Northern Railway Tender

If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.

Northern Railway - NR Tender

Goods
Ireps
Opening Date16 Jul 2024
Closing Date6 Aug 2024
Tender Amount₹ 33,25,551.07 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Wiring for 5 pin 5 Amps plug points 5 Amps capacity with 2x1.5 sq.mm FRLS PVC insulated 04 unsheathed multistranded copper conductor s/core cable in recessed PVC conduit pipe 25 mm dia including provision of 3 pin 5 Amps socket outlet with 5 Amps piano type switches and earthing of 3rd pin and MS box with 14 SWG GI wire as required at site.

112

91

10302.88

... More
Wiring for 3 pin 15 Amps plug points 15 Amps capacity with 2x2.5 sq.mm FRLS PVC insulated 05 unsheathed multistranded copper conductor s/core cable in recessed PVC conduit pipe 25 mm dia including provision of 3 pin 15 Amps socket outlet with 15 Amps piano type switches and earthing of 3rd pin and MS box with 14 SWG GI wire as required at site.

55

166

9152

... More
Supply, fixing, testing and commissioning of LED tube light system wattage 18 Watt to 20 Watt complete with all mounting arrangement & accessories & flexible copper wire for connection from ceiling rose as per ISS/IR rules & site requirement as per CEE/NR Specification No.CEE/NR/121-Elect/PS/2018 (Rev '3') Dated 28.06.2018 & CEE/NR/121-Elect/PS/2019 (Rev.4) dated 04.11.2019 or latest,

650

557

362050

... More
Supply of 100x100x60 mm deep M.S switch box conforming to IS 5133 ( Part - I ) - 1969(latest version) with white Phenolic laminated sheet cover of approved make on front of box with brass screws & cup washers, recessing as per Tech. Specification including earthing.

40

49

1988.8

... More
Supply of 180x100x60 mm deep M.S switch box conforming to IS 5133 ( Part - I ) - 1969(latest version) with white Phenolic laminated sheet cover of approved make on front of box with brass screws & cup washers, recessing as per Tech. Specification including earthing.

50

71

3566

... More
Supply of 300x200x100 mm deep M.S switch box conforming to IS 5133 ( Part - I ) - 1969(latest version) with white Phenolic laminated sheet cover of approved make on front of box with brass screws & cup washers, recessing as per Tech. Specification including earthing.

40

178

7133.2

... More
Supply of Piano Type switch 5A (1-way) as per IS 4949 -1968(latest version) /Bell push as per IS 10 4794 ( Part 2 ) -1986(latest version)/flush type socket outlet as per IS 1293 -1988(latest version) & installation on the recessed switch box including cutting of phenolic laminated sheet, connection, testing & commissioning as per Tech. Specifications.

480

16

8020.8

... More
Supply and recessing/fixing of 25mm (Medium) PVC conduit pipe conforming to IS 9537/Pt.III/1983 or Latest Version with accessories,junction box, etc including making chase, plastering/clamping etc as per technical specifications.

5500

34

192005

... More
Supply of becklite Ceiling rose 3 plate & installation on the Junction Box of laid conduit including connections, Testing & commissioning as per Tech. Specification.

40

13

540

... More
Supply, fixing,testing and commissioning of energy efficient 230V, 50Hz a c ceiling fan size of 13 1400mm sweep having wattage of 35/40W, range of voltage operation atvarious speed - 120 to 260V AC, speed of 270 to 290 RPM with 5 step speed control electronic regulator, copper winding complete as per IS :374 - 1979 or laterst,IE rule & site requirement. MakeBajaj, Usha, Havells,Crompton, Orient or equivalent.

65

2318

150675.2

... More
Supply, fixing,testing and commissioning of 380mm sweep, 1400 rpm (approx) propeller type exhaust fan complete as per IS, IE rule & site requirement.Make Usha, Orient,Bajaj or equivalent

20

3129

62581.4

... More
"Design, Manufacture, supply, fixing, testing and commissioning of single sided LED type signages 15 at station name board of suitable size as per CEE/NR Specification No.CEE/NR/121- Elect/PS/2018 (Rev '3') Dated 28.06.2018 & CEE/NR/121-Elect/PS/2019 (Rev.4) dated 04.11.2019 or latest,and as per site requirement. Note:- Static/single sided board of different sizes name is required. prior approval of message color and size to be taken from competent authority."

48

1430

68644.8

... More
Supply & erection of 103 mm Inner dia Double Walled Corrugated pipe in ground under Railway track/road as required and as per explanatory note.

