Military Engineer Services Tender

... More
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.

Military Engineer Services - MES Tender

Works
Electrical Works
Eprocure
Opening Date30 Apr 2025
Closing Soon24 May 2025
Tender Amount₹ 14,88,300 
Notes
Download

Costs

Summary

Repair Maint Of External Water Supply Electric Supply Distribution System Dg Set Alongwith

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
S&F in replacement of 120 watts LED Flood light for highly efficient LED Flood light with lens made of pressure die cast aluminium housing, extruded aluminium heat sinks & enclosed with toughened glass IP-66 fitted on the wall/ roof top/ pole/ High Mast tower etc. with the help of nuts, bolts, clamps PCC work including connection with 2.5 Sqmm 3 core copper wire from MCB to light fitting with and including PVC pipe and, complete all as specified and directed by Engineer-in-Charge. Note :- All T&P i.e ladder, tools, safety gloves etc will be provided by the contractor without any extra cost.

8

-

-

... More
g) lmpeller Cast iron

1

-

-

... More
Taking up or down U/S choked CI/DI pipe 100 mm dia iincluding relaying after cleaing all fitting including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

20

-

-

... More
Supply & laying, jointing and testing DI pipe "K-7" ISl marked 100 mm dia. Socket and spigot push fit tighten joints in trenches, complete all as specified and directed by Engineer-in-Charge.

11

-

-

... More
M&L for Taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable of size from 10 to 50 Sqmm 2 to 4 core including relaying of bricks, sand and refixing as existing, complete all as specified and directed by Engineer-in-Charge. Note: (i) Straight through joints measured and paid seaprately. (ii) Excavation, Returning, filling, removal will be measured and paid separately.

80

-

-

... More
Taking out old U/S and supply and fix CI body NRV valve conforming to IS of size 80 mm dia complete with nuts, bolts, rubber, gasket etc including, ISI marked, including jointing material such as rubber gasket, bolts, nuts, etc suitable for size, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
Supply and install 160 AH, 12 V Maintanance free battery with copper battery terminals and leads, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of Cable end jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F in replacement of Synthetic Insulating Mat for Electrical Instrument of size 2.5mx1mx12mm, complete all as specified and directed by Engineer-in-Charge.

3

-

-

... More
M&L for in replacement of auto voltage regulator complete with wire connection and connecting to existing field coil 12/24 Volt DC for cap of 7.5 KVA to 40 KVA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L for preparation of old PCC surfaces and applying alternativeiy in yellow and black one coat of synthetic enaml black paint to PCC pole upto 1 mtr height from ground level to LT pole including numbering of pole with black paint, complete all as specified and directed by Engineer-in-Charge.

15

-

-

... More
M&L for dismantling/ disconnecting electric connection of underground HT, XLPE Cable ,11KV upto 95 Sqmm from both sides and locating the fault in HT cable of any size/ type with fault locating machine in the entire length and removing the moisture from HT cable charging the HT cable with the help of modern fault detector equipment by reputed agency and reconnecting and commissioning of cable after testing, complete all as specified and directed by Engineer-in-Charge. Note :(i) The work will be executed after obtaining proper shutdown from main power house after liase with Engr in Charge. (ii) The earth work, cable protection and sand filling including allied works deemed to be included in quoted rate. Note:- Cable length cable 1000 RM

1

-

-

... More
M&L for cross arms, bracings, supports, clamps angle iron, flats and back plates fabricated from MS structural steel sections including nuts, bolts and washers of suitable sizes including welding, bending (cold or hot), drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminum paint over one coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.

