Military Engineer Services Tender

If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date26 Jun 2024
Closing Date3 Sep 2024
Tender Amount₹ 41,50,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply and fixing pre-painted galvalume aluminium zinc coating GI bared corrugated steel roof sheet 0.50 mm thick of an column having tensile strength of 550mpa fixed with self-drilling screws complete all as specified and directed

177

-

-

... More
Material and labour for preparation of steel surfaces exceeding 10 cm with or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed

89.5

-

-

... More
Surface excavation n.exc 30cm deep and averaging 15cm deep in soft/loose soil all as specified and directed.

135

-

-

... More
Materials and labour for broken bricks hard core of gauge n.exc 63mm deposited spread and leveled in layers n.exc 15cm thick watered and rammed to a true surface complete all as specified and directed

13.5

-

-

... More
Material and labour for 100mm thick cement concrete 1:4:8 type D-2 (using 20mm grade stone aggregate) as in sub base of flooring all as specified and directed

135

-

-

... More
Material and labour for 25mm sand cushion, filling under floors or in foundations including watering and consolidation all as specified and directed

3.38

-

-

... More
Material and labour for 60mm thick machine pressed precast concrete interlocking paver block and shape and size conforming to IS -15658-2006 of M-35 Grade with grey cement and pigment complete all as specified and directed.

135

-

-

... More
Material and labour for PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in sides of rounded or chamfered on edges of interlocking tiles complete all as specified and directed.

1.5

-

-

... More
Supply, erection, testing and commissioning of 16m high mast light system for 8 luminaires (raising & lowering type with motor and manual) having following specifications & accessories. (a) High Mast : The high mast light system of 16m high mast, (made up of 2 sections) entirely high mast structure (internally and externally) and all MS part shall be hot dip galvanized. The high mast shall be of continuously tapered polygonal cross section of 20 sides made up of two sections having sheet thickness 4mm min for lower section and 3 mm min for upper section. The mast shaft shall be manufactured from high tensile steel plate conforming to S355 grade as per BS-EN 10 025 having longitudinal welded seam only and without any circumferential weld joint. The minimum dimension across flats of top shall be 150mm and bottom (base) 360 mm or as recommended by OEM. The base plate shall have thickness 25mm and diameter 560mm min. It shall have door at suitable height of size 1200x250mm min or as recommended by OEM having vandal resistance, weather proof type with pad locking facility. The base flange shall be provided with supplementary gussets between the bolt holes. The door opening shall be carefully designed and reinforced with welded steel section, so that the mast section at the base shall be unaffected and undue buckling of the cut portion is prevented.

2

-

-

... More
(b) Luminaires Carriage: Hot dip galvanized luminaire carriage of suitable diameter designed to install symmetrically 8 Nos luminaries fabricated from ERW tubes in two halves having bolted flanged joints at side with stainless steel bolts and nuts to permit removal from an erected mast. Holes are to be provided in the bottom side of the tubes to act as conduit for wiring cables. Luminaires fixing arms and plates are to be welded to the carriage. Carriage shall have fitted with buffer arrangements to prevent damage to the mast finish during movement. Suitable junction box (as applicable) shall be cast aluminium weather proof provided on the carriage assembly for terminating the trailing cable and power cable to luminaries. (c) Winch/ Power tool: The double drum winch shall be completely self-sustaining without the need for brake shoe, springs or clutches and self-lubricating type by means of an oil bath. The worm gear ratio shall be of suitable ratio and having safe working load 750 Kg min. The drums are to be grooved to provide the perfect seat for the stable and tidy rope lay arrangement for distortion free rope and termination. The winch shall have provision to operate electrically through power tool or manually in case of power failure. Three phase single speed, 6 pole high power motor of 1 HP rating min or as recommended by OEM suitable to lift the load mounted on plate to adjust the length of motor of chain shall be provided in base compartment.

