Military Engineer Services Tender
... More
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
₹ 1,06,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Summary
Cwe/pat/t-67/2021-22repair Maintenance Of Ht Lines Ht Swithgear And Allied Works In Old Cantt At Patiala Mil Stn Under Ge North Patiala
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_MES_487012_1Bid Award Id
ViewTender No
CWE/PAT/67/2021-22Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed.
422.85
-
-
... More
Removing surplus soil to a distance not exc. 50 M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed.
177
-
-
... More
Supply and spreading fine sand in trenches for cushioning of under ground cable/filling of cable ducts all as directed by Engr-in-Charge at site. Note:- Only punned thickness 18 cm shall be measured for payment purpose
117
-
-
... More
M & L for Un-reinforced precast concrete cable cover class HV, type 1, flat, size 300 mm X 180mm x 40mm complete all as specified and directed.
5720
-
-
... More
Material and labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate for coping around the pole strut above ground level, foundation of stay etc. including neccassory form work and finishing the surface fair and even without using extra cement all as directed and specified
5
-
-
... More
M&L providing precast cement concrete (1:2:4) type B1 20 mm graded aggregate set in cement mortar 1:4 cover slab (for cable duct) with plain faces
4
-
-
... More
Taking down unserviceable HT cable and Supply, laying, jointing and testing HT XLPE cable, cross section area 185 Sqmm, 3 core, 11000 V, screened, PVC 'E' grade insulated bedded, galvanised steel (heavy duty ) strip or wire armoured with aluminium conductor, pressure earthed system, conforming to IS 7098 (Part-1 ) 1977 and Part-II of 1985, laid in pipes / ducts / trenches, under floor and roads or fixed to wall etc including taking out old unserviceable cable, any type, complete all as specified and directed.
800
-
-
... More
All as per item No. 10.00 above but of size 120 sqmm X 3 core
300
-
-
... More
All as per item No. 10.00 above but of size 95 sqmm X 3 core
200
-
-
... More
Dismantling of HT 11 KV cable of any size and relaying of serviceable cable after rectification of fault HT Joint and cable shall be replaced as per site requirements (excavation and work shall be measured and paid seprately).
1250
-
-
... More
Dismantling/taking out old ACSR conductor wire in any size from poles of HT / LT over head lines conductor and Re- stretching of ACSR Conductor of any size on HT/LT over head line 11000 volts grade incl earth continuity wire incl bindng properly, replacement of jumper with existing / suitable size of ACSR conductor complete all as specified and directed.
2
-
-
... More
Material and labour for ACSR conductor Weasel to dog (6/1/2.59 to 6/1/4.72) any size to be drawn straight horizontal on over head lines on existing poles including stringing, stretching, binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etc complete all as specified and directed.
2
-
-
... More
M & L for MS tube light grade galvanised of size 80mm dia with all fittings and laid in trenches / under roads/ under floors/ fixing on poles and walls with clamps complete all as specified and directed.
30
-
-
... More
All as per item No 16.00 above but of size 100 mm dia.
40
-
-
... More
S&F for Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core x XLPE armoured aluminium conductor cable of size 70 to 95 sqmm complete all as specified and directed.
4
-
-
... More
All as per item No 18.00 above but of size 120 to 185 Sqmm.
3
-
-
... More
All as per item No 18.00 above but of size 240 to 300 sqmm.
3
-
-
... More
M &L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core x XLPE armoured aluminium conductor cable of size 70 to 95 sqmm complete all as specified and directed.
3
-
-
... More
All as per Srl item No 21.00 above but of size 120 to 185 sqmm.
3
-
-
... More
All as per Srl item No 21.00 above but of size 240 to 300 sqmm.
2
-
-
... More
M &L for Cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core x XLPE armoured aluminium conductor cable of size 70 to 95 sqmm complete all as specified and directed.
3
-
-
... More
All as per Srl item No 24.00 above but of size 120 to 185 sqmm.
6
-
-
... More
All as per Srl item No 24.00 above but of size 240 to 300 sqmm.
