Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Military Engineer Services - MES Tender
Eprocure
Opening Date13 Oct 2018
Closing Date1 Dec 2018
Tender Amount₹ 14,26,067 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 29,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_MES_218966_1Bid Award Id
ViewTender No
CWE BKN TENDER NO 37 OF 2018Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Description as per srl item No-3 but for cross sectional area 120 Sqmm 3.5 core 1100 volts grade complete all as specified and as directed by Engineer-in-Charge.
165
-
-
... More
Description as per srl item No-3 but for cross sectional area 95 Sqmm 3.5 core 1100 volts grade complete all as specified and as directed by Engineer-in-Charge.
80
-
-
... More
Supply & fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination coldshrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified as directed by Engineer-in-Charge.
4
-
-
... More
Supply and fix cable jointing kit for 11KV grade cable for Indoor/Outdoor straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 .5 / 4 core XLPE, armoured, Al conductor cable of size 95 to 150 sqmm,typecomplete all as specified as directed by Engineer-in-Charge.
6
-
-
... More
Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge.
165
-
-
... More
Returning, filling in approved soft/loose soil including spreading, leveling, watering and well ramming in layers each n.exc 25cm complete all as specified and as directed by Engineer-in-Charge.
125
-
-
... More
Removing surplus soil to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed by Engineer-in-Charge.
40
-
-
... More
M& L for sand cushioning and cover (using local tibba sand), 80 mm thick before laying of cable and 150 mm thick after the cable is laid, complete all as specified and as directed by Engineer-in-Charge. (Note : 1. Approved local tibba dry sand after removal of vegetations, grass and other deleterious substances shall be used for sand cushioning and cover. 2. For payment purpose , only punned thickness will be measured).
30
-
-
... More
Supplying and laying un-reinforced, precast concrete cable cover class HVP, type-I with peak size 300 mm x 180 mm x 40mm all as specified and directed by Engineer-in-charge
2263
-
-
... More
Supplying and laying for GI pipe light grade 100 mm bore (ISI marked) laid in trenches/ road crossings/ fixed to poles /walls/ path /drain/floors with and including all necessary clamps, nut bolts and washers etc all fitting as required, supplied and fixed in repairs, complete all as specified and as directed by Engineer-in-Charge.
18
-
-
... More
Supplying, Installing, commissioning & testing of automatic intelligent power factor corrector (AIPFC ) Capacitor Bank of capacity 100 KVAR with staging 1+2+3+4+5+5+5+10+10+15+15+25 LT 3 Phase 440 Voltages 50 Hz AC supply system to improve power factor 0.80 to 0.98 automatic step wise switched capacitor panel platform mounted outdoor type, weather proof, dust vermin proof, made out of M.S sheet 3.15 mm thick and MS angle iron 40 mm X 40 mm X 6 mm frame, factory fabricated as modulate in construction duly powder coated light Grey / Cream color paint , front openable panel shutters with locking arrangement to facilitate easy maintenance , exhaust fan cooled , having cable entry gland , provision of angle iron legs / hooks for mounting of panel in platform ( as & where required ) , 40 x 6 mm copper bus bar and necessary internal connections with 10 Sq.mm , 4 Sq.mm & 1.5 Sq.mm insulated stranded copper conductor complete comprising of the followings :
(a) AIPFC micro processor based relay 12 stage -01 No
(b) MCCB 2/0 Amps 4 pole 16 kA –01 No
(c) Capacitor duty Contractors 3 phase 1,2,3,4,5,5,5,10,10,15,15,25KVAR = 12 Nos (e) HRC fuse link 02 A with base 20A =12 Nos.
(d) MCB 3 pole 10 KA up to 32 Amps = 012 Nos.
(f) Indicator Lamp LED type complete = 12 Nos.
(g) Voltmeter 0-500 V,AC of size 96 mm x 96 mm with selector switch = 01 No
(h) Ammeter 0 – 100 A of size 96 mm x 96 mm with selector switch = 01 No
(j) Current Transformer of ratio 160/5 , 15 VA = 04 Nos.
