Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date7 Jul 2023
Closing Date3 Aug 2023
Tender Amount₹ 47,50,000
Costs
EMD
₹ 95,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_608317_1Bid Award Id
ViewTender No
GE (A) SOG - Token No 29/23-24Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
S&F pin type insulator of size 100mm height, 65 mm dia porcelain, vitreous white, brown or green insulator suitable for 1100 volts grade including one galvanized mild steel spindle, two GI washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
184
-
-
S&F pre-stressed cement concrete pole, 9 metre long of cross section 102mm x 172mm at top and 102mm x 279mm at bottom, class 10, complying with requirements of IS-1678-1998 erecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and yellow colour up to 1.5 metre height from top of PCC coping of poles including numbering of poles with synthetic enamel paint black in 80mm high letters over 150mm x 230mm yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. Note : PCC for foundation and earth work shall be measured and paid for separately.
48
-
-
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge
2.96
-
-
M&L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation of poles, filling & mass concrete including necessary form work complete all as specified and directed by Engineer-in-charge .
2.63
-
-
M & L for PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing complete all as specified and directed by Engineer-in-charge
23.08
-
-
Suppyling, installing, testing and commissioning of factory made outdoor type bus bar chamber having MCCB 63 Amps, 4 pole, 415 volts, 3 phase, 4 wire, 50 Hz, outer shell shall be made out of 3.15mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 100 Amps aluminium bus bar fixed horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 63 Amps MCCB including provision for taking out incoming and outgoing cable detacheable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer-in-Charge.
Note :- (i) Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account.
(ii) All cables to be connected with busbar will be properly thimbles.
5
-
-
Suppyling, installing, testing as in replacement and commissioning of factory made outdoor type bus bar chamber having MCCB 250 Amps, 4 pole, 415 volts, 3 phase, 4 wire, 50 Hz, outer shell shall be made out of 3.15mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, outer door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 160 Amps aluminium bus bar fixed horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 400 Amps MCCB including provision for taking out incoming and outgoing cable detacheable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer-in-Charge.
Note :- (i) Cost of PCC, excavation and earth work is included in the unit rate of this item nothing extra shall be paid on this account.
(ii) All cables to be connected with busbar will be properly thimbles.
1
-
-
Supply, install, commissioning of 15 metre high 20 sided polygon highmast lighting system fabricated out of BS-EN 10025 or equivalent 355 Mpa material in two sections, hot dip galvanised (single dip) internally & externally having uniform coating thickness of 85/ 65 micron for bottom & top section respectively as per BS 729 and with one longitudinal weld and having no circumferential weld suitable for wind velocity of 180 Km/hr as per IS -875 (Part-3) duly provided with accessories like head frame, steel wire rope 6mm dia (7/19 construction with central core SS) trailing cable double drum winch, galvanised lantern carriage arrangement suitable for 09 luminaires symmetrically and end finial. The mast shall have an integral power tool installed inside the base compartment for its operation as per manufacturers design/ details complete all as specified and directed by Engineer-in-Charge. Highmast light includes the following :-
(i) Supply, and fixing of foundation bolts manufactured from special steel alongwith nuts, washers, anchor plates and templates etc as required as manufacturers recommendations suitable for design life not less than 25 years.
(ii) Erection and commissioning of high mast with the help of suitable equipments and wiring of luminaries with all all copper conductor, cable of suitable size & providing flexible steel conduit pipe of ¾"mm dia for protection of cable.
3
-
-
Contd/-... item No 11
(iii) Drawing, design and casting of suitable shallow foundation with RCC M-25 mix concrete for high mast considering the safe bearing capacity of soil as 10 tonne/ Sqm at 2.00 metre depth duly approved by GE - 01 Job
(iv) Casting of suitable foundation with RCC M-25 mix concrete for panel as per manufacturers recommendations.
