Military Engineer Services Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
0Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_684299_1Tender No
3007/JOB/SOIL/01/E3Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://defproc.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Note:Under this test following results also be provided: (a) Grain size analysis, identification & classification of soil.
(b) Unit weight (bulk density), natural moisture content, liquid limit, plastic limit. Shrinkage limit, plasticity index, specific gravity.
(c) Dry density, degree of saturation of soil.
(d) Free swelling index & swelling pressure if expansive soil is encountered.
(e) Shear parameters (C- analysis).
(f) Consolidation test & permeability test.
(g) Depth of water table below ground level.
(h) Presence of loose soil. If any and its depth.
(j) If weak soil with lesser N value as specification in table-1 of IS 1893 (Part-) 2016 is encountered then evaluation of liquefaction potential shall be assessed and remedial action to be adopted shall be specified.
(k) SPT test shall be done at 1.0m interval.
(l) Recommendation for filling under floor and filling under protection including plinth protection.
(m) For open foundation, calculation of net SBC at 1.5m, 2m, 3.0m from shear as well as settlement criteria. SBC values shall be calculated based on C- analysis as well as SPT value. For calculation formula given in IS 6403 shall be used.
(n) Recommendation regarding type of foundation to be adopted & net SBC/Pile capacity to be adopted. Also, recommendation shall be given regarding stability of soil and soil stabilization required, if any.
(o) Borehole position duly marked on plan and their distance from adjacent prominent reference points. Plan size of bldgs shall also be marked in the plan. This plan shall be signed by GE, AGE & Soil consultant.
(p) Bore log details shall be as per Appx 'D' of IS 1892 N values depth wise shall also be shown in bore log details. Bore log details shall be signed by GE, AGE & soil consultant.
(q) Colour photograph on A4 size photo paper of the site with the locations of the boreholes duly flagged should be submitted. The photographs should also preferably include any reference structure and the identification of the same be marked.
(r)Undisturbed soil sample shall be collected at 1.5m interval and at change of strata.
-
-
-
Bore hole dia shall be 150mm, Depth of bore shall be decided as per the soil condition and may be taken 25m or N value reaches 50, whichever is earlier for OHR.
1
-
-
Crushing strength, degree of weathering (CR value) and RQD of rock samples
1
-
-
Chemical analysis of soil and recommendation and type of cement to be used for RCC foundation
10
-
-
Chemical analysis of ground water (water to obtained from bottom of bore hole)
5
-
-
K-value of soil 0.5m depth required in case of swimming pool/UG water retaining structure.
2
-
-
Plate load test for ascertaining SBC at the proposed level of foundation specified for OHT only.
1
-
-
Modulus of subgrade reaction.
1
-
-
As per IS-1892 clause 3.6.5.3, drilling for 3.0m depth inside the rock is essential to ensure that boulders or layers of cemented soil are not mistaken for rock.
1
-
-
Note :- A CD containing video evidence of the depth of each borehole and machinery deployed at site location will be provided which is inclusive in above quoated rate
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%