Military Engineer Services Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
₹ 80,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_MES_519623_2Bid Award Id
ViewTender No
CWE/ASR-08/2022-23Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Returning, filling in, and including spreading, levelling,watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
34.8
-
-
M&L for Sand cushioning to underground cable 8cm before laying the cable and 15cm (punned down to 18 cm) after laying and stretching the cable complete all as specified.
16.2
-
-
M/L Sub Class 'B' brick including taken out old broken unsv brick for covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified.
1.6
-
-
M&L for PCC ( 1:2:4) type B1 using 20 mm graded stone aggregate for coping pedestal of poles. Including necessary form work fair finished to exposed surface complete all as specified and directed.
0.12
-
-
M&L for PCC ( 1 : 3 : 6 ) type C2 using 40mm graded stone aggregate for foundation of poles and stay assembly complete all as specified and as directed.
12
-
-
Servicing /Repair / calibration to HT Pannel having vaccum circuit breaker 11 KV rating of capacity 250MVA and current rating upto 630 Amp by replacing defective/ wornout parts, adjustment of gaps for smooth operation all as detailed below:-
(a) Cleaning of VCB with air blower and removing dust particles.
(b) Cleaning of insulating places of VCB by using CTC/ CRC/ Thinner as required and recommended (c) Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limits, readjust as recommended.
(d) Cleaing the main contacts to remove carbon or any other unwanted particals if visible.
(e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
(f) Checking / repair and replacement of all minor ac/dc electrical wiring for electrical/ mannual operationof HT panel loading and all others function based on the ac/dc operation of HT panel etc complete in all respect as specified
(g) Checking of all nuts/ bolts springs, levers, latches, connectors etc and adjustment etc required and recommended.
(h) Recording IR Values of CTs and PTs
(j) Cleaning of bus bar spout.
(k) Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations.
Note :- (i) The cost of minor parts ie nuts ,bolts,spring washers,dust cover ring of isolarors contacts,clips pins for release prop,Y phase shrouded over side stop pin,and all other minor parts ie packing essentially required to make the panel dust proof shall be deemed to be included in the rate quoted by the contractor . (ii) The servicing will be carried as per norms of OEM. (iii) Shut down for carrying out maintenance work shall be given by Engineer -in-Charge / JE EM Incharge as per availability/ suitabuility of time , contractor will not ask for complete shut down in one time. Quoted cost includes all visit & working cost of Electrician. No extra amout will be paid to the contractor.
12
-
-
S & F in replacement &testing and commissioning of resin current transformer dual core dual ratio for protection and class I accuracy.suitable for 11 KV, 200-100/5+5A of primary wound type with adjustable VA bourden and accuracy in clearing the CT wiring with primary and secondary injection kit including identification to the base and connecting links to HT/VCB to match with the existing system complete all as directed Make - as per OEM HT panel manufacturers.
3
-
-
S & F in replacement &testing and commissioning of resin current transformer dual core dual ratio for protection and class I accuracysuitable for 11 KV, 100-50/5+5A of primary wound type with adjustable VA bourden and accuracy in clearing the CT wiring with primary and secondary injection kit including identification to the base and connecting links to HT/VCB to match with the existing system complete all as directed Make - as per OEM HT panel manufacturers and to be approved by GE.
4
-
-
S & F in replacement &testing and commissioning of resin current transformer dual core dual ratio for protection and class I accuracy suitable for 11 KV, 50/25 /5+5A of primary wound type with adjustable VA bourden and accuracy in clearing the CT wiring with primary and secondary injection kit including identification to the base and connecting links to HT/VCB to match with the existing system complete all as directed Make - as per OEM HT panel manufacturers and to be approved by GE.