3
-
-
... More
M & L for Earthing complete with galvanized earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground to the depth of not less than 2.25 mtr below ground level with top edge of earth plate or a depth not less than 1.50 m below ground level connected to GI wire 4mm dia by means of galvanized bolts, nuts check nuts and washers and necessary excavation and earth work PCC 1:2:4 type B-1 using 20mm graded brick aggregate for earth pit RCC cover , charcoal & common salt filled in alternate layers funnel with 20mm bore light grade watering pipe, 15mm dia GI pipe light grade for projection of earth lead, wire mesh and connected to earth point including testing on all as specified and shown in electric plate No 3 of SSR part I.
5
-
-
... More
M & L for Earthing complete with galvanized earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground to the depth of not less than 2.25 mtr below ground level with top edge of earth plate or a depth not less than 1.50 m below ground level connected to GI strip 32 x 6mm as earth lead by means of galvanized bolts, nuts check nuts and washers and necessary excavation and earth work PCC 1:2:4 type B-1 using 20mm graded brick aggregate for earth pit RCC cover , charcoal & common salt filled in alternate layers funnel with 20mm bore light grade watering pipe, 40mm dia GI pipe light grade for protection of GI strip, wire mesh and connected to earth point including testing on all as specified and shown in electric plate No 3 of SSR part I.
5
-
-
... More
S& F in repair Switch air break, gang operated triple pole vertical type mechanically operated, mounted on 15 insulator and steel frame, with operating mechanism worked from ground level for current rating 200 Amps 11000 Volt grade complete all as specified and directed.
5
-
-
... More
All as per Srl item No 29.00 above but current rating 400 Amps.
3
-
-
... More
M & L for Cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections incl nuts, bolts, washers, welding, bending cold or hot,, drilling holes for bolts in any shape or size as indicated or directed and inclusive or one primer coat, one under coat and one finishing coat of super enamel paint complete all as specified and directed.
1
-
-
... More
M&L for Painting to bottom of existing PCC poles 11 mtr long pole upto 2.5 mtr from ground level to be painted with 30 cm height each in black and Red colour alternatively ,total of 5 Nos connecting from the Top PCC coping and making pole No with paint as per approved pattern complete all as specified and directed (Note:-The numbering shall be hand written only stencils shall not be allowed ,size of letter shall be 50 mm high and 10 mm wide.)
80
-
-
... More
M & L for Painting of cross arm and MS channel , nut bolts, clamps etc on HT two Pole Structure of 11 Mtr Long after preparing/Scrapping the metal surface with emery sheet in all respect for making smooth surface and painted with one coat of primer and two coats of aiuminium paint
10
-
-
... More
M &L for Painting of cross arm and MS channel , nut bolts, clamps etc on HT four Pole Structure of 11 Mtr Long after preparing/Scrapping the metal surface with emery sheet in all respect for making smooth surface and painted with one coat of primer and two coats of aiuminium paint. Note for item No28 & 29 ;- Bottom of the pole up to 2.5 meter from ground level to be painted with two coats synthetic enamel paint ( every 50cm block ,yellow & black ) & writing the pole & feeder no. and marking with black paint in coming and outgoing cable all as specified .
10
-
-
... More
M&L for Servicing and painting of 11 KV GOD by cleaning the contact ,Pin insilator with CTC and applying the Patrollium Jelley at the contact point /down rod links for smooth operation including replacing the rusted /corroded bolts and nuts(using GI Nuts& Bolts)and deffective insulator of GOD as required at site. Painting shall be done by after preparing/scrapping the metal surface with emery sheet in all respect and painted with one coat of primer and two coat of synthetic enamel paint including cross arm/MS channel and male female contact in red/yellow/blue colour Note:-Insulator shall be measured and paid under relevant items
10
-
-
... More
Suppy Male/Moving contact
6
-
-
... More
Supply Female/Fixed Contact
6
-
-
... More
Supply Copper Tinned Strip
6
-
-
... More
M & L in replacement silica gel breathers assembly transparent PVC body with top and bottom posn pressed with metallic cover filled with silica gel blue in colour and suitable for fixing on existing size 15/20/25 mm dia as per site requirement for transformers of capacity up to315 KVA complete all as specified.
