Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 33,600Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_MES_505529_1Bid Award Id
ViewTender No
8598/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
M&L for Point wiring with PVC insulated (FRLS) unsheathed multi stranded copper conductor cable of size 1.5 Sqmm with PVC insulated (FRLS) unsheathed multi stranded copper conductor cable of size 1.5 Sqmm as earth continuity wire to be drawn in and including PVC casing capping not less than 20 mm width with all accessories and fittings, fixed on surface including providing wooden rectangular block for mounting switches, sockets, fan regulators etc with 3 mm thick plastic laminated sheet cover and making good disturbed surfaces, complete all as specified and directed for the following: -
One light/ceiling fan/exhaust fan/bell buzzer point controlled by one, one way switch of 5/6 Amps.
193
-
-
Ditto all as per item No 4.00 (here-in-above) but one 5 Pin, 5/6 amps socket outlet point on independent board, controlled by one, one way 5/6 Amp switch.
62
-
-
Ditto all as per item No 4.00 (here-in-above) but one 5 Pin, 5/6 amps socket outlet point on same board, controlled by one, one way 5/6 Amp switch.
42
-
-
M&L Point wiring with PVC insulated (FRLS) unsheathed multi stranded copper conductor cable of size 2.5 Sqmm, with PVC insulated (FRLS) unsheathed multi stranded copper conductor cable FRLS of size 2.5 Sqmm as earth continuity wire to be drawn in and including PVC casing capping not less than 20 mm width with all accessories and fittings, fixed on surface for one socket outlet 15 amp on independent board including providing wooden rectangular block for mounting switches, sockets, fan regulators etc with 3 mm thick plastic laminated sheet cover and making good disturbed surface, complete all as specified and directed.
48
-
-
S&F switch piano flush type 5/6 Amps, 230 volts, single pole, one way, ISI marked, complete all as specified & directed.
291
-
-
Supply and fixing switch socket combination, 5/6 and 15/16 Amps, 230 volt, multi pin, flush type universal, complete all as specified and directed.
48
-
-
Supply and fixing socket outlet, 5/6 Amps, 230 volt, five pin, flush type universal, complete all as specified and directed.
104
-
-
S&F in renewal of stepped type electronic fan regulator, flush type, 230 volts AC, single pole, humming free, fixed on the existing phenolic laminated sheet, complete all as specified and directed.
19
-
-
S&F ceiling rose surface type PVC/Polycarbonate isolated body, 65x 50mm, 3 terminals, complete all as specified & directed.
143
-
-
S&F PVC/polycarbonate lamp holder, angular/batten type with back plate, ISI marked complete all as specified & directed.
34
-
-
S&F bell push AC, SP, 240 volts, flush type, 5 Amp/ 6 Amp, complete all as specified and directed.
4
-
-
S&F in renewal of call bell, AC, 230 volts, single pole, ISI marked complete all as specified & directed.
4
-
-
S&F in renewal of wall mounted LED Tube light fittings, batten type with bipin holders, powder coated steel with & including retrofit 18 watt LED tube, internally prewired, complete all as specified and directed.
54
-
-
S&F of wall mounted LED Tube light fittings, batten type with bipin holders, powder coated steel with & including retrofit 18 watt LED tube, internally prewired, complete all as specified and directed.
40
-
-
S&F in renewal of wall mounted LED Tube light fittings, batten type with integrated LED tube, powder coated steel with & including retrofit 11 watt LED tube, internally prewired, complete all as specified and directed.
6
-
-
S&F in renewal of LED building security light fitting, 25 watt, pressure die cast aluminium housing with IP 66 deg of protection, complete with & including 0.55 m long street light bracket made of 32 mm bore GI light grade tubing including necessary clamps, nuts, bolts, washers etc, complete all as specified and directed.
6
-
-
S&F in renewal of LED ceiling panel light fitting (2'x2') 36 Watt, 230 Volt AC, recessed mounting mirror optic luminiare with paralite louver complete, suitable for false ceiling/grid of size 605x605 mm, complete with electronic driver, connector block and all accessories, duly prewired, including connecting up with three core twisted flexible copper conductor cable of size 14/.0060, complete all as specified and directed.