-

-

-

... More
Mechanical torque limiter mounted on motor shaft for start/ stop transmission of motion shall be provided. The power tool shall be supplied with required wiring & accessories suitable to match with High mast control panel. (d) Hot dip galvanized head frame as a capping unit of the mast of the welded steel construction and provided with guides and separators between the rope and cable complete with aluminium pulleys with bush bearing mounted through stainless steel shaft suitable to accommodate wire rope and multi core trailing cables. The head frame to be provided with guides and stops with PVC buffer for the locking of the luminaire carriage. The pulley shall be covered with a hot dip galvanized canopy. The suspension wires shall be made of stainless steel wires rope of AISI 316 grade, 7/19 construction with central core in the same material of 6mm dia. The breaking load capacity of wire rope should be 2350 Kg x 2 minimum. The end termination luminaire carriage shall be with stainless steel thimble etc. (e) The multi core flexible power trailing cable from base compartment to junction box at luminaries carriage shall be EPR insulated PCP sheathed 1100 volts grade copper conductor with male female connectors of 4.0 Sqmm having suitable cores for 9 Nos luminaires or above as required at site for control of these lights as directed by Engineer-in-Charge. The system shall have in-built facilities for testing the luminaries while carriage in lowered position.

-

-

-

... More
(f) One number heavy duty hot dip galvanized lightning finial shall be provided for the mast. The lightning finial shall be minimum 1.2 M in length or as required so that the lantern carriage also comes within the safety zone and shall be provided at the centre of the head frame. It shall be bolted solidly to the head frame to get a direct conducting path to the earth through the mast. The lightning finial shall not be provided on the lantern carriage under any circumstances in view of safety of the system. A suitable space shall be provided at base of the mast to connect with earthing. The mast shall have single/double dome LED aviation light at the top of suitable capacity. (g) Mast shall be erected with foundation bolt set comprises of anchor plate with 8 Nos high tensile studs/bolts with nuts. The foundation bolt shall be TS600, 24mm diameter, 750 mm long or as recommended by OEM. (h) Construction of shallow foundation with suitable grade concrete or as recommended by OEM for the high mast considering the safe soil bearing capacity at site as 10 T/ sqm at 2 metre depth with all materials and labour complete as per OEM drawing after approval of Engineer-in-Charge. The rate also include the cost of PVC/GI pipe 3 inch dia required to be fixed in foundation concrete for the passage of cable.

-

-

-

... More
Notes : (i) The quoted rate include the cost any type of special T&P, tools, equipments required at site for erection, installation of the complete high mast light system. The quoted rate include the cost of any control/junction box for lights, foundation other accessories, items which is necessary for the satisfactory functioning of the high mast light system but not mentioned in here. (ii) The contractor shall provide genuineness/ authentication certificate from manufacturer to confirm that High mast is of make approved by Deptt as specified in CA. No payment shall be released till contractor provide the same. Make of Mast: Bajaj/Crompton/Surya

-

-

-

... More
Supply and fixing LED flood light fitting of 150 watt in epoxy/ powder coated pressure die-cast aluminium housing with, heat resistant toughened clear glass fixed with SS screws controlled with potted CVCC type, BIS marked electronic driver duly enclosed of approved brand only in housing having protection against over voltage, short circuit and open circuit and surge protection against lightening of 5 KV minimum in circuit and 5 KV outside the driver but inside the fixture with IP-66, Class-1 protection for LED and control gear compartments with high power LED chips of rating 2.5 to 3 watt (maximum) with colour temperature 5700 K(max) with secondary optics modular lenses provided to minimize glare and for better distribution of light suitable for voltage band 120 volts to 270 volt, power factor 0.95 (minimum) having efficacy 110 lumens/watt on 16m high mast pole all as specified and directed

16

-

-

... More
Material and labour for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thickness buried directly in ground (earth pit not less than 2.25meters deep below ground level) with top edge of the plate not less than 1.5meters below normal ground level, connected to galvanised earth strip 32x6 mm as earthing strip by means of GI bolts, nuts, check nuts and washers including surrounded on all sides by 15cm thick layer of charcoal dust, salt, including earth strip protected by 40mm dia GI light grade pipe, PCC pit of 1:2:4 & reinforced PCC top cover 50mm thick, earth pit angle frame of size 25mmx25mmx3mm with excavation and earth work in any type of soil, light grade GI watering pipe 20mm dia with funnel and wire-mesh complete all to as shown in electrical plate no 3 of SSR Part I 2009 connected main switch board or as required at site all as specified and testing on completion. Note: (a) The rate quoted include the cost of GI strip & GI protection pipe light 40mm dia bore light grade upto 7.5 metres. PCC Chamber shall be constructed at least 0.50m away from on the earth pit electrode and pipe for watering shall be provided in slanting manner. (b) If the results are not found satisfactory, then 2nd earthing will be re-done without any cost payable to Contractor