(v) Supply and fix integral aviation obstruction light comprising of aluminium housing with polycarbonite enclosures - LED type - 02 Nos
(vi) Supply and installaton of control panel (KIOSK) (out door, double door) with auto control timer switch unit with digitial time switch of capacity 63 Amps tripple pole & neutral (TPN) MCB incomer housing suitable for circuit for operation of mast including suitable control circuit for power tool motor complete as per manufacturer recommendations - 01 Job (vii) All necessary Excxavation and earthwork in any type of soil including returning, filling and removal of surplus soil to distance not exceeding 50 metre completed all as specified and directed by Engineer-in-Charge.
(viii) Contractor shall submit Manufacturer guarantee certificate for a period not less than 05 years.
-
-
-
S&F LED flood light of 170 watt with high pressure die cast housing with lens with lument output 6000K complete (including LED, drive and internally prewired) with on board 5 KV surge protection with 10 KV external SPD. The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP 66 protection as per IS 10322-1982 (part-I) with latest amanedments and input voltage range 140-300V AC, frequency 50-60 Hz, P.F should be more than 0.9. The efficiency of LED luminaries system shall be more than 100 lumens per watt and FRLSH cable PVC insulated stranded copper conductor, 1100 volts grade, 2.5 sqmm x 3 core of ISI marked for light to ceiling rose complete including arrangement of mounting for street light as required at site complete all as specified and directed by Engineer-in-charge.
27
-
-
Supply, fixing and testing LED Street / Security light fitting of 60 Watt, 5700K - 6500 K (including LED drive and internally prewired) complete with body robust, corrosion resistant, superior finish and without any cracks or through holes, made in a single piece by high pressure die cast aluminum alloy. The luminaries shall be monolithic construction totally enclosed dust and water proof with IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distortion THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second including 10 KV surge protection in built or external. Driver should be constant current constant voltage driver. Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection, no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degree Centigrade to 50 degree Centigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection. Cover should not degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including connection for street light from pole box with 1.5 Sqmm, 3 core PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked including addition / alteration in bracket (if required) for fixing light fitting complete all as specified and directed by Engineer-in- charge.
55
-
-
Notes for srl Item No 13 :- (a) Tenderer shall submit test report of LED street light fitting from Government accredited test laboratory for LM - 79 and LM - 80 .
(b) Contractor has to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. Contractor shall obtain warranty from the manufacturer of product on their letter head and submit the same to deparment alonwith his letter head. The product will be replaced free of cost in the following case :- (i) Manfacturing defects
(ii) Failure due to mechanical and electrical impact.
(iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries.
(c) All LED light/luminare must meet the provision laid down in IS - 16101 , 16102 Part -I/II ,16103 Part -I , 16104 ,16105 ,16106 , 16108/2012 and 15885 Part -II / Section 13.
(d) Scope of work shall include supply and fixing street light fittings on street light bracket fixed on poles, If street light fitting requires to fixed on existing street light bracket and any addition alterration required in bracket for fixing street light, In that case cost of additional / alteration is included in the unit rate of this item, which also includes needful T & P and required accessories such as 1.5 sqmm, 3 core PVC insulated stranded copper conductor cable for connection from pole box to light fitting etc complete including making connection, testing etc complete .No extra payment is admissible on this account. (e) Light fittings shall be provided with 10 KV surge protection as mentioned in description of item. If 10 KV surge protection is not provided in light fitting for which cat part is mentioned in BOQ. Contractor has to provide light fitting with 10 KV surge protection without any extra cost to department.
(f) Contractor shall write CA No on street light fitting with synthetic enamel paint which should be visible from ground level. Cost of the same is included in the unit rate of this item nothing shall be extra paid on this account.
-
-
-
S&F street light bracket made out of 32mm dia GI pipe light grade 1.2m long , bent to shape at 120 degree angle from vertical fixed along pole with and including required number of clamp made out of Flat iron 25mm x 6mm with nuts, bolts ,washers etc. duly painted with two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed by Engineer-in-charge.