4
-
-
S&F in renewal of LED surface mounted down light fittings, 20 Watt, powder coated steel with & including 20 watt LED tube, internally prewired, complete all as specified and directed.
8
-
-
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact
and corrosion resistant including thermal management in multiple optics complete with IP -65/66 protection, complete all as specified and directed.
10
-
-
M & L for street/road light GI mounting bracket made out of steel tube, medium grade, 40 mm dia (or higher size to suit the opening of the fitting) 1.50 mtr long by hydraulic pressed mechine bend to require arc shape and fixed to pole with 02 Nos MS flat iron clamps of suitable size fixed with bolts, nuts and washers including drilling holes and grouting with the same for fixing bolts as required & incl duly painted with two coat of aluminum paint over a coat of aluminum red oxide primer and fixing with lights fittings on the existing old street light poles complete all as specified and directed. Note :- Cost of Necessary tools and plants such as ladders, hydra for renewal of mounting brackets, light fittings, nuts, bolts etc shall be deemed to be included in the unit rate quoted.
10
-
-
S&F MCB, 6 to 32 Amps, Single Pole, 240 Volt, 10 KA 'B' curve including all accessories, complete all as specified and directed.
54
-
-
S&F MCB, 6 to 32 Amps, Single Pole & Neutral, 240 Volt, 10 KA 'B' curve including all accessories, complete all as specified and directed.
17
-
-
S & F, MCB TPN 63 Amps, 415 volts, four pole, B-curve, rupturing capacity 16KA conforming to IS-8828-1996, IEC-60898, complete, all as specified & directed by Engineer-in- charge.
2
-
-
S & F factory made MCB DB made of sheet steel phosphatised, powder painted with bus bar 200 A, neutral link, earth bar and Din rail, 240 Volts SPN with 12 ways, Double door, complete all as specified and directed.
Note for items of MCB DB - (1) The unit rate includes for cutting the brick walls to accommodate DB to make flush to wall.
(2) The unit rate includes for making good the disturbed surfaces including finishes to match with the adjoining surface.
6
-
-
S & F factory made MCB DB made of sheet steel phosphatised, powder painted with bus bar 200 A, neutral link, earth bar and Din rail, 240 Volts SPN with 8 ways, Double door, complete all as specified and directed.
3
-
-
S & F factory made MCB DB made of sheet steel phosphatised, powder painted with bus bar 200 A, neutral link, IP-43-IK09 protection grade, earth bar and Din rail, 415 Volts TPN with 4 ways, Double door, complete all as specified and directed.
2
-
-
S&F of sub main wiring with two runs of single core PVC insulated and unsheathed FRLS multistranded copper conductor cable of size 6 Sqmm LT, 1100 volts grade, drawn through and including 20 mm dia PVC non metallic surface conduit with accessories such as socket, elbow, junction box, bell mouth, reducer, bend and flexible conduit etc. and fittings and one run of 6 sqmm single core multistranded FRLS copper conductor cable green colour as earth continuity conductor, complete all as specified & as directed.
Note :- Two runs of cable one run of earth wire and one run of PVC non metallic conduit of 20mm dia shall be measured as one run length. Cable required for connection to DBs shall deemed to be included and shall not be measured separately. Earth wire shall run inside the PVC conduit.
350
-
-
S&F of exhaust fan of 300 mm sweep made of PVC body operative on 230 volts, AC with louver shutter and including provn of making appropriate hole in brick/stone walls complete including connecting with and including PVC insulated three core 23/.0076 copper conductor cable, rubber insulated from ceiling rose to exhaust fan motor and writing MES No with black synthetic enamel paint 2.0 cm high complete all as specified and directed.
6
-
-
S&F of ceiling fans of 1200 mm sweep five star rating & including all accessories such as down rod, canopy, blade set comprising of three blades, hanging arrangement with rubber block, nuts, bolts, washers, split pins, capacitor etc complete with and including PVC insulated twisted twin core 23/0.0076 copper conductor flexible rubber insulated cable of required length from connector/ceiling rose to fan motor including testing, commissioning and painting with black synthetic enameled paints MES number upto 2.5 cm high, complete all as specified and directed.