4

-

-

... More
Material and labour for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thickness buried directly in ground (earth pit not less than 2.25meters deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of GI bolts, nuts, check nuts and washers including surrounded on all sides by 15cm thick layer of charcoal dust, salt, including earth wire protected by 40mm dia GI light grade pipe, PCC pit of 1:2:4 & reinforced PCC top cover 50mm thick, earth pit angle frame of size 25mmx25mmx3mm with excavation and earth work in any type of soil, light grade GI watering pipe 20mm dia with funnel and wire-mesh complete all to as shown in electrical plate no 3 of SSR Part I 2009 connected main switch board or as required at site all as specified and testing on completion. Notes : (a) The rate quoted include the cost of wire & GI protection pipe light 40mm dia bore light grade upto 7.5m. PCC Chamber shall be constructed at least 0.50m away from on the earth pit electrode and pipe for watering shall be provided in slanting manner. (b) If the results are not found satisfactory, then 2nd earthing will be re-done without any cost payable to Contractor

4

-

-

... More
Supply, install, testing and commissioning of feeder pillar, of size 0.6m x 0.6m x 0.4m (Min), outdoor cubicle type weather and vermin proof totally enclosed made out of 3 mm thick CRCA sheet machine pressed, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz with locking arrangement, removable bottom gland plate with sufficient numbers of circular cable entry holes including glands, prewired complete duly powder coated (7 tank Min.) with supporting legs of angle iron of size 40 x 40 x 6mm of length 100cm long duly grouted in PCC (1:3:6), 40cm below ground level and 60cm above ground including construction of masonry /PCC platform complete all as specified and directed. The panel shall be comprising of following. (i) MCB TPN 40 A 'C' curve -02 Nos (ii) Contactor 32 Amp 3 Pole for auto on/off of light -01 No (iii) MCB SP-32 Amp-01 No (iv) Astronomical Digital timer - 01 No (v) Toggle/selector switch for auto/ manual operation-01 No (vi) Digital Multifunction meter -01 No to display Volt, Amp, KWH, frequency etc. (vii) LED indicator R,Y,B-01 set (viii) CT's set of 3, 100/5 Amp rating (ix) Control system for motorized control of High mast to lower and raise the luminaire carriage through motor with push button, contactor. Note:- The panel shall have sliding bolt also for locking arrangement. The 'FRONT' & 'REAR' side 'DANGER' sign notice plate shall be provided on doors

2

-

-

... More
Material and labour for boring hole under the road / pavement / hard standing with the help of trenchless technology using ultra sound technique and necessary machine for inserting GI Pipe up to 50mm mm not less than one metre below ground level complete all as specified & directed by Engineer-in-Charge. Note: The GI pipe shall be measured and paid separately

8

-

-

... More
Supply and fixing galvanised pipe light grade (IS-1239) 50 mm bore for passing of cable fixed to poles/walls/lay under floor complete with and including fittings as required compete all as specified and directed Engineer-in-Charge

10

-

-

... More
Supply, laying, jointing and testing XLPE insulated, PVC sheathed, steel strip or wire armoured electric cable 1100 volt grade (heavy duty) with stranded aluminium conductor of size 16 Sqmm, 4 core laid in trenches, in floor, in duct, through pipes/ culvert or along the pole/ wall complete all as specified and directed

350

-

-

... More
Supply, laying, jointing and testing XLPE insulated, PVC sheathed, steel strip or wire armoured electric cable 1100 volt grade (heavy duty) with stranded aluminium conductor of size 185 Sqmm, 3.5 core laid in trenches, in floor, in duct, through pipes/ culvert or along the pole/ wall complete all as specified and directed