0.3

-

-

... More
S&F in replacement of underground cable XLPE insulated screened armoured and PVC bedded HT 11000 volts grade (heavy duty) with aluminium conductor 3 core, 95 Sqmm, laid in ducts/through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

60

-

-

... More
S&F in replacement of Cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 sqmm to 185 sqmm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L for repair and calibration of FIP, fuel injectors including replacement of barel plunger and cup ’O’ rings alongwith Plunger spring,Roller bearing, element, Delivery valve, Fuel injector nozzle element for 7.5 KVA to 40 KVA DG Set and testing of the same after completion, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L for taking down U/S choked GI tubing and connection 40/50 mm size relaying after cleaning of including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

70

-

-

... More
Taking up or down U/S choked GI tubing and connection 25 mm size relaying after cleaing all fitting including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

80

-

-

... More
S&F in replacement of brick masonary valve pit (type B) of size 1.5 m X 1.5 m X 1.5 m (internal of chember) depth to be reckoned from the top of PCC in foundation to top the MS cover as 1.5 mtr and including MS sheet cover fabricated from 3 mm thick MS sheet and frame of angle iron 40 mm x 40 mm 6 mm with fixing arrangement , hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame , inlcuding necessary excavation and earth work in any type of soil , returning , filling in approved soil disposal of surplus soil to a distance not exc. 50 mtr , 150 mm thick PCC (1:4.8) type D-2 using 40 mm graded stone aggregate as in foundation , brick work in cement motor (1:6) 15 mm thick plastering cement mortoar (1:4) (both internally and externally) 100 mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of Cable end jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 sqmm to 185 sqmm, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
All as per item No 44 but DG set 125 to 250 KVA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Taking out submersible pumpset of any capacity and type from the borewell of any depth for carrying cut repairs including cleaning and applying one coat of anti corrosive paint and lowering the same in position and commissioning after carrying out the repairs as required, complete all as specified and directed by Engineer-in-Charge. Note - i) Rewinding of burnt out winding of motor and repairs to pumpset will be measured under relevant items of schedule.

2

-

-

... More
Removing unserviceable PVC water proof cable of any size as obtained trom lowering of submersible pump set and S&F PVC water proof copper cable of size 3 core 2.5 sgmm suitable for submersible pump set, complete all as specified and directed by Engineer-in-Charge.

40

-

-

... More
S&F in replacement of LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade, heavy duty with aluminium conductor 240 Sqmm 3.5 core laid in ducts/ through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

40

-

-

... More
Returning, filling in including spreading, leveling, watering and well ramming in layers each not exceeding 25 cm thickness, complete all as specified and directed by Engineer-in-Charge.

57.7

-

-

... More
Repairing and rewinding of transformer/ Voltage Stablizer from certified company of cap up to 200 KVA incl, complete all as specified and directed by Engineer-in-Charge. following repairs : (i) Removing top cover of the transformer and taking out the complete core assembly from the transformer incl drain out th transformer oil from the transformer and clean the conservator. (ii) Cutting and remove the old burnt HT coil winding from the limbs and rewinding the limbs by new copper wire as suitable size/ as per existing gauge with proper insulation and varnishing complete and heating the coil after winding. (iii) Cutting and remove the olci burnt LT coil winding from the limbs and rewinding the limbs by new copper wire as suitable size/ as per existing gauge with proper insulation and varnishing complete and heating the coil after winding. (iv) Reassembling the complete core assembly and testing.

150

-

-

... More
M&L for cement conceret in foundations, filling and mass conceret with 40mm graded aggregate Type C2 1:3:6, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply & laying, jointing and testing DI pipe "K-7" ISl marked 150 mm dia. Socket and spigot push fit tighten joints in trenches, complete all as specified and directed by Engineer-in-Charge.

11

-

-

... More
Taking down U/S CI/DI pipe 150 mm dia including all fitting and connection Note The cast of including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

12

-

-

... More
M&L for Cl fittings for Spigot & Socketed pipe as bends, tapers, tee pieces any type angle/ radius and straight connection pieces etc, upto 150 mm dia pipe as in repair etc, complete all as specified and directed by Engineer-in-Charge.

20

-

-

... More
Supplying of calcium hypochloride 65-70% chlorine content in granular form to mix with drinking water which is received at Pump house for purifing the water & mainaining its PPM, complete all as specified and directed by Engineer-in-Charge. Make:- Declibac Technologies or Equivalent approved by GE

148

-

-

... More
M&L Danger plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for LT, 20X15 cm size, complete all as specified and directed by Engineer-in-Charge.