55
-
-
S&F street light pole box of size not less then 300x200x105mm, made of high quality thermo plastic polystyrene, weather proof, dust, jet water proof, chemical, acid corrosion, impact, insulated & shock proof IP 65 for outdoor Installation with internallly embedded gasket (PUR) including MCB SP 6 Amps 01 No along with left side hinge door (notch arrangement not acceptable) & premoulded knockout all sides including back of the base must. The box fitted with 10 sqmm stud type terminal - 04 Nos including Elimex stud type TB 4 Nos. Note :- (i) Cost of flat iron clamp is deemed to included in unit rate of this items. Nothing extra shall be paid on this account.
(ii) Size of junction box for different mafufacturer may slightly varried from size mentioned in description of item. Contractor has to provide junction box as per cat No mentioned against make of junction box. where cat No is not mentioned against any make, in that case junction box of size mentioned in description has to provide, if exact size of junction box is not available, then next higher size junction box has to be provided. Nothing extra shall be paid on this account.
6
-
-
S&F three phase automatic street light switch suitable for 5 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights with three number two pole power contractors 40 Amps (Type - MU40-2P, Cs90119) with coil voltage 220 / 240 V and incoming MCBs single pole - 03 Nos, outgoing MCBs single pole - 03 Nos of rating 32 Amps & circuit wiring with single core multi stranded of size 10 Sqmm. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is 30 Lux and for switching OFF 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. The sensor along with suitable power contactor (S), Incoming -outgoing MCB's should be enclosed in a Rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure with hinged lid confirming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass option). The enclosure sould be mounted on 40mm x 40mm x 5mm angle iron structure and the structure height minimum 600mm and must be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer in charge.
Make :- KAKATIYA ENERGY SYSTEM PVT LTD (Swadeep 02EC5KW3P) or equivalent cat part No in makes mentioned in Appendix 'A' here-in-after
3
-
-
S&F single phase automatic street light switch suitable for 3 KW load complete with Infrared sensor based NATURE SWITCH for automatic switching of street / security lights with three number two pole power contractors 40 Amps (Type - MU40-2P, Cs90119) with coil voltage 220 / 240 V and incoming MCBs single pole - 03 Nos, outgoing MCBs single pole - 03 Nos of rating 32 Amps & circuit wiring with single core multi stranded of size 10 Sqmm. Lighting switch operation should be based on natural light lux level. Required illuminance level for switching ON is 30 Lux and for switching OFF 10 Lux. The sensor should also have part night operation facility for 4,5,6,........11 & 12 hours. The sensor along with suitable power contactor (S), Incoming -outgoing MCB's should be enclosed in a Rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure with hinged lid confirming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass option). The enclosure sould be mounted on 40mm x 40mm x 5mm angle iron structure and the structure height minimum 600mm and must be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and directed by Engineer in charge.
Make :- KAKATIYA ENERGY SYSTEM PVT LTD (Swadeep 02EC3KW1P) or equivalent cat part No in makes mentioned in Appendix 'A' here-in-after
2
-
-
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 32mm x 6mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat iron and perforated water pipe 20mm dia GI medium grade of length 2.25 metre and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 3mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed by Engineer-in-charge.
Notes :-(i) Cost of GI strip upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item.
(iii) Cost of GI tubing upto 7.5m is included in the quoted rate of this item.
(iv) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber.
(v) Minimum weight of reinforcement for RCC cover shall be 1 KG.
24
-
-
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 25mm x 4mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required Nos of mild steel clamp made out 25mm x 3mm flat iron and perforated water pipe 20mm dia GI medium grade and top with socket & plug and bottom connected to earth plate by slit and two bolts / nuts / washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009 including taking down old unserviceable earthing complete all as specified and directed by Engr-in-charge.
Notes :-(i) Cost of GI strip upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item.
(iii) Cost of GI tubing upto 7.5m is included in the quoted rate of this item.
(iv) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber.
(v) Minimum weight of reinforcement for RCC cover shall be 1 KG.
2
-
-
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 10 sq mm 2 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge.
Notes :- (i) Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ (ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions.