190

-

-

... More
Excavation in trenches in soft/loose soil not exceeding 1.50m wide and not exceeding 1.50m in depth for laying of cables and getting out complete all as specified and directed by Engineer-in-Charge

66.2

-

-

... More
Returning, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed by Engineer-in-Charge

34.8

-

-

... More
Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge

31.4

-

-

... More
Material and labour for sand cushioning with a layer of sand 8cm thick before laying of cable and 15cm thick after laying of cable and trenches punned down to thickness of 18cm complete all as specified and directed. Note: Punned thickness of 18 cm will be measured and paid

25.5

-

-

... More
Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-Charge

2.96

-

-

... More
Supply, installations, testing and commissioning of flat plate solar water heater 200 LPD with electrical backup thermo syphon type with heat exchanger suitable class. The hot water tank shall be made of SS 304 having 1.6mm thickness sheet minimum with PUF insulation or other suitable insulation material having density 40 Kg/ Cum cladded with powder coated sheet. The heat collector plate shall have suitable insulation and sheet with riser and heater tubes/ pipes. The absorber solar water heater shall have minimum 2/ 3 Kw element with thermostat and temp gauge. The quoted rates including cost of necessary item support structure for collector and hot water storage tank duly painted complete. The flat plate collector shall have Cu-Cu (copper type) 2.5 Cum area -02 Nos as per IS-12533 part-I, as per MNRE guideline complete all as specified and directed. Note : The quoted rate deemed to be included cost of any item which is required for functioning, but not mentioned above.

2

-

-

... More
Supply and fixing hot water pipe duly insulated with glass wool and aluminium cladding 15mm bore and connecting up complete all as specified and directed

20

-

-

... More
Supply and fixing hot water pipe duly insulated with glass wool and aluminium cladding 20mm bore and connecting up complete all as specified and directed

20

-

-

... More
Supply and fixing hot water pipe duly insulated with glass wool and aluminium cladding 25mm bore and connecting up complete all as specified and directed

20

-

-

... More
Supply and fixing GI tubing medium grade 25mm bore (in any length) with required fitting duly laid in trenches and connecting up complete all as specified and directed

50

-

-

... More
Supply and fixing globe or gate valve of size 25mm dia with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed

2

-

-

... More
Supply and fixing globe or gate valve of size 20mm dia with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed

2

-

-

... More
Supply and fixing globe or gate valve of size 15mm dia with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed

2

-

-

... More
Supply and fixing bib taps 15mm bore, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferruled but fancy type complete all as specified and directed

6

-

-

... More
Material and labour for taking water connection from existing main water pipe line by cutting, threading existing pipes of size upto 50mm dia in position and fixing including fittings complete with any type of earth work required at site all as specified and directed

1

-

-

... More
Material and labour for submain wiring with two run of PVC insulated unsheathed multi-stranded copper conductor RFLS wire 4.0 Sqmm 1100 Volts grade and including 4 Sqmm FRLS PVC insulated, multi-stranded, unsheathed copper wire green in colour as earthing lead on casing caping of suitable size complete all as specified and directed Note : Two run of 4.0 Sqmm cable and one run of 4 Sqmm cable as earth continuity conductor with casing caping shall be measured & paid as one unit

60

-

-

... More
Material and labour for submain wiring with two run of PVC insulated unsheathed multi-stranded copper conductor RFLS wire 6.0 Sqmm 1100 Volts grade and including 6 Sqmm FRLS PVC insulated, multi-stranded, unsheathed copper wire green in colour as earthing lead on casing caping of suitable size complete all as specified and directed Note : Two run of 6.0 Sqmm cable and one run of 6 Sqmm cable as earth continuity conductor with casing caping shall be measured & paid as one unit

60

-

-

... More
Supply and fixing single pole and neutral sheet metal enclosure with two pin and earth plug and socket complete with one single pole MCB 16 Amps all as specified & directed by Engineer-in-Charge

2

-

-

... More
Supply and fixing 500 ltrs rotational moulded polythine water storage tanks (cylinder vertical with closed top) hoisted and fixed in position including ball brass valves, high pressure with polythene float and fly nut complete screw for iron pipe or brass ferrule all as specified in SSR Part-I