4

-

-

... More
Taking out U/S & M&L for run lead joints for 150 mm dia spigot and socketed CI pipe fittings including spun yarn etc, complete all as specified and directed by Engineer-in-Charge.

6

-

-

... More
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or area conduit pipe or fixed to poles or any other indicated situation for loop earthing etc. As required 25X4mm dia galvanised iron strip, complete all as specified and directed by Engineer-in-Charge.

12

-

-

... More
S&F in replacement of Cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 50 sqmm to 95 sqmm, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
Taking up or down U/S choked CI/DI pipe 80 mm dia iincluding relaying after cleaing all fitting including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

25

-

-

... More
M&L for preparation of old steel surfaces and applying alternatively in yellow and black one coat of synethic enamel black paint to steel tabular, pole upto 1 mtr height from ground level and remaining with two coats aluminium paint to LT poles including numbering of pole with black paint, complete all as specified and directed by Engineer-in-Charge.

20

-

-

... More
M&L for opening pump set split case monoblock/ Centrifugal pump type coupled to electric motor of capacity 5 HP, make kirloskar, Compton from motor coupling after isolating the electric and earth lead connections opening the pump set for repair/ overhauling & proper alignment of shaft etc including replacing the items with new items given vide item below, reassemblying the pumpset greasing connecting, testing and commissioning complete including necessary Lathe works, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F in replacement of Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 20 mm bore iron pipe and fixed including testing, complete all as specified and directed by Engineer-in-Charge.

5

-

-

... More
S&F in replacement of brick masonary valve pit (type B) of size 1m X 1m X 1m (internal of chember) depth to be reckoned from the top of PCC in foundation to top the MS cover as 1.5 mtr and including MS sheet cover fabricated from 3 mm thick MS sheet and frame of angle iron 40 mm x 40 mm 6 mm with fixing arrangement , hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame , inlcuding necessary excavation and earth work in any type of soil , returning , filling in approved soil disposal of surplus soil to a distance not exc. 50 mtr , 150 mm thick PCC (1:4.8) type D-2 using 40 mm graded stone aggregate as in foundation , brick work in cement motor (1:6) 15 mm thick plastering cement mortoar (1:4) (both internally and externally) 100 mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L Eart continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduitl pipe or fixed to poles or any other indicated situation for loop earthing etc. As required 4 mm dia galvanised iron or steel wir, complete all as specified and directed by Engineer-in-Charge.

10

-

-

... More
Comprehensive Annual Maintenance of RO Plant Make- ION Exchange Plant scheme-GMA-20-NGMF20-INDRO-401 installed at SMC of unit area including checking, testing, cleaning of Filter, chemical filling, gasket fitting complete membrance of plant by carrying out Inspection visit and service visit quarterly complete along with attending breakdown on phone calls along with maintaining log sheet of plant, complete all as specified and directed by Engineer-in-Charge. Note :- (i) (a) Visits - (Including Service and Inspections) (b) Break Down calls will be attended under AMC Two calls (excluding annual visit 4 Nos) (c) LOGSHEET or analysis purpose shall be maintained. (d) Provision of tools-tackles & labour. (e) Physical inspection for system and related things like Dosing systems, carbon filters and entire Plant (f) Observation of Pressure at Sand Filter Inlet / Outlet and System Pressure. (g) RO Membrane Cleaning. (h) Open backwash for Sand filter and Carbon Filter. (j) Checking Method of operation and necessary advice will be given to operation staff. (k) Training to Staff and Operators. (l) Audit Reports and Suggestions. (m) Pump servicing in ION Exchange scope (Feed Pump & Transfer Pump). (ii) Scope of Supply of material. (i) Membrane Cleaning Chemicals - 6Kgs - (lon Exchange Make). (ii) Antiscalent (8111) - 30 Kgs - (lon Exchange Make) (iii)Cartridges - lon Exchange Make-6 Nos. (iv) Instrument (Conductivity Meter) Calibration. (v) Water Analysis Reports Note: Membrance of size 4" is also included in the scope of work all as specified and as directed by Engr- in charge.

