Military Engineer Services Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Military Engineer Services - MES Tender
Machinery and Tools
Eprocure
Opening Date10 Sep 2024
Closing Date8 Oct 2024
Tender Amount₹ 40,00,000
Costs
EMD
₹ 80,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Repair/replacement/maintenance Of E/m Items And Accessories At Mil Stn Beas Under Ge Kapurthala.
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_673573_1Bid Award Id
ViewTender No
GE KPT- /2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Repair/Replacement/Maintenance of E/M items and accessories at Mil Stn Beas under GE Kapurthala.
Repair/Replacement/Maintenance of E/M items and accessories at Mil Stn Beas under GE Kapurthala.
Repair/Replacement/Maintenance of E/M items and accessories at Mil Stn Beas under GE Kapurthala.
BOQ Items
(c) One socket outlet 3 Pin, 5 Amp on independent board
40
-
-
(d) One socket outlet 3 Pin, 5 Amp on same board.
20
-
-
(e) One bell point controlled by one bell push
4
-
-
(f) One light point controlled by two, two way switch
4
-
-
All as per item No 2 here in before but 2.5 Sqmm P.V.C insulated un sheathed cable with stranded copper conductor for 6 pin 6/16 Amp switch socket combination on independent board complete all as specified and as directed by Engineer-in-Charge.
20
-
-
M & L for point wiring for one light / fan / bell point with 1.5 sqmm cable PVC unsheathed and insulated copper multistranded conductor ( FRLS ) 1100 Volts grade cable ( red colour cable to be used for live connection and black colour cable to be used for neutral connection ) controlled by one way switch drown through and including PVC concealed conduit with all accessories including 1.5 sqmm copper multistrand conductor (FRLS ) 1100 Volts grade unsheathed PVC insulated ( green colour ) continuity earth wire connected to common earth dolly and sunk cast pressed steel terminal box made out of MS sheet 1.25 mm thick for mounting of fittings like switch , socket and fan regulator with 3 mm thick hylum laminated sheet cover complete all as specified and as directed by Engineer-in-Charge :-
(a) One light point controlled by one, one way switch
850
-
-
(b) One fan point controlled by one, one way switch
70
-
-
(c) One socket outlet 3 Pin, 5 Amp on independent board
130
-
-
(d) One socket outlet 3 Pin, 5 Amp on same board.
60
-
-
(e) One bell point controlled by one bell push
5
-
-
(f) One light point controlled by one, two way switch
5
-
-
All as per item No 5 here in before but 2.5 Sqmm P.V.C insulated un sheathed cable with stranded copper conductor for 6 pin 6/16 Amp switch socket combination on independent board complete all as specified and as directed by Engineer-in-Charge.
140
-
-
All as per item No 5 here in before but 4.0 Sqmm P.V.C insulated un sheathed cable with stranded copper conductor for 6 pin 6/16 Amp switch socket combination on independent board complete all as specified and as directed by Engineer-in-Charge.
20
-
-
S&F switch piano flush type single pole one way 6 Amp complete all as specified and as directed by Engineer-in-Charge.
1290
-
-
S&F switch piano flush type single pole one way 15 Amp complete all as specified and as directed by Engineer-in-Charge.
180
-
-
S&F socket out let 2 in 1, 3 pin 5 Amp flush type complete all as specified and as directed by Engineer-in-Charge.
250
-
-
S&F socket out let 2 in 1, 3 pin 15 Amp flush type complete all as specified and as directed by Engineer-in-Charge.
180
-
-
M&L for ceiling rose, surface Bakelite 65 x 17.50 mm of three terminals PVC/Polycarbonate,isolated body complete all as specified and as directed by Engineer-in-Charge.
820
-
-
Taking down old unserviceable regulator & supply & fix electronic type fan regulator stepped type on existing phenolic laminated sheet etc. suitable for ceiling fan complete all as specified and as directed by Engineer-in-Charge.
40
-
-
S & F in repair Bell push flush type 5 Amp complete all as specified and as directed by Engineer-in-Charge.
9
-
-
S & F in repair PVC/Polycarbonate Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings type with back plate suitable for batten fittings complete all as specified and as directed by Engineer-in-Charge.
120
-
-
S & F in repair Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed by Engineer-in-Charge.
10
-
-
S & F in repair Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth complete all as specified and as directed by Engineer-in-Charge.