6
-
-
... More
M & L in replacement silica gel breathers assembly transparent PVC body with top and bottom posn pressed with metallic cover filled with silica gel blue in colour and suitable for fixing on existing size 15/20/25 mm dia as per situ requirement for transformers of capacity 400 KVA to 715 KVA.
4
-
-
... More
Supply and fix smooth natural stone river pebbles of size 40 to 50 mm oval/round in shape as per directed by Engr-in-charge.
40
-
-
... More
M & L including removing green vegetation, roots, bushes, etc from surrounding of Transformers/Poles/ substations etc. All as directed by Engineer-in- charge.
2000
-
-
... More
Supply and fix Lightening arrestor Non Linear metal oxide type conform to IS 3070 (part I) complete with all fittings transmission classes suitable for 11 KV out door type complete all as specified and directed including taking down the existing LA. All as specified and directed.
14
-
-
... More
Disconnecting and taking down of transformer indoor/outdoor type 11000/415 volts having capacity 50 to 100 KVA, transportation to contractor’s workshop for repairs, strip opening of transformer after unscrewing nuts /bolts screws and connected accessories such as breather, conservator tank, temp gauge, taking out the core for replacement of defective parts and transportation back to the site after repairs and installing, connecting up, testing and commissioning at the site complete all as specified and directed. Notes : -
(a) Transformer oil shall be drained out by the contractor in suitable capacity MS drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule.
(b) Rewinding of both HT & LT coils shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item.
4
-
-
... More
All as per Srl item No 44.00 here-in-before above, but capacity 160 KVA to 200 KVA.
4
-
-
... More
All as per Srl item No 44.00 here-in-before above, but capacity 250 KVA to 500 KVA.
4
-
-
... More
Supply and replacement of HT coils made out of super enameled HT copper winding wire of transformers having capacity 50 to 500 KVA all as specified and directed
680
-
-
... More
All as per item No 47 here-in-before but with aluminium winding wire.
400
-
-
... More
Supply and replacement of LT coils made out of super enameled LT copper strip of transformers having capacity 50 to 500 KVA all as specified and directed
Note :- Coil to be replaced shall have same number of turns, gauge insulation value matching with manufacturer’s design.
400
-
-
... More
Supply, install, testing and commissioning HT 11 KV , 3 Phase 50 Cycles, totally enclosed , metal clad with drawable type vacuum circuit breaker AIS panel stand alone type used as bus coupler having rupturing capacity 350 MVA as per ISO 9001and IS 14001 certification and as per IEC 62271-100-200 with short circuit rating 18.4 KA for 3 Sec having one No 630A horizontal isolation, horizontal draw out type vacuum circuit breaker with copper bus bar of suitable rating , floor mounting , trolley mounted complete with following:-
(a) Manually & motor operated ( 230V, AC, 50 Hz ) spring charged trip free type incorporating mechanical as well electrical ON/OFF indication “OFF” push button test/ service position limit switches with 5 +5NC breaker auxiliary contacts in service position.
(b) Epoxy cast wound current transformer (CT) dual range 11 KV of ratio 200-100/5A with digital metering and protection core including necessary control wiring:- (i) 15 VA burden for protection ( class 5P 10) (ii) 15 VA burden for metering (accuracy class 10)
(c) Protection arrangement for the breaker shall comprise of the following :- (i) Numerical IDMT relay with shunt trip on 24 V DC, consisting 2 element over current relay with setting from 50 to 200% (step of 25%) and one element earth fault relay with setting form 20 to 80% ( step of 10%) (ii) Trip circuit supervision relay (iii) Anti pumping relay RE -300 (iv) Test terminal block fuses, circuit label, phase indication lamp etc as per standard
2
-
-
... More
(d) The following meters are to be provided (i) Digital voltmeter range 0-12KV with built in selector switch and suitable for 110V AC 96x96 Sqmm dial surrounded terminal. (ii) Digital Ammeter range 0-1200A with built in selector switch dual graduated scale 96x96 Sqmm dial surrounded terminal (iii) Suitable for 24V , DC supply, healthy indication lamp and switch. (iv) Control : T-N-C (trip neutral and close) breaker control switch with indicating arrangement. (v) Danger plate (as per manufacturer instructions) (vi) set of circuit breaker ON/OFF/Auto trip/Spring charger /Trip circuit healthy indicating lamp LED (vii) Anti condensation space heater / thermostat.