1

-

-

... More
M&L for painting of Centrfugal pumps with motor alongwith 10 mtr pipe suction/ deivery of capacity 5 HP with two coats of synethic enamel Paint, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
Repair/Repalce of DOL starter suitable upto 10 HP submersible pump set of 3 phase including necessary intermal wiring with suitable copper wire including testing and commissioning, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
a) Supply only pump shaft sleeve made out of gun metal

2

-

-

... More
M&L for cable joint for water proof cable of 3 core 2.5 sqmm flat copper cable including testing and commissioning , complete all as specified and directed by Engineer-in-Charge.

4

-

-

... More
f) Supply ball/roller bearing complete

6

-

-

... More
S&F in replecement MCCB 125 Amp 3 Pole of rupturing capacity 16 KA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in deep for foundation of poles/ stays/ pipes/ Cables/ Pipe lines etc and getting out in soft/ loose soil, complete all as specified and directed by Engineer-in-Charge.

32.8

-

-

... More
Supply & laying synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 KV size (2x1 Mtr) for electrical purpose as per IS 15652-2006(superseding IS 5424) suitable for electrical shock safety, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engineer-in-Charge.

33

-

-

... More
Taking out old U/S and supply and fix CI body NRV valve conforming to IS of size 150 mm dia complete with nuts, bolts, rubber, gasket etc including, ISI marked, including jointing material such as rubber gasket, bolts, nuts, etc suitable for size, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
M&L for Prepration of old Steel Surfaces and applying two coat of synthetic enamel white/ silver paint to Steel tubular Pole height of pole 9/11 mtr from ground level alternative in and 1 mtr height from ground level Yellow and black strips of 30 CM height each including numbering of Pole No with black paint, and painting of coping, complete all as specified and directed by Engineer-in-Charge.

68

-

-

... More
Supply & laying 25 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and directed by Engineer-in-Charge.

66

-

-

... More
S&F in replacement of Cable end jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L for filtration/dehydration of transformer oil up to break down valve reaching upto 50 KV dilectric strength, complete all as specified and directed by Engineer-in-Charge. NOTE : Contractor will arrange filtration plant machine at site of transformer. Dehydration work will be carried out in working condition and electric supply will be taken from same transformer.

600

-

-

... More
M&L for Rewinding of cap upto 25 HP Submercible pump motor 41 5 Volt 3 phase after disconnecting electric cable and eath lead, suction and delivery pipes. The borewell depth 150 mtr from ground level of borewell using lifting crane or tripod or any other method lift the submercible pump with motor directed by Engineer-in-Charge shifting to work shop, dismantling the motor assemble and removing the burnt out copper winding of stator and Rotar cleaning the stator slots and core assembly, rewinding stator and Rotar with suitable gauge super enamelled copper wire with insulating papers and insulation cloths, varnishing the winding and baking heating for acheiving the required insulation resistance, re-assembling the motor and testing complete, incl transporting back to site and fixing motor to it orignal place. Reconnecting electric cable and earth leads etc testing and commisioning complete in all respect all as directed by Engr-in-charge for the following capacity, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F in replecement MCCB 200 Amp 4 Pole of rupturing capacity 36 KA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade, heavy duty with aluminium conductor 16 Sqmm 4 core laid in ducts/ through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

150

-

-

... More
Taking out old U/S and supply and fix CI body sluice valve PN 1.6 conforming to IS of size 100 mm dia complete with nuts, bolts, rubber, gasket etc including, ISI marked, including jointing material such as rubber gasket, bolts, nuts, etc suitable for 100 mm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Taking up or down U/S choked GI tubing and connection 20 mm size relaying after cleaing all fitting including all excavation earth work, complete all as specified and directed by Engineer-in-Charge.

