Military Engineer Services Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 20,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_688610_1Tender No
CA NO. AGE(I) KNS/Token No. 16 /2024-2025Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://defproc.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
S&F Step protection MCCB,3 Pole,415 V, 250 A,36 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Step protection MCCB,3 Pole, 415V,125 A, 36 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Step protection MCCB,3 Pole,415V, 63 A,36 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Capacitor duty contactor with damping resistors for 100KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Capacitor duty contactor with damping resistors for 50 KVAr with aux cont complete all as specified and directed by Engineer-in-Charg
1
-
-
... More
S&F Capacitor duty contactor with damping resistors for 25 KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F 25 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
3
-
-
... More
S&F 3 Phase HD Harmonic Detuned filter reactor(copper wound), 50 KVAr,7%,440 V, Class H complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F OT Switch disconnector handle For 63 to 250 A MCCB complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
S&F LED Indicator(Red or Green) complete all as specified and directed by Engineer-in-Charge.
12
-
-
... More
Repair & maintenance of APFC panel of capacity 100 KVAr ,400 A ,415 V compartmentalized, Indoor Floor mounted and replacing the defective parts, neccesary wiring & its insulation and make it complete operational upto full capacity with automation complete all as specified and directed by Engineer-in-Charge. Note:- The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts . The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' as supply only.
2
-
-
... More
S&F APFC microprocessor control relay 12 step ICT For 100 KVAr complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Step protection MCCB,3 Pole,415 V, 400 A, 36 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Step protection MCB,3 Pole,415 V, 63 A, 10 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
3
-
-
... More
S&F Step protection MCB,3 Pole,415 V, 6 to10 A, 10 kA breaking capacity as per existing complete all as specified and directed by Engineer-in-Charge.
6
-
-
... More
S&F Capacitor duty contactor with damping resistors for 20 KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
S&F Capacitor duty contactor with damping resistors for 15 KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Capacitor duty contactor with damping resistors for 10 KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
4
-
-
... More
S&F Capacitor duty contactor with damping resistors for 7.5 KVAr with aux cont complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F 20 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F 15 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
S&F 10 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
6
-
-
... More
S&F 7.5 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F 4 KVAr Heavy duty Capacitor Square type complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S&F Auto Manual disconnector Switch For contactor complete all as specified and directed by Engineer-in-Charge.
10
-
-
... More
S&F LED Indicator(Red and Green) complete all as specified and directed by Engineer-in-Charge.
15
-
-
... More
S&F Ultra heavy duty power Detuned filter reactor enclosed box type 3 phase having the technical specification :- 415V,25 KVAr, 3 x 150 Mfd, 50Hz as per IEC 30931:2002, 13585: 2012 including disconnecting & taking down old unserviceable etc complete all as specified and directed by Engineer-in-Charge.
2
-
-
... More
M &L for Disconnecting the electric connection and draw out Air circuit Breaker (ACB) carefully of any make of capacity upto 3200 Amps for servicing the ACB by removing dust, cleaning and checking the serviceability of the parts and testing, refixing it after servicing at the original position complete all as specified and directed by Engineer-in-Charge.
12
-
-
... More
M& L for Cleaning of APFC panel by removing dust,pigeon poo etc from inner and outer surface by amren paper to make look aesthetic, cleaning and checking the serviceability of the parts and testing, refixing it after servicing at the original position complete all as specified and directed by Engineer-in-Charge.
6
-
-
... More
Supply ,installation, commissioning and testing in replacement of ACB 1250 Amp ( fixed on existing panel) 415 volt, 4 pole with thermal magnetic release(manual Fixed type) complete with spreader terminals complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
Supply installation, commissioning and testing in replacement of ACB 3200 Amp ( fixed on existing panel) 415 volt, 4 pole with microprocesser based with current and time setting complete with spreader terminals complete all as specified and directed by Engineer-in-Charge.
1
-
-
... More
S & F Digital Multi function meter or load manager of size 96 x96 mm AC 3 Phase(inbuilt selector switch),Low starting current 6mA (for LG) 50mA(for MicroG) Auxillary supply 230 V AC, 3 line display having range 5-5000 mA.Accuracy class 0.5S complete complete all as specified and directed by Engineer-in-Charge.