540
-
-
All as per item No 20 above but cable of cross sectional area 25 sq mm 4 core
380
-
-
All as per item No 20 above but cable of cross sectional area 50 sq mm 3.5 core
52
-
-
All as per item No 20 above but cable of cross sectional area 120 sq mm 3.5 core
50
-
-
All as per item No 20 above but cable of cross sectional area 400 sq mm 3.5 core including taking out old cable
700
-
-
Supplying, laying, jointing, comissioning and testing of PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25 sqmm 4 core confirming to IS : 1554 (Part-I 1988) laid in tenches along poles through pipe etc complete all as specified & as directed by Engineer –in-charge.
Notes :- (i) Excavation, earth work, sand cushioning, cable protection and GI pipe shall be measured & paid for separately under respective items of BOQ (ii) Road cutting / floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall deemed to be inclusive of the above provisions.
180
-
-
All as per item No 25 above but cable of cross sectional area 16 sq mm 4 core including taking out old unserviceable cable
850
-
-
Supplying, jointing and testing heat shrinkable type straight through cable jointing kit, suitable for cable of size 25 to 50 Sqmm, 3.5 core aluminium conductor 1100 Volts including making connections complete all as specified and directed by Engineer-in-Charge.
4
-
-
All as per item No 27 above but suitable for cable of size 300 sqmm to 400 sqmm.
4
-
-
S&F stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 16 mm dia x 1800mm long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator with over all dimensions 90x140mm and clearence of hole 25.5mm, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.
Note : Excavation, earthwork and PCC in foundation shall be measured and paid seperately under respective items of BOQ.
21
-
-
S&F cross arms, bracings, stiffeners, supports, clamps and back plates fabricated from structural steel confirming to Fe-290 (Gde E-165) including nuts, bolts, washers, welding, binding cold or hot, drilling holes for bolts, in any shape or size complete all as specified and directed by Engr-in-Charge.
Note :Exposed steel surface shall be treated with two coats of synthetic enamel paint over a coat of red oxide primer and unexposed surface of steel sections shall be applied one coat of red oxide primer.
8.3
-
-
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft / loose soil & getting out complete all as specified and directed by Engineer-in-Charge.
693.8
-
-
All as per serial item No. 31 here-in-above but depth exc 1.5 mtr & not exc 3mtr
3.52
-
-
Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soft/loose soil complete all as specified and directed by Engineer-in-charge.
414.67
-
-
Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and directed by Engineer-in-charge.
263.13
-
-
M&L for dry sand (Tibba sand) and punning for cushioning to underground cable complete all as specified and directed by Engineer-in-charge
Note: - Punning thickness shall be measured for payment purpose.
146.43
-
-
M & L for brick protection with old size sub class 'B' bricks laid flat, length of bricks across the route of underground cable all as specified and directed by Engineer-in-Charge.
5.68
-
-
M & L for brick protection with old size sub class 'B' bricks laid flat, length of bricks across the route of underground cable including taking out old bricks all as specified and directed by Engineer-in-Charge.
9.4
-
-
S&F Galvanized iron tubing, 15mm bore light grade, ISI marked, including all fittings and laid in trenches / under road / drains, fixed to poles / walls with required numbers of clamps made out of 25x3mm flat iron, bolts, nuts and washers for protection of LT electric cable complete all as specified and as directed by Engineer-in-charge.
Notes :- (i) Excavation & earthwork shall be measured & paid for separately under respective items of BOQ
(ii) Cost of flat iron clamp is included in the unit rate of this item. Nothing extra shall be paid on this account.
30
-
-
All as per item No 38 above but 40mm bore tubing
40
-
-
All as per item No 38 above but 40mm bore tubing indluding taking down old unserviceable GI pipe
9
-
-
All as per item No 38 above but 50mm bore tubing
15
-
-
All as per item No 38 above but 80mm bore tubing
24
-
-
All as per item No 38 above but 100mm bore tubing indluding taking down old unserviceable GI pipe
18
-
-
S&F 20mm bore galvanized steel water tubing medium grade with & including all fittings, laid in trenches complete all as specified and directed by Engineer-in-charge.