60

-

-

... More
M&L for flushing of the existing borewells of size 150 mm dia upto 250 feet depth by drilling machine by mechanical method or PVC pipe method into the above well connected to a pneumatic compressor after taking out the submersible pumpset with necessary hoisting equipment and flushing the bore well complete with compressor air and fushing bore well till discharge of fresh water is obtained subject to entire satisfaction of Engr-in-charge and lowering down the submersible pump set in its position, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of Switch air break gang operated tripple pole mechanically operated from ground level mounted on 12 insulators, outdoor type suitable for vertical installation single break provided with locking arrangement for operating handle including seven levers "Navtal" lock consisting of mild steel channel, HT post top insulator copper alloy high pressure asembly with drop out expulsion fuses for phases, operating rod of 25mm dia medium grade G.I pipe complete confirming to IS-1018 of 1972 with continous current rating 200Amps, 11000 volts grade, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply & laying 50 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and directed by Engineer-in-Charge.

36

-

-

... More
S&F Battery lead copper wire with thimble and terminal heavy duty made out of brass & 100 cm length of lead, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F in replecement MCCB 63 Amp 4 Pole of rupturing capacity 16 KA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
M&L for Rewinding of pump motor 41 5 Volt 3 phase after disconnecting electric cable and eath lead, suction and delivery pipes, from 09 mtr depth of sewage well or pump house or any location directed by Engineer-in-Charge. shifting to work shop, dismantling the motor assemble and removing the burnt out copper winding of stator and Rotar cleaning the stator slots and core assembly, rewinding stator and Rotar with suitable gauge super enamelled copper wire with insulating papers and insulation cloths, varnishing the winding and baking heating for acheiving the required insulation resistance, re-assembling the motor and testing complete, incl transporting back to site and fixing motor to it orignal place. Reconnecting electric cable and earth leads etc testing and commisioning complete in all respect all as directed by Engr-in-charge for the following capacity, complete all as specified and directed by Engineer-in-Charge. Note:- Proper gate passes will be produced by Engineer-in-Charge at the time of payment of RAR.

-

-

-

... More
S&F in replacement of LT cable straight through joint kit size 6 sqmm to 25 Sqmm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply & Fill in replacement of new transformer oil up to minimum level, break down value of transformer oil should not be less than 50 KV, complete all as specified and directed by Engineer-in-Charge.

150

-

-

... More
S&F in replacement of LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade, heavy duty with aluminium conductor 25 Sqmm 4 core laid in ducts/ through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

100

-

-

... More
S&F in replacement of LT cable straight through kit size 150 sqmm to 300 Sqmm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Taking down electric motor cap upto 15HP 415 volt couped to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop , checking the serviceability of ball bearing both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
M&L for 1.2 m x 2.5 m flex board and drawing of substation schematic diagram/ Station Water Suppy/Electric Supply Layout using landard drafting tool Auto CAD. One set of drawing shall be submitted to the Deptt for scrutiny of drawing and final prints of drawing shall be submitted there after making all weather redium reflector board pedestal type or wall mounted or roof mounted as per site requirement, complete all as specified and directed by Engineer-in-Charge. i. Preparation of drawing of Substation schematic/ Water supply/ Electric Supply diagram using standard drafting tools Auto CAD. ii. Duly printed radium Flex board with MS frame of size 1.2 m x 2.5 m and other fixing accessories. iii. Submission of soft copy for correction and approval from Engr in Charge. iv. Submission of three hard copies of drawing prepared on A3 size paper

2

-

-

... More
S&F in replacement of Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 25 mm bore iron pipe and fixed including testing, complete all as specified and directed by Engineer-in-Charge.

5

-

-

... More
Suppling & laying old size sub class 'B’ bricks laid flat in trenches over the cable with length of bricks perpendicular to the direction of cable, adjacent/ abutting each other, complete all as specified and directed by Engineer-in-Charge.

2922

-

-

... More
S&F in replacement of Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics including connection with 2.5 Sqmm 3 core copper wire from MCB to light fitting with and including PVC pipe complete with IP 65/ 66 protection, complete all as specified and directed by Engineer-in-Charge.