7
-
-
... More
S & F Digital AC voltmeter 96 x96mm AC Range 0-15KV, Accuracy 1.0 PTR 11KV/110V, Auxillary supply 230V AC ,3 line display complete all as specified and directed by Engineer-in-Charge.
12
-
-
... More
S & F Digital Ammeter 96 x96 mm AC 3 Phase(inbuilt selector switch),Auxillary supply 230 V AC, 3 line display having range 5-5000A complete all as specified and directed by Engineer-in-Charge.
12
-
-
... More
Material and labour for repairing of existing LT panel by welding, replacing of 06 Nos of broken hinges as per existing size all as directed .
10
-
-
... More
Supplying ,installing,commisioning and testing for APFC panel 125 KVAr ,3 phase , 4 wire system, Rated voltage 415 (+/- 10) %Volts with Rated frequency 50 (+/- 5)%Hz ,Auto Manual operation , Variable and selectable switching time,Continuous indoor operation in standardized modular epoxy powder coated sheet steel enclosures having panel ventilation, cable bottom entry having Duca power super heavy duty series used rated at ,H-class 5.6% tuning rating as MCCB as incomer and HRC fuse for back up protection with IP protection 40 complete with following specifiction:- (a) Automatic PF controller having intelligent Microprocessor based power factor controller with PF display (b) Microprocessor based overvoltage & overcurrent protection (c) Incomer MCCB 400 A (d) Each capacitor bank/stage shall be controlled by MCCB/MCB and AC3 duty contractor of suitable rating (e) Detuned harmonic suppression filter of copper material rated for 5.67 % of capacitive reactance for individual capacitor control has to be provided (f) Digital multifunction meter for all parameters (g) Automatic PF controller(12 stage)-01 Nos complete as specified and directed.
1
-
-
... More
Supplying and fixing voltage stablizer of capacity 7.5 KVA, 230V, single phase air cooled having voltage control range 90V to 270 V with fully copper windings and auto shutdown facility to save energy complete as specified and directed.
2
-
-
... More
Supplying and fixing voltage stablizer of capacity 5 KVA, 230V, single phase air cooled having voltage control range 90V to 300 V with fully copper windings and auto shutdown facility to save energy complete as specified and directed.
2
-
-
... More
Supplying and fixing Time switches FM1 with 150hrs battery backup, quartz daily basis 110- 240 V AC base/Din mounting complete as specified and directed.
2
-
-
... More
Supplying and fixing Digital Time switches 110-240 V AC base/DIN 50 ON/OFF Each mounting complete as specified and directed.
2
-
-
... More
Supplying and fixing Digital Astro pro switches 110-240 V AC 1 Phase-2W 2C/O, Base/DIN 50 ON/OFF Each mounting complete as specified and directed.
2
-
-
... More
Supplying and fixing Contactors MNX 18 for street light timer complete all as specified and directed.
4
-
-
... More
S & F Rotary switch,Local-Remote,auto manual Switch,On off switch ,90 degree operation,Auxillary supply 230 V AC,complete as specified and directed.
15
-
-
... More
S & F instrumentation Ammeter/ voltmeter selector switch ,90 degree operation,Auxillary supply 230 V AC, complete as specified and directed.
10
-
-
... More
S & F TNC, breaker control switches,25A ,90 degree operation,Auxillary supply 230 V AC, complete as specified and directed.
10
-
-
... More
S & F CT 5A metering -Tape wound haviing CT ratio 300/5 to 100/5 .Burden value 15 to 10, Accuracy class 1.0 with ID min 45 to 30mm and OD max 90 to 80 mm, Auxillary supply 230 V AC, complete as specified and directed.
10
-
-
... More
Supply and fixing wire netting of galvanised steel wire, 1.40mm dia of mesh size 12 mm for protection of transformer/panel inside Sub station from outside reptile,rabbit and pigeon to cover window etc complete as specified and directed.
119
-
-