installation ,testing and commissioning of Auto-manual -off selector switch complete all as specified and directed by Engineer-in-Charge.

6

-

10

... More
Supplying ,installation ,testing and commissioning of 3 core armored aluminium cable 10 sqm. complete all as specified and directed by Engineer-in-Charge. Make-HAVELLS/PHENOLEX/RR KABEL

15

-

10

... More
Taking out unserviceable analog type voltmeter from the panel boards, supply and fixing analog type voltmeter of 0-500 volt range suitable for three phase supply including connection and testing complete all as specified and directed by Engineer-in-Charge. Make AE/IMP/C&S/L&T

10

-

10

... More
Taking out unserviceable selector switches from the panel boards, supply and fix selector switches, 4 position, for volt meter and ammeter suitable for three phase supply including connection and testing complete all as specified and directed by Engineer-in-Charge.Make AE/IMP/C&S/L&T

8

-

10

... More
Taking out unserviceable analog type ammeter from the panel boards, supply and fixing analog type ammeter of 0-500 Amps range without CTs suitable for three phase supply including connection and testing complete all as specified and directed by Engineer-in-Charge. Make AE/IMP/C&S/L&T

8

-

10

... More
Taking out unserviceable LED type indicator lamp unit from the panel boards , supply and fix LED type indicator lamp unit of red/ yellow/ blue/ green/ Amber with bulb including connection and testing complete all as specified and directed .Make AE/IMP/C&S/L&T

8

-

10

... More
M&L for preparation of old plastered or unplastered surface of wall and applying two coats of white wash complete all as specified & directed by Engineer-in-Charge.

200

-

10

... More
Note : Notes : (i) Amount of credit for retrieved materials is mentioned in Sch 'A' Section-II of tender documents in pdf form which will be deducted while acceptance of tender offline. (ii) Contractor will liable for penality of Rs 500/day if he fail to intertain the complaints given to him on next day.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.