80

-

-

... More
Returning and filling in including spreading, leveling, watering and well ramming in layers each not exceeding 25 cm thickness, complete all as specified and directed by Engineer-in-Charge.

29.5

-

-

... More
Repair Replacement of single phase preventor cum tow tevet water guard Suitable for 4 to 7.5HP submersible pump set, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
d) Supply only water seal

5

-

-

... More
S&F in replacement of LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade, heavy duty with aluminium conductor 95 Sqmm 3.5 core laid in ducts/ through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

40

-

-

... More
M&L Danger plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT, 25X20 cm size, complete all as specified and directed by Engineer-in-Charge.

4

-

-

... More
M&L for earthing in replacement with Galvanised Steel earth plate electrode 60cm X 60cm X 6 mm thick buried directly ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised iron strip 25X4 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of glavanised iron and thimbles and protected by light grade 40 mm dia Gl pipe connected up to main LT Panel / Test point and Gl pipe medium grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40 mm graded stone aggregate, including demolition of old earthing, excavation and earth work in any type of soil , returning filling in approved soil and disposal ot surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2020(Part-I), complete all as specified and directed by Engineer-in-Charge.

3

-

-

... More
M&L for servicing of DG set 7.5 KVA to 40 KVA by draining out engine oil, removing oil filter, replace with new one and refill the engine oil, Clean P-uel Feed Pump, replace primary and secondary fuel filter along with '0‘-Ring, replace paper type air filter and safety cartrige, Replace air cleaner oil bathe type, Check Alignment of exhaust system, Check belt tension and tighten or loosen belt tension as per requirement, Blow compressed air with the help of blower on radiator fins to clean it, Check all the clips and tighten if required, Clean Battery terminals with cotton clothe Apply acid proof grease or petroleum jelly on battery terminals, Check electrolyte level of bakery and top up distilled water if electrolyte level is low, Check electrical connection of starter and tighten if required check belt tension on charging alternator and adjust if required. Check output voltage of charging alternator. Tighten all the foundation nuts and bolts if required, check LLOP and HWT with multimeter, Check stopper and adjust tightness of link wire if required check tightness of wiring connection and adjust accordingly, Remove RWL clean it check with multimeter and refit it, Clean body of generator from inside and outside properly, complete all as specified and directed by Engineer-in-Charge.

3

-

-

... More
Note for Item No. 41.00 1) Quoted rate include cost of oil filters, fuel filters and air filters. 2) Ouoted rate inclue labour and transport charges. 3) Cleaning Clothes required is deemed to be included in quoted rates. 4) Engine oil, distilled water, LLOP and HWT shall be measured seperately.

-

-

-

... More
(ii) 5 HP

2

-

-

... More
Supply & laying 40 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and directed by Engineer-in-Charge.

20

-

-

... More
e) Supply only pump Shaft

1

-

-

... More
b) Supply only key for main shaft

4

-

-

... More
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or area conduit pipe or fixed to poles or any other indicated situation for loop earthing etc. As required 25X3mm dia Aluminium strip, complete all as specified and directed by Engineer-in-Charge.

12

-

-

... More
S&F in replacement of LT cable XLPE insulated, armoured and PVC bedded 1100 volts grade, heavy duty with aluminium conductor 70 Sqmm 3.5 core laid in ducts/ through pipes, in floor, on poles, in trenches, complete all as specified and directed by Engineer-in-Charge.

40

-

-

... More
c) Supply only check nut

5

-

-

... More
S&F coupling complete (engine-alternator) in all respect with rubber flange as per existing shape/ size, With nut & bolts of suitable for 125 KVA to 250 KVA DG Sets, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of battery charger for DG set Upto 140 KVA Capacity or or equivalent 230 VAC , 6 A, having display Suppply, Battery ful, Charging and operating switch ON/OFF and all accessories to required to fix in DG Set , complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply & laying 20 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and directed by Engineer-in-Charge.