2

-

-

... More
Supply and fixing structural steel cross arm, channels, brackets, angles, MS flat of size including for any pipe of cutting, drilling for fabrication of cold water staging/ support structure of suitable height include preparation of surfaces, primer with one coat of red oxide and painting with two coat of synthetic enamel paint included any item which required complete all as specified and directed

3

-

-

... More
Supply, Install, testing and commissioning complete Diesel Engine driven generating set silent type with AMF panel, 415 volts, 3 phase, 160 KVA cap at NTP, 0.8 power factor, 50 Hz, conforming to CPCB IV+ emission & noise level norms, including microprocessor based controller, control panel and other standard accessories as per manufacturer's design and recommendations with and including following:- (a) ALTERNATOR: Alternator AC, 3 phase, 415 volts, 4 wire 160 KVA rated at NTP, power factor 0.8, 1500 rpm, self-excited, self-regulated, screen protected & drip-proof, brushless design, self-regulated through an AVR with ±1%, IP 23 protection with insulation class 'H' directly coupled with engine with suitable flexible coupling complete brushless, 1500 rpm, self-excited, self-regulated, AC, and conforming to conditions under IS 4722,1460 BS-5514,5000 and ISO 8528,3046. (b) DIESEL ENGINE: Diesel engine of suitable BHP for above alternator, water cooled, turbo charged, 12/24 volts electric battery start, multi-cylinder complete with flywheel and all standard accessories, fittings & fixtures as per manufacturer recommendations complete required for safe running and operation. The salient features of accessories shall be as under:- (i) Flywheel housing (ii) Air cleaner wet/dry type (iii) Fuel Filter

1

-

-

... More
(iv) Fuel Injection system incl. Injection pump, solenoid switch, nozzle as per manufacturer's specifications (v) Lubricating oil filter (vi) Lubricating oil pump (vii) Turbocharger (viii) Radiator for liquid cooling (ix) 12/24 volts starting system consisting of batteries of capacity as recommended by manufacturer, battery connections with copper leads and with lugs of adequate size, initial charging of batteries, battery charger/ generator with regulator, starter motor, starter gear, start and stop push buttons, ignition key and switch. (x) Exhaust silencer complete with exhaust pipe of suitable size (xi) Electronic governing. (xii) Battery charger with float and boost mode (xiii) Radiator cooling system comprising of radiator, radiator fan belt, water pump with belts, thermostat. (xiv) Fuel hoses. (xv) Built-in fuel tank of suitable capacity in base frame for fuel, supply lines as required at site and as per manufacturers recommendation including return and overflow as well as fuel filling arrangements. (xvi) Air intake system (xvii) Common base frame of sturdy design with anti-vibration pads for engine & alternator. (xviii) First filling of lub oil and coolant.

-

-

-

... More
(c) AMF CONTROL PANEL: AMF Control panel shall be Microprocessor Relay based panel made out of suitable thick CRCA sheet of 14/16 gauge complete factory made dust and vermin proof, totally enclosed with front opening of 415V 3 phase, 4 wire system AC 50 Hz, having Copper busbar of and MCCB of suitable rating with overload and short circuit protection, Current transformers, and other required elect items with incoming and outgoing termination.

-

-

-

... More
(d) Gen set controller : It should be a electronic micro processor based generator set monitoring and control system mounted in the Gen set control panel .It should provide a simple operator interface to the generator set, manual and remote start/stop control, shutdown fault indication, and indication of battery voltage, oil pressure, water/ engine temp, engine rpm, hour meter and protection against low oil pressure, high water temperature and over speed of engine. It should have all the functions necessary to locally or remotely start and stop and protect the generator set. The display should be able to display Voltage L-L & L-N, current, KVA, KW, Frequency, Oil pressure, water temperature and all other parameters as per OEM recommendation. (e) Acoustic insulated enclosure/canopy for Generating set:- Acoustic enclosure shall be factory made up of suitable thickness (as recommended by OEM) CRCA sheet powder coated insulated with suitable insulation material so as comply with the 75 dBA at a 1m sound level or latest norms and conforming to the provisions of environment (protection) rules. The doors and glass window shall be as per manufacturer's design. (f) Foundation : Suitable size PCC/ RCC plinth foundation as per manufacturer recommendation shall be provided in this over all quoted rates.