19
-
-
M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized iron earth wire of 4 dia by means of bolts, nuts, check nuts and washers of galvanized iron including 15 mm bore light grade GI tubing for protection of earth wire, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 5 and including dismantling of old u/s earthing complete all as specified and directed.
Notes: - (a) Irrespective of whatever is shown in plate No 5 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b) Item includes the cost of GI pipe for protection of earth wire and earth wire upto 7.5 m. Any variation below or above shall be measured and paid for separately under relevant item of this Sch ‘A’.
4
-
-
M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized iron earth wire of 4 dia by means of bolts, nuts, check nuts and washers of galvanized iron including 15 mm bore light grade GI tubing for protection of earth wire, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 5 complete all as specified and directed.
Notes: - (a) Irrespective of whatever is shown in plate No 5 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b) Item includes the cost of GI pipe for protection of earth wire and earth wire upto 7.5 m. Any variation below or above shall be measured and paid for separately under relevant item of this Sch ‘A’.
3
-
-
Supplying, laying, jointing testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade of cross-sectional area 25 Sqmm, 4 core, laid in trenches / ducts / encased in GI pipe / fixed to pole/wall complete all as specified and directed.
240
-
-
Supplying, laying, jointing testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade of cross-sectional area 16 Sqmm, 2 core, laid in trenches / ducts / encased in GI pipe / fixed to pole/wall complete all as specified and directed.
120
-
-
Supplying, laying, jointing, testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade (ISI marked), laid in trenches / ducts / encased in GI pipe / fixed to pole/wall with necessary angle iron support, clamp, nut , bolts etc and including taking down old unserviceable existing XLPE LT UG cables complete all as specified and directed for following cross sectional areas of cables :- Notes for Srl item Nos. 35, 36, 37 & 37.10 to 37.40 :- (i) Excavation, earth work, sand cushioning, cable protection cover & GI pipes shall be measured and paid for separately under respective items of BOQ. (ii) Rate deemed to be inclusive of connecting up with control gear including cable glands and cable lugs.
Cross Sectional area of cable 120 Sqmm, 3.5 core
250
-
-
Cross Sectional area of cable 95 Sqmm, 3.5 core
140
-
-
Cross Sectional area of cable 70 Sqmm, 3.5 core
200
-
-
Cross Sectional area of cable 50 Sqmm, 3.5 core
455
-
-
Cross Sectional area of cable 35 Sqmm, 3.5 core
185
-
-
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m deep for foundation etc or for shafts, column footings or for laying cables etc not exc 10 Sqm on plan and getting out in soft/loose soil, complete all as specified and directed.
310.8
-
-
Returning filling in excavated soil including spreading, levelling, watering and well ramming in layers not exc 25 Cm, complete all as specified and directed.
173.5
-
-
Removing excavated materials (soil) not exc 50 m distance and depositing where directed at a level not exc 1.5 m above the starting point, complete all as specified and directed.
137.3
-
-
M&L dry clean Sand filling in trenches around underground cables for earth cushion, complete all as specified and directed. Note: - Depth of sand shall be measured after punning.
93.8
-
-
Supplying and laying pulverized fuel Ash-lime bricks (Fly ash bricks - non modular size), laid flat adjoining each other as in protection to UG cables, complete all as specified and directed.
11680
-
-
Cutting of road / hardstanding upto a size not exceeding 20 cm in width and not exceeding 60 cm in depth for laying of LT UG cable protection pipe line, making good the disturbed portion so as to match existing finishing or with PCC 1:2:4 type B1 complete all as specified and directed.
25
-
-
M&L in renewal of 80 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
18
-
-
M&L in renewal of 40 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
6
-
-
M&L of 40 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed.
11
-
-
S & F of factory made bus bar boxes outdoor type made of CRCA sheet 3.15mm thick of size 500mmx400mmx250mm having aluminium bus of rating 200 Amps and including MCCB, four pole 63 Amps having rupturing capacity 16 kA complete all as specified and directed.