2
-
-
S & F in replacement &testing and commissioning of Analog ammeter (0-200A /100) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
2
-
-
S&Fixing in replacement & testing and commissioning of Analog ammeter (0-100A /50A) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
8
-
-
S&Fixing in replacement &testing and commissioning of Analog ammeter (0-50 /25A) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
4
-
-
S&Fixing in replacement &testing and commissioning of Analog voltmeter (0-15KV) suitable to function with built selector switch suitable for 11KV HT VCB panel flush pattern square type 96 mm x 96 mm with adopter or as per existing including wiring complete all as specified and directed.
8
-
-
S&Fixing in replacement & testing and commissioning of Digital ammeter (0-200A /100) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
5
-
-
S&Fixing in replacement & testing and commissioning of Digital ammeter (0-100A /50A) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
12
-
-
S&Fixing in replacement & testing and commissioning of Digital ammeter (0-50 /25A) suitable for 11 KV VCB range having 200/100/5A ratio suitable for function selector switch suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
6
-
-
S & F in replacement &testing and commissioning of Digital voltmeter (0-15KV) suitable to function with built selector switch suitable for 11KV HT VCB panel flush pattern square type 96 mm x 96 mm with adopter or as per existing including wiring complete all as specified and directed.
20
-
-
S&Fixing in replacement & testing and commissioning Indication lamps DC 24 volts with showing red, yellow and green in colour of 22.5mm dia to monitor on HT panel board suitable for 11KV HT VCB panel supply complete all ,as specified and directed.
20
-
-
S&Fixing in replacement & testing and commissioning Indication lamps AC 220 volts with showing red, yellow and green in colour of 22.5mm dia to monitor on HT panel board suitable for 11KV HT VCB panel supply complete all ,as specified and directed.
20
-
-
S&Fixing in replacement & testing and commissioning Vacuum interrupter for R/Y/B phase for VCB of cap 630/800 Amp complete all as specified, as per OEM HT panel manufacturer.
3
-
-
S&Fixing in replacement &testing and commissioning Isolating contact for R/Y/B phase for VCB of cap 630/800 Amp complete all as specified, as per OEM HT panel manufacturer.
12
-
-
S & F in replacement &testing and commissioning Maintenance free dry batteries of 2V, 100 AH electrically connected to each other battery to VCB and power pack as required at site and directed.
110
-
-
M&L for electromat suitable for 11 KV insulation of thickness not less than 3mm all as specified
20
-
-
S & F in replacement & testing and commissioning 80W ,230 V AC single phase rated strip space heater with switch and thermostat for space heating complete all as specified and directed
40
-
-
Taking down the existing unsv HT panel controls relay any type and S&F & testing and commissioning of numerical relay microporcesser base retrofit to the existing Panels and programming the relays to overlaod and earthfault setting with respect to the setting of HT Panel issued at PSPCL 11 KV Sub Station al as specified and directed.
8
-
-
Material and labour for old painted surface of Steel by brushing / cleaning of stain of grease , spots with thinner and applying a coat of epoxy panting on outer face of HT panel to match with the original based colour all as specified complete in all respect and directed by the Engr in Charge Note :- Cost of Marking of SM Nos/ MES Nos, in coming / out going feeder location wise shall be deemed to included in rate quoted by the contractor.
10
-
-
Servicing /Repair to HT Pannel of make Alstom/ areva/ having vaccum circuit breaker 11 KV rating of capacity 250MVA and current rating upto 630 Amp by replacing defective/ wornout parts, adjustment of gaps for smooth operation all as detailed below:-
(a) Cleaning of VCB with air blower and removing dust particles.
(b) Cleaning of insulating places of VCB by using CTC/ CRC/ Thinner as required and recommended (c) Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limits, readjust as recommended.
(d) Cleaing the main contacts to remove carbon or any other unwanted particals if visible.
(e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
(f) Checking / repair and replacement of complete DC electrical wiring for electrical/ mannual operationof HT panel loading measuring IR values.
(g) Checking of all nuts/ bolts springs, levers, latches, connectors etc and adjustment etc required and recommended.
(h) Recording IR Values of CTs and PTs
(j) Cleaning of bus bar spout.
(k) Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations.
