If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.

Military Engineer Services - MES Tender

Works
Eprocure
Opening Date28 Sep 2024
Closing DateCancelled
Tender Amount₹ 78,00,000 
Notes
Download

Costs

Summary

Spl Repair And Replacement Of Ber Ac Plant And Misc Works

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Condenser Water Pump Set Supply, erection, testing and commissioning of centrifugal mono block condenser water pump set of capacity 7.5 HP capable of delivering minimum 14.3 LPS of water against 24 mtr head each comprising of the following complete all as specified and directed. (a) 1 No.- mono block type pump. (b) 1 No. - Suitable HP TEFC squirrel cage induction motor with class 'F' insulation 2900 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply. (c) 2 Nos. -100 mm dia dial type pressure gauges. (d) Lot- Mounting frame with Anti vibration pads. Lot-PCC cement concrete foundation for the pump unit (1 working simultaneously & 1 standby- Each of 100% cap).

3

-

-

... More
Air Handling Units Supply, Installation, testing and Commissioning of double skin floor mounted air handling units suitable for 25 TR chiller fabricated & assembled complete with minimum 5000 cfm as per load requirement to be worked out by contractor as required basd on the scheme to be approved by GE. Made of 25 mm thick panels consisting of GI casing of thickness 0.6mm outside layer and 0.6mm inside layer, injected at factory by moulding machine acoustic insulation with 12mm fiber glass rigid board with tissue paper and 22 gauge aluminium prefabricated sheet fitted with nut bolt and in the plenium and ducting inside the building shall be insulated with nitrle rubber of 12-15mm thick complete with blower section and filter section with filter of 10 micron at 90% efficiency, chilled water coil constructed out of copper tubes not less than 0.5mm thickness and aluminum fins, Suitable capacity TEFC drive squirrel cage induction motor 415 ± 10% volts, centrifugal forward / backward curved fan suitable for 50 mm SP, access door etc. complete all as specified and directed. Maximum face velocity across the coil shall be 500 FPM and each 6 Row Deep Ch. Water Cooling Coil. RH to be maintained at 50 %±5 of following capacities and comprising of following:-

2

-

-

... More
Ser item No 4.00 (Contd.....) (a) Coil of copper tube and aluminum construction sized at maximum face velocity of 500 FPM. (b) Pre filter of 10 micron at 90% efficiency on the face of the coil in return air stream. (c) Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2007 and high efficiency. (d) Fan belt drive package. (e) Vibration isolators. (f) Fan outlet velocity not exceeding 10 mps. (g) Filter section comprising washable pre filters down to 20 microns 90% efficiency, fine filter down to 5 microns, 99 % efficiently including zero filter 0.3 microns.

-

-

-

... More
Supply, Installation, testing and commissioning of Finned type Strip Heater of 3.0 KW x 09 Nos. for Winter Heating Kit and 3 KW x 09 Nos. for Monsoon reheating complete with all controls and control wiring etc all as specified and directed by Engg-in-charge.

1

-

-

... More
Cooling Tower Supply, Installation, testing and commissioning of FRP cooling tower of minimum 55 TR heat rejection capacity with FRP water basin PVC fillings with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, statically & dynamically balanced axial flow type fan direct driven or driven through reduction gear box with TEFC induction motor , suction screen, make up quick filling arrangement, over flow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling lower interior, installed on MS girders (MS-I sections) fixed in masonry foundations with cement concrete footing, second class brick work in cement mortor 1:6; all accessories, basin fittings, fan, fan motor suitable for 415 Volt supporting structure, anti vibration mountings etc. complete and 50 HZ power supply having isolator panel with MCB at cooling tower and with following technical data and complete all as specified and directed. Note :- Conditions for Water flow/tower, Ent. Water Temp, Basin water Temp as per manufactures recommendation suitable for chiller.

