Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 1,26,700Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_636651_1Bid Award Id
ViewTender No
83869/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Tender documents with errata and amendments
BOQ Items
(b)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 10 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(c)
(i) 25 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 50 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 25 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 25 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(d)
(i) 50 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 100 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 50 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 50 kVAR 7% detuned reactor copper wound – 2 Nos
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 180 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 800 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 50 kVAR X 2 Nos + 25 kVAR X 2 Nos + 10 kVAR X 2 Nos + 5 kVAR X 2 Nos (total eight steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
1
-
-
(A) INCOMING:
(i) MCCB rated current(In): 400A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 8 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling.
-
-
-
(B) OUTGOING: (a)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 10 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(c)
(i) 25 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 50 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 25 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 25 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(d)
(i) 50 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 100 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 50 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 50 kVAR 7% detuned reactor copper wound – 2 Nos Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 80 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 320 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 40 kVAR X 1 No + 20 kVAR X 1 No + 10 kVAR X 1 No + 5 kVAR X 1 No + 2.5 kVAR X 2 Nos (total six steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
2
-
-
(A) INCOMING:
(i) MCCB rated current(In): 160A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 6 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling.
-
-
-
(B) OUTGOING: (a)
(i) 2.5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 2.5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 2.5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 5 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(c)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 10 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(d)
(i) 20 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 40 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 20 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 20 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(e)
(i) 40 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 80 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 40 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 40 kVAR 7% detuned reactor copper wound – 1 No
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 20 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 80 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 10 kVAR X 1 No + 5 kVAR X 1 No + 2.5 kVAR X 2 Nos (total four steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
2
-
-
(A) INCOMING:
(i) MCCB rated current(In): 40A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 4 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling
-
-
-
(B) OUTGOING: (a)
(i) 2.5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 2.5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 2.5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 5 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(c)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 10 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 1 No
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Supplying & laying in trenches, in road cutting and along pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
6
-
-
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
150
-
-
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 70 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
150
-
-
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
150
-
-
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
115
-
-
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
70
-
-
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
56
-
-
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling, hand punning down complete all as specified and as directed. Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
32.5
-
-
Supply & laying unreinforced precast concrete cable cover class LV type 2, flat shape, dimension 300 mm X 180 mm X 40 mm as per IS 5820: 1970 complete all as specified and as directed.
1964
-
-
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
40
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 120 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 500 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 40 kVAR X 2 Nos + 20 kVAR X 1 No + 10 kVAR X 1 No + 5 kVAR X 2 No (total six steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
2
-
-
(A) INCOMING:
(i) MCCB rated current(In): 250A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 6 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling
-
-
-
(B) OUTGOING: (a)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 10 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(c)
(i) 20 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 40 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 20 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 20 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(d)
(i) 40 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 80A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 40 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 40 kVAR 7% detuned reactor copper wound – 2 Nos
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 100 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 500 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 50 kVAR X 1 No + 25 kVAR X 1 No + 10 kVAR X 2 Nos + 5 kVAR X 1 No (total five steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
6
-
-
(A) INCOMING:
(i) MCCB rated current(In): 250A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 5 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling
-
-
-
(B) OUTGOING: (a)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 5 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(b)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 10 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(c)
(i) 25 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 50 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 25 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 25 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(d)
(i) 50 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 100 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 50 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 No
(vi) 50 kVAR 7% detuned reactor copper wound – 1 No
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 245 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 1000 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 100 kVAR X 1 No + 50 kVAR X 2 Nos + 25 kVAR X 1 No + 10 kVAR X 1 Nos + 5 kVAR X 2 Nos (total seven steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
1
-
-
(A) INCOMING:
(i) MCCB rated current(In): 500A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 7 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling
-
-
-
(B) OUTGOING: (a)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 10 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(c)
(i) 25 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 50 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 25 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 25 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(d)
(i) 50 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 100 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 50 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 50 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(e)
(i) 100 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 200 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 100 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 100 kVAR 7% detuned reactor copper wound – 1 No
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Designing, manufacturing, supplying, fixing, erecting, testing and commissioning LT APFC panel with capacitor bank, conforming to IS 16636: 2017, 60 kVAR, outdoor installations, rated system voltage of the panel 440 V ± 10%, rated frequency 50 Hz, 3 phase, 4 wire, delta connected, rated impulse withstand voltage 8 kV, free standing, pedestal mounted, made of cold rolled close annealed sheet of minimum 2 mm thick for the load bearing structure and minimum 1.6 mm thick for door and partition, 50⁰C ambient temperature, IP 54 Ingress Protection, 250 Amp rated copper busbar, metallized polypropylene (MPP) dielectric type, resin filled box type, self-healing type, shunt capacitor as per IS 13340: 2012, switching configuration: 30 kVAR X 1 No + 10 kVAR X 2 Nos + 5 kVAR X 1 No + 2.5 kVAR X 2 Nos (total six steps), suitable protection in line with IEC and IS for overheating, over current, earth fault, over voltage, short circuit, thermal overload and over pressure, suitable size power and control cable as per Indian Standards, powder coated in grey colour, including microprocessor based automatic power factor correction controller with human machine interface, cooling fans, capacitor duty contactors, 7% detuned reactors, two earth terminals in the panel and as per the details mentioned below complete all as specified and as directed and shall be including the followings: -
1
-
-
(A) INCOMING:
(i) MCCB rated current(In): 125A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply – 1 No
(ii) Microprocessor based automatic power factor correction controller (minimum 6 steps)- 1 No
(iii) Cooling Fans to be provided for forced cooling
-
-
-
(B) OUTGOING: (a)
(i) 2.5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 2.5 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 2.5 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(b)
(i) 5 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 15A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 5 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 5 kVAR 7% detuned reactor copper wound – 1 No
-
-
-
(c)
(i) 10 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 2 Nos
(ii) MCCB rated current(In): 20 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 2 Nos
(iii) 10 kVAR capacitor duty contactors – 2 Nos
(iv) ON indication lamp – 2 Nos
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 4 Nos
(vi) 10 kVAR 7% detuned reactor copper wound – 2 Nos
-
-
-
(d)
(i) 30 kVAR MPP dielectric type, resin filled box type, self-healing type, shunt capacitor- 1 No
(ii) MCCB rated current(In): 63 A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply – 1 No
(iii) 30 kVAR capacitor duty contactors – 1 No
(iv) ON indication lamp – 1 No
(v) 230 V AC ON, OFF push button with 2NO + 2 NC – 2 Nos
(vi) 30 kVAR 7% detuned reactor copper wound – 1 No
Note: (a) The kVAR rating of capacitor mentioned is for rated voltage of 440 V. However, the capacitor shall be provided for rated voltage of 480 V by enhancing the kVAR rating suitably.
-
-
-
Supplying & laying in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
6
-
-
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
20
-
-