100

341

34105

... More
Transportation, Laying, underground/road/Railway track, recessing in platform /wall along with Rly. 17 Track/in laid RCC/GI pipe as required 1.1 KV grade LT XLPE insulated armoured, aluminium conductor cable including making chase & plastering after laying of cable/digging of cable trench, sand cushioning, protective covering with second class bricks, provision of cable route marker as per Tech. Specification including end terminations with Aluminium Clamping socket/lugs, testing and commissioning of upto 25 sq.mm

3000

57

172710

... More
Transportation, Laying, underground/road/Railway track, recessing in platform /wall along with Rly. 18 Track/in laid RCC/GI pipe as required 1.1 KV grade LT XLPE insulated armoured, aluminium conductor cable including making chase & plastering after laying of cable/digging of cable trench, sand cushioning, protective covering with second class bricks, provision of cable route marker as per Tech. Specification including end terminations with Aluminium Clamping socket/lugs, testing and commissioning of Above 25 sq.mm

2500

55

137725

... More
Supply & erection of 5M pole with single arm bracket hot dip galvanized octagonal pole with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with single pole MCB and terminals as per explanatory note

26

7821

203358.74

... More
"Supply and erection of 45 W LED Street light fitting operating voltage single phase 230 volts AC, 20 50Hz complete with all accessories as per CEE/NR Specification No.CEE/NR/121- Elect/PS/2018 (Rev '3') Dated 28.06.2018 & CEE/NR/121-Elect/PS/2019 (Rev.4) dated 04.11.2019 or latest, including connection with 2x2.5 sq.mm PVC insulated multi stranded FRLS copper conductor cable, testing, commissioning & earthing required as per specification"

125

3195

399391.25

... More
Supply and fixing of bracket on pillar or as required made out of GI pipe 1 M 40mm dia class B GI pipewith ISI marked of approved make & shape suitable bracket shall be fixed with double clamp made of 40x5 mm GI clamp & suiatable GI nut bolt & washer & as per explanatory note

45

456

20553.3

... More
Supply, fixing, testing and commissioning of 1 KVA online UPS with 36 V battery bank, suitable for 22 working on single phase 230 V, 50 Hz, with SMF battery 12 V, 42 Ah , 2 years warranty. UPS make:- Microtek, Hitachi, Luminous & Amron or similar , Battery make:- Exide, Amron, HBL, Luminous & Amar raja Or similar. Each online UPS should be with 12 V/ 42 Ah SMF battery- 03 Nos. online UPS should be with 12Volt/42AH SMF Battery-03 Nos. ( Warranty Period : Upto 24 months from the date of supply)

2

29500

59000

... More
Supply, fixing, testing and commissioning of 2 KVA On line UPS Single phase output voltage 220- 23 230V (+/-1%), Sinewave IGBT-PWM with inbuilt isolation transformer operated on 72V Battery bank as per IS: 16242/IEC 62040 or latest, with provision of 12 Volt 65ah SMF-VRLA Battery (06 nos) battery should be confirming to JISC 8702/1998 with latest amendments. Warranty for UPS and battery: minimum 2 years Make of UPS & Battery: Luminous, Microtek, Sukam or Equivalent.

2

83957

167914

... More
Earthing arrangement by providing earth electrode of GI pipe 50 mm dia (B class) 4.5 meter long 24 with flange including 6 SWG GI earth wire from earth pipe to connecting point on switch board to distribution board/pole etc. as per site requirement including masonry enclosure as per Tech specification at annexure 'A' relevant ISS & IE rules and site requirements. A suitable CI/MS/RCC cover as approved by Rly . Representative, cover with locking arrangement shall be provided.

40

2230

89224

... More
Supply & recessing/fixing on surface 6 SWG GI wire for loop earthing as required as mentioned in explanatory note.

350

8

3076.5

... More
Supply, erection, testing and commissioning of the following Double door wall mounted Pre- fabricated L.T. Distribution Boards of approved make, as per explanatory note & comprising; (i) Incoming MCB 40 A DP 10 KA B/C - 1 No. (ii) Outgoing MCB 6 to 32 A. SP 10 KA B/C - 4 Nos.

22

1527

33610.5

... More
Design, manufacturing of floor mounted MS feeder post made of MS sheet 16 SWG Die pressed of size 550mm x 450mm x 275mm deep complete with Aluminium bus bars four Nos. having cable glands 2 Nos. duly grouted with cement concrete ratio 1:2:4 duly earthed with earthing terminals.