-

-

-

... More
Notes : (a) Entire DG Set shall be procured from one of the manufacturer . (b) Operation and maintenance manual, spare parts list manual shall also be supplied within overall cost quoted. (c) Pre-commissioning test with strip heater load shall be carried out by representative of Accepting officer/IEM and cost of testing, FOL, any T&P, testing equipment required etc is deemed to be included in unit rate quoted. (d) POL/Fuel for testing till the satisfactory results are achieved, shall be arranged by the contractor without any extra cost to the Deptt.

-

-

-

... More
Material and labour for boring hole under the road / pavement / hard standing of any width with the help of trenchless technology using ultra sound technique and necessary machine not less than 1m below ground level for laying pipes/ cables complete all as specified

5

-

-

... More
Material and labour for cutting of existing PCC surface any type for laying cables/pipes of size 150mm width and upto 150mm depth complete all as specified

20

-

-

... More
Supply and fixing galvanised pipe light grade of 80 mm bore in any length as required including jointing pipe with socket at site for passing of cable fixed to poles/walls/laid under floor, roads etc. complete with and including fittings as required compete all as specified and directed Engr-in-Charge

24

-

-

... More
Material and labour for earthing with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI strip 32mm x 6mm upto test point (made of GI strip) and Al strip 25x3.15mm from test point to equipment in and including GI pipe 40mm bore light grade as protection pipe (from top of earth plate up to the body of equipment) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300 x 300 x 300mm (top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate and angle iron frame including necessary excavation/ earth work in any type of soil/rock, test point of GI strip and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.(cost of protection pipe/earth strip up to 7.5metres will be included in the unit rate quoted by the contractor) complete all as specified and directed

4

-

-

... More
Supply Install, testing and commissioning of LT Distribution Panel (Approx min size 1200 x 1000 x 450mm), cubicle type, outdoor type, factory fabricated made out of 3.15mm thick CRCA sheet outer & 2mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming MCCB and TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC/ epoxy insulator . The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC/ Epoxy insulators having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall have colour coated sleeves. The cubicle shall have frame work on bottom with 60 CM long 4 legs of size 50 x50 x 6mm angle iron, grouted in PCC 1:3:6 as directed by Engr-in-Charge. A detacheable gland plate of thickness not less than 3 mm thick should be used at the botom for entry of armoured cable of adequate size compression glands The panel shall have powder coated finish with RAL 7032 SIEMENS GRAY Structure after seven tank phosphating treatment, front & back opening type, and having 2 Nos danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door & LT Panel indicated in Hindi and English with double door shutter and shall have louvers and airvent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-

1

-

-

... More
(i) Bus bar strip, four pole and capacity 400 Amps copper, coloured with plastic coated insulated and sleeves in four colours (Red, Yellow, blue and black ) fixed on porcelain insulators with necessary nuts and bolts and washers etc. (ii) INCOMING : -  (a) MCCB 250 Amp, 415 V, 36 KA, Ics=100%Icu, 4 pole, adjustable thermal & fixed magnetic type -01 No. (b) Indicator with LED lamps for RYB -01 set (c) Digital multifunction meter for showing parameter V, A, F, W, KVA, PF, KWh  (d) Digital Ammeter (0-400) Amps for each MCCB outgoing with suitable set of CTs

-

-

-

... More
(e) Digital Voltmeter (0-500) Volts (iii) OUTGOING : - (a) MCCB 160 Amp, 415V, 25 KA, Ics=100%Icu, 4 pole thermal & fixed magnetic type -01 Nos. (b) MCCB 63 Amp, 415V, 16 KA, Ics=100%Icu, 4 pole thermal & fixed magnetic type -02 Nos. (c) MCB 32 Amp, TPN, 415 V, 10 KA, -02 Nos. Note :- The LT panel should be CPRI approved as per IS -5039 of 1983.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.