1

-

-

... More
Control Panel for AHU Supply, install, test and commissioning of LT Panel board made out of 3.15 mm CRCA Sheet indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening of 415 Volts 3 phase 4 wire 50 Hz having aluminum bus bar capacity 350 Amps and half neutral with copper bus bar RYB duly insulated complete with digital type Ammeter, volt meter, selector switch including internal wiring with copper conductor including two coats of primer and one coat of spray painting including connecting all incoming and outgoing cable feeders with necessary lugs ferrules etc . The panel should have angle iron support on the base all around including PCC foundation support , well finishing with cement mortar comprising of the following switchgear and accessories are as under:- (a) Incoming : MCCB 200 Amps 4 Pole 25 KA-01 No (b) Outgoing : MCCB 4P 32 Amp - 2 No with DOL starter for AHU motor, over load relay with built in single phasing protection for The compartment shall contain an indicating lamp with MCB for ‘ON’ status of motor. (c) MCCB 4P 63 Amp - 3 No for Pre Heater and Re Heater Bank complete (01 Spare) . The compartment shall contain an indicating lamp with MCB for ‘ON’ status of heater. (d) LED based indicator lamp sets comprising of three colours - 02 sets. (e) Voltmeter 0 - 500 Volts, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch - 01 set. (f) Ammeter 0 - 400 Amps, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch including CTs of required capacity - 01 sets. (g) Single phasing preventer 1 No on incoming supply. (h) Phase sequence correction.

1

-

-

... More
Electrical Cables Supply, laying in replacement and connecting XLPE insulated, armoured heavy duty electric cable of following size cross sectional area 3.5 core with aluminum conductor, 1100V Grade, confirming to IS 7098(Part 1) 1988 (latest revised), in trenches/ducts/poles /pipes/walls etc. complete all as specified and directed for following:

-

-

-

... More
3.5 C x 95 Sqmm (aluminum) for main

70

-

-

... More
3.5 C x 70 Sqmm (aluminum) for main

40

-

-

... More
3.5 C x 50 Sqmm (aluminum) for Chillers .

30

-

-

... More
3.5 C x 35 Sqmm (aluminum) for Main cable to AHU panels.

20

-

-

... More
3.5 C x 25 Sqmm (aluminum) for Pre Heaters.

20

-

-

... More
4 C x 10 Sqmm (aluminum) for Re Heaters.

20

-

-

... More
3 C x 4 Sqmm (aluminum) for Chilled Water , Condenser pumps, CT Fan & AHU Blowers motor.

100

-

-

... More
4C x 1.5 Sqmm (copper) for Controls

100

-

-

... More
M&L in replacement for earthing complete with GI earth plate electrode 60cm x 60cm x 6.3mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with top edge of the plate not less than 1.5 meter below normal ground level, connected to and including galvanized iron strip 25X4mm as earth lead by means of GI bolts, nuts, check nuts and washers, earth pit surrounded by picked layer of coal dust and 15 mm thick mixture in equal ratio of magnesium sulphate & copper sulphate in all around bottom and top and watering pipe 20mm bore of GI medium grade with funnel all as shown in electrical plate NO 5 of SSR Part I (2009) and connecting to earthing test point, including CI cover, frame and PCC (1:3:6), type C-2, using 20mm graded stone aggregate as in earthing pit with CI cover and framing including necessary earth work etc, complete all as specified and directed. Note :- (a) PCC chamber shall be constructed at least one meter away from building and shall be provided in slanting manner. (b) PCC pit cover shall be precast of RCC 1:2:4, type B-1, 80 mm thick, reinforced with XPM weighting not less than 4 Kg (sqm in lieu of CI).

10

-

-

... More
Piping Supply, laying / fixing, testing and commissioning the following nominal sizes of chilled Water plumbing pipes MS ‘C’ CLASS as per IS: 1239, inside the building (with necessary clamps, vibration isolators and fitting like valves, flanges, union etc. but excluding valves, strainers, gauges etc.) cut to required lengths and welded at joints and inclusive of accessories like elbows, tees, reducers, sockets etc. including insulating with 19 mm (for all pipes) and 13mm (for drain pipe) thick closed cell chemically cross linked fire retardant nitrile rubber of 18mm thick duly covered with aluminium cladding. The thermal conductivity of the material should not exceed 0.035 W/Mk at an average temp of 40 deg C, covered with aluminum faced foil complete with application with rubber based adhesive Pidilite SR 998 and 50mm x 3 mm thick self adhesive tape on both longitudinal & transverse joints simultaneously, all as specified and repairing damage to building etc.and conforming to the specified specification for following sizes:

-

-

-

... More
80 mm dia

30

-

-

... More
65 mm dia

20

-

-

... More
50 mm dia

10

-

-

... More
Supply, installation, testing and commissioning of following types of valves, strainers, gauges in chilled water & cond water plumbing and adequately supported complete all as specified and directed. Providing and fixing in position the following butterfly valves :-

-

-

-

... More
80 mm dia Valves

2

-

-

... More
65 mm dia Valves

4

-

-

... More
50 mm dia Valves

4

-

-

... More
Supply and fixing in position the following manual balancing valves complete all as specified and directed :-

-

-

-

... More
80 mm dia Valves

3

-

-

... More
50 mm dia Valves

3

-

-

... More
Supply and fixing in position the following ‘Y’ Strainers complete all as specified and directed :-

-

-

-

... More
80 mm dia

3

-

-

... More
65 mm dia

2

-

-

... More
Supply and fixing in position the following ‘Check Valves complete all as specified and directed :-

-

-

-

... More
80 mm dia Valves.