29

3563

103334.83

... More
Supply of super energy efficient ceiling Fan 32/35W,BEE 5 star rated,1200mm sweep,230AC,50HZ,single phase AC supply,Air Delivery 220 Cu.Meter/Minute power consumption 32/35W,speed 28 320RPM with tolerance limit +-10% as per IS standard,PF 0.95,class of insulation B.The ceiling fan shall be surge immunity test passed for 2.5KV,EMI/EMCT test,high voltage protection beyond 275 volt AC and low voltage start ability at 80Volt AC.The overall specification shall be confirming to IS 374-1979 with amend No.1,2,3,4,5,6 or latest.Make-orient model Eco tech with remote,Bajaj or Havells.

100

2286

228604

... More
"Installation, connection with twin core FRLS PVC insulated flexible copper cable 14/0.0076 inch testing and commissioning of 1200/1400 mm sweep A.C. Ceilling Fan with regulator (on installed CI/MS box) with earthing as per tech specification. "

100

66

6650

... More
Supply of Single Phase Propeller Type Ventilating An(Exhaust Fan) Excise Duty --No. Of Poles 4 Sweep Size- 380 Mm(15 Inch) Rpm- 1400, Model No.Hd Ef 380/15 Inch Of Make Action Air Or Similar Of Havells/Cg

10

2685

26850.7

... More
Supply, fixing,testing and commissioning of LED BED LIGHT 1 WATT WITH COOL WHITE INBUILT DRIVER as per CEE/NR Specification. No.CEE/NR/121- Elect/PS/2018 (Rev '3') Dated 28.06.2018

40

1361

54456.4

... More
Wiring for light and fan points with 2x1.5 Sq.mm FRLS PVC insulated unsheathed multistranded 33 copper conductor s/core cable in the existing recessed PVC conduit pipe as above as required with piano type switches, Ceiling Roses/Holders, MS boxes with phenolic sheet laminated cover, J. Boxes, Fan boxes including earthing of MS box & fan boxes with 4 mm dia GI wire including fixing of fan regulators (Short Point)

115

146

16801.5

... More
Wiring for light and fan points / Bell points with 2x1.5 Sq.mm FRLS PVC insulated unsheathed 34 multistranded copper conductor s/core cable in the existing recessed PVC conduit pipe as above as required with piano type switches, Ceiling Roses/Holders, MS boxes with phenolic sheet laminated cover, J. Boxes, Fan boxes including earthing of MS box & fan boxes with 4 mm dia GI wire including fixing of fan regulators (Medium Point)

140

191

26790.4

... More
Wiring for light and fan points with 2x1.5 Sq.mm FRLS PVC insulated unsheathed multistranded 35 copper conductor s/core cable in the existing recessed PVC conduit pipe as above as required with piano type switches, Ceiling Roses/Holders, MS boxes with phenolic sheet laminated cover, J. Boxes, Fan boxes including earthing of MS box & fan boxes with 4 mm dia GI wire including fixing of fan regulators (Long Point)

65

222

14462.5

... More
Supply, fixing, testing and commissioning contained drinking water cooler capacity 150 LTR with Non CFC refrigerant ) energy efficient compressor cooling capacity LTR/HR 150, storage type , confirming to IS- 1475-1 PART 1, of 2001 or latest make blue star, voltas or Similar.

2

36134

72269.74

... More
Supply, fixing, testing and commissioning of 35 Ltrs.water heater geyser BEE 5 star rating 2KW glass coated heating element , CFC free high density PUF insulation , inner tank extreme hard water resistance , 37 suitable for high rise building & pressure pump , suitable for 230V 50Hz AC supply Make: Havells model -Monza EC or equivalent model as Racold model Eterno 2 or make AO Smith model HSE-vas-035L.Note: sample is to be submitted for consignee approval before making supply of material is to be accepted through OEM or OEM authorized dealer only

8

7552

60416

... More
Supply, fixing and commissioning of 1x32 amp DP MCB complete in enclosure with earthing terminals. The MS box should be painted after red oxide primer as per requirement at site.

10

629

6292.6

... More
Supply, erection, testing and commissioning of the following Double door wall mounted Pre- fabricated L.T. Distribution Boards of approved make, as per explanatory note & comprising; (i) Incoming MCCB 4Pole 63 A 35 KA B/C - 1 No. (ii). Outgoing MCB 6 to 32 A. SP 10 KA B/C (4 Nos. On each Phase) - 12 Nos.

3

15023

45069.69

... More
Supply, Erection, Fixing, Testing and commissing of LT panel having incoming 1x250 Amp MCCB 35kA FP with outgoing of 2x125 Amp MCCB 35 kA FP, 1x63 Amp MCCB 35 kA FP and 4x32 Amp 35 KA FP MCCB with Amp meter, volt meter and indicator. Make of MCCB &MCB M/s Legrand, Havells, Schenider

1

169632

169632.64



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.