(l) Replacement of all dc supply wiring with proper coding nos for complete control of Indicators ,numerical relays of HT panel
Note :- The cost of minor parts ie nuts ,bolts,spring washers,dust cover ring of isolators contacts,clips pins for release prop,Y phase shrouded over side stop pin,and all other minor parts ie packing essentially required to make the panel dust proof shall be deemed to be included in the rate quoted by the contractor. (ii) The servicing will be carried as per norms of OEM. (iii) Shut down for carrying out maintenance work shall be given by Engineer -in-Charge / JE E/M Incharge as per availability/ suitabuility of time it may be one breaker in one day , contractor will not ask for complete shut down in one time. Quoted cost includes all visit & working cost of Electrician. No extra amout will be paid to the contractor.
15
-
-
Repair to HT Pannel of make kirloskar having vaccum circuit breaker 11 KV rating of capacity 250MVA and current rating upto 630 Amp by replacing defective/ wornout parts, adjustment of gaps for smooth operation all as detailed below :-
(a) Cleaning of VCB with air blower and removing dust particles.
(b) Cleaning of insulating places of VCB by using CTC/ CRC/ Thinner as required and recommended (c) Checking the arcing contact gap of vaccum intrupter if gap exceeds the permissible limits, readjust as recommended.
(d) Cleaing the main contacts to remove carbon or any other unwanted particals if visible.
(e) Dismantling and cleaning the insulated surfaces and arc barrier with CTC and CRC.
(f) Checking / repair /replacement of complete AC electrical wiring for electrical/ mannual operationof HT panel loading measuring IR values.
(g) Checking of all nuts/ bolts springs, levers, latches, connectors etc and adjustment etc required and recommended.
(h) Recording IR Values of CTs and PTs
(j) Cleaning of bus bar spout.
(k) Checking of all moving parts for proper functioning of VCB and adjustment as per manufacturer recommendations.
(l) Replacement of complete dc supply wiring with proper coding nos for complete control of Indicators ,numerical relays and all others function based on the dc operation of HT panel etc complete in all respect as specified.
Note :- The cost of minor parts ie nuts ,bolts,spring washers,dust cover ring of isolarors contacts,clips pins for release prop,Y phase shrouded over side stop pin,and all other minor parts ie packing essentially required to make the panel dust proof shall be deemed to be included in the rate quoted by the contractor . (ii) The work will be carried as per norms of OEM. (iii) Shut down for carrying out maintenance work shall be given by Engineer -in-Charge / JE E/M Incharge as per availability/ suitabuility of time it may be one breaker in one day , contractor will not ask for complete shut down in one time. Quoted cost includes all visit & working cost of Electrician. No extra amout will be paid to the contractor.
15
-
-
S & Fixing in replacement &testing and commissioning of power factor meter of multifunction suitable for HT VCB panel flush pattern square type 96mm x 96mm with adopter including wiring complete all as specified and directed.
8
-
-
Strip Opening the busbar of suitable size the HT VCB panel , removing the old teared/ unsv insulation from the bus bar checking the IR value before fixing the HT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 11 kv busbar not less than 3mm thick having dielectric strength not less than 15kv/mm and HT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified . Note :- Test sheet of IR value shall be submitted by the contractor no cost extra shall be paid by the department and all testing requirement shall be fulfill deposited by the contractor.
21
-
-
S&F in replacement & testing and commissioning tripping coil operated by AC or DC supply complete with electric copper wire of suitable all as specified and directed
9
-
-
S&F in replacement & testing and commissioning closing coil operated by AC or DC supply complete with electric copper wire of suitable all as specified and directed
9
-
-
S&F in replacement bakelite kitkat complete with HRC fuse 2-20 amps of suitable suitable for HT panel blaclor grey in colour including necessary nuts for fixing in position all as specified and directed
40
-
-
Supply and fix spring charging electric motor suitable for VCB of cap 800 Amp with complete accessories complete all as specified and as directed.