2

-

-

... More
65 mm dia Valves.

2

-

-

... More
Supply and fixing in position the industrial type pressure gauges size 150mm complete all as specified and directed and recommended by manufacturers design.

20

-

-

... More
Supply and fixing in position the mercury-in- glass industrial type 150mm dia thermometers complete with fittings complete all as specified and directed.

22

-

-

... More
Supply, installation, testing and commissioning of 3 way mixing / diverting valve of size 80 mm dia with proportional cooling only thermostats for the Air Handling Units complete with required controls wiring / installation kit etc. as per drawings complete all as specified and directed.

1

-

-

... More
Supply, fixing, testing and commissioning of condenser water pipes of MS class ‘C’ of following sizes and material along with necessary clamps, vibration isolators and fittings such as bends, tees etc but excluding strainer and gauges etc adequately supported on rigid supports / buried in ground including excavation & return filling etc complete all as specified and directed.

-

-

-

... More
100 mm dia.

40

-

-

... More
65 mm dia.

20

-

-

... More
50 mm dia.

20

-

-

... More
Expansion Tank Supply,installation,testing and commissioning of PVC expansion tank of size 500 Litres complete with suitable with Al. foil faced FR- XLPE / XPE 19 mm thick of minimum bulk density 28±4Kg/cum and applied with Pidilite SR 998 complete with air vent and drain connection with float valve, quick fill and control valves etc. complete all as specified and directed.

1

-

-

... More
Make Up Tank Supply,installation,testing and commissioning of PVC make up tank of size 5000 Litres complete with air vent and drain connection & overflow, make up connection with float valve &PCC foundation with suitable height etc. complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
Air Distribution/ Ducting M&L for ducting SA GI sheet metal ducts made of GI sheet of Class -VIII as per IS -277 having minimum GI sheet of size 120 GSM zinc coating of following thickness for supply air ducting as per IS - 655 complete all as specified and directed.

-

-

-

... More
24 gauge galvanized sheet steel

450

-

-

... More
22 gauge galvanized sheet steel

306

-

-

... More
20 gauge galvanized sheet steel

85

-

-

... More
Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resin sleeve as per the approved shop drawings complete all as specified and directed.

1

-

-

... More
Supply, fabrication, installation and testing the grills / Diffusers for Supply Air made of extruded Aluminum section with powder coated paint and GI VCD as per the approved shop drawings complete all as specified and directed.

8

-

-

... More
Supplying, fixing, testing and commissioning of power coated extruded aluminum section of 120 G thick for fresh air grill in weather maker room with volume control dampers, bird screen etc complete all as specified and directed.

2

-

-

... More
Supply, installation, testing and commissioning of motorized combined fire damper made of 20 G GI sheet complete with control panel, inter connecting wiring at locations shown in approved shop drawings and complete all as specified and directed for following:

-

-

-

... More
Fire Dampers.

2

-

-

... More
Actuators

1

-

-

... More
Control Panel & Wiring

1

-

-

... More
Supply, installation, testing and commissioning of acoustic insulation of SA Duct in AHU Rooms as shown on drawing with 25 mm thick resin bonded fiber glass, of 32 kg/cum density, covered with tissue paper and 26 G Aluminum perforated sheet complete all as specified and directed.

70

-

-

... More
Supply, installation, testing and commissioning of thermal insulation of Duct with 13 mm thick carried out with nitrile rubber foam complete all as specified and directed.