(k) 440 Volt 3 Phase Power Capacitors double dielectric heavy duty suitable for 1,2,3,4,5,5,5,10,10,15,15,25 KVAR-01 No each
1
-
-
... More
Supplying, installing, testing and commissioning of factory made OUTDOOR type LT cubical panel board suitable for operation on 415 Volts, 3 phase, 4 wire, 50Hz supply system including bus bar chamber in center(vertically) and cable relay either side, outer shell shall be made out of 3.15 mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fixed with hinges and locking arrangements etc suitable to accommodate the under mentioned fittings and inner shell shall be made out of 2 mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front open able single door with half nob type locking , including provision for taking out incoming and outgoing cables duly marked with riveted letter plates of appropriate size for each feeder /block cable, danger board, detachable plate at bottom for cable entry including double compression type cable gland for each incoming and outgoing etc. and MC 100 pedestal for grouting in floor with suitable nut, bolts, washers etc. including foundation,all as specified and directed including following. (a) 600 Amps aluminium bus bar for phases and 300 Amps for neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in separate compartment and internally prewired.-01 set. (c) MCCB 3 pole 500 Amps 36KA including shunt trip coil-01 Nos . (d) MCCB 3 pole 160 Amps 25KA including shunt trip coil-04 Nos. (d) MCCB 3 pole 100 Amps 16KA including shunt trip coil-01 Nos. (e) Digital multi function meter ( Volt meter 0-500V,Ammeter 0-500A, frequency meter, power factor meter. (f) Indicating lamp 240 volts LED type - set of three (g) internal All links with copper conductor or solid aluminum bus bar of adequate capacity. (h) CTs 500/ 5 Amps - set of three.
1
-
-
... More
Description as per srll item No-15 but consisting the following -(a) 400 Amps aluminium bus bar for phases and 200 Amps for neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty epoxy insulators in separate compartment and internally prewired.-01 set. (c) MCCB 3 pole 160 Amps 25KA including shunt trip coil-01 Nos . (d) MCCB 3 pole 100 Amps 25KA including shunt trip coil-01 Nos. (d) MCCB 3 pole 40 Amps 10KA-10Nos. (e) Digital multi function meter ( Volt meter 0-500V,Ammeter 0-200A, frequency meter, power factor meter. (g) Internal All links with copper conductor or solid aluminum bus bar of adequate capacity. (f) Indicating lamp 240 volts LED type - set of three. (h) CTs 160 / 5 Amps - set of three.
2
-
-
... More
Material and labour for construction of platform for transformer in PCC in the ratio 1: 2: 4 Type B-1 using 20mm graded crushed stone aggregates of size 3.0 m length x 2.0 m width x 1.20 m height from ground level including rendering 15mm thick with cement mortar 1:4 with fair finishing without using extra cement including two coats of white wash complete all as specified and as directed by Engineer-in-Charge. ( Note:- Drawings of foundation of transformer's plateform shall be approved by GE before execution of work.)
1
-
-
... More
M&L for earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 0 metres length,buried directly and referably vertically in ground (earth pit not less than 3.75 m below normal ground level) with top edge not less than 1.25 metres below ground level the earth electrode surrounded by adequate qty of charcoal dust and salt to a packed thickness 15 cm on all sides, connected to galvanized earth lead 32mm x 6mm thick strip upto 7.50 mtrs with and including nuts bolts, check nuts and washers of galvanised iron or steel /riveted to earth electrode at one end and connecting to test point/equipment atthe other end , GI strip encased in and including 40 mm dia GI light grade pipe with all fittings from top of earth electrode to equipment fixed with and including required number of mild steel clamp made out of 25mm x 3mm , nuts, bolts,washersat and perforated water pipe 20mm dia GI medium grade of length 1.0 metre and connected to earth electrode with 40x20 mm reducer socket including funnel,wire mesh etc. PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 3mm MS angle iron frame, excavation & earth work complete all specified and as shown in electrical plate No. 2 of MES Schedule Part-I of SSR-2009. complete all as specified and directed by Engr-in-charge.
Notes :- (i) GI strip upto earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover (iv) Pipe electrode shall be tappered at the bottom and provide with 12mm holes (staggered) at 75mm centre to centre upto 2 m .