10
-
-
S&F in repair Modular switch 6 Amp 250 V AC one way one module complete all as specified and as directed by Engineer-in-Charge.
70
-
-
S&F in repair Modular switch 16 Amp 250 V AC one way with indicator one module complete all as specified and as directed by Engineer-in-Charge.
70
-
-
S&F in repair Modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and as directed by Engineer-in-Charge.
70
-
-
S&F in repair Modular Socket 6A/16A - 2/3 pin combined 2 module complete all as specified and as directed by Engineer-in-Charge.
70
-
-
S&F in repair modular Fan regulator step type, 120W - 2 module complete all as specified and as directed by Engineer-in-Charge.
20
-
-
Supply and fix in repair Metal flush mounting box of 1/2 Module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix in repair Metal flush mounting box of 3 Module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix in repair Metal flush mounting box of 4 Module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix in repair Metal flush mounting box of 6 Module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 1 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 2 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 3 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 4 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 6 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Supply and fix Metal in repair White cover plate with frame, 8 module complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Taking doun old unsv sub main and M&L for sub main wiring with two runs of single core PVC insulated, unsheathed copper condutor, multi stranded cable of size 2.50 Sqmm 1100 volts grade drawn PVC concealed conduit of size 19/20 mm (ISI marked) including PVC accessories complete incl cutting and chasing and making good etc including one run of 2.50 Sqmm single core copper conductor multi-stranded PVC insulated, unsheathed cable as earth wire continuity conductor complete all as specified and directed by Engineer-in-Charge. Note : Two run of 2.50 Sqmm cable one run of 2.50 Sqmm cable as earth continuity conductor and one run of PVC Conduit shall be measured & paid as one unit.)
300
-
-
Taking doun old unsv sub main and M&L for sub main wiring with two runs of single core PVC insulated, unsheathed copper condutor, multi stranded cable of size 4.00 Sqmm 1100 volts grade drawn PVC concealed conduit of size 19/20 mm (ISI marked) including PVC accessories complete incl cutting and chasing and making good etc including one run of 4.00 Sqmm single core copper conductor multi-stranded PVC insulated, unsheathed cable as earth wire continuity conductor complete all as specified and directed by Engineer-in-Charge. Note : Two run of 4.00 Sqmm cable one run of 4.00 Sqmm cable as earth continuity conductor and one run of PVC Conduit shall be measured & paid as one unit.)
200
-
-
Taking doun old unsv sub main and M&L for sub main wiring with two runs of single core PVC insulated, unsheathed copper condutor, multi stranded cable of size 6.00 Sqmm 1100 volts grade drawn PVC concealed conduit of size 19/20 mm (ISI marked) including PVC accessories complete incl cutting and chasing and making good etc including one run of 6.00 Sqmm single core copper conductor multi-stranded PVC insulated, unsheathed cable as earth wire continuity conductor complete all as specified and directed by Engineer-in-Charge. Note : Two run of 6.00 Sqmm cable one run of 6.00 Sqmm cable as earth continuity conductor and one run of PVC Conduit shall be measured & paid as one unit.)
160
-
-
Supply and fix LED decorative box batten type light fitting 20 watt Make : Crompton Greaves or equivalent in Bajaj/Philips with LED Tube rod 4 feet 20 watt along with all accessories, pre-wired fixed on wall/ceiling and connecting up complete with 3 core flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-charge.
805
-
-
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. and connecting up complete with 3 core flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-charge.
30
-
-
Supply and fixing round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed by Engineer-in-Charge.
45
-
-
Supply and fixing in repair LED Security light fitting 35 watt Pressure die cast aluminium housing, heat resistant toughened glass with frame IP 66 Protection cat Part No LSTN-30-CDL of Make - crompton Greaves or equivalent in Philips/Bajaj complete fitting including 1.5 mtr long 40/50 mm (Suitable size for fixing of LED light fitting) bore GI pipe mounting bracket/Clamp made to shape for fixing on pole with 40 mm x 6 mm flat iron clamp 02 numbers with 16 mm dia bolts, nuts and washers all as specified and directed by Engineer-in-Charge. Note : Contractor shall provide 2 years written manufactures warranty for the LED fixture complete including driver from the certified date of completion.
5
-
-
Supply and fix in repair LED Bulk head fitting 10 watt highly cost effective compact, ultra low energy, modern design utility bulkhead suitable for indoor and outdoor applications with IP 65 protection complete with all accessories and connecting up complete with 3 core flexible cable white of size 23/0.0076 complete all as specified and as directed by Engineer-in-Charge.