(e) All wiring necessary for the above incl interconnection. The size of the conductor shall not be less than 1.5Sqmm copper wire where required. (f) Necessary MS cable box for cable termination at input and output.
(g) Per pack with charging system
-
-
-
... More
All as per item No 49 here-in-before but with aluminium winding wire or strip.
320
-
-
... More
Strip opening of transformer of capacity 50 to 160 KVA, 11 KV /433 volts indoor /outdoor type of any make after unscrewing nuts & bolts, screws and connected accessories such as breather, conservator tank, temp gauge etc. for replacement of defective parts such as replacement of leaking gaskets, replacement of worn out/burnt out studs, checking and cleaning of contacts of tap changer and re-assembling the transformer after replacing the defective parts/repair complete all as directed. Notes : (i) Payment of defective parts to be replaced shall be measured and paid for separately under respective item of this schedule.
(ii) The cost for replacement of packing material such as top gasket, shall deem to be included in the unit rate quoted by the contractor against this item
(iii) The repair/strip opening of transformers shall be carried out at site of its installation without taking down/removal of transformer from the site of installation..
5
-
-
... More
All as per item 50 here-in-before but of transformer above 200 KVA to 750 KVA.
4
-
-
... More
Supply only LT porcelain bushing and heat resistance gasket with brass/copper studs washer and rubber bush etc for Transformer of Cap up to 250 KVA.
3
-
-
... More
Supply only LT porcelain bushing and heat resistance gasket with brass/copper studs washer and rubber bush etc for Transformer of Cap 300 KVA to 750KVA.
6
-
-
... More
Supply only HT 11 KV porcelain bushing with brass/copper studs and gaskets and rubber bush etc for Transformer of Cap upto 750 KVA
6
-
-
... More
Supply and Replace Gun metal gate valve ISI marked with Iron wheel head, screwed both ends for iron pipe or for socket or union for 25 mm bore pipe including taking down existing gate valve in existing transformers of any capacity complete all as specified . Note:Draining out and refilling of transformer oil shall be deemed included in quoted rate.
4
-
-
... More
Supply and Replace Explosion vent diaphram suitable size as per sample
4
-
-
... More
M&L for Taking down defective/unserviceable distrubution transformers from pole mounted/rested on plateform under GE (N) Patiala after disconnecting Elect connection and shifting to E/M store yard and collect the serviceable transformer from E/M store yard and further transportation to the site for installing including electric connections, testing and restore elect supply complete. For distrubution transformer of capacity from 63 to 250 KVA capacity, within distance of 10 to 15 Km within from the AGE E&M New Cantt/old Cantt and back to directed location/place. (Complete manpower and necessary transport /T & P shall be contractors own arrangement at no extra cost) Repair shall not part of Job.
6
-
-
... More
.- Ditto- all as per item no. 59 above but of size for distribution transformer of 300 to 500 KVA capacity.
4
-
-
... More
M&L for painting the transformers complete by two coat of approved colour synthetic enamel spray painting after preperation of the surfaces and one coat of red oxide paint and writing SM/MES No,capacity of transformer and date of oil testing etc Transformer of capacity 25 KVA to 160 KVA all as directed
3
-
-
... More
M&L for painting the transformers complete by two coat of approved colour synthetic enamel spray painting after preperation of the surfaces and one coat of red oxide paint and writing SM/MES No,capacity of transformer and date of oil testing etc Transformer of capacity 200 KVA to 315 KVA all as directed
10
-
-
... More
M&L for painting the transformers complete by two coat of approved colour synthetic enamel spray painting after preperation of the surfaces and one coat of red oxide paint and writing SM/MES No,capacity of transformer and date of oil testing etc Transformer of capacity 400 KVA to 750 KVA all as directed
8
-
-
... More
M&L for pin point fault locating through vehicle mounted fault locating machine for the HT cable 11 KV of 95 to 300 sqmm 3 core all as specified and directed
6
-
-
... More
M&L for GI strip 32 x 6 mm as earth continuity lead beyond test point fixed to wall on batten or recess or chases or buried in ground or drawn in conduit pipe complete all as specified and directed.