66

-

-

... More
All as per item No 41 but of DG set 140 KVA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 40 mm bore iron pipe and fixed including testing, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply only spare parts for replacing item as follows:-

-

-

-

... More
S&F in replacement of LT cable straight through kit size 50 sqmm to 120 Sqmm, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in deep for foundation of poles/ stays/ cables/ Pipe lines etc and getting out in soft/ loose soil, complete all as specified and directed by Engineer-in-Charge.

90.7

-

-

... More
M&L Relaying/ Rerouting including taking down unservicable HT XLPE cable from trench of any size and any type after fault detection including neccessary connection, complete all as specified and directed by Engineer-in-Charge. Note :- Excavation work measured and paid seperately.

53

-

-

... More
Supply, fabricate and fixing MS framed equal angle grills,gratings, framed guard bars,ladder, framework of Valve pit cover. water tanks. shallow wells etc, or similar work as ordered and fabricated from MS rolled section of any size and shape as directed and fixed at position with all fixing accessories, complete all as specified and directed by Engineer-in-Charge.

30

-

-

... More
M&L for Taking down unserviceable LT UG cable any type from trenches and removing the fault and relaying of LT UG cable after rectifying the fault and making cable in serviceable condition of 1100 V grade UG cable cf size from 95 to 240 sqmm, 3.5 core including relaying of bricks, sand and refixing as existing, complete all as specified and directed by Engineer-in-Charge. Note : (i) Straight through joints measured and paid seaprately. (ii) Excavation, Returning, filling, removal will be measured and paid separately.

40

-

-

... More
M&L for Replacement of U/S ball / roller bearing of above motor bearing of existing make with providing of high grade grease, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F in replacement Time switches with battery backup 3P module, 24 hours programm, programable every 30 min, backup of 100 hrs current capacity 16 Amps, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engineer-in-Charge.

3.28

-

-

... More
Taking out old U/S and supply and fix CI body sluice valve PN 1.6 conforming to IS of size 150 mm dia complete with nuts, bolts, rubber, gasket etc including, ISI marked, including jointing material such as rubber gasket, bolts, nuts, etc suitable for 150 mm, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
M& L for cleaning of RCC Under ground tank reservoir up to 40000 gallon capacity by drain out the contaminated muddy water from bottom surfaces of the tank by using of pump and motor and cleaning the inside and bottom surfaces of walls with help of wire brush and using specified dosage of Potassium permanganate and cleaned water than drain out completely material tc the entire satisfaction of Engr-in-Charge with and including writting letters 5 CM height capacity of Tank and date of Cleaning of tank, with synthectic enamel paint on the other surface of the tank, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
(i) 7.5 HP

2

-

-

... More
M&L for sand cushioning with a layer of sand 8 cm thick before laying of cables and 15 cm thick after laying of cable in trenches, complete all as specified and directed by Engineer-in-Charge.

27.2

-

-

... More
S&F in replecement MCCB 350 Amp 4 Pole of rupturing capacity 36 KA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replecement MCCB 100 Amp 3 Pole of rupturing capacity 16 KA, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply & laying 80 mm bores of tubes 'medium grade' galvanised with all fittings and fixed complete laid in trenches, complete all as specified and directed by Engineer-in-Charge.

18

-

-

... More
M&L for cleaning of overhead water reservoir 50000 gallon capacity on 25 meter staging by cleaning entire internal surface by removing dirt sludge etc with wire brush by applying bleaching power and freash water and clean entire surface respectively with fresh water and draining out soiled water including Lime washing inside the tank the capacity of sump and date of cleaning with white paint over black painted surface, complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F post top lantern 20 watts 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed by Engineer-in-Charge.

18

-

-

... More
S&F in replacement of Self starter 12 volts DC for Kirloskar, Cummins & Ashoka Layland engine, complete all as specified and directed by Engineer-in-Charge.

1

-

-

... More
S&F in replacement of Gun metal globe or gate valve (ISI marked), with iron wheel head, screwed both ends, suitable for 50 mm bore iron pipe and fixed including testing, complete all as specified and directed by Engineer-in-Charge.

4

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.