2
-
-
Supply and fix spring charging electric motor suitable for VCB of cap 630 Amp with complete accessories complete all as specified and as directed.
5
-
-
Material & labour for providing 20mm broken stone aggregate including spreading and levelling complete all as specified and directed.
30
-
-
Supply, jointing ,testing in repair end termination jointing kit heat shrinkable out door type ,suitable for HT 11000 volts grade cable of size 185 sqmm 3 core complete all as specified.
7
-
-
Supply and fixing in replacement of muster trip relay voltage 220 volt DC VAZ type complete all as specified and as directed.
10
-
-
Supply and fixing in replacement of limit switch for 11 KV VCB of complete all as specified and as directed.
15
-
-
M&L for earthing complete with Copper earth plate electrode 30x60x3.15mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to copper strip of size 20x3 mm and 40 mm dia bore 7.5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 40 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
10
-
-
S&F in replacement for copper strip of size 20x3 mm from test point to transformer or other places complete all as specified and directed.
75
-
-
M&L for construction of platform of size 3000X 2500 x 1500 mm for transformer having side finished, PCC (1:4:8) up to 30 CM in foundation and PCC at top porion of platform up to 25 CM thick with suitable size MS bars, brick work with cement mortar (1:4) and complete plaster work of 15 mm thick to exposed surface in CM (1:4) including necessary MS work ( i.e. MS jali/fencing/MS angle ) on the top of platform around transformer up to height 3 feet including necessary opening from one side and necessary stairs complete all as specified in Zonal typical drawing and as directed by Engr-in-Charge.
1
-
-
Supply , jointing ,testing in repair straight through jointing kit heat shrinkable indoor type ,suitable for HT 11000 volts grade cable of size 120 to 185 sqmm 3 core complete all as specified.
5
-
-
Supply and fixing in replacement of 11KV support insulator suitable for 11KV VCB (VCB make Areva,Kirloskar & CG ), dismantling and mantling of VCB Panel labour charge,high quality 11KV VCB busbar Insulation Material and Nutbolts included in quoted rates complete all as specified
18
-
-
Supply and erect steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts nuts & screws as specified type 410 SP-55 ( 11 mtr long) erecting in position all as specified/shown on drawing and as directed by Engr-in-Charge
Note: (i) Excavation Earth work and foundation will be measured and paid seperately under relevent items.
16
-
-
M & L in replacement cross arms bracings supports clamps and back plates fabricated from structural steel sections including nut bolts washers welding bending cold and hot drilling holes for bolts in any shape or size as indicate or directed and inclusive of one primer coat one under coat and one finishing coat of paint.
15
-
-
Supply and Laying in replcement of cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (Heavy duty_) LT 1100 volt grade with stranded aluminium conductor of size 120 sqmm 3.5 core complete all as specified and directed. Make : KEI / Grandlay / Polycab
216
-
-
M&L for Dimmer for 250 KVA servo voltage controller suitable for servo voltage stablizer complete all as specified and as directed.
3
-
-
M&L for PC Board suitable for 250 KVA servo voltage stablizer complte all as specified and as directed
3
-
-
M&L for 10 Kg Servo motor suitable for 250 KVA servo voltage controller complte all as specified and as directed.
3
-
-
Supply and fixing out door type , polymer , triple pole, 11000 volts mechanically operated Air break switch, mounted on 15 Nos insulators and steel frame, with operating mechanism worked from ground level for current rating up to 200 amps and all accessories ie pipe clamp etc complete, all as specified and directed. Make - Pactil/OBLUM/ABB,Jaipuria/Rastriya/BHEL.
15
-
-
M&L for HT lightening arrestor for outdoor use, expulsion type, POLYMER complete with all fittings, transmission class, discharge capacity 65kilo amps, minimum working pressure 11000volts grade conforming to IS complete all as specified and directed Make - Pactil/OBLUM/ABB/Jaipuria/Rastriya/BHEL.