25
-
-
... More
M&L for fixing the name boardfabricated with PVC Sheet 2mm thick of size 1.5x3 feet and fixed suitable GI Clamp on 2/4 pole structure including writing the detail of Sub Stn and feeder etc with blue background & white colour Letter as directed by Engr -in Charge.
20
-
-
... More
Boring of holes under road, pavement, hard standing manually suitable to pass through 80 to 100 mm bore GI tubing and cable etc complete all as specified and directed.
40
-
-
... More
Opening of VCB/Ring main unit) 11 KV of Capacity 630/ 800 Amps for servicing, cleaning, tightening of loose mechanical mechanism, greasing,inspection of Busbar,CTs/PTs internal wiring of control panel ,indicators,measuring of IR value ,callibration of relays matching with 66 KV Grid replacement of unserviceable spare parts testing of tripping system and removing all type of dust and settled dirt by means of required T&P all as specified and directed by Engr-in-charge (spares shall be measured & paid separately) and testing complete all as specified and driected. List of spares as under :-
5
-
-
... More
Supply Ashida numerical OC/EF protection relay ADR241Sin nrepair complete all as specified
2
-
-
... More
Supply ON/OFF button
4
-
-
... More
Supply 2 PA' Mechanism for breaker in repair complete all as specified
Make: ABB
2
-
-
... More
Supply 3PKE' Mechanism in repair complete all as specified
Make: ABB
2
-
-
... More
Supply Linking between K&A mechenism in repair complete all as specified
2
-
-
... More
M&L for Periodical cutting of trees /trimming of branches along the HT overhead lines in a girth of 03 mtrs on either side of the conductors including removing the same and dumping complete all as directed by Engr-in-Charge. Note : Expenditure for necessary tool and plants required for Periodical cutting of trees / trimming of branches along the HT / LT overhead lines are deemed to be included in rate quoted by the contractor.
900
-
-
... More
M & L for Dehydration of Transformer oil through on load mobile stream line transformer oil filteration plant at various site at various capacity installed at Floor /Pole and plinth mounted with all accessories connected to Transformer to carrying out filteration of oil for desired di electric strength ie not less than 60 KA at 2.5 mm Gap all as specified and directed by Engr-in-charge
8000
-
-
... More
Supply and filling up of fresh transformer oil as in topping up/levelling up after dehydration having dielectric strength not less than 60 KV at 2.5 mm gap conforming to IS -335/1993 all as specified and directed:
2000
-
-
... More
Material & labour danger notice plate of 1.6 mm thick, mild steel sheet, 25 x 20 cm for HT poles, vitreous enamelled white with letters, figures and conventional skull and bones, in signal red colour, fixed with MS clamps, bolts and nuts of suitable size as approved complete all as directed at site.
30
-
-
... More
Testing of 11 KV assets by a competent authority ie – Power Grid Corporation of India / CPRI lab (testing to be carried only through Govt / semi – Govt body ). The equipments to be tested are as under – HT VCB/RMU 11 KV , three phase 50 Hz, 1250 amps,40 KA For 1 Second 04 Nos & HT VCB 11KV , three phase 50 Hz, 630amps,40 KA For 1 Second 09 NOs - Total =10 Nos . Following tests to be carried out on each breaker –
(i). IR Value for OPEN - incoming -earth , incoming – out going -earth , for close – incoming- earth (ii)Tripping and closing time observed
(iii) Operation – both manual and through motor
(iv)Functioning of indications
(v)Continuity (vi)Polarity test (vii)Testing of all the protection relays – ie o/c , earth fault , instantaneous , trip suspension , auxiliary relay etc
(viii)Greasing /oiling of all the moving parts (ix)Operation / working of charging motor and limit switch
Note – (i) Any part /spare found defective during testing shall be repaired / replaced for which payment shall be made separately (ii)Test sheet shall be prepared as per PS and shall be kept on record in sub division.