1
-
-
Supplying, installation, commissioning and testing of outdoor type, weather proof, factory made LT panel (Kiosk) of suitable size made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 600 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including MS channel frame of ISMC 75 at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: -
(A) INCOMING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 315 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three.
(c) Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 01 No.
(d) Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No.
(B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos.
(b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 03 Nos.
(c) MCB 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 16 KA – 02 Nos.
Note :- (i) Necessary approval of drawings of LT feeder pillar box shall be approved by GE before placing order by the Contractor.
(ii) Cost of above aspects is deemed to be included in quoted rates.
1
-
-
Supplying, installation, commissioning and testing of outdoor type, weather proof, factory made LT feeder pillar box (Kiosk) of suitable size made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 600 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including MS channel frame of ISMC 75 at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: -
(A) INCOMING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 160 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three.
(c) Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 01 No.
(d) Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No.
(B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 03 Nos.
(c) MCB 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 16 KA – 02 No.
Note :- (i) Necessary approval of drawings of LT feeder pillar box shall be approved by GE before placing order by the Contractor.
(ii) Cost of above aspects is deemed to be included in quoted rates.
1
-
-
Supplying, installation, commissioning and testing of outdoor type, weather proof, factory made LT panel (Kiosk) of suitable size made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 600 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including MS channel frame of ISMC 75 at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: -
(A) INCOMING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 250 Amp rating with rupturing capacity 36 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three.
(c) Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 01 No.
(d) Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No.
(B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 200 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 100 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(c) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 02 Nos.
(d) MCB 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 16 KA – 03 Nos.
(e) Electronic digital type Volt meter, 0-500 volts with selector switch - 01 No.
Note :- (i) Necessary approval of drawings of LT feeder pillar box shall be approved by GE before placing order by the Contractor.
(ii) Cost of above aspects is deemed to be included in quoted rates.
1
-
-
Supplying, installation, commissioning and testing of outdoor type, weather proof, factory made LT panel (Kiosk) of suitable size made of 3.15 mm thick CRCA sheet duly powder coated, having double door opening (front & rear) with locking arrangement, provision of entry & exit CP brass glands for cables, having bus bar chamber with 4 No heat shrink insulated aluminium bus bar of 600 Ampere capacity and including all connection with aluminium busbar strip, provided with danger notice plate with skull & bone sign, including making all electrical incoming and outgoing electrical cable connection with new lugs, gland to be provided at cable entries and including MS channel frame of ISMC 75 at the base of panel only for grouting purpose & necessary cement concrete 1:2:4 type B1 for grouting of panel stand and connecting the panel with existing earthing and including dismantling of old u/s existing panel comprising of the following: -
(A) INCOMING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 315 Amp rating with rupturing capacity 25 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) Phase indicator LED type indicating lamp (RYB) with copper control wiring - 01 set of three.
(c) Electronic digital type Ampere meter, 0-500 Amp with selector switch, square 96x96 mm - 01 No.
(d) Electronic digital type Volt meter, 0-500 volts, square 96x96 mm with selector switch - 01 No.
(B) OUTGOING: - (a) MCCB, 4 pole, 415 volts, 50 Hz, AC, 250 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 01 No.
(b) MCCB, 4 pole, 415 volts, 50 Hz, AC, 63 Amp rating with rupturing capacity 16 KA microprocessor based adjustable thermal and adjustable magnetic setting– 03 Nos.
(c) MCB 415 volts, AC, three pole & neutral, 32 Amp, breaking capacity 16 KA – 02 Nos.
Note :- (i) Necessary approval of drawings of LT feeder pillar box shall be approved by GE before placing order by the Contractor.
(ii) Cost of above aspects is deemed to be included in quoted rates.
1
-
-
M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 25x4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 32x6 mm size for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: - (a) Irrespective of whatever is shown in plate No 3 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b) Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m.
16
-
-
S & F of factory made bus bar chamber outdoor type made of CRCA sheet 3.15mm thick of size 800mmx400mmx250mm having aluminium bus of rating 400 Amps mounted on porcelain insulators housed in box complete all as specified and directed.
4
-
-
Evaluation Notes How It Works ?