450

-

-

... More
Control Panel for AC Plant Supply , installation, test and commissioning of LT Panel board made out of 3.15 mm CRCA Sheet indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening of 415 Volts 3 phase 4 wire 50 Hz having aluminum bus bar capacity 400 Amps and half neutral with copper bus bar RYB duly insulated complete with digital type Ammeter, volt meter, selector switch including internal wiring with copper conductor including two coats of primer and one coat of spray painting including connecting all incoming and outgoing cable feeders with necessary lugs ferrules etc . The panel should have angle iron support on the base all around including PCC foundation support , well finishing with cement mortar comprising of the following switchgear and accessories are as under:- ( AC Plant room )

1

-

-

... More
Ser item No 28.00 (Contd.....) (a) Incoming : MCCB 250 Amps 4 Pole 50 KA-01 No (b) Outgoing MCCB FP 63 Amp - 4 Nos ( One for each Chiller & 01 No spare) (c) MCCB FP 20 A Amp - 05 Nos( One for each condenser & chiller pump & 01 No spare) (d) MCCB FP 40 Amp - 1 No ( One for cooling tower) (e) MCB 32 Amps TPN 1 No for light DB (f) Aluminum bus bar rating 400 amps (g) LED based indicator lamp sets comprising of three colours - 06 sets. (h) Voltmeter 0 - 450 Volts, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch - 01 set for incoming (j) Ammeter 0 - 400 Amps, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch including CTs of required capacity - 01 sets for incoming (k) Ammeter 0 -100 Amps, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch including CTs of required capacity - 03 sets for chiller . (l) Ammeter 0 -100 Amps, Digital display, flush mounted 96mm square 3 phase 4 wire with selector switch including CTs of required capacity - 05 sets for pumps and cooling tower (m) Single phasing preventer-1 No on incoming supply. (n) Star delta starter on each chiller -03 Nos and DOL starter on each pump -04 Nos shall be provided.

-

-

-

... More
Supply and installation in replacement of phase frequency corrector of capacity 75 HP of 3 phase corrector for 3 phase for central ac plant and other 3 phase items , electrically controlled with interlocking system duly pre wired with multistranded copper wire of durable rating , powder coated metallic housing with hanged door and indicator for each phase. current rate 60A- 100A, Voltage rating 440V all as specified and directed by Engr-in- Charge.

1

-

-

... More
Supply and fixing cable tray of size 200 x 50 mm, 1.2 mm thick perforated type powder coated with coupler plates complete all as specified and directed.

50

-

-

... More
Excavation in trenches in any type soil /rock (soft/loose/hard/dense soil/rock) n.exc 1.5 mtr wide and n.exe 1.5 mtr in depth for foundation, laying of pipe etc n.exc. 10 sqm on plan and n.exe 1.5 mtr in depth and getting out complete all as specified and as directed by Engineer-in-charge. Note : while removing the pipe line ,the contractor shall replaced the broken tiles with new as per existing . The quoted rates shall be deemed to include for all the materials / T&P / machinery used in this item. Nothing extra shall be admissible on this account.

18.9

-

-

... More
Returning, filling in, including spreading, leveling ,watering and well ramming hard / dense soil in layers n.exc. 25 cm each layers complete all as specified and directed by Engineer-in-charge.

9.86

-

-

... More
Removal of excavated material & surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge.

9.04

-

-

... More
M & L for sand cushioning with dry coarse sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.

8.91

-

-

... More
Supplying and laying reinforced precast concrete cable cover Class LV, Type II, flat, size 300mm x 180mm x 40mm complete all as specified and directed.

611

-

-

... More
Notes for AC Plant :- (a) The installation shall be taken over by MES provisionally after the plant has been commissioned and successful completion of Phase-I test as specified and provisional completion certificate shall be issued by GE to contractor. After provisional completion, Phase-II test shall be conducted within 12 months. Final completion certificate shall be issued after successful completion of Phase-II test. No claim on account of prolongation of work due to delay in successful completion of all Phase-II tests by contractor shall be admissible. (b) Contractor shall prepare his own drawings, heat load calculation, equipment layout and piping layout, layout and design of AHUs, ducts with suitable cfm as per area taking into account all requirements, specifications and ground conditions and shall be got vetted from any IIT /NIT and thereafter the same shall be submitted to GE for approval. All these activities shall be completed within 45 Days from the date of commencement of work as per WO No.1. The Contractor shall execute the work based on these drawings duly approved by department (called working drawings). These cost factors shall be deemed included in unit rates quoted and nothing extra shall be paid on this account.

-

-

-

... More
Notes for AC Plant :- (c) The contractor's quoted rate shall be deemed to include the Cost of Manning & Operation (as applicable) of complete AC Plant by employing one number of staff having qualification and experience as specified (AC Plant operator) in one shift of 8 hours per day on all working days after successful completion of Phase - I test until successful completion of last phase-II seasonal test or twelve (12) months from date of issue of provisional completion whichever is later

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.