10
-
-
Supply and fixing LED light fitting 2X16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete with all accessories and connecting up complete with 3 core flexible cable white of size 23/0.0076 complete all as specified and as directed by Engineer-in-Charge.
25
-
-
Supply and Fixing of Flameproof cum Waterproof LED Bulk Head light fitting of 15W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size complete with all accessories and connecting up complete with 3 core flexible cable white of size 23/0.0076 all as specified and directed by Engineer-in-Charge.
15
-
-
Taking down carefully ceiling fan/exhaust fan/ wall mounted fan of any size from existing location and carrying out cleaning & servicing including replacement ball bearing and Re-winding painting with synthetic enamel paint by spraying, greasing and heat warnishing and refixing the same in same location/new location and connecting up and including provision of twisted three core PVC insulated flexible cord of 0.75 Sqmm copper conductor of required length from ceiling rose/connector to fan complete all as specified and as directed by Engineer-in-Charge.
160
-
-
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and connecting up and including provision of twisted three core PVC insulated flexible cord of 0.75 Sqmm copper conductor of required length from ceiling rose/connector to fan complete all as specified and as directed by Engineer-in-Charge.
35
-
-
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300 mm and connecting up and including provision of twisted three core PVC insulated flexible cord of 0.75 Sqmm copper conductor of required length from ceiling rose/connector to fan complete all as specified and as directed by Engineer-in-Charge.
30
-
-
Taking down carefully Gysers of capacity 25 Ltr from existing location and carrying out cleaning of inner tank with descaling compound repairing including changing of u/s components(excluding heating element thermostate), including painting with synthetic enamel paint by spraying, and re fixing the same in same location/new location complete all as specified and as directed by Engineer-in-Charge.
40
-
-
Supply only Heating element 2000Watt with traingular/round base mounting suitable for 25 Ltr capacity as specified and directed complete all as specified and as directed by Engineer-in-Charge.
25
-
-
Supply only Thermostarter suitable for Gyser of Capacity 25 Ltr as specified and directed complete all as specified and as directed by Engineer-in-Charge.
25
-
-
Supply only Fan capacitor 2.5 MFD complete all as specified and as directed by Engineer-in-Charge.
120
-
-
Taking down old US MCB DB and S & F in Repair sheet metal enclosure for MCB DB double door single pole & Neutral 4 way with 200 Amps rated bus bar complete all as specified and as directed by Engineer-in-Charge.
6
-
-
Taking down old US MCB DB and S & F in Repair sheet metal enclosure for MCB DB double door single pole & Neutral 8 way with 200 Amps rated bus bar complete all as specified and as directed by Engineer-in-Charge.
12
-
-
Taking down old US MCB DB and S & F in Repair sheet metal enclosure for MCB DB double door Triple pole & Neutral 4 way with 200 Amps rated bus bar complete all as specified and as directed by Engineer-in-Charge.
6
-
-
Material and Labour for Tripple pole and neutral DB's 4 Way suitable for mounting MCBs as outgoing and incoming Isolator 100 Amp TPN complete vertical load line type including all fixing material / accessories for double door DB, complete all as specified and as directed by Engineer-in-Charge.
Note : Incoming Isolator and outgoing MCB SP will be measured and paid separaterly
4
-
-
Taking down old unsv MCB and Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SP 6 To 32 AMP complete with connection testing and commissioning. complete all as specified and as directed by Engineer-in-Charge.
180
-
-
Taking down old unsv MCB and Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SPN 32 AMP complete with connection testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
15
-
-
Taking down old unsv MCB and Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SPN 40 to 100 AMP complete with connection testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
11
-
-
Taking down old unsv MCB and Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of TPN 40 To 100 AMP and current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
6
-
-
Taking down old unsv MCB and Supply and fixing Isolator 4 pole, 415V 10KA 'C' MCCBs 100 Amps, 415V, 16KA, 4 Pole for vertical load line type DB complete with connection testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
4
-
-
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC
insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 4 sq. mm 02 core nominal cross section in service connections complete all as specified and directed by Engr-in-Charge.
90
-
-
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC
insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 6 sq. mm 02 core nominal cross section in service connections complete all as specified and directed by Engr-in-Charge.
182
-
-
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as specified and as directed by Engineer-in-Charge.
4
-
-
Evaluation Notes How It Works ?