Note :- Excavation and earthwork shall be measured and paid for separately under respective items of BOQ.
144
-
-
All as per item No 44 above but 25mm bore tubing
270
-
-
All as per item No 44 above but 40mm bore tubing
550
-
-
S&F gun metal globe or gate valve 20mm bore with iron wheel head, screwed both ends for iron pipes complete all as specified and directed by Engineer-in-charge.
1
-
-
S&F gun metal globe or gate valve 25mm bore with iron wheel head, screwed both ends for iron pipes complete all as specified and directed by Engineer-in-charge.
1
-
-
S&F gun metal globe or gate valve 40mm bore with iron wheel head, screwed both ends for iron pipes complete all as specified and directed by Engineer-in-charge.
1
-
-
M&L for Construction of brick masonry of valve pit of internal size 90cm x 90cm x 90cm including necessary excavation and earth work in soft/loose soil, brick work, plastering, white wash, PCC coping, MS frame made out of angle iron of size 40mmx40mmx6 mm, MS sheet cover of 3 mm thick fixed to angle iron frame by means of hinges welded to frame and painting with 2 coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces and grouting the frame in PCC 1:2:4 type B-1 including handle and locking arrangement with one number 50 mm dia brass pad lock, complete all as specified and directed by Engineer - in - Charge Note :- (i) Brick wall shall be 23 cm thick built in cement mortar (1:4) (ii) Internal plaster shall be 15 mm thick in cement mortar (1:4) and external plaster upto 450mm from top shall be 20mm thick in CM (1:6) and remaining external surface shall be flush pointing in CM (1:6) as the work proceeds.
(iii) PCC in foundation shall be 15 cm thick in cement concrete (1:4:8) type D2 using 40 mm graded stone aggregate extended 15 cm all around from the external face of the walls. (iv) PCC coping shall be 15 cm thick in cement concrete ( 1:2:4) type B1 using 20 mm graded stone aggregate including grouting of angle iron frame in PCC. (v) Three coats of white wash to internal surfaces of valve pit.
(vi) Depth of valve pit shall be reckoned from the top of PCC in foundation.
1
-
-
All as per Srl item No 50 above but valve pit of internal size 120cm x 120cm x 120cm
1
-
-
M&L cutting and threading work of existing 80/100mm GI/CI pipe line and making connection of new pipe line of 25mm bore with & including insertion of new GI Tee including excavation & earth work in any type of soil complete all as directed.
1
-
-
M&L cutting and threading work of existing 80/100/150mm GI/DI pipe line and making connection of new pipe line of 40mm bore with & including insertion of new GI Tee including excavation & earth work in any type of soil complete all as directed.
1
-
-
M&L for road cutting for laying of water supply pipe lines upto 40 mm dia including returning filling in and making good surface with sub base, PCC, and premixed carpet etc. complete all as directed by Engineer-in-charge .
24
-
-
S&F air termination, single pointed aluminium rod 12 mm dia single pointed 300 mm long complete all as specified and directed by Engineer -in-Charge.
4
-
-
S&F aluminium strip of size 25x3.00 mm with saddles and fixing screws etc for roof conductors and down conductors above ground complete all as specified and directed by Engineer -in-Charge.
30
-
-
S&F test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed including 3 Nos, 8mm dia, 25 mm long hexagonal screw complete all as specified and directed by Engineer -in-Charge.
2
-
-
S&F cast iron / Pressed steel terminal boxes 100mm x 100mm x 60mm deep for accomodate the test point terminal block with 3mm thick plastic laminated sheet cover complete all as specified and directed by Engineer -in-Charge. ----------------------------------------------------------------------------
Note :- A sum of Rs. 205625/- will be deducted on account of credit for dismantled/ demolished / taken down material. Please refer details on Srl Page No. 23 (Schedule of Credit) of